HVAC Safety Standards and Compliance
HVAC Safety Standards and Compliance
Safety Critical
HVAC & Natural Ventilation
PR DC MI ER element:
Heating, Ventilation and Air Conditioning system (HVAC) shall, with respect to accidental events:
• Provide pressurisation of rooms to prevent ingress of smoke or gas (see SCE-08 Ignition prevention where hazardous area classification for internally ventilated hazardous areas is defined)
• Provide smoke ventilation for internal fire conditions
• Ensure acceptable working and equipment environment
• Dilute and remove concentrations of HC gas, smoke and toxic gases (see SCE-08 Ignition prevention where hazardous area classification for internally ventilated hazardous areas is defined)
System Boundaries:
• Layout of facility (in relation to natural ventilation)
• AHU’s
• Inlets/exhausts
• Ducting
• Penetrations
• Dampers
• HVAC field instrumentation (where not included in the F&G system)
Interface to F&G system
Note: Requirements for naturally ventilated open hazardous areas and for dilution ventilation for turbine enclosures are covered by PS-08 Ignition Prevention Performance Standard
Functionality/
Safety Critical Reliability or Function/ Subsystem or Component
Performance Standard Activity Number Activity Description Phase Reference Documents
Element Availability / / Hazardous Event
Survivability
PS-12.01 Review detail drawings, D&IDs and type approvals for
Vessel ventilation systems and associated vessel ventilation systems and associated Architectural General Arrangement
Prevent through over-pressurisation, penetrations to confirm that they provided in
penetrations shall be provided in compliance with Drawings
the ingress of flammable or toxic compliance with SOLAS and class society
SOLAS and class society requirements.
HVAC functionality gas/air mixtures into non-hazardous PS-12/01-01 requirements. Design
Note: Similar Performance Standard exists to cover HVAC Penetration Detail Drawings
areas. Alarm on sustained loss of
the Temporary Refuge Ref: SCE-13.
positive pressure.
Type Approvals
PS-12.02
Review HVAC Specification, HVAC D&IDs and F&G
Areas / enclosures / rooms that are provided with
Cause & Effects to confirm that appropriate systems Suppliers Documentation
pressurisation of rooms to prevent ingress of
Prevent through over-pressurisation, are specified to detect loss of positive pressure below
smoke or gas shall comply with IEC 60079 part 13
the ingress of flammable or toxic 50 Pa for more than 30 sec. to any protected areas HVAC Calculations
and with IP Model Code of Safe Practice Part 15.
HVAC functionality gas/air mixtures into non-hazardous PS-12/02-02 specified, and initiate an alarm at the CCR. Procurement
Pressurisation in these areas shall be monitored
areas. Alarm on sustained loss of HVAC D&IDs
(50pa) and alarm initiated on loss of pressurisation
positive pressure.
to the CCR.
FAT Reports
Guidance Note:
PS-12.02 Review vendor’s data sheets and specifications and
Areas / enclosures / rooms that are provided with FAT reports to confirm that equipment required for
Prevent through over-pressurisation, HVAC D&IDs
pressurisation of rooms to prevent ingress of HVAC pressurisation (e.g. supply and extract fans,
the ingress of flammable or toxic
smoke or gas shall comply with IEC 60079 part 13 pressure control dampers) are in accordance with the
HVAC functionality gas/air mixtures into non-hazardous PS-12/02-03 Construction Mechanical Completion Records
and with IP Model Code of Safe Practice Part 15. requirements of the HVAC specification, calculations
areas. Alarm on sustained loss of
Pressurisation in these areas shall be monitored and D&IDs
positive pressure. Test Records
(50pa) and alarm initiated on loss of pressurisation
to the CCR
PS-12.02 Confirm by inspection and review of mechanical
Areas / enclosures / rooms that are provided with completion records that the following equipment is
Prevent through over-pressurisation, pressurisation of rooms to prevent ingress of installed in accordance with the HVAC D&IDs:
the ingress of flammable or toxic smoke or gas shall comply with IEC 60079 part 13 • HVAC supply and extract fans; HVAC D&IDs
HVAC functionality gas/air mixtures into non-hazardous and with IP Model Code of Safe Practice Part 15. PS-12/02-04 • HVAC pressure control dampers; and Design
areas. Alarm on sustained loss of Pressurisation in these areas shall be monitored • appropriate systems to detect loss of positive F&G Cause & Effect Diagrams
positive pressure. (50pa) and alarm initiated on loss of pressurisation pressure below 50 Pa for more than 30 sec. to the
to the CCR. protected areas specified
PS-12.02 Confirm by witness testing and review of signed off
Prevent through over-pressurisation, Areas / enclosures / rooms that are provided with commissioning procedures that HVAC systems
the ingress of flammable or toxic pressurisation of rooms to prevent ingress of provide a positive differential pressure of at least 50
HVAC functionality gas/air mixtures into non-hazardous smoke or gas shall comply with IEC 60079 part 13 PS-12/02-05 Pa between protected areas as per approved design Construction F&G Cause & Effect Diagrams
areas. Alarm on sustained loss of and with IP Model Code of Safe Practice Part 15. and the external ambient conditions (during conditions
positive pressure. Pressurisation in these areas shall be monitored corresponding as far as is practicable to normal
(50pa) and alarm initiated on loss of pressurisation platform operating conditions)
Prevent through over-pressurisation, PS-12.02 Confirm by witness testing and review of signed off
the ingress of flammable or toxic Areas / enclosures / rooms that are provided with commissioning procedures that loss of positive
HVAC functionality gas/air mixtures into non-hazardous pressurisation of rooms to prevent ingress of PS-12/02-06 pressure below 50 Pa for more than 30 sec. to the Commissioning F&G Cause & Effect Diagrams
areas. Alarm on sustained loss of smoke or gas shall comply with IEC 60079 part 13 protected areas specified initiates an alarm at the
positive pressure. and with IP Model Code of Safe Practice Part 15. CCR
N/A Covered in the PS XXXX (previous one, to be
Layout Drawings
PS-12.03 changed when numbering is done)
Loss of positive pressure below 30 Pa for more
Prevent through over-pressurisation, HVAC D&IDs
than 30 sec. to any areas provided with over-
the ingress of flammable or toxic
pressurisation protection shall initiate an alarm at a
HVAC functionality gas/air mixtures into non-hazardous PS-12/03-01 Design HVAC Data Sheets
normally manned area.
areas. Alarm on sustained loss of
Note: Ref: SCE-11 Passive Fire Protection, for
positive pressure. Architectural Details
external doors with self-closing mechanism.
Type Approvals
Penetrations Details
PS-12.07
Fire dampers shall be provided with; Confirm by witness of testing that fire dampers closure
- local manual closure from outside of the protected is provided with:
area, - local manual closure from outside of the protected HVAC D&IDs
HVAC functionality Control, Operability & Sizing - remote manual closure from the CCR, and PS-12/07-02 area, Design
Both of the above areas shall be provided with - remote manual closure from the CCR, and HVAC Data Sheets
damper closure status indication. Both of the above areas shall be provided with damper
closure status indication.
PS-12.08
Review suppliers documentation to confirm that fire
Fire dampers shall be arranged to fail safe close
dampers are fail safe close (without external source of
(without external source of power) on loss of
power) on loss of instrument air or control signal,
HVAC functionality Control, Operability & Sizing instrument air or control signal, unless designated PS-12/08-02 Construction HVAC D&IDs
unless designated to remain open where defined by
to remain open where defined by operational
operational requirements.
requirements.
Fire dampers shall be arranged to fail safe close Confirm by witness of testing that fire dampers fail safe
(without external source of power) on loss of close (without external source of power) on loss of
HVAC functionality Control, Operability & Sizing instrument air or control signal, unless designated PS-12/08-03 instrument air or control signal, unless designated to Procurement Suppliers Data
to remain open where defined by operational remain open where defined by operational
requirements. requirements.
PS-12.09
Confirm by review of suppliers data that each fire
Fire dampers shall close automatically on activation
damper Is provided with an integral heat detection
of a heat detection device provided integral to the
HVAC functionality Control, Operability & Sizing PS-12/09-01 device which will close the damper automatically on Construction Suppliers Data
damper.
exposure to excessive heat or a fire.
HVAC equipment shall be designed to maintain Review HVAC suppliers test reports to confirm that
acceptable operating temperature and humidity for HVAC equipment functions in accordance with design HVAC D&IDs
HVAC functionality Control, Operability & Sizing essential safety equipment that is required to PS-12/10-02 requirements specified in activity no. PS-12/03-04a. Construction
operate under emergency conditions. Mechanical Completion Records