CCCC - Duct Bank 1200 mm2 132 KV Single Circuit (Filling 1.5 K.M-W)
CCCC - Duct Bank 1200 mm2 132 KV Single Circuit (Filling 1.5 K.M-W)
Induced currents in metallic layers as a fraction of conductor current (applied to all single phase circuits) : 0.0
Results Summary
Daily Load X coordinate Y coordinate Conductor
Cable No. Cable ID Circuit No. Feeder ID Cable Phase Cable Frequency Ampacity [A]
Factor [m] [m] temperature [°C]
1 1200-132KV-YEMEN 1 A 60.0 1.0 -0.4 1.5 87.5 939.3
2 1200-132KV-YEMEN 1 B 60.0 1.0 0.0 1.5 90.0 939.3
3 1200-132KV-YEMEN 1 C 60.0 1.0 0.4 1.5 87.5 939.3
Steady State Summary
CYMCAP Version 8.1 Revision 2
Study: Current Calculations
Execution: Duct Bank 1200 mm2 132 kV single Circuit
Date: 11/16/2023 11:45:06 AM
Simulation Data
Installation type: Multiple Ductbanks
Steady State Option Equally Loaded
Ambient temperature [°C] 40
Native Soil Thermal Resistivity [K.m/W] 1.5
Consider Non-Isothermal Earth Surface No
Consider effect of soil dry out No
Consider Electrical interaction between circuits No
Induced current in metallic layers as a fraction of conductor current (applied to all
0
single phase circuits)
Dielectric Losses
Armor/Pipe Losses
Total Losses
Reactance of Conductor
Surge Impedance
Others
Dielectric Stress at Insulation Inner Surface
No. Symbol Description Unit Cable No.1 Cable No.2 Cable No.3
1 Cable Equipment ID 1200-132KV-YEMEN 1200-132KV-YEMEN 1200-132KV-YEMEN
Normal Operation IEC 60287-1-1
Conductor AC Resistance
DC Resistance of the conductor at 20°C
Dielectric Losses
13 tanδ Dielectric Loss Factor 0.001 0.001 0.001
14 ε Insulation Relative Permitivity 2.5 2.5 2.5
Cable Capacitance
Mutual Reactance
Spacing Factor (applied when spacing between cable uneven or non-equal minor section length)
33 t₁ Insulation Thickness Between Conductor and Screen [mm] 21.0 21.0 21.0
34 ρTi Thermal Resistivity of Insulation [K.m/W] 3.5 3.5 3.5
Thermal Resistance of Jacket/Pipe Coating
Thermal resistance associated to the temperature rise due to surrounding heat sources