Potterton Profile 30,40,50,60,80 e
Potterton Profile 30,40,50,60,80 e
IMPORTANT This appliance must be installed and serviced by a competent person as stated in the Gas Safety (Installation
and Use) Regulations 1994.
Profile boilers are certified for safety, it is therefore important that no external control devices (e.g. flue dampers,
economisers, etc.) be directly connected to these appliances unless covered by these installation instructions or otherwise
recommended in writing. Any direct connection of a control device not approved by Potterton could invalidate the certificate
and the normal warranty.
LIST OF CONTENTS - Page 2
General Page No. 2 Site Requirements Page No. 3
Optional Extras Page No. 2 Technical Data Page No. 6
Accessories Page No. 3 Installation Instructions Page No. 11
Installation Data Page No. 3 Commissioning Page No. 18
Boiler Dimensions Page No. 3 Health and Safety Information Back Page
Control Systems, Pipework and
Wiring Guide Supplied in
User’s Instructions Literature Pack
GENERAL - Page 2
Potterton Profile boilers are fully automatically controlled All boilers can be supplied with either of the following types
wall mounted fan powered balanced flue appliances, using of flue system:
a cast iron heat exchanger and are available in five outputs
ranging from 5.86-23.44kW (20,000-80,000 Btu/h). 1) Standard horizontal flue system suitable for wall
thickness of 100mm (4 in.) to 510mm (20 in.).
The boilers which are designed to provide domestic hot 2) 2 metre horizontal flue system which provides a
water and/or central heating must be used on INDIRECT maximum flue length Of 1955mm (77 in.).
hot water systems only. The cast iron heat exchangers are 3) Vertical flue system which allows the flue to pass
suitable for use on open vented gravity domestic hot through a flat roof and terminate at a maximum height
water/pumped central heating systems or fully pumped of 1980mm (78 in.) measured from the top of the boiler
systems which may be sealed or open vented. case.
R.c ½
*NOTE:
IF PIPEWORK IS TO BE RUN DOWN THE BACK OF THE BOILER
THE NORMAL CLEARANCE OF 25mm BETWEEN THE REAR OF
THE BOILER AND WALL CAN BE INCREASED TO 35mm IF
DESIRED BY INVERTING THE BOILER MOUNTING PLATE DURING
INSTALLATION
Ensure that the gas supply pipe and meter are large enough 100mm (4 in) at the bottom of the boiler.
for this appliance and any others that may be run off the
same meter. Reference should be made to B56891 Additional clearances to these are required during
installation for lifting the boiler and 127mm (5 in) is required
Boiler Mounting Surface at the top of the boiler for access to the pipe connections.
The boiler must be mounted on a flat wall, which may be of
combustible material and must be sufficiently robust to take Ventilation
the weight of the boiler. The requirements of the local If the boiler is to be installed in a confined space such as a
authorities and the Building Regulations must be adhered to. cupboard, the space will need ventilating. Openings must be
provided at the top and bottom of the Cupboard each of
IMPORTANT NOTICE: which should have a free area as shown in TABLE 1. Further
TIMBER FRAMED HOUSES details for installation of a boiler within a compartment are
given in BS 6798.
If the appliance is to be fitted in a timber framed building, it
should be fitted in accordance with British Gas Publication TABLE 1
‘Operational Procedures for Customer Service’ Part 19. If in AIR VENT AREAS
any doubt, advice should be sought from the local region of PROFILE
British Gas. in2 cm2
30e 16 103
Clearances Around the Boiler 40e 21 135
The following minimum clearances must be maintained after 50e 26 170
installation, for correct operation and servicing of the boiler: 60e 32 206
80e 43 277
610mm (2 ft) at the front of the boiler
If the openings draw air from outside the building the free
5mm (0.2 in) each side of the boiler areas may be halved. Refer to BS 5440 Part 2 for further
guidance.
Balanced Flue Terminal and Ducting
INFORMATION RELATING TO VERTICAL FLUING IS
The fresh air inlet and flue ducts can be run from either the PROVIDED IN THE PACK CONTAINING THE VERTI-CAL
left, right, rear or top of the boiler to a miniature terminal on FLUE SYSTEM.
the outside of the building.
NOTE
The minimum spacings from the terminal to obstructions and Where a flue terminal is fitted less than 1000mm from a
ventilation openings are shown in FIG. 3. For information plastic or painted gutter or 500mm from painted eaves, an
appertaining to horizontal flue lengths reference should be aluminium shield of 1000mm length should be fitted to
made to FIG. 4. underside of gutter or eaves.
If a terminal is fitted less than 2m above a balcony, above Any car port or other add-on extension should consist of a
ground or above a flat roof to which people have access roof or a roof and one other wall. If it consists of a roof and
then a suitable terminal guard should be fitted. (P.l.L. No. two other walls − the installation shall be treated as suspect
205792). and further advice sought.
MAXIMUM
LENGTH ‘X’
STANDARD FLUE 510mm
SYSTEM (20in)
1 METRE FLUE 955mm
SYSTEM (37in)
ELECTRICITY SUPPLY
A 240 volts -~ 50Hz, single phase electricity supply fused to The supply to the boiler and its associated equipment should
3 amperes, must be provided in accordance with the latest be controlled by an exclusive 3A fused double pole switch
edition of the I.E.E. Wiring Regulations and any other local (having at least 3mm contact separation in both poles) so that
regulations that may apply. The current rating of the wiring complete isolation from the supply can be achieved to enable
to the boiler must exceed 3 amperes and have a cross servicing work to be carried out in safety.
sectional area of at least 0.75mm2 in accordance with
B56500 Table 16.
TECHNICAL DATA
Maximum working head 30.5m (100 ft) Gas supply connection Rc. 1/2 (i/2in BSP
Minimum working head on Female)
Fully Pumped systems 305mm (1 ft)
Minimum circulating head Water Content Models 30e, 40e
on Gravity systems 1.2m (4ft) 6.0 litre (1.32 gal)
Gas supply pressure 20mbar Models 50e, 60e &
Maximum Flow temperature 820C 80e
Electricity supply 240v~-50Hz fused 6.5 litre (1.43 gal)
at 3A
Power consumption 80 watts Appliance Weight-installed Models 30e, 40e
(excluding pump) Appliance Weight-lift 52kg (115 Ibs)
Flow/Return connection 22mm copper on 46kg (101 Ibs)
30e, 40e models
28mm copper on Appliance Weight-installed Models 50e, 60e &
50e, 60e, 80e Appliance Weight-lift 80e
models 62kg (137 Ibs)
53kg (117 Ibs)
SITE REQUIREMENTS - Page 7
BOILER INJECTOR GAS RATE INPUT OUTPUT BURNER PRESSURE
SIZE SIZE m3/h (ft3/h) kW(Btu/h) kW(Btu/h) mbar in wg
Min 2.9mm 0.73(25.8) 7.83(26702) 5.86(20000) 5.9 2.4
30e 0.9(31.95) 9.69(33068) 7.33(25000) 7.8 3.1
Max 1.05(36.92) 11.20(38217) 8.79(30000) 10.4 4.2
Min 3.1mm 1.09(38.34) 11.63(39682) 8.79(30000) 8.4 3.4
40e 1.24(43.8) 13.29(45336) 10.26(35000) 10.8 4.3
Max 1.39(49.23) 14.93(50955) 11.72(40000) 13.4 5.4
Min 3.5mm 1.39(50.23) 15.24(52000) 11.72(40000) 8.7 3.5
50e 1.58(55.74) 16.90(57692) 13.19(45000) 11.0 4.4
Max 1.75(61.84) 18.76(64000) 14.65(50000) 12.8 5.1
Min 3.8mm 1.79(63.09) 19.14(65300) 14.65(50000) 10.3 4.1
60e 1.94(68.55) 20.79(70950) 16.12(55000) 12.0 4.8
Max 2.11(74.4) 22.57(77000) 17.58(60000) 14.0 5.6
Min 4.4mm 2.18(77.1) 23.39(79800) 17.58(60000) 8.5 3.4
80e 2.5 (88.4) 26.82(91503) 20.52(70000) 11.0 4.4
Max 2.82(99.71) 30.25(103200) 23.45(80000) 14.0 5.6
Gravity domestic hot water circuits should have a minimum 1. Dissipating a minimum of 1 kW (3400 Btu/h)
circulating head of 1.2 m (4ft). See FIG. 8. 2. Maintaining a minimum water flow through the boiler of 9
litres/mm (2 gal/mm).
To ensure optimum boiler performance on both gravity hot water
and fully pumped systems a change-over switch is incorporated in A suggested method of meeting these requirements by using a
the boiler control box. The boiler is supplied with the switch set for bathroom radiator fitted with two lockshield valves is shown in
sealed or open vented fully pumped systems. FIGS. 6, 7.
If the boiler is to be used on a system with gravity hot water the Additional system information can be found in the Control Systems,
switch should be set at the GRAVITY position. In addition the bulb Pipework and Wiring Guide.
of the overheat thermostat should be repositioned as shown in
FIG. 21. SEALED SYSTEMS (FULLY PUMPED)
To prevent reverse circulation in the gravity circuit when the pump Installation
is running an injector disc is provided to form an injector tee at the
return connection on the boiler. See FIG. 20. The installation must comply with the requirements of BS 6798 and
BS 5449 Part 1. The B.G. publication “British Gas Specification for
On all systems the pump should be wired to the boiler terminal Domestic Wet Central Heating Systems” should also be consulted.
block. To prevent nuisance operation of the overheat thermostat, it
is important that where electrically operated zone valves are used Safety Valve
the boiler is wired so it does not cycle when the zone valves are
closed. Also, systems fitted with controls that close both hot water A non adjustable spring-loaded safety valve, preset to operate at 3
and central heating circuits while the boiler is still hot, must be bar (451bf/in2) shall be used. It must comply with BS 6759 Part 1
fitted with a by-pass circuit to dissipate the residual heat within the and include a manual testing device. It shall be positioned in the
boiler. flow pipe either horizontally or vertically upwards and close to the
boiler. No shut-off valves are to be placed between the boiler and
Further information on by-pass arrangements is provided in later the safety valve. The valve should be installed into a discharge
notes and illustrations. pipe which permits the safe discharge of steam and hot water such
that no hazard to persons or damage to electrical components is
Drain off taps should be fitted in the pipework close to the boiler caused.
and in the low points of the system.
Pressure Gauge
Note: Although the system can be emptied using the drain off taps
installed in the pipework around the system, to empty the boiler it is A pressure gauge incorporating a fill pressure indicator, covering
necessary to remove the drain off cap positioned within the boiler the range 0-4 bar (60 lbf/in2) shall be fitted to the system. It should
case. See FIG. 2. be connected to the system, preferably at the same point as the
expansion vessel. Its location should be visible from the filling
Combined Gravity Hot Water Pumped Central Heating point.
Systems. Where a cylinder thermostat and zone valve is used to
control the temperature of the hot water it is recommended that a Expansion Vessel
by-pass be installed in the gravity circuit. A suggested method of
doing this is shown in FIG. 8 where the bathroom radiator is A diaphragm type expansion vessel to B54814 Part 1 shall be fitted
connected into the gravity circuit and is fitted with two lockshield close to the inlet side of the pump. The connecting pipework
valves. Mechanically operated thermostatic domestic hot water should not be less than 15 mm (½ in nominal). Pipework
temperature control valves which allow the boiler to operate when connecting the expansion vessel should not incorporate valves of
the valve is closed or partially closed MUST NOT BE FITTED. any sort. Methods of supporting the vessel are supplied by the
manufacturer. The nitrogen or air charge pressure of the expansion
Fully pumped Systems vessel shall not be less than the hydrostatic head, (height of the
top point of the system above the expansion vessel). To size the
With the change-over switch in the control box set at the FULLY expansion vessel it is first necessary to calculate the volume of
PUMPED position, the pump will be controlled by an over-run water in the system in litres. The following volumes may be used
thermostat. This will ensure that the pump will continue to run after as a conservative guide to calculating the system volume.
boiler shut down if the water temperature in the boiler is high, thus
preventing nuisance operation of the overheat thermostat. Boiler Heat Exchanger: 6.5 litres
Small Bore Pipework: 1 litre per kW of
If a three port diverter valve is used as shown in FIGS. 6, 7 a by- system output
pass is not necessary since one circuit is always open. Micro Bore Pipework: 7 litres
Steel Panel Radiators: 8 litres per kW of
Where a pair of two port valves are used, a by-pass is system output
Low Water Capacity Radiators: 2 litres per kW of
system output
Hot water Cylinder: 2 litres
SITE REQUIREMENTS - Page 9
If the system is extended, the expansion vessel volume may Method of Make-Up
have to be increased unless previous provision has been Provision shall be made for replacing water loss from the
made for the extension. Where a vessel of the calculated system either:—
size is not available, the next available larger size should be i) from a make-up vessel or tank mounted in a position
used. higher than the top point of the system, and connected
The boiler flow temperature is controlled at approximately through a non-return valve to the system on the return
820C. side of hot water cylinder or the return side of all heat
emitters.
The vessel size can now be determined from the following or
table where V=System volume in litres. ii) where access to a make-up vessel would be difficult by
using the mains top up method or a remote automatic
pressurisation and make-up unit as illustrated in FIG. 7
Vessel Charge Pressure(bar) 0.5 1.0 METHODS 1 and 2.
Expansion Vessel Volume (litres) V x 0.11 V x 0.087 There shall be no connection to the mains water supply or
to the water storage tank which supplies domestic water
even through a non-return valve, without the approval of the
Cylinder local Water Authority.
The hot water cylinder must be an indirect coil type or a Filling Point
direct cylinder fitted with an immersion calorifier suitable for
operating at a gauge pressure of 0.3 bar (51 bf/in2) in The system shall be fitted with a filling point at low level
excess of safety valve setting. Single feed indirect cylinders which incorporates a stop valve to BS1 010 and a double
are not suitable for sealed systems. check valve (approved by the National Water Council) to be
fitted in this order from the system mains, Refer to FIG. 7.
Method 1.
FIG. 9 TEMPLATE
FIG. 10 BOILER MOUNTING PLATE
Place template in proposed boiler position ensuring it is
level (the minimum side clearances are automatically Remove template and carefully cut flue outlet hole through
allowed for) wall. If necessary make good around hole to enable holes
‘B’ to be drilled. (If internal flue fitment kit is being used refer
REAR FLUING to instructions supplied with kit).
Drill holes ‘A’ using a 7 mm drill
Mark holes ‘A’, ‘B’, ‘D’, large flue outlet hole and side of Drill holes ‘B’ and ‘D’ using a 5 mm drill
boiler reference lines throught slots ‘C’.
Using wall plugs, screws and washers (accessory pack A)
SIDE FLUING attach boiler mounting plate to wall. Ensure that it is level
and the correct way up, i.e. to provide the clearance at the
Mark hole positions ‘A’, ‘D’ and side of boiler reference lines rear of the boiler allowed for when marking out using the
through slots ‘C’. template. See also NOTE on FIG. 1.
Mark large flue outlet hole and holes ‘B’ using the thick lines Insert wall plugs into holes ‘B’ (accessory pack B) and hole
on the template for minimum clearance at the rear of the ‘D’ (accessory pack D).
boiler and the thin dotted lines for maximum clearance. See
NOTE on FIG. 1. Insert flue sealing collar into wall and secure with screws
provided, (accessory pack B). Make good the internal wall
surface around flue sealing collar.
INSTALLATION INSTRUCTIONS - Page 12
CUTTING AIR/FLUE DUCTS
1. Measure from outside face of wall to the side of boiler 1. Measure wall thickness (dimension ‘Y’).
casing reference line (dimension ‘x’). 2. Take air/flue duct assembly and measuring from the
2. Take air/flue duct assembly and measuring from the flanged end, mark and cut the outer air duct and inner
flanged end, mark and cut the outer duct and inner flue flue duct to dimension ‘Y’, plus 45 mm. Ensure that
duct to dimension ‘x’ plus 20mm. Ensure that both both ducts are cut squarely.
ducts are cut squarely. NOTE
Cutting length remains the same for minimum or
maximum clearance at the rear of the boiler.
NOTE: During assembly the seam in the air duct should be 3. Engage four screws from accessory pack ‘C’ into the
so arranged that when installed, the seam in the duct will be pre-drilled holes in the terminal and screw fully home.
uppermost. These screws which are self drilling will pierce the air
duct and secure the terminal to air duct.
1. Slide rope sealing ring on to air duct.
2. Engage the terminal on to the ends of the inner flue On models 30e, to 50e, it is necessary to drill four pilot
duct and press fully home. holes in the air duct.
INSTALLATION INSTRUCTIONS - Page 13
The controls cover should have been removed when plate. Remove the remaining screws securing the fan
unpacking the boiler, if not remove controls cover by opening mounting plate and remove the mounting plate complete
the door covering the securing screw on the underside of the with fan.
controls cover, see FIG. 14. Undo securing screw, pull
controls cover forward 10mm, lower to release from the four Disconnect the two flexible tubes from the flue elbow.
side fixings and pull forward clear of the thermostat knob.
Remove the four brass securing nuts and lift off the flue
Remove door by undoing the two lower fixing screws and lift elbow, taking care not to damage the gasket.
door off the two upper hinge brackets.
NOTE:
Remove the screws securing the combustion chamber front If side fluing, loosen the two brass securing nuts beneath the
panel and remove panel. flue elbow outlet and remove the other two.
Tilt the flange and withdraw the elbow.
Disconnect the fan supply leads from the connector adjacent
to the fan. Leaving in place the three screws identified with a The boiler is supplied with the left hand flue outlet sealing
red circle or adjacent ‘F’ mark in fan plate removed. If another flue outlet direction is required,
remove the appropriate flue outlet sealing plate and transfer
it to the left hand position.
INSTALLATION INSTRUCTIONS - Page 14
LIFTING THE BOILER
Locate the studs on the air duct flange through the boiler Position boiler on its mounting bracket so that the sides of
casing and secure using four wing nuts (accessory pack F). the boiler line up with the reference lines ‘C’ on the rear wall.
Rotate the left hand adjustment screw to align one of the When side fluing, slide the elbow extension onto the elbow
holes in the base plate with hole ‘D’ in the wall. Working and ensure that it is pushed on fully. Engage the screw from
through the hole in the leg, secure the base plate to the wall accessory pack ‘C’ into the pre-drilled hole in the elbow
using the screw from accessory pack D. Make good the wall extension and screw fully home. The screw which is self
surface around the flue terminal. Fit optional terminal wall drilling will pierce the elbow and secure the extension to the
plate if required. elbow.
INSTALLATION INSTRUCTIONS - Page 15
FIG. 20A PROFILE 30e and 40e FIG. 20B PROFILE 50e, 60e and 80e.
Following the pump manufacturer’s instructions connect the Gravity Domestic Hot Water/Pumped Central
Heating Systems.
pump supply wires to terminals marked PUMP L,N, ‘ ’-on the
Switched live from external gravity domestic hot water control
boiler terminal block. Route the cable through the plastic bush in
circuit to terminal marked MAINS ‘SwL’. Switched live from
the rear of the control box as illustrated in FIG. 24 and secure,
external pumped central heating control circuit to terminal
using the cable clamp.
marked MAINS ‘L’. Neutral to terminal marked MAINS ‘N’.
Route a four core cable through the plastic bush in the rear of Earth to terminal marked ‘ ’ adjacent to cable clamp. See
the control box and the cable clamp as illustrated in FIG. 24 and NOTE.
connect it to the boiler input terminals as follows:—
If there are no external controls fitted connect the SwL terminal
Fully Pumped Systems. to permanent live in the junction box.
Permanent live to terminal marked MAINS ‘L’.
Neutral to terminal marked MAINS ‘N’.
NOTE:
Earth to terminal marked ‘ ’ adjacent to cable clamp. Ensure that the earth conductor is longer than the L, N & SwL
See NOTE. from the point of anchorage, so that the current carrying
Switched live from external controls to terminal marked conductors become taut before the earth conductor if cable is
MAINS ‘SwL’. pulled out of the cable clamp. When the wiring has been
If there are no external controls fitted connect the SwL completed close the control box and replace the securing screw.
terminal to permanent live in the junction box.
FIG. 25
COMMISSIONING - Page 18
Open Vented Systems Refit the combustion chamber front panel.
Remove the pump and flush out the system thoroughly
with cold water. Refit the pump. Fill and vent the system. Fit the case door into position by lifting it onto the top hinge
Examine for leaks. brackets and secure it with the lower two fixing screws.
The whole of the gas installation including the meter should Ensure that the time control, if fitted is in an on condition,
be Inspected and tested for soundness and purged in and that the room and/or cylinder thermostats, where fitted
accordance with the recommendations of BS6891. are set to high temperatures.
Test pilot unions for gas soundness as follows:— Turn boiler Switch on the external electricity supply to the boiler. In the
thermostat to the ‘0’ position. event of an electrical fault after installation of the appliance,
preliminary electrical system checks must be carried out as
Unplug the gas control valve supply lead from the control described in the BG multimeter instruction book. The checks
box and plug it into the test socket adjacent to the boiler to be carried out are:-
thermostat knob, see FIG. 24. A. Earth Continuity
B. Short Circuit
Turn on gas at the gas service cock. C. Polarity
D. Resistance to Earth
Ensure that the time control if fitted is in an ON condition,
and that the room and/or cylinder thermostats where fitted Refer to Fault Finding Chart FIG. 31
are set to high temperatures. Turn the boiler thermostat on and to a high setting and after
a period of time the main burner will light, this can be
Switch on the external electricity supply to the boiler. observed through the sight glass in the front cover of the
boiler. The time period can vary upwards of 45 seconds,
Gas will flow to the pilot only. It will not be ignited as the depending on the amount of air in the pipework.
ignition system is de-energised.
Test for gas soundness around the boiler components using
Using a leak detection fluid, check pilot unions for gas leak detection fluid.
soundness. Turn the boiler thermostat to ‘0’.
Turn off the external electicity supply and gas service cock. NOTE:
Remove gas control valve plug from the test socket and refit There could be a delay in lighting if the control knob is
the plug into the socket on the left hand side of the control switched on and off and then on again rapidly.
box see FIG. 24.
With the burner set to its correct pressure, the firing rate Gravity Hot Water/Pump Over-Run Thermostat
given in TECHNICAL DATA should also be obtained and this The function of this thermostat is determined by the position
should be checked by meter reading at least 10 minutes in which the GRAVITY/FULLY PUMPED SYSTEM selection
after the main burner has been lit. When the pressure and switch is set. The thermostat is pre-set and no adjustment is
rate are correct replace the brass cover screw on WHITE possible.
RODGERS gas control valve. On the FULLY PUMPED switch position it will operate as a
Shut down the boiler remove the pressure gauge and refit pump over-run thermostat and will keep the pump running
the screw in the test nipple ensuring that a tight seal is after the boiler has shut down, as long as the water
made. temperature within the boiler is above approximately 800C.
Remove the self-adhesive arrow from the inspection ticket On the GRAVITY switch position it will operate in series with
tied to the burner supply pipe and stick it to the Data Plate the boiler thermostat when only the gravity domes-tic hot
inside the controls cover to indicate the appropriate burner water circuit is in operation.
setting pressure. It will over-ride the boiler thermostat when the water
Refit the controls cover. temperature within the boiler is above 800 C.
Relight the boiler and heat the system to maximum. Check Overheat Thermostat
for water leaks, turn the boiler off, drain the system whilst The overheat thermostat is pre-set and no adjustment is
hot. possible. It will require manually resetting if an overheat
Refill the system and on sealed systems adjust to the correct condition occurs. Access to the reset button is through a
cold fill pressure. Set the pressure gauge pointer to the hole in the underside of the controls cover, see FIG. 2.
system design pressure. Other Boiler Controls
If a by-pass circuit is fitted the by-pass valve should be All boiler mounted controls are designed so that if any fault
adjusted with the boiler operating under minimum load should occur they will fail safe. No further setting or checking
conditions to maintain sufficient water flow through the boiler is necessary.
to ensure that the overheat thermostat does not operate External Controls
under normal operating conditions. Check that any other external control connected in the
Pilot Burner system, such as clocks and thermostats, control the boiler as
The pilot is pre-set and no adjustment is required. The pilot required.
flame envelope should cover the electrode tip and spark User’s Instructions
earthing strip see FIG. 30. If the pilot flame is not as A User’s Instructions leaflet is provided with this boiler but
illustrated, remove and clean the pilot as described in the the householder must have the operation of the boiler and
Servicing Instructions Section 3, PILOT BURNER, Page 22. system explained by the Installer. The householder must
Boiler Thermostat also be advised of the importance of annual servicing and of
At its minimum and maximum settings, the thermostat the precautions necessary to prevent damage to the system
should control the water flow temperature at approximately and building, in the event of the system remaining out of
550C—820C (1300F—1800 F). commission in frost conditions.
The thermostat has been calibrated by the makers and no
attempt should be made to re-calibrate it on site. Turn the
thermostat to the ‘0’ position and check that the main burner
shuts down.
COMMISSIONING - Page 20
All parts likely to require servicing are readily accessible. By A. Remove controls cover by opening the door
removing the cover from the boiler controls and removing the covering the securing screw on the underside of the
front door from the boiler, most components are exposed. controls cover, see FIG. 14. Undo securing screw,
Remove the front of the combustion chamber to gain access pull controls cover forward 10mm, lower it to release
to the main and pilot burner and the ignition electrode. it from its four side fixings and pull forward clear of
Removal of the fan and its mounting plate exposes the flue the thermostat knob.
system, i.e. the flue elbow and fluehood. These must be
removed to gain access to the flueways in the heat B. Remove door by undoing the lower fixing screws
exchanger for cleaning. and lift door off the two upper hinge brackets.
The following notes apply to the boiler and its controls but it
should be remembered that attention must also be paid to
the heating circuit itself including radiator
E. Remove the screws securing the fan mounting plate E. Refit the pilot injector to the pilot burner and assemble the
leaving in place the three screws identified with a red pilot to the aluminium tube.
circle or adjacent ‘F’ mark in fan plate.
Remove mounting plate complete with fan. F. Secure the pilot assembly to the main burner using two
hexagonal screws.
F. Disconnect the two flexible tubes from the flue elbow or
adapter. G. Fully tighten the union nut connecting the aluminium tube
to the pilot. Check for gas soundness at this joint by
G. Loosen the two brass securing nuts beneath the flue following the procedure described in the commissioning
elbow outlet and remove the other two. Tilt the flange and section of these instructions, Page 18.
withdraw the elbow. Take care not to damage the gasket.
On vertically flued boilers remove the four brass nuts and H. Ensure that the spark gap is as illustrated in FIG.30
slide the vertical flue adapter up into the flue duct.
H. Unscrew the four nuts and lift off the fluehood taking care
not to damage the rope seal.
Lower and lift out vertical flue adapter.
J. Unplug the electrical supply leads for the gas control valve
from the control box. See FIG. 29.
C. Slide the flue elbow into the flue duct or lower flue adapter A. Check the combustion chamber insulation for damage. If
and secure to the fluehood using four nuts. Ensure that damaged replace as described under replacement.
the gasket between the fluehood and elbow or adapter is
undamaged and a good seal is obtained. 5. MAIN BURNER
D. Reconnect flexible tubes to elbow or adapter. A. Lightly brush any deposits from the top of each blade and
NOTE: Red tube connects the front aluminium tube in the ensure there is no fluff in the entry of the burner venturi. If
upper chamber to the lower connection on elbow or on re-assembly the burner flame picture is incorrect or the
adapter each being identified with a red ring. correct gas rate or burner pressure cannot be obtained,
remove the burner and gas control assembly and
3. PILOT BURNER thoroughly clean the burner. Clean or replace the injector.
In the event of the above procedures not rectifying the
The following operations are only necessary if the pilot flame is flame appearance, disconnect the burner from the gas
distorted or the wrong size, i.e. too small. control valve at the flanged connection and replace the
burner and injector.
A. Unscrew the aluminium pilot tube from the pilot assembly.
Take care not to damage the electrode. B. Refit the burner and gas control valve assembly into the
boiler, ensuring that the locating pin on the rear of burner
B. Unscrew the two hexagonal head screws secur-ing the engages correctly into the rear support bracket. Make sure
pilot (and shield on 80e) to the main burner and remove that the sealing gasket is in place and undamaged
the pilot assembly, be careful that the pilot injector does between the burner flange and the case. Secure the
not fall out during this operation. assembly with two screws.
5. Unscrew the two hexagonal head screws securing the pilot green/yellow wire from earth post
(and shield on 80e) to the main burner and remove the pilot
assembly, be careful that the pilot injector does not fall out 5. Release the control by lifting it from the four retaining lugs.
during this operation.
6. Remove electronic control.
Unscrew electrode retaining nut and withdraw the electrode.
7. Replacement is the reverse of removal.
6. Replacement is the reverse of removal. On re-assembly
ensure that the spark gap is as illustrated in FIG. 30. 8. Follow the full commissioning procedure as detailed in the
COMMISSIONING section of these instruc-tions. Page 18.
7. Follow the full commissioning procedure as detailed in the
COMMISSIONING section of these instruction. Page 18. PRESSURE SWITCH
COMBUSTION CHAMBER INSULATION 4. Remove the screw securing the pressure switch to the bracket
in the control box. Lift pressure switch from bracket.
1. Switch off the external electricity supply by disconnecting the
plug at the socket or switching off the external isolating switch. 5. Disconnect the two plastic tubes. NOTE: the red tube is
connected to the pressure switch connection identified with a
2. Remove main burner as described in ‘Preparing the Boiler for red ring, or adjacent red spot.
Servicing’, operations A, B, C, I, J, K, L, M.
6. Disconnect the three electrical leads, white wire from terminal
3. Bend back retaining tabs and replace insulation. It is necessary No. 1, or NC orange from terminal No. 2 or NO and brown from
to first remove the side insulation when replacing the rear. terminal No. 3 or C. Refer to FIGS 27, 28.
4. Replacement is the reverse of removal. 7. Replacement is the reverse of removal. Ensure that the plastic
tubes are not kinked on re-assembly.
5. Follow the full commissioning procedure as detailed in the
COMMISSIONING section of these instructions. Page 18. 8. Follow the full commissioning procedure as detailed in the
COMMISSIONING section of these instructions. Page 18.
FUSE, ELECTRONIC CONTROL, PRESSURE SWITCH, BOILER
THERMOSTAT, OVERHEAT THERMOSTAT, GRAVITY HOT OVERHEAT THERMOSTAT
WATER/PUMP OVERRUN THERMOSTAT
4. Remove door by undoing the two lower fixing screws and lifting
The following initial operations 1-3 are necessary to remove and door off the two upper hinge brackets.
replace any of the above items.
5. Disconnect the two push on electrical connections from the
1. Switch off the external electricity supply by discon-necting the overheat thermostat terminals.
plug at the socket or switching off the external isolating switch.
6. Remove the nut securing the overheat thermostat to its
2. Remove controls cover by opening the door covering the mounting bracket.
securing screw on the underside of the controls cover see
FIG. 14. Undo securing screw, pull controls cover forward 7. Noting the route taken by the capillary, loosen the plastic screw
10mm, lower it to release it from its four side fixings and pull retaining the thermostat bulb and withdraw bulb from its
forward clear of the thermostat knob. pocket. Remove the split grommet in the base of the boiler,
feed the thermostat capillary and bulb through the hole.
3. Remove control box securing screw and lower control box.
8. Replacement is the reverse of removal. Ensure the rubber
FUSE 1 amp grommet in the base of the boiler makes a good seal around
the capillary. Ensure that the capillary is secure in the clips
4. The fuse is located on the electronic control and can be provided. Refer to FIG. 21.
replaced by lifting it from its holder.
9. Follow the full commissioning procedure as detailed in the
5. Replacement is the reverse of removal. Refer to FIGS. 27, 28. COMMISSIONING section of these instructions. Page 18.
4. Disconnect six way plug, two way plug and electrode lead from 4. Remove door by undoing the two lower fixing screws and lifting
the electronic control. Refer to FIGS. 27, 28. door off the two upper hinge brackets.
Disconnect the flying leads of the electronic control as 5. Disconnect the fan supply leads from the connector adjacent to
follows:— the fan.
7. Disconnect the electrical connections as follows:— 4. Remove door by undoing the lower fixing screws and lifting
door off the two upper hinge brackets.
White from terminal C(3). White from NC(2)
5. Disconnect the electrical connections as follows:—
Refer to FIGS. 27, 28.
2 red wires from terminal NO(4)
8. Pull off the outer thermostat knob.
2 brown wires from terminal NC (2)
9. Remove inner thermostat post by undoing the two securing
screws. 1 white and 1 blue wire from terminal C (3)
10. Remove the nut securing the thermostat to the control box. 6. Remove the screws securing the thermostat to the control box.
11. If the boiler is fitted with a left hand flue, remove the flue elbow 7. Remove the split pin retaining the thermostat bulb in the pocket
as described in Section 1 Preparing the Boiler operations F, G, and withdraw the bulb.
page 22.
8. Remove the split grommet in the base of the boiler. Feed the
12. Remove the clip securing the thermostat bulb to the flow pipe. capillary and bulb through the hole.
13. Remove the split grommet in the base of the boiler and the split 9. Replacement is the reverse of removal. The bulb of the new
grommet in the fan chamber. Feed the capillary and bulb thermostat should be coated with heat conducting paste.
through the holes. Ensure the rubber grommet makes a good seal around the
capillary.
14. Replacement is the reverse of removal. The bulb of the new
thermostat should be coated with heat conducting paste. 10. Ensure that the capillary is secure in the clips provided. Follow
Ensure the rubber grommets in the base of the boiler and the the full commissioning procedure as detailed in the
fan chamber make a good seal around the capillary. COMMISSIONING section of these instructions. Page 18.
Under the Consumer Protection Act 1987 and section 6 of the Health and Safety at Work Act 1974,
we are required to provide information on substances hazardous to health.
Small quantities of adhesives and sealants used in the product are cured and present no known
hazards.
Known Hazards Some people can suffer reddening and itching of the
skin. Fibre entry into the eye will cause foreign body
irritation.
Irritation to respiratory tract.
Thermostat
Back Page