Cable Installation Method Codes
Cable Installation Method Codes
The following table is based around the tables of Appendix 4 of BS 7671:2008 and provides reference
method codes appropriate to a given installation type. For further information on these reference
methods the BS 7671 should be consulted and should greater clarity be required the IET contacted
directly.
Number of
Description Reference Method
cores
Enclosed in conduit in thermally insulating wall Any A
Enclosed in conduit or trunking on a wall Any B
Clipped direct Any C
Direct in ground or in ducting in ground, in or around buildings Any D
In free air or on perforated cable tray Multi-core E
In free air or on perforated cable tray Single-core F or G
4D5 (Twin & Earth) cable above a plasterboard ceiling
Twin & Earth 100
covered by thermal insulation not exceeding 100mm in
4D5 (Twin & Earth) cable above a plasterboard ceiling
Twin & Earth 101
covered by thermal insulation exceeding 100mm in
4D5 (Twin & Earth) cable in a stud wall with thermal
Twin & Earth 102
insulation with cable touching the inner wall surface
4D5 (Twin & Earth) cable in a stud wall with thermal
Twin & Earth 103
insulation with cable not touching the inner wall surface
Methods of Installation
Reference Method A
For example, Installation Methods 1 and 2 of Table 4A2, (non-sheathed cables and multi-core cables in conduit in a thermally
insulated wall).
The wall consists of an outer weatherproof skin, thermal insulation and an inner skin of wood or wood-like material having a
thermal conductance of at least 10 W/m².K. The conduit is fixed such that it is close to, but not necessarily touching the inner
skin. Heat from the cables is assumed to escape through the inner skin only. The conduit can be of metal or plastic.
Reference Method B
For example, Installation Method 4 of Table 4A2, (non-sheathed or sheathed cables in conduit mounted on a wooden or masonry
wall) and B2, item Installation Method 5 of Table 4A2, (multi-core cable in conduit on a wooden wall).
The conduit is mounted on a wooden wall such that the gap between the conduit and the surface is less than 0.3 times the conduit
diameter. The conduit can be metal or plastic. Where the conduit is fixed to a masonry wall the current-carrying capacity of the
non-sheathed or sheathed cable may be higher.
Reference Method C
For example, Installation Method 20 of Table 4A2 (single-core or multi-core cable on a wooden wall).
Cable mounted on a wooden wall so that the gap between the cable and the surface is less than 0.3 times the cable diameter.
Where the cable is fixed to or embedded in a masonry wall the current-carrying capacity may be higher. NOTE: The term
'masonry' is taken to include brickwork, concrete, plaster and similar (but excluding thermally insulating materials).
Reference Method D
For example Installation Method 70 of Table 4A2, (multi-core un-armoured cable in conduit or in ducts in the ground).
The cable is drawn into a 100mm diameter plastic, earthenware or metallic ducts laid in direct contact with soil having a thermal
resistivity of 2.5 K.m/W and at a depth of 0.8 m. The values given for this method are those stated in this Part of BS 7671 and are
based on conservative installation parameters. If the specific installation parameters are known, (thermal resistance of the ground,
ground ambient temperature, cable depth), reference can be made to the cable manufacturer or the ERA 69-30 series of
publications, which may result in a smaller cable size being selected. NOTE: The current-carrying capacity for cables laid in direct
contact with soil having a thermal resistivity of 2.5 K.m/W and at a depth of 0.7 m is approximately 10 % higher than the values
tabulated for Reference method D.