Manual Actuador HoneyWell
Manual Actuador HoneyWell
PRODUCT DATA
SPECIFICATIONS
Supply voltage 24 Vac/dc -15%/+20%, 50/60 Hz
Nominal voltage 24 Vac/dc, 50/60 Hz
Power consumption
MN7505 5 VA / 2 W
MN7510 5 VA / 2 W
Control signal
Modulating (0)2...10 Vdc
Floating/2-Position 24 Vac/dc
Ambient limits
Ambient operating limits -5...+140 °F (20...+60 °C)
Ambient storage limits -22...+176 °F (-30...+80 °C)
Relative humidity 5...95%, non-condensing
Safety
Protection standard IP54
Protection class II as per EN 60730-1
Overvoltage category II
Lifetime
GENERAL Full strokes
Repositions
60000
1.5 million
This non-spring return direct-coupled damper actuator Mounting
provides modulating and floating/2-position control for: Round damper shaft 3/8 in…5/8 in.
• air dampers, Square damper shaft 1/4 in…1/2 in.; 45° steps
• VAV units, Shaft length min. 1-5/8 in.
• air handlers,
• ventilation flaps, End switches (when included)
• louvers, and Rating Class II
• reliable control for air damper applications with up to 10 Triggering points 5° / 85°
sq ft / 44 lb-in. (5 Nm) and 20 sq ft / 88 lb-in. (10 Nm) (seal- Torque rating 44 lb-in. (5Nm) / 88 lb-in. (10Nm)
less damper blades; air friction-dependent).
Runtime for 90°
mod. (dc / 50/60 Hz ac) 90 sec
FEATURES floating (dc / 60 Hz ac)
floating (50 Hz ac)
90 sec
110 sec
• Declutch for manual adjustment Rotation stroke 95° + 3°
• Adjustable mechanical end limits Dimensions see “Dimensions” on page 8
• Removable access cover for direct wiring
Weight (without cables) 1.0 lbs.
• Mountable in any orientation
• Function selection switch for selecting modulating or Noise rating 35 dB(A) max. at 1 m
floating/2-position control
BASIC FEATURES
Fig. 2. Function selection switch
1 Power-Off Behavior
2 If power is removed, the shaft adapter remains in position.
Service/Off
If the function selection switch is set to the “Service/Off”
position, then all rotary movement is cancelled, and all control
Modulating Floating/2-Pos. signals are ignored, thus allowing the actuator to be manually
operated safely.
U(0[2]...10V) 5 5
4 CCW(24V~/+) 4
Y(0[2]...10V) 3 CW(24V~/+) 3
~ 2 ~ 2
3 24v ~/+ 1 1
4 2... 10 V
0...10 V
Floating/2-Position Run Mode
Dir
Service/Off
Rev
5 Without Feedback Signal
10...0 V
10...2 V
6 If, however, the function selection switch has been set to one
of the two floating/2-position control settings - but the actuator
has not been wired for a feedback signal (see Fig. 12 and Fig.
13) - then as soon as operating power is applied, the shaft
M23089 adapter will run according to the control signals applied.
63-2633
EN0B-0545GE51 R0805 2
N05, N10 SERIES DAMPER ACTUATORS FOR MODULATING AND FLOATING CONTROL
Table 1 describes, for the floating mode, the shaft adapter Table 3 describes, for the modulating mode, the shaft adapter
behavior (“stops,” rotates “CCW,” or rotates “CW”) in behavior (“stops,” rotates “totally CCW,” rotates “totally CW,”
dependence upon the control signals applied to terminals 3 runs to “proportional” position, or runs to “50%” of max.
and 4 and upon the function selection switch setting. stroke) in dependence upon the control signals applied to
terminals 3 and 4 and upon the function selection switch
Table 2 describes, for the 2-position mode, the shaft adapter setting.
behavior (“stops,” rotates “CCW,” or rotates “CW”) in
dependence upon the control signals applied to terminals 3
and 4 and upon the function selection switch setting.
between min. control signal plus 0.24 V open proportional -- stop -- proportional
and max. control signal minus 0.24
24 Vac/dc 50% -- stop -- 50%
3 63-2633
EN0B-0545GE51 R0805
N05, N10 SERIES DAMPER ACTUATORS FOR MODULATING AND FLOATING CONTROL
100 95
(BEFORE)
FINAL POSITION OF SHAFT ADAPTER (% OF MAX. STROKE)
100
UPPER DEAD BAND (9.76 TO 10.0 V)
100 NEW POSITION OF UPPER
(% OF MAX.)
(DEGREES)
50 N
TIO
AP
AD
R N
TE O
AF TI
AP NEW POSITION OF LOWER
0 AD
(AFTER) E MECHANICAL END LIMIT
RANGE OF PROPORTIONAL R
ACTUATOR MOVEMENT FO
BE
(0.24 TO 9.76 V)
0 0
LOWER DEAD BAND (0 TO 0.24 V) (BEFORE)
0 CONTROL SIGNAL (V) 10.0
0
M23093
0 0.24 5.0 9.76 10.0
CONTROL SIGNAL (V) M23091
Fig. 5. Adaption (function selection switch set to
0...10 V)
Fig. 3. Final shaft adapter position in dependence upon Adaption will be carried out whenever the actuator is in the
control signal (example function selection switch setting modulating mode or the floating plus feedback mode or the 2-
of 0...10 V) position plus feedback mode and
• the control signal's value rises up into the upper dead band
(i.e. to more than the max. control signal minus 0.24 V) or
drops down into the lower dead band (i.e. to less than the
(% OF MAX. STROKE)
min. control signal plus 0.24 V), after which the shaft
adapter must then remain at the respective (upper or
50 lower) mechanical end limit for at least 3 seconds.
However, in this case, the actuator will then recognize the
position of only the respective (upper or lower) mechanical
end limit.
Overriding
An override is a condition in which a 24 V signal is applied to
0
0 5 10
terminal 4 of an actuator in the modulating mode, thus
FEEDBACK SIGNAL (V) M23092
causing the actuator to ignore the control signal at terminal 3,
whereupon it will instead move to a position of 50% of its
maximum stroke (see Table 3).
Fig. 4. Feedback signal in dependence upon current
position of shaft adapter (example function selection Feedback
switch setting of 0...10 V) If correspondingly wired (see Fig. 10, Fig. 11 and Fig. 12), the
actuator provides, via terminal 5, a feedback signal
Adaption proportional to the actual position of the shaft adapter.
Adaption is a function in which the actuator re-maps its
feedback signal and control signal in accordance with
repositioned mechanical end limits (see also Fig. 6) and thus MANUAL ADJUSTMENT
recognizes their new positions.
IMPORTANT
To prevent equipment damage, you must remove
power or set the function selection switch to the
“Service/Off” position before manual adjustment.
63-2633
EN0B-0545GE51 R0805 4
N05, N10 SERIES DAMPER ACTUATORS FOR MODULATING AND FLOATING CONTROL
Mounting Instructions
All information and steps are included in the Installation
Instructions (Product Literature No. 62-0224) supplied with
each actuator.
Mounting Position
The actuators can be mounted in any position (IP54 is
dependent upon orientation; see Fig. 9). Choose a mounting
position permitting easy access to cables and controls
M23094
After adjusting the mechanical end limits, the user should M23095
trigger adaption (see section “Adaption”).
Fig. 8. Mounting for IP54
INTERNAL END SWITCHES NOTE: Further, in order to guarantee IP54, only original
Honeywell grommets may be used.
The internal end switches “A” and “B” are changeover
switches which are activated when the shaft adapter moves Anti-Rotation Bracket and Screws
past a position of 5° and 85°, respectively (see also Table 5).
If the actuator is to be mounted directly on a damper shaft,
use the anti-rotation bracket and screws included in the
delivery package. The min. distance between the center of the
CHANGEOVER SWITCH A CHANGEOVER SWITCH B damper shaft and the middle of the anti-rotation bracket is
ACTIVATED WHEN SHAFT ACTIVATED WHEN SHAFT
ADAPTER MOVES PAST 5° ADAPTER MOVES PAST 85° 3.35 in.; a max. of 4.25 in. is allowed (see also Fig. 14).
5 63-2633
EN0B-0545GE51 R0805
N05, N10 SERIES DAMPER ACTUATORS FOR MODULATING AND FLOATING CONTROL
CAUTION
FLOATING: DIR
ACTUATOR
To avoid personal injury (electrical shock) and to 1
V
prevent equipment damage, before wiring, you 2
must remove power. 1 24 VAC
2
3 OR +
Access Cover
4 OR N/A
0[2]... 10 V 5 FEEDBACK
2... 10 V
IMPORTANT REQUIRED FOR FEEDBACK USE 0... 10 V
Dir
Once the access cover has been removed, please 1 LINE VOLTAGE POWER SUPPLY. Service/Off
take care to avoid damaging any of the parts now PROVIDE DISCONNECT MEANS AND Rev
accessible. OVERLOAD PROTECTION AS REQUIRED. 10... 0 V
10... 2 V
2 24 VDC SUPPLY ACCEPTABLE.
The access cover can be unscrewed and removed in order to M23098
MN7505, MN7510
TWO-POSITION: DIR
1 ACTUATOR
5
2
3
4
5
1
4
1
2
3 V
1
S2
S1 2
S3 1
S5 24 VAC
S6
2S
1 2
S3
S 3 OR +
S5
S6
4 OR N/A
0[2]... 10 V 5 FEEDBACK
2
REQUIRED FOR FEEDBACK USE 2... 10 V
0... 10 V
Dir
REMOVABLE 1 LINE VOLTAGE POWER SUPPLY. Service/Off
ACCESS COVER PROVIDE DISCONNECT MEANS AND Rev
M23096 OVERLOAD PROTECTION AS REQUIRED. 10... 0 V
10... 2 V
Fig. 9. Access Cover 2 24 VDC SUPPLY ACCEPTABLE.
M23099
4 POS 50%
0[2]... 10 V 5 FEEDBACK
2... 10 V
= OVERRIDE OPTION 0... 10 V S1 S2 S3 S5 S6
Dir
1 LINE VOLTAGE POWER SUPPLY. Service/Off
PROVIDE DISCONNECT MEANS AND Rev M23110
OVERLOAD PROTECTION AS REQUIRED. 10... 0 V
10... 2 V
2 24 VDC SUPPLY ACCEPTABLE. Fig. 13. End switches
M23097
63-2633
EN0B-0545GE51 R0805 6
N05, N10 SERIES DAMPER ACTUATORS FOR MODULATING AND FLOATING CONTROL
mode
NOTE: All cables connected to these terminals must be equipped with spark suppression.
S2, S3 change-over switch A (S1/S2 opens and S1/S3 closes when shaft adapter moves CW past 5°; reverts to
original state when shaft adapter moves CCW past 5°).
S5, S6 change-over switch B (S1/S5 opens and S1/S6 closes when shaft adapter moves CW past 85°; reverts to
original state when shaft adapter moves CCW past 85°).
7 63-2633
EN0B-0545GE51 R0805
N05, N10 SERIES DAMPER ACTUATORS FOR MODULATING AND FLOATING CONTROL
DIMENSIONS
1-5/8
(41)
3-11/32
5-9/32 (85)
(134)
4-1/4
(108)