EN 50600 Standards For Data Centres - and Their International Implementation

The document discusses EN 50600 standards for data centres and their international implementation. It provides information on Mike Gilmore's involvement in establishing standards through various committees. It also references documents from the CEN-CENELEC-ETSI Coordination Group on Green Data Centres that map standardization demands and provide definitions for data centres in a sustainable manner.

Uploaded by

Gustavo Pires
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
196 views14 pages

EN 50600 Standards For Data Centres - and Their International Implementation

The document discusses EN 50600 standards for data centres and their international implementation. It provides information on Mike Gilmore's involvement in establishing standards through various committees. It also references documents from the CEN-CENELEC-ETSI Coordination Group on Green Data Centres that map standardization demands and provide definitions for data centres in a sustainable manner.

Uploaded by

Gustavo Pires
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 14

EN 50600 standards

for data centres


-
and their
international
implementation

EN 50600 standards for data centres


-
and their international implementation

Mike Gilmore, e-Ready Building Limited

Layer One
Greece

6th October 2017

www.it-cabling.com www.e-readybuilding.com
© 2017 e-Ready Building Limited P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721
Mike Gilmore
Standards Activities
EN 50600 standards
for data centres Member
- JTC1 SC25 WG3: “Generic Cabling”
and their
international Member
implementation JTC1 SC39: “Sustainability by and for IT”
Data centres - Design and Resource Efficiency KPIs

Chairman
TC215
Electrotechnical Aspects of Telecommunication Equipment
Convenor
TC215 WG1: Cabling design
Meeting Secretary
Mike Gilmore, FIET
TC215 WG2: Cabling installation - QA and installation practices
Member
Managing Director
TC215 WG3: Facilities and infrastructures (data centres)
e-Ready Building Limited
Member
CEN/CLC/ETSI CG Green Data Centres
Mobile:
+44 (0)786 011 0563 Past-Chairman
e-mail: TCT/7: Telecommunications - Installation Requirements
mike.gilmore Chairman
@ TCT/7/1: Cabling: Infrastructure design, planning and commissioning
e-readybuilding.com Meeting Secretary
TCT/7/2: Cabling; Installation and UK implementation
FIA e-mail: TCT/7/3: Facilities and infrastructures
[email protected]
Layer One
Greece Fibreoptic Industry Association Director
www.fia-online.co.uk standards@fia
6th October 2017

www.it-cabling.com www.e-readybuilding.com
© 2017 e-Ready Building Limited P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721
The Green Data Centre Coordination Group
CEN CENELEC (CLC) ETSI
EN 50600 standards European Committee European Committee European
for Standardization for Electrotechnical Telecommunications
for data centres Standardization Standardis Insitute
-
and their
international
implementation CEN-CENELEC-ETSI
CO-ORDINATION GROUP
GREEN DATA CENTRES

STATUS REPORT
An in-depth mapping of the
standardisation demands of
energy efficient and sustainable
data centres
BROCHURE
Primary objectives:
A “laymans” guide to
• provide basic definitions
the standardisation
• differentiate types of deliverable
• product, design, operation actions to support the
• define topic boundaries delivery of energy
• map existing deliverables efficient and sustainable
• identify opportunities data centres
• minimise duplication
• within ESOs and ISO/IEC

updated Q4 2017 updated Q4 2017


Layer One
Greece
ftp://ftp.cencenelec.eu/EN/EuropeanStandardization/HotTopics/ICT/GreenDataCentres/GDC_landscape_Ed4(2017).pdf

6th October 2017


ftp://ftp.cencenelec.eu/EN/EuropeanStandardization/HotTopics/ICT/GreenDataCentres/GDC_Brochure_Ed4(2017).pdf

www.it-cabling.com www.e-readybuilding.com
© 2017 e-Ready Building Limited P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721
What is a Data Centre?

COMMON DEFINITION IN EUROPE AND INTERNATIONAL STANDARDS


EN 50600 standards
for data centres structure, or group of structures, dedicated to the centralized accommodation, interconnection and
- operation of information technology and network telecommunications equipment providing data
and their storage, processing and transport services together with all the facilities and infrastructures for
international power distribution and environmental control together with the necessary levels of resilience and
implementation security required to provide the desired service availability.
Note: a structure can consist of multiple buildings and/or spaces with specific functions to support the primary function.
Note: the boundaries of the structure or space considered the data centre which includes the information and communication
technology equipment and supporting environmental controls can be defined within a larger structure or building.

Data

Data Data
Data

not restricted to
allows data centres inside other types of premises
dedicated premises
not restricted to buildings allows caves, containers etc.

no size discrimination “comms rooms” to multi-floor “football fields”

Layer One
Greece

6th October 2017

www.it-cabling.com www.e-readybuilding.com
© 2017 e-Ready Building Limited P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721
Data Centre Standardisation - CENELEC

EN 50600 standards 50600 SERIES - STANDARDS AND TECHNICAL REPORTS


for data centres
- Information technology - Data centre facilities and infrastructures
and their
international
implementation EN 50600-1:2012 General concepts EN 50600-1:2018

DESIGN

EN 50600-2-1:2014 Building construction EN 50600-2-1:2019

EN 50600-2-2:2014 Power supply EN 50600-2-2:2018

EN 50600-2-3:2014 Environmental control EN 50600-2-2:2018

EN 50600-2-4:2014 Telecommunications cabling

EN 50600-2-5:2016 Security systems

OPERATION

EN 50600-3-1:2016 Management and operational information

RESOURCE EFFICIENCY KPIs

EN 50600-4-1:2016 General requirements EN 50600-4-1 A1:2018

EN 50600-4-2:2016 Power Usage Effectiveness (PUE) EN 50600-4-2 A1:2019


Layer One
Greece EN 50600-4-3:2016 Renewable Energy Factor (REF) EN 50600-4-3 A1:2019

6th October 2017

www.it-cabling.com www.e-readybuilding.com
© 2017 e-Ready Building Limited P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721
Data Centre Standardisation - CENELEC

EN 50600 standards 50600 SERIES - STANDARDS AND TECHNICAL REPORTS


for data centres
- Information technology - Data centre facilities and infrastructures
and their
international
implementation CLC/TR 50600-99-1 Energy management - Recommended practices Annual update

“Best Practices” V8.1 (2017)


(annual update)

CLC/TR 50600-99-2 Sustainability - Recommended practices 2019

CLC/TR 50600-99-3 Guidance to the application of EN 50600 Series 2019

Layer One
Greece

6th October 2017

www.it-cabling.com www.e-readybuilding.com
© 2017 e-Ready Building Limited P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721
Data Centre Certification

EN 50600 standards EN 50600-1:2012


for data centres
- EN 50600-2-1:2014
and their Interest has grown exponentlally
international EN 50600-2-2:2014 since the document set was completed
implementation
EN 50600-2-3:2014 Certain 3rd Party organisations wished to
“certify”
EN 50600-2-4:2014
data centres
EN 50600-2-5:2016 against EN 50600

EN 50600-3-1:2016

3rd PARTY CERTIFICATION


3rd Party certifiers have to prove that they fulfil the conditions of the EN ISO/IEC 17065 - which
requires those bodies to undergo an assessment carried out by an accreditation body. This
assessment includes inter alia the proof of neutrality, competence, impartiality etc.

Standards bodies are not in a position to judge whether or not an organization offering
certification meets the underlying requirements - that is the role of accreditation specialists.

Some standards such as ISO 9001 and ISO 27001 are written specifically to enable a formal
certification by a 3rd Party body.

Standards in the EN 50600 series do not define the appropriate procedure, leaving this to bilateral
Layer One
contracts or even national or regional legislation to define a process of certification.
Greece
At the time of writing no such process has been defined and there are no accreditation bodies
6th October 2017
associated within standard.

www.it-cabling.com www.e-readybuilding.com
© 2017 e-Ready Building Limited P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721
Why CLC/TR 50600-99-3?

WHAT CAN BE CERTIFIED?


EN 50600 standards
for data centres
- An organization under a general design process certification (e.g. ISO 9000), who uses EN 50600
and their as a tool when designing data centres (i.e. the designer is applying the design process correctly)
international
implementation

A data centre “owner” under a systems management process (e.g. ISO 27000), who uses EN
50600-3-1 in a management process.

WHAT CANNOT BE CERTIFIED?

The design or operation of a data centre according to EN 50600 series standards

CLC/TR 50600-99-3 Guidance to the application of EN 50600 Series 2019

EN 50600-99-3 summarises what the key requirements of


the EN 50600 standards are
and how to “conform” to EN 50600
Layer One
Greece

6th October 2017

www.it-cabling.com www.e-readybuilding.com
© 2017 e-Ready Building Limited P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721
Data Centre Design Standardisation

EN 50600 standards Information technology - Data centre facilities and infrastructures -


EN 50600-1
for data centres General requirements
-
and their Business impact analysis
international AND
implementation risk analysis

Energy efficiency
Availability Physical security
enablement

Class 1 Zone 1 Level 1


Class 2 Zone 2 Level 2
Class 3 Zone 3 Level 3
Class 4 Zone 4

Protection against
• unauthorised access
• internal fire
• other internal environmental events
• external environmental events

Layer One
Greece
EN 50600-2-x Design standards
6th October 2017

www.it-cabling.com www.e-readybuilding.com
© 2017 e-Ready Building Limited P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721
International Relationships - Status

EN 50600 standards CLC TC215 WG3 ISO/IEC JTC1 SC39 WG1 AND WG3
for data centres
-
and their
international
implementation EN 50600-1:2012 General concepts ISO/IEC TS 22237-1: 2019

DESIGN

EN 50600-2-1:2014 Building construction ISO/IEC TS 22237-2: 2019

EN 50600-2-2:2014 Power supply ISO/IEC TS 22237-3: 2019

EN 50600-2-3:2014 Environmental control ISO/IEC TS 22237-4: 2019

EN 50600-2-4:2014 Telecommunications cabling ISO/IEC TS 22237-5: 2019

EN 50600-2-5:2016 Security systems ISO/IEC TS 22237-6: 2019

OPERATION

EN 50600-3-1:2016 Management and operational information ISO/IEC TS 22237-7: 2019

The ISO/IEC TS documents will migrate to ISO/IEC full standards

This will begin an iterative process in Europe alos


Layer One
Greece

6th October 2017

www.it-cabling.com www.e-readybuilding.com
© 2017 e-Ready Building Limited P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721
Key Performance Indicators

TECHNICAL KPIs
EN 50600 standards
for data centres ... assessing energy consumption for a number of specific operating conditions and also across a
- combination of such operating conditions
and their
international Assuming those operating conditions reflect the probable operating environment .. a customer may
implementation make valued judgements in relation to the appropriateness of the Technical KPI

For example, a design of power supply that is more task efficient under high load conditions may be
inappropriate for users who plan to predominantly operate under low load conditions (and vice versa)

OBJECTIVE KPIs
... relate to specific elements of energy management for operational infrastructures including:
energy consumption, task efficiency, energy re-use and renewable energy

... define requirements for the measurement of operational infrastructures i.e. taking into account the
real operating conditions over a defined period of time

GLOBAL KPIs

Objective KPIs... may be combined using a formula appropriate to the specific operational
infrastructure to produce one or more Global operational KPIs which reflects the overall performance
of the operational infrastructures against wider energy management targets
...which may be self-imposed by the operators or externally applied by legislators

Layer One
Greece

6th October 2017

www.it-cabling.com www.e-readybuilding.com
© 2017 e-Ready Building Limited P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721
International Relationships - KPIs

EN 50600 standards CLC TC215 WG3 ISO/IEC JTC1 SC39 WG1 AND WG3
for data centres
- Defining measurement methods - NOT performance requirements
and their
international Influenced by design and operation of data centres
implementation -
but not linked to any standards for design or operation

DATA CENTRE RESOURCE EFFICIENCY KPIs

ISO/IEC 30134-1:2016 General requirements EN 50600-4-1:2016

ISO/IEC 30134-2:2016 Power Usage Effectiveness (PUE) EN 50600-4-2:2016

ISO/IEC 30134-3:2016 Renewable Energy Factor (REF) EN 50600-4-3:2016

ISO/IEC 30134-6:2019 Energy Reuse Factor (ERF) EN 50600-4-6:2019

Impact of ISO 52000 standards for energy


ISO/IEC TR 21897
performance of buildings

ISO/IEC TR 21587 Data Centres - Excess Electrical Energy

SERVER EQUIPMENT KPIs

IT Equipment Energy Efficiency for servers


ISO/IEC 30134-4:2019 EN 50600-4-4:2019
(ITEEsv)

Layer One IT Equipment Energy Utilization for servers


ISO/IEC 30134-5:2019 EN 50600-4-5:2019
Greece (ITEUsv)

6th October 2017 ISO/IEC TR 21836 Server Energy Effectiveness Metric

www.it-cabling.com www.e-readybuilding.com
© 2017 e-Ready Building Limited P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721
Summary

EN 50600 standards
CENELEC TC215
for data centres
- committed to priducing an integrated set of documents
and their (both European Norms and Techncial Reports)
international for the
implementation DESIGN, OPERATION AND RESOURCE EFFICIENCY OF
all types and scales of
DATA CENTRES

50600 SERIES
CONFORMANCE
-
NOT CERTIFICATION

Success leading to international acceptance

EN and ISO/IEC will harmonise by continuous iteration

KEEP TRACK OF DEVELOPMENTS

GREEN DATA CENTRE BROCHURE


Layer One
Greece

6th October 2017

www.it-cabling.com www.e-readybuilding.com
© 2017 e-Ready Building Limited P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721
Close

EN 50600 standards
for data centres
-
and their
international
implementation
EN 50600 standards for data centres
-
and their international implementation

Mike Gilmore, e-Ready Building Limited

Layer One
Greece

6th October 2017

www.it-cabling.com www.e-readybuilding.com