22CC1143-C-022 Rev. 00 PVC Conduits & Fittings
22CC1143-C-022 Rev. 00 PVC Conduits & Fittings
LOTAM
25 /11/2023
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
ISAM M. KHAIRY KABBANI & National Marketing Est. Type DB, EB, and EPC-40-PVC Type tests PQ Letter:
INSULATION FACTORY COMPANY Co. Ltd. Conduits (NAMCODUCT) conducted at ACES Based on S&SD letter #MPQ4561946-Class IV(b)
Saudi Arabia P. O. Box 16375, Jeddah (Arab Company for -2018_Class I(b) dated April 05, 2022, ISAM M.
21464. Kingdom of Saudi Laboratories & Soil), KHAIRY KABBANI & INSULATION FACTORY
Plant -Dammam 2nd industrial City Arabia. Jeddah, Saudi COMPANY – is pre-qualified for PVC Conduits
0 50 365 1754 Arabia dated August and Fittings for underground Cables as
Street No 95, 7202- Unit No. 3520, Ad [email protected] 19, August 21, conforming to National Grid SA specification
Dammam 34332-2770 m October 19 and 23-TMSS-01, Rev.01, with the following
November 17, 2021 conditions:
Dammam
WARRANTY:
Contact Person - MR. Omar Al-Sasa, Ten (10) year Extended Warranty as confirmed,
Mr. Mahmoud Awwad/ through letter # Nil, dated 06/03/2022 shall be
Phone - +966 138342544,+966 13 892 applicable for all supplies made by M/S ISAM M.
3543 KHAIRY KABBANI & INSULATION FACTORY
Email ID - COMPANY, DAMMAM, KSA
[email protected]
Contact Person Email ID -
[email protected],
[email protected]
Website - www.ikkgroup.com
6. 3 Page 1 of 2
Connection of Al-Nazeem S/S 8271 with 132kv Network in Riyadh City
PTS#22CC1143 & Contract Number:. 4400019349
EPC-40-PVC
8"= 200mm
8.18mm
TDP
RIYADH, KSA
04/12/2023
National Marketing Est. Co. Ltd. www.namat.com
Mechanical Properties
PSI 7,000
Tensile Strength D - 638 / type1
MPA > 48.0
PSI 500,000
Modulus of Elasticity in Tension D - 639 / type1
MPA >3447.0
PSI 14,500
Flexural Strength D - 790 proc. B
MPA 93
Izod Impact D - 256 Ft-Lbs / In of notch 0.65
Hardness (Rockwell) D - 785 Rockwell "R" 119
Thermal Properties
D - 696 in/in/°F 3.0X10-5
Coefficient of Thermal Linear Expansion
D - 696 mm/mm/°C 5.4X10-5
Vicat Softening Point D - 1525 (Rate A) °C > 80
Heat Deflection D - 648 (264 psi) °C (°F) > 70 (158)
Electrical Properties
Dielectric Strength D - 150 Volts/Mil 1413
Dielectric Constant D - 150 60cps at 30 °C 3.7
Volume Resistivity D - 257 Ohm/cm at 95 °C 1.2 X 1012
Flammability Properties
Flammability rating UL - 94/0.062 Rating V-0
Flame Spread ASTM E84 10
Smoke Developed ASTM E84 250
Limiting Oxygen Index UL 94 43%
Burning Rate Self Extinguishing
2
NAMCODUCT®
Conduits, tubings & Ducts
SASO & british standard
SASO GSO IEC 61386-21/2014 & bs-en-61386 pipes Table 02
NAMCODUCT® Conduits are offered in 2.9 meters long and black/ white color
Note: Previously BS6099
AMERICAN STANDARD
nema tc-2
Electrical Plastic Tubing (EPT) & Conduit (EPC-40 & EPC-80)
Dimensions of Electrical Plastic Tubing
Table 03
EPT-A-PVC EPC-40-PVC EPC-80-PVC
Trade Metric Outside
Size Size Diameter Min. Wall Min. Inside Min. Wall Min. Inside Min.Wall Min. Inside
Thickness Diameter Thickness Diameter Thickness Diameter
inch mm inch mm mm mm mm mm mm mm
The above table confirms to SEC Specification 23 - TMSS 01 Table 03 (EPC 40).
EPT-A-PVC Electrical Plastic Tubing for encasement in concrete, EPC 40 Electrical Plastic Conduit for normal duty
application & EPC 80 Electrical Plastic Conduit for heavy-duty application
Note: Pipe Length: Standard 3 / 6 meters
www.namat.com 3
Connection of Al-Nazeem S/S 8271 with 132kv Network in Riyadh City
PTS#22CC1143 & Contract Number:. 4400019349
compliance Statement
Project Title: Connection of Al-Nazeem S/S 8271 with 132kv Network in Riyadh City.
Contract No: 4400019349
22CC1143
TDP
RIYADH, KSA
TDP
RIYADH, KSA
EPC-40-PVC
6"= 155mm
7.11mm
TDP
RIYADH, KSA
04/12/2023
National Marketing Est. Co. Ltd. www.namat.com
Mechanical Properties
PSI 7,000
Tensile Strength D - 638 / type1
MPA > 48.0
PSI 500,000
Modulus of Elasticity in Tension D - 639 / type1
MPA >3447.0
PSI 14,500
Flexural Strength D - 790 proc. B
MPA 93
Izod Impact D - 256 Ft-Lbs / In of notch 0.65
Hardness (Rockwell) D - 785 Rockwell "R" 119
Thermal Properties
D - 696 in/in/°F 3.0X10-5
Coefficient of Thermal Linear Expansion
D - 696 mm/mm/°C 5.4X10-5
Vicat Softening Point D - 1525 (Rate A) °C > 80
Heat Deflection D - 648 (264 psi) °C (°F) > 70 (158)
Electrical Properties
Dielectric Strength D - 150 Volts/Mil 1413
Dielectric Constant D - 150 60cps at 30 °C 3.7
Volume Resistivity D - 257 Ohm/cm at 95 °C 1.2 X 1012
Flammability Properties
Flammability rating UL - 94/0.062 Rating V-0
Flame Spread ASTM E84 10
Smoke Developed ASTM E84 250
Limiting Oxygen Index UL 94 43%
Burning Rate Self Extinguishing
2
NAMCODUCT®
Conduits, tubings & Ducts
SASO & british standard
SASO GSO IEC 61386-21/2014 & bs-en-61386 pipes Table 02
NAMCODUCT® Conduits are offered in 2.9 meters long and black/ white color
Note: Previously BS6099
AMERICAN STANDARD
nema tc-2
Electrical Plastic Tubing (EPT) & Conduit (EPC-40 & EPC-80)
Dimensions of Electrical Plastic Tubing
Table 03
EPT-A-PVC EPC-40-PVC EPC-80-PVC
Trade Metric Outside
Size Size Diameter Min. Wall Min. Inside Min. Wall Min. Inside Min.Wall Min. Inside
Thickness Diameter Thickness Diameter Thickness Diameter
inch mm inch mm mm mm mm mm mm mm
The above table confirms to SEC Specification 23 - TMSS 01 Table 03 (EPC 40).
EPT-A-PVC Electrical Plastic Tubing for encasement in concrete, EPC 40 Electrical Plastic Conduit for normal duty
application & EPC 80 Electrical Plastic Conduit for heavy-duty application
Note: Pipe Length: Standard 3 / 6 meters
www.namat.com 3
Connection of Al-Nazeem S/S 8271 with 132kv Network in Riyadh City
PTS#22CC1143 & Contract Number:. 4400019349
compliance Statement
Project Title: Connection of Al-Nazeem S/S 8271 with 132kv Network in Riyadh City.
Contract No: 4400019349
22CC1143
TDP
RIYADH, KSA
TDP
RIYADH, KSA
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
:DWHU6ZHOODEOH7DSHV%HWZHHQ
Water blocking material between strands * 6WUDQGV/D\HUV
Semi-Conducting 6HPL&RQGXFWLQJ
Conductor Moisture Impervious layer Material Tape 7DSH
Average thickness, mm
1200, 2000, 2500 mm² 1.50
Minimum thickness, mm
1200, 2000, 2500 mm² 1.35
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
4.3.3 Insulation:
SUPER CLEAN 683(5&/($1
Material XLPE ;/3(
Nominal thickness, mm 18.0
Minimum thickness, mm 16.2
Diameter over insulation, mm *
Thermal resistivity, K.m/W *
Relative permittivity or
*
dielectric constant (ε)
Loss factor (δ ) *
Specific Resistance, MΩ-km
*
(Actual Test Value)
68%-(&772$0$18)$&785,1*72/(5(1&(2)>PP@
.
[PPð&8;/3(/$7+'3(132N9&DEOH
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
4.3.7 Jacket:
Material HDPE +'3(
Nominal thickness, mm 4.50
Minimum thickness, mm 4.05
Overall cable diameter, mm * (Approximate)
6.0 PACKING
a. Total quantity required, m As per B.O.Q.
b. Are matched sets of cable reel length
required? Please refer to our Commercial offer.
b. If "YES", how many reels are
required per set? Please refer to our Commercial offer.
c. Tolerance in cable length of
matched reel sets Please refer to our Commercial offer.
e. Conductor weight, kg/km * (Approximate)
f. Cable weight, kg/km * (Approximate)
g. Reel and cable weight, kg * (Approximate)
h. Cable length per reel, m * ц5%
i. Cable reel diameter, mm * (Approximate)
j. Cable reel width, mm * (Approximate)
.
[PPð&8;/3(/$7+'3(132N9&DEOH
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
* Based on the standard trench of a single circuit in flat formation in a backfill duct bank at 1.45 m depth with 400 mm
axial phase spacing, 40 ºC soil temperature, 2 ºC.m/W soil thermal resistivity (dry value), 1.2 ºC.m/W thermal backfill
resistivity (dry value) and cross bonded system.
Official Seal/Stamp
of the Company & Date
.
PROJECT TITLE : CONNECTION OF AL NAZEEM S/S 8271, with 132kV /
1200mm2 Network, In Riyadh City.
CONTRACT NO.: 4400019349 PTS NO.: 22CC1143
TABLE OF CONTENTS
1.0 SCOPE
4.1 General
4.2 Design Criteria
4.3 Rating
4.4 Material
4.5 Fabrication
4.6 Dimensions and Sizes
5.0 MARKINGS
6.0 TESTS
LIST OF FIGURES
2. Straight Couplings
3. 5-Degree Couplings
4. 5-Degree Bends/Elbows
7. Bell-End Coupling
8. Fitting Plugs
1.0 SCOPE
2.0 CROSS-REFERENCES
This Material Standard Specification shall be read in conjunction with the latest revision of
National Grid Saudi Arabia General Specification No. 01-TMSS-01, titled "General
Requirements for All Transmission Equipment/Materials" which shall be considered as an
integral part of this TMSS.
This TMSS shall also be read in conjunction with National Grid Saudi Arabia Purchase
Order or Contract Schedules for project, as applicable.
The latest amendments/revision of the following Code and Standard shall be applicable for
the equipment/material covered in this TMSS. In case of conflict, the vendor/manufacturer
may propose equipment/material conforming to Industry Code and Standard other than that
quoted hereunder without jeopardizing the requirements of this TMSS.
3.1 ASTM D1784 Standard Specification for Rigid Poly (Vinyl Chloride)
(PVC) Compounds and Chlorinated Poly (Vinyl Chloride
(CPVC) Compounds
3.2 ASTM D2564 Standard Specification for Solvent Cements for Poly Vinyl
Chloride (PVC) Plastic Piping Systems.
3.3 ASTM D4396 Standard Specification for Rigid Poly (Vinyl Chloride) (PVC)
and Chlorinated Poly (Vinyl Chloride) (CPVC) Compounds
for Plastic Pipe and Fittings Used in Non-pressure
Applications.
3.4 ASTM F402 Standard Practice for Safe Handling of Solvent Cements,
Primers, and Cleaners Used for Joining Thermoplastic Pipe
and Fittings.
3.5 ASTM F656 Standard Specification for Primers for Use in Solvent
Cements Joints of Poly(Vinyl Chloride) (PVC) Plastic Pipe
and Fittings.
3.7 NEMA TC 3 Polyvinyl Chloride (PVC) Fittings for Use with Rigid PVC
Conduit and Tubing.
3.8 NEMA TC 6 and 8 Polyvinyl Chloride (PVC) Plastic Utilities for Underground
Installations.
3.9 NEMA TC 9 Fittings for Polyvinyl Chloride (PVC) Plastic Utilities Duct
for Underground Installation.
3.10 UL 651 UL Standard for Safety Schedule 40, 80, Type EB and A
Rigid PVC Conduit and Fittings
4.1 General
4.1.1 The PVC conduits and fittings shall be of manufacturer’s standard design and
shall meet or exceed the requirements of this specification in all respects.
4.2.1 A maximum soil ambient temperature of 40ºC shall be regarded as the basic
temperature with service conditions referenced in 01-TMSS-01.
4.2.2 The types of extra-strength rigid plastic utility duct for installation of
underground communication and electrical wire and cable shall be as
follows:
a. Type DB: PVC conduit and fitting designed for direct burial in
underground trenches without requirement for
encasement in concrete.
b. Type EB: PVC conduit and fitting designed for encased burial
in concrete inside or outside buildings and substations.
4.3 Rating
4.3.1 Rated voltage of the power cables shall be 69 kV, 110 kV, 115 kV, 132 kV,
230 kV or 380 kV.
4.3.2 PVC conduits and fittings shall withstand the continuous operating
temperature of the power cables at 90ºC as per UL 651.
4.3.3 PVC conduits and fittings shall withstand the maximum emergency
conductor overloading temperature mentioned in National Grid Saudi Arabia
material specification # 11-TMSS-02, Rev.01 clause# 4.2.3 (for 1500 hours
during the life of cable).
4.3.4 PVC conduits and fittings rating data shall be as specified in Table 1 and 2,
respectively.
4.4 Material
4.4.1 Plastic conduits shall be made from rigid PVC plastic compound that meets
the minimum cell classification of PVC 12154 as defined in ASTM D4396
and shown in Table 1.
4.4.5 Joints
Joints shall be made with either fittings or integral belled ends. The
PVC solvent-cemented type joining system shall be used.
4.5 Fabrication
4.5.1 PVC plastic conduits and fittings shall be homogeneous throughout and free
from visible cracks, holes , burrs, foreign inclusion, or other defects
that could damage insulated wires or cables.
4.5.2 Overall PVC conduit length including the integral bell or coupling shall
be 6.10m ± 0.03m or (20ft ± 1in).
4.5.3 Dimensions of conduits shall be as per clause 4.6 and dimensions of fittings
shall be as per attached figures 2 to 11 and tables 7 to 24.
4.6.1 The dimensions of each size of conduit shall be in accordance with Tables
3 (as per NEMA TC 2) and Table 4 (as per NEMA TC 6 & 8).
4.6.2 The PVC conduits may have belled ends. Dimension of integral belled-
ends or integral couplings of each size of conduit shall be in accordance
with the Table 5 (as per NEMA TC 2) for EPC-40-PVC type and Table
6 (as per NEMA TC 6 & 8) for EB and DB types. Figure 1 shows the
integral belled- end conduit.
4.6.3 Except for trade sizes, all dimensions in Tables 1 to 25 are in millimeters.
B
A
C
Figure 1: Integral Belled-End Conduits
5.0 MARKINGS
5.1 All required markings shall be legible and so applied as to remain legible
under handling and installation practices.
5.2 The PVC conduit and fitting shall be marked with the following:
5.3 Each shipping box shall be printed with the following information:
6.0 TESTS
All test results shall be provided for review and acceptance by National Grid Saudi Arabia.
6.1 The PVC plastic conduits and fittings shall be tested in accordance with NEMA
or equivalent Standards referenced to in this specification.
6.2 Deflection resistance test for EPC-40-PVC Conduit shall be made according to
NEMA TC 2 Table 4-1.
6.3 Impact resistance test for EPC-40-PVC Conduit shall be made according to NEMA
TC 2 Table 4-2 and for EB & DB PVC Conduit shall be made as per NEMA TC 6 &
8 Table 4-1.
6.4 Duct Stiffness test for EB & DB PVC Conduit shall be made according to
NEMA TC 6 & 8 Table 4-2.
6.5 The PVC plastic conduit shall be tested as per UL 651 for 90ºC continuous
operation.
6.6 Resistance to Specific Reagents shall be made for PVC plastic conduits according
to UL 651 Clause 17.
N C
Figure 2 : Straight Couplings
C E
Socket Depth (mm) Wall N
Trade size Metric Thickness Minimum
(inch) designators Maximum Minimum Minimum1 (mm)
(mm)
¾ 21 38.10 18.26 2.41 2.38
1 27 47.62 22.22 2.54 2.38
1¼ 35 50.80 23.83 3.05 2.38
1½ 41 50.80 26.97 3.05 2.38
2 53 50.80 28.58 3.30 2.38
2½ 63 76.20 37.31 4.19 4.76
3 78 79.38 40.49 5.49 4.76
3½ 91 82.55 42.85 5.74 4.76
4 103 85.73 44.45 6.02 4.76
5 129 92.08 49.20 6.55 4.76
6 155 95.25 53.96 7.11 6.35
8 200 165.10 123.83 - -
1
Minimum wall thickness indicated shall be applicable at any point of socket.
C
Trade size Metric M N
(inch) designators Socket Depth Maximum Minimum
Minimum (mm) (mm)
(mm)
2 53 44.45 69.5 2.4
3 78 73.03 100.8 2.8
3½ 91 79.38 114.3 2.8
4 103 85.73 127.8 2.8
5 129 101.60 158.8 3.6
6 155 127.00 190.5 3.6
5º
C
Figure 3: 5-Degree Couplings
Table 9: Dimensions for EPC-40-PVC type 5-degree couplings
C E
Socket Depth (mm) Wall N
Trade size Metric Thickness Minimum
(inch) designators Minimum 1 (mm)
Maximum Minimum
(mm)
¾ 21 38.10 18.26 2.41 2.38
1 27 47.62 22.22 2.54 2.38
1¼ 35 50.80 23.83 3.05 2.38
1½ 41 50.80 26.97 3.05 2.38
2 53 50.80 28.58 3.30 2.38
2½ 63 76.20 37.31 4.19 4.76
3 78 79.38 40.49 5.49 4.76
3½ 91 82.55 42.85 5.74 4.76
4 103 85.73 44.45 6.02 4.76
5 129 92.08 49.20 6.55 4.76
6 155 95.25 53.96 7.11 6.35
1Minimum
8 wall thickness indicated shall be applicable at any point of socket. -
200 165.10 123.83 -
M R
C
N C
M D B A
M X
N C
F B A M
Trade Socket Inside Diameter at Entrance Socket Inside Diameter at Bottom Wall Throat Diameter
Socket Depth (mm) thickn
Size (mm) (mm) (mm)
1
(Inch) Average Average -ess
Tolerance Max. Min. Tolerance Max. Min. Max. Min. (mm) Max. Min.
¾ 27.03 ± 0.10 27.28 26.77 26.57 ± 0.10 26.82 26.31 38.10 18.26 2.41 20.93 18.85
1 33.78 ± 0.13 34.04 33.53 33.27 ± 0.13 33.53 33.02 47.62 22.22 2.54 26.64 23.98
1¼ 42.60 ± 0.13 42.90 42.30 42.04 ± 0.13 42.34 41.73 50.80 23.83 3.05 35.05 31.55
1½ 48.72 ± 0.15 49.02 48.41 48.11 ± 0.15 48.41 47.80 50.80 26.97 3.05 40.89 36.80
2 60.78 ± 0.15 61.09 60.48 60.17± 0.15 60.48 59.87 50.80 28.58 3.30 52.50 47.24
2½ 73.41 ± 0.18 73.79 73.02 72.85 ± 0.18 73.23 72.47 76.20 37.31 4.19 62.71 56.44
3 89.28 ± 0.20 89.66 88.90 88.70 ± 0.20 89.08 88.32 79.38 40.49 5.49 77.92 70.13
3½ 101.96 ± 0.20 103.25 100.71 101.40±0.20 101.78 101.02 82.55 42.85 5.74 90.12 81.10
4 114.88 ± 0.23 115.95 113.41 114.07 ±0.23 114.45 113.70 85.73 44.45 6.02 102.26 92.02
5 142.06±0.25 143.33 140.80 141.05±0.25 141.80 140.38 92.08 49.20 6.55 128.19 115.37
6 169.11±0.28 170.38 167.84 168.00±0.28 168.76 167.23 95.25 53.98 7.11 154.05 138.63
8 220.22 ± 0.38 221.62 218.82 218.69 ± 0.38 220.09 217.68 165.10 123.83 - - -
1
Minimum wall thickness indicated shall be applicable at any point of socket.
N C
B A M
N C
M B A
1 27 33.401 20 100
List of Materials
National Marketing Est. Co. Ltd.
شركة المؤسسة الوطنية للتسويق المحدودة
Letter of Recommendation
We are pleased to inform you that your organization has successfully completed the
Certification audit for the below scope:
The issuance of the certificate will take six weeks from the date of this recommendation
letter.
I take this opportunity to congratulate you and members of your team for this achievement.
Should you need more information, please do not hesitate to contact the undersigned.
Best regards
Muhammad Haris
Operations & Technical Manager - Certification
BUREAU VERITAS
P.O. Box 20189 | Al-Khobar 31952 | Kingdom of Saudi Arabia.
Tel. : +966 (13) 8821071 , Ext - 129 | Fax : +966 (13) 8821072| Mobile: +966 55 988 3982
Email : [email protected] | Web : http://www.bureauveritas.com
Connection of Al-Nazeem S/S 8271 with 132kv Network in Riyadh City
PTS#22CC1143 & Contract Number:. 4400019349
Certificate of Conformance
Connection of Al-Nazeem S/S 8271 with 132kv Network in Riyadh City
PTS#22CC1143 & Contract Number:. 4400019349
Company Catalogue
cable management
conduit system
Distributed by
National Marketing Est. Co. Ltd.
@NAMATksa @NAMATksa Namat_ksa (NAMAT) NAMAT ksa
www.namat.com Direct No. +966 9200 18858
who we are?
Isam M. Khairy Kabbani Plastic & Insulation Factory Company
(IKKPF) is a member of the IKK Group of Companies, one of the
100 Top Companies and largest corporations in Saudi Arabia,
headquartered in Jeddah. IKKPF manufacturing base is located
in Dammam, the KSA’s second Industrial City. It is specialized
in producing electrical cable management conduit pipes and
fittings as per Saudi, British & American standards.
A market leader serving traders and contractors in the Our modern manufacturing equipment and long expertise
KSA and neighboring countries through supplying high in plastic processing ensures that the utmost product
quality conduits and fittings. Our products not only meet standards and quality is maintained for all produced
the highest local and international standards, but are items. We are also dedicated in catering to our customer
ideally suited to the environmental conditions of the needs, on-time delivery, providing the right products on
kingdom and its neighbouring countries. the right time.
FOUNDER's
message
Growth, in all its facets, has been a distinguishing factor at IKK Group, ever since our inception.
Our philosophy envisions growth as a universal concept that represents multiple possibilities and
touches all aspects of life. This explains why we have put in motion some of the most ambitious
plans, aligned to the needs of the Kingdom. The continuing expansion of our key business verticals
places us at an eminent level.
IKKPF’s strategic growth policy is to primarily focus on its With best wishes,
end-user industry. We shall continue to invest in the core
competencies to stay ahead of the curve and capitalize Isam M. Khairy Kabbani
on the opportunities arising globally. Our practice of Founder
continuously innovating and experimenting to improve
the product quality has yielded results always. We intend
to be one of the largest producers of electrical conduits
www.namat.com 1
National Marketing Est. Co. Ltd. www.namat.com
Mechanical Properties
PSI 7,000
Tensile Strength D - 638 / type1
MPA > 48.0
PSI 500,000
Modulus of Elasticity in Tension D - 639 / type1
MPA >3447.0
PSI 14,500
Flexural Strength D - 790 proc. B
MPA 93
Izod Impact D - 256 Ft-Lbs / In of notch 0.65
Hardness (Rockwell) D - 785 Rockwell "R" 119
Thermal Properties
D - 696 in/in/°F 3.0X10-5
Coefficient of Thermal Linear Expansion
D - 696 mm/mm/°C 5.4X10-5
Vicat Softening Point D - 1525 (Rate A) °C > 80
Heat Deflection D - 648 (264 psi) °C (°F) > 70 (158)
Electrical Properties
Dielectric Strength D - 150 Volts/Mil 1413
Dielectric Constant D - 150 60cps at 30 °C 3.7
Volume Resistivity D - 257 Ohm/cm at 95 °C 1.2 X 1012
Flammability Properties
Flammability rating UL - 94/0.062 Rating V-0
Flame Spread ASTM E84 10
Smoke Developed ASTM E84 250
Limiting Oxygen Index UL 94 43%
Burning Rate Self Extinguishing
2
NAMCODUCT®
Conduits, tubings & Ducts
SASO & british standard
SASO GSO IEC 61386-21/2014 & bs-en-61386 pipes Table 02
NAMCODUCT® Conduits are offered in 2.9 meters long and black/ white color
Note: Previously BS6099
AMERICAN STANDARD
nema tc-2
Electrical Plastic Tubing (EPT) & Conduit (EPC-40 & EPC-80)
Dimensions of Electrical Plastic Tubing
Table 03
EPT-A-PVC EPC-40-PVC EPC-80-PVC
Trade Metric Outside
Size Size Diameter Min. Wall Min. Inside Min. Wall Min. Inside Min.Wall Min. Inside
Thickness Diameter Thickness Diameter Thickness Diameter
inch mm inch mm mm mm mm mm mm mm
The above table confirms to SEC Specification 23 - TMSS 01 Table 03 (EPC 40).
EPT-A-PVC Electrical Plastic Tubing for encasement in concrete, EPC 40 Electrical Plastic Conduit for normal duty
application & EPC 80 Electrical Plastic Conduit for heavy-duty application
Note: Pipe Length: Standard 3 / 6 meters
www.namat.com 3
National Marketing Est. Co. Ltd. www.namat.com
AMERICAN STANDARD
tc-6 & 8 pipes
PVC Plastic Utilities Duct for underground installations
Dimensions of underground utilities duct
(Minimum Modulus of Elasticity 500,000psi) Table 04
inch mm mm mm mm mm mm mm
SASO standard
uPVC Conduits/ Ducts
Size and dimensions as per SSA 14/15, GS 675/1997 & DIN 8061/62 Table 05
Nominal Series 2 (SDR 51) Series 3 (SDR 34.4) Series 4 (SDR 21) Series 5 (SDR 13.5)
Outside Nominal Wall Nominal Wall Nominal Wall Nominal Wall
Diameter Nominal Wt. Nominal Wt. Nominal Wt. Nominal Wt.
Thickness Thickness Thickness Thickness
BAHRAIN Specs
uPVC Utilities Duct / Conduit
as per EDD (Size and dimension as per BS 3506) Table 08
Outside Diameter Wall Thickness
Nominal
Class B Class C Class D Class E
Pipe Size Min Max
Min Max Min Max Min Max Min Max
inch mm mm mm mm mm mm mm mm mm mm
4 114.10 114.50 3.4 3.8 4.5 4.0 6.0 6.6 7.3 7.8
6 168.00 168.50 4.5 5.0 6.6 6.0 8.8 9.7 10.8 11.9
Note: Ducts are offered in 5.8 or 6 meters in length with grey or black color and solvent cement end socket.
NAMCODUCT®
SPLIT DUCT Table 09
Split Duct is the fastest and easiest way to repair The fast and easy
broken ducts and is also cost effective. Cutting and Nominal method of installing
Segment
replacing of your conductors. Size duct around existing
The male - female groove design leads the industry cable for repair
degree (°) inch
in providing a strong, rigid solution for duct repair and temporary
situations. The interlocking design allows the split duct 45° 2" - 6" installations as Sch.
sections to be staggered and butted together. Joints 40 and 80.
may be sealed with tape and reinforced with plastic or 22 1/2° 2" - 6"
metallic straps to produce a rigid, stable unit. Split Sleeve Coupling
11 1/4° 2" - 6" for Joining Split Duct
Available in 2" through 6" diameters, this product to existing duct for
line also contains couplings and sweeps necessary to Two 45° Elbow may be
Sch. 40 and 80.
complete the system. segmented for 90°
www.namat.com 5
National Marketing Est. Co. Ltd. www.namat.com
NAMCODUCT®
fittings/ conduit accessories
british standard FITTINGS
bs 4607 Part 3
Standard Coupling Expansion Coupling
Available in Black color. White color upon request. Available in Black color. White color upon request.
6
3 Way Terminal Junction Box 4 Way Terminal Junction Box
Available in Black color. White color upon request. Available in Black color. White color upon request.
Loop in Box
Available in Black color. White color upon request.
Screws
Screws for Junction Boxes
Size Std. Packs
Code No. Size Std. Packs
mm pcs Code No.
mm pcs
LPIN020B 20 40 ZSCRW012 12.35 X 4 200
LPIN025B 25 40 Screws for Saddle & Base
Size Std. Packs
Code No.
mm pcs
ZSCRW010 10.00 X 4 200
www.namat.com 7
National Marketing Est. Co. Ltd. www.namat.com
Bends
Available in Black color. White color upon request.
8
Suggested Specification for pec Duct
Base & Inter Spacer
Duct (Conduit) bank shall be encased in concrete with
at least three inches of concrete at the top and bottom
and two inches on each side. A horizontal and vertical
separation between the ducts of 2 inches/50.8 mm shall
be maintained by installing IKK PF high impact spacers
with horizontal and vertical locking intervals of 1.5 Meters
to 2 Meters.
NAMCODUCT®
FABRICATED LONG RADIUS BENDS
nema standard (nema tc-3 Bends using NEMA TC-2 pipes) Table 12
Radius Socket Depth (B) Radius Socket Depth (B)
Nominal Size Outside Dia.
(R) Max Min (R) Max Min
inch inch mm inch inch inch mm mm mm
1/2" 0.840 21.34 4.00 1.500 0.652 101.60 38.10 16.56
3/4" 1.050 26.67 4.50 1.500 0.719 114.30 38.10 18.26
1" 1.315 33.40 5.75 1.875 0.875 146.05 47.63 22.23
11/4" 1.660 42.16 7.25 2.000 0.938 184.15 50.80 23.83
1 1/2" 1.900 48.26 8.25 2.000 1.062 209.55 50.80 26.97
2" 2.375 60.32 9.50 2.000 1.125 241.30 50.80 28.58
2 1/2" 2.875 73.02 10.50 3.000 1.469 266.70 76.20 37.31
3" 3.500 88.90 13.00 3.125 1.594 330.20 79.38 40.49
4" 4.500 114.30 16.00 3.375 1.750 406.40 85.73 44.45
6" 6.625 168.28 30.00 3.750 2.125 762.00 95.25 53.98
8" 8.625 219.08 40.00 6.500 4.875 1016.00 165.10 123.83
nema standard (nema tc-9 Bends using NEMA TC-8 & 6 pipes) Table 13
Outside Dia. U.S. Customary Unites Metric
Nominal 22°, 30° 22°, 30°,
45° & 90° 22° & 30° 45° & 90° 22° & 30°
Size 45° & 90° 45° & 90°
Radius Radius Sweep Radius Bends, Radius Bends, Radius Sweep Radius
inch inch mm degree degree feet degree degree feet
18, 24, 36, 18, 24, 36, 0.46, 0.61, 0.91, 0.46, 0.61, 0.91,
2" 2.375 60.32 12 1/2 3.8
48, 60 48, 60 1.22, 1.52 1.22, 1.52
18, 24, 30, 18, 24, 36, 0.46, 0.61, 0.76, 0.46, 0.61, 0.91,
3" 3.500 88.90 12 1/2 3.8
36, 48, 60 48, 60 0.91, 1.22, 1.52 1.22, 1.52
18, 24, 36, 18, 24, 36, 0.46, 0.61, 0.91, 0.46, 0.61, 0.91,
4" 4.500 114.30 12 1/2 3.8
48, 60 48, 60 1.22, 1.52 1.22, 1.52
5" 5.563 141.30 36, 48, 60 48, 60 12 1/2 0.91, 1.22, 1.52 1.22, 1.52 3.8
6" 6.625 168.28 48, 60 48, 60 12 1/2 1.22, 1.52 1.22, 1.52 3.8
www.namat.com 9
National Marketing Est. Co. Ltd. www.namat.com
SASO standard
DIN/ SASO Bends using SSA 14/15, GS 675/1997 & DIN 8061/62
Socket Depth Curvature Table 14
Nominal Outside
S.No. Radius Average
Diameter Max (B) Min (B) Length (z)
mm mm mm mm mm
1. 16 90.00 32.00 16.00 141.30
2. 20 101.60 38.10 16.56 159.51
3. 25 114.30 38.10 18.26 179.32 S2 S1
4. 32 146.05 47.63 22.23 229.23 z
5. 40 184.15 50.80 23.83 289.11 R B
6. 50 209.55 50.80 26.97 328.94
7. 63 241.30 50.80 28.58 378.84 y
8. 75 266.70 76.20 37.31 418.72 d1
9. 90 330.20 79.38 40.49 518.41 90°
10. 110 406.40 85.73 44.45 638.04 d2
11. 140 762.00 90.00 48.50 1196.34 C
12. 160 762.00 95.25 53.96 1196.34
13. 200 952.00 165.10 123.83 1494.64 y
14. 225 952.00 165.10 123.83 1494.64
14. 250 1000.00 170.00 130.00 1570.00
15. 280 1168.00 180.00 140.00 1833.76
16. 315 1168.00 190.00 150.00 1833.76
QATAR Specs
Qatar National Broadband Network Co. (QNBC) Bends Table 15
Outside Internal Duct Inside Dia Inside Dia
Wall Socket Effective Actual Duct
Dia of Dia at SPIGOT of Socket of Socket Radius
Thickness Length Duct Length Length
Duct Type Duct at Entry at Entry at Shoulder
(d1) (d2) (S2) (S1) (R)
mm mm mm mm mm mm meter meter mm
Duct Bend
96.5 ± 0.2 3.25 ± 0.2 90.0 97.1 ± 0.1 96.1 ± 0.1 100 1.3 ± 0.005 1.4 ± 0.005 0.50
D54/90°
Duct Bend
56.5 ± 0.2 3.25 ± 0.2 50.0 57 ± 0.1 56 ± 0.1 70 0.8 ± 0.005 0.87 ± 0.005 0.25
D56/90°
Duct Bend
96.5 ± 0.2 3.25 ± 0.2 90.0 97 ± 0.1 96 ± 0.1 100 1.4 ± 0.005 1.5 ± 0.005 1.0
D54/30°
Duct Bend
56.5 ± 0.2 3.25 ± 0.2 50.0 57 ± 0.1 56 ± 0.1 70 1.0 ± 0.005 1.07 ± 0.005 0.50
D56/30°
WELD ON
PLAS TIC P IP E C E ME NT
CLEAR MEDIUM BODIED FAST SETTING
This is solvent cement (adhesive) is specially designed for electrical
and telecommunication duct installation manufactured by IPS Weld-On Adhesive, Inc., U.S.A.
Distinct characteristics of the proposed 701 Weld-On Cement;
1. Clear, Medium bodied, Fast setting solvent.
2. Highly viscous - 500 cPs of a medium body.
3. Meets the requirement for Low VOC (Volatile Organic Compound)
4. Adheres to a standard for PVC material ASTM D1755.
5. Can Brush Sizes were carefully chosen for the smallest pipe & fitting size.
For Sizes & Code Nos. please see the table below; Table 16
Code No. Sizes Std. Packs
A D A D A
L L L
www.namat.com 11
Connection of Al-Nazeem S/S 8271 with 132kv Network in Riyadh City
PTS#22CC1143 & Contract Number:. 4400019349
Company Profile
COMPANY PROFILE
National Marketing Est. Co. Ltd.
The Company
National Marketing Est. Co. Ltd. (NAMAT) is engaged in the building materials distribution
business in the kingdom of Saudi Arabia. The company was formed in 1970 to be the sole
distributor of “New Products Industries” Factory (NEPRO-PLAST), it is considered the first
leading company in the Gulf area specialized in the field of uPVC and CPVC pipes and fittings.
Nowadays, NAMAT is representing several major international manufacturers and considered a
leader in trading Plastic and non-Plastic pipes and fittings, accessories for water network, well
casing, corrugated optic ducts (COD), electrical conduits, food waste disposals, and a wide
variety of other products.
NAMAT is a subsidiary of IKK Group of Companies which is one of the largest conglomerates in
the Kingdom of Saudi Arabia. The IKK Group is a diversified group operating in the fields of
trading, manufacturing, and contracting for the construction industry. It is composed of 15
independent companies. These companies operate through 156 divisions, branches, and outlets
that are spread over 9 countries covering all major cities in the region. IKK Group has
maintained a ranking among the top 100 companies in the kingdom of Saudi Arabia in the last
10 years. It is ranked the 39th top company in Year 2008 with revenues close to one billion US
dollars in fiscal 2008.
NAMAT employs more than 500 staff with yearly revenues exceeding 800 millions of Saudi
Riyals. Its Headquarter is located in the Red Sea coastal city of Jeddah. NAMAT has established
the standards for quality and excellence in its field through-out the 40 years it has been
servicing its customers in the K.S.A. market. One of the major strengths of NAMAT in the
market is its investment in its sales force to serve its trader and contractor clients through-out
K.S.A. market. The existing sales force compromise of more than 100 qualified sales
representatives, which are proportionally distributed throughout the Kingdom.
Mission
To continue our market leading position in the building materials services business. NAMAT is
committed to delivering a wide range of high quality products to our local and regional
customers. Will continue to search out and secure distribution rights for newer high quality
products. We understand our customer's needs and will work hard to provide them the right
products at the right time.
Distribution Infrastructure
NAMAT has 20 primary branches for distribution located in the major metropolitan areas and
cities across the K.S.A. NAMAT has a fleet of more than 100 trucks and vans for delivering its
products which enables it to provide service to all its customers in less than 24 hours. It has
Revision: 3
14/08/10 Page | 1
COMPANY PROFILE
National Marketing Est. Co. Ltd.
warehousing capacity to stock materials in the excess of 100,000 square meters of space.
Inventory control is strictly monitored through an Enterprise Resource Planning (ERP) system to
ensure that adequate supplies are always available within its customers reach. All invoicing
records and customer transactions are accurately issued and easily tracked through the ERP
system. In addition to NAMAT’s strong distribution network within K.S.A. market, it has an
export department that serves other major markets in the region including all Gulf countries,
Yemen, Sudan, Egypt, Jordan, Syria, Lebanon, Pakistan, Iran, Morocco, Tunisia, and other
African countries.
Distribution Agreements
NAMAT has established strong relations and made several distribution agreements with local and
world class manufacturers in Europe and USA to market and sell their products in K.S.A. market
and other neighboring markets. Following is the list of main manufacturers:
NEPRO (sister company): manufacturer of PVC/CPVC pipes & fittings and HDPE pipes -KSA
IPS Corporation: manufacturer of Weld-On Solvent Cements and Cleaners for joining plastic
materials –USA
Henkel: manufacturer of Tangit adhesive and Cleaner for joining plastic materials –Germany
Friatec: manufacturer of HDPE electro-fusion fittings and valves –Germany
Baenninger: manufacturer of HDPE butt-welding fittings -Germany
DYKA: manufacturer of PVC sewerage Terra Cotta fittings -Holland
FIP: manufacturer of PVC Pressure Metric Fittings and Valves -Italy
GIRPI: manufacturer of PVC Drainage fittings for Solvent Welding -France
Praher: manufacturer of PVC valves –Austria
IPEX: manufacturer of PVC & CPVC fittings –USA
Tyco-Bayard: manufacturer of cast iron valves, Fire Hydrants and accessories – France
Tyco-Talbot: manufacturer of pipe Saddles and associated equipment to water industry -UK
SPEARS: manufacturer of PVC and CPVC fittings and Valves –USA
Charlotte: manufacturer of PVC DWV fittings and Cast Iron Pipe Systems –USA
Ford: manufacturer of water meter boxes -USA
Franken Plastik: manufacturer of indicator plates –Germany
In-Sink-Erator: manufacturer of food waste disposals –USA
OptiRoad Inc.: manufacturer of Corrugated Optic Duct (COD) –South Korea
Revision: 3
14/08/10 Page | 2
COMPANY PROFILE
National Marketing Est. Co. Ltd.
NEPRO Pipes:
PVC pipes from 16 - 710mm OD are manufactured in different classes suitable for 2, 4, 6,
10 & 16 Bar working pressure according to SASO 14 & 15/1996, DIN 8061, 8062, &
19532, Pr EN 1401, & Pr EN 1452-2, and ISO 4422, These pipes can be produced in
different colors such as Gray, Orange, Black, White & Blue Etc... ).
PVC pipes from 1/2 inch up to 8 inches diameter according to ASTM D-1784, 1785. SCH
40 & 80.
PVC pipe sizes from 1/2 inch up to 8 inches diameter in different classes (B,C,D & E)
according to BS 3505 & 3506.
PVC pipe according to NEMA standard TC-2, TC-6 and TC-8.
PVC Perforated pipe for underground de-watering.
PVC water well casing and screen according to DIN 4925 part I, II, and III standards
CPVC FlowGuard pipes different sizes for Sch80 according to ASTM F441
HDPE pipes from 20mm to 400mm OD are manufactured according to DIN 8074 and DIN
EN 12201-2 standards
NAMAT Fittings:
NAMAT PVC Sch40 and Sch80 fittings according to ASTM D-2466 & 2467
NAMAT CPVC Sch80 fittings according to ASTM F437 & F439
NAMAT Soil, waste, and drainage fittings according to ISO 3633 & ISO 4435 which
complies with SASO 1397 & 1399 in orange-brown color RAL 8023
NAMAT PVC & CPVC Brass insert fittings
Solvent Cements, primers, and cleaners from IPS (Weld-On) and Henkel (Tangit)
DCI valves, fire hydrant, and project accessories from Tyco/Bayard -France
Revision: 3
14/08/10 Page | 3
COMPANY PROFILE
National Marketing Est. Co. Ltd.
Other products:
Corrugated Optic Ducts (COD) for fiber-optic and power cables from OptiRoad –S. Korea
Food waste disposals and steaming hot water taps from In-Sink-Erator -USA
Reference Projects
NAMAT’s strong presence in the market and its diverse high quality products enable it to be
approved by most of the consultants and be well qualified for the mega projects in K.S.A and
the surrounding markets. Below is a list of some of the major projects NAMAT has actively
involved in:
K.S.A. Projects:
Revision: 3
14/08/10 Page | 4
COMPANY PROFILE
National Marketing Est. Co. Ltd.
Revision: 3
14/08/10 Page | 5
COMPANY PROFILE
National Marketing Est. Co. Ltd.
Management Team
The management team of NAMAT is highly trained with diversified international and local
experience in their own fields. The continuous growth of NAMAT is a testimony to the
commitment and dedication of management and staff. The organizational chart of NAMAT is
provided below.
IKK Group
Chairman
IKK Group
Vice Chairman
Export Manager
Revision: 3
14/08/10 Page | 6
Connection of Al-Nazeem S/S 8271 with 132kv Network in Riyadh City
PTS#22CC1143 & Contract Number:. 4400019349
Method of Statement
METHOD OF SOLVENT WELDED JOINT INSTALLATION
1. Joint Preparation - Cut pipe square with axis, using a fine tooth saw with a miter box or guide.
Remove all burrs and break the sharp lead edges.
2. Cleaning & Priming-Surface to be joined must be cleaned and free of dirt, moisture, oil and
other foreign material.
3. Mark on spigot the full length of the socket side to make sure that the spigot will fit exactly the
socket length.
4. Application of solvent cement - PVC solvent cement is fast drying and should applied as
quickly as possible, consistently with good workmanship. Follow up the manufacturer’s
recommendation to both spigot and socket side with an adequate quantity of cement.
5. Joint Assembly - While both the inside socket surface and the outside surface of the spigot
of the pipe are wet with solvent cement, forcefully bottom the spigot in the socket. Turn the
pipe or fittings 1/4 turn during assembly (but not after the pipe is bottomed) to distribute
the cement evenly. Hold for a while until handling strength is developed. Assembly should be
completed within 30 seconds after the last application of solvent cement.
6. After assembly wipe excess cement from the pipe at the end of the socket. Gaps in the
cement bead around the pipe perimeter may indicate a defective assembly. Handle the newly
assembled joints carefully after 1 hour.
For 100 Joints u se the following amounts of adhesive and primer (Table No. 13)
Sub-supplier: N/A
Sub-Supplier Job
N/A
No:
Location: N/A
Pre-Inspection Meeting
Primary Contact: N/A Yes No
Summary Attached:
Phone: N/A E-mail : N/A Summary Report Attached: Yes No
RECOMMENDED ACTION:
N/A
DAYS TRAVEL DISTANCE:
INSPECTION TIME 4 Days -- --
HOURS HOURS : MI KM
Technical
Muhammad Shahzad Bhatti Date: 24 Nov 2021 Project Coordinator : Jiovanni Sagcal
Specialist:
This report is made solely on the basis of the Client’s instructions and/or information and materials supplied. It is not intended to be a
recommendation for any particular course of action. Intertek does not accept a duty of care or any other responsibility to any person other
than the Client in respect of this report and only accepts liability to the Client insofar as is expressly contained in the terms and conditions
governing Intertek's provision of services. Intertek makes no warranties or representations either express or implied with respect to this report
save as provided for in those terms and conditions.
1.0 ATTENDEES
2.0 MATERIALS
-- PVC Conduits
QUANTITY
PRODUCT / MATERIAL / ITEM ORDERED PRESENTED ACCEPTED
PO ITEM NO. TAG / SERIAL NO. ACCEPTED TO
NAME QUANTITY THIS VISIT THIS VISIT
DATE
N/A
N/A
Following Tests are witnessed at ACES Lab during the visits carried out on 18 & 19 Aug 2021, 19 Oct 2021, 17 Nov 2021.
Samples of 6” Diameter:
EB – 35
1‐ Impact Resistance Test As per NEMA TC 6&8:
5 samples no tearing or cracking in all samples,
NEMA Requirements all 5 shall pass if one failed 5 new should be added for total of 9 out of 10
passing.
Results-Acceptable
DB – 120
1‐ Impact Resistance Test As per NEMA TC 6&8:
5 samples no tearing or cracking in all samples
NEMA Requirements all 5 shall pass if one failed 5 new should be added for total of 9 out of 10
passing.
Results-Acceptable
Samples of 8” Diameter:
‐ EPC – 40
1‐ Deflection Resistance Test As per NEMA TC2:
Average of 3 results 99.73% retained thickness,
NEMA TC2 Requirements Min % retained is 70.
Results-Acceptable
Samples of 2” Diameter:
‐ EPC – 40
1‐Resistance to specified reagents Test As per UL651:
@0 day, @60 days, @90 days -weight & crushing
Results-Acceptable.
7.0 NON-CONFORMANCES
- N/A
10.0 PHOTOGRAPHS
E&DD/E&DD-EOA REPLY:
C Comments D Rejected
* 1) Compliance is noted.
2)The given above approval does not relieve the contractor from his contractual responsibility and
obligation to meet all requirements of Contract and SOW /TS.
Should you have any question, please contact Mohammed Shariq on extension 8-4972.
JAFAR A. AL-HEJJI
Lead Engineer
E&DD/E&DD-EOA/C&MEU
MS /MA : ms
Attachment: a/s
cc: E&DD Letter File (soft copy)
Route: MA/MS
1 OF 1
Review of Contractor's Submittal (CSPD)
NOTE : Acceptance does not release the Contractor from his responsibilities in performing the work in strict
conformance with Contract, Scope of Work and Technical Specifications.