CHILLER SELECTION
User Halit Gök (UNTES) Date 13.11.2023
Reference:
SELECTİON
Family FullPOWER EVO
TCAVTZ 2345-31715
Model TCAVTZ 2655
Webcode FPE21
The images are for reference purposes only and may not represent exactly the models or the equipment subject of this document.
The certified standard performances and the certified software tool version can be verified in www.eurovent-certification.com
CONSTRUCTİON FEATURES
Packaged air-cooled water chiller with axial fans. Range with semi-hermetic screw compressors and R134a refrigerant gas.
T - High temperature/efficiency version
POWER SUPPLY: 400V/3PH/50HZ
TYPE OF COIL: MCHX-MICROCHANNEL COIL
STEPLESS CAPACITY CONTROL: CCL -STEPLESS CAPACITY CONTROL
CONDENSING CONTROL: FI-CONDENSING CONTROL
ELECTRONIC EXPANSION VALVE: EEV-ELECTRONIC EXPANSION VALVE
EFFICIENCY OPTIMIZER: EEO - EER OPTIMIZER
EXCHANGER: STE-SHELL AND TUBE EVAPORATOR
PUMPING GROUP MANAGEMENT: VPF_R
○ Load-bearing structure and panels in galvanised and RAL 9018 painted sheet metal; galvanised steel sheet metal base.
○ The structure consists of two sections:
• technical compartment that houses the compressors, the electrical panel and the main components of the cooling circuit;
• aeraulic circuit dedicated to housing the heat exchanger coils and electric fans.
○ High efficiency semi-hermetic screw compressors and specifically developed to function with R134a refrigerant and with linear capacity control
down to 16% at part load. The compressor has star-delta starting with reduced starting current by means of an equaliser valve and load
partialisation, complete with integral protection and crankcase heater.
○ The compressors are also equipped with cut-off valves on the refrigerant discharge pipe.
○ Water side shell and tube exchanger with dry countercurrent heat expansion. The shell and tube exchanger is made of carbon steel with copper
pipes, air bleed valve and water drain tap, with differential pressure switch and rubber insulation closed cell polyurethane foam with plastic
protection against UVA rays.
○ Air side heat exchanger with MCHX micro-channel coils.
○ Electric helical fans with external rotor, supplied with internal circuit breaker protection, complete with protection mesh and proportional
electronic device (FI option) for pressurised and continuous adjustment of the fan rotation speed down to outdoor air temperature of -10°C when
operating as a chiller.
○ Victaulic-type hydraulic connections.
○ Differential pressure switch that protect the unit from any water flow interruptions (flow switch - FW option).
○ Cooling circuits consisting of an annealed copper pipe (EN 12735-1-2) complete with: a cartridge dryer filter, load fittings, a manually reset safety
pressure switch on the high pressure side, an LP and HP transducer, safety valves on high and low pressure side, a valve upstream of the filter, a
liquid indicator, insulation of the intake line, and an electronic expansion valve.
○ Unit with IP24 protection rating.
○ The unit is complete with a charge of R134a refrigerant.
ELECTRİCAL PANEL
○ Electrical panel (IP54) can be accessed by opening the front panel, in compliance with EN 60204-1/IEC 60204-1 Standards in force, fitted with
opening and closing via specific tool.
○ Complete with:
• electrical wiring arranged for power supply 400-3ph-50Hz;
• numbered electric cables;
• auxiliary circuit power supply 230V-1ph-50Hz derived from main power supply;
• main power supply switch with interlocking safety door isolator;
• protection fuses for each compressor (optional is the version with circuit breaker switches protecting each compressor);
• automatic thermal overload switch to protect the motor-driven fans;
• auxiliary circuit protection fuse;
Date: 13.11.2023
Family: FullPOWER EVO - Model: TCAVTZ 2655 Software Release: 20231009/20231009
The certified standard performances and the certified software tool version can be verified in www.eurovent-certification.com
Rhoss Spa - Via Oltreferrovia, 33033 Codroipo (UD) - ITALY
Tel.+39 0432 911611 - Fax +39 0432 911600 - email:
[email protected] - web: http://www.rhoss.com 1/5
CHILLER SELECTION
• compressors power contactore;
• remote machine controls: ON/OFF;
• remote machine controls: compressor operating light and general lock light.
○ Programmable microprocessor electronic board handled by the keyboard inserted in the machine.
○ This electronic board performs the following functions:
• adjusts and controls the temperature settings of the water exiting the machine; safety delays; of the system/recovery pump; of the compressor
operating hour meter and the system/recovery pump hour meter; of the electronic antifreeze protection that is automatically activated when the
machine is off (accessory); of the functions that control the intervention mode of the individual parts forming the machine;
• complete protection of the unit, possible shutdown and display of all the triggered alarms;
• compressor protection phase sequence monitor;
• unit protection against low or high phase power supply voltage (CMT accessory);
• display of the settings implemented on the display; of the in/out water temperature on the display; the condensation and evaporation; of the
alarms on the display;
• multilingual menu user interface;
• automatic pump operating time balance (DP1-DP2 installations);
• automatic activation of the pump in standby in the event of an alarm (DP1-DP2 installations);
• outdoor temperature management to control the set-point climate compensation (which can be enabled from the menu);
• displayed inlet water temperature at the recovery unit/desuperheater;
• alarm code and description;
• alarm history management (menu protected by factory password).
○ In particular, for every alarm, the following are memorised:
• date and time of intervention;
• in/out water temperature values as soon as the alarm was triggered;
• the evaporation and condensation pressure values at the time of the alarm;
• alarm delay time from the switch-on of the connected device;
• compressor status at the time of the alarm;
• outdoor air temperature display;
• set work set-point;
• status of the fans upon the alarm;
• set anti-freeze set-point;
• overheating, intake temperature and EEV valve opening pitch.
○ General synoptic on the state of the unit:
• compressor status;
• fan regulation status;
• electronic thermostatics operation status.
○ Advanced functions:
• Pump Energy Saving management;
• evaporator pump control KPE, contactor recovery pump command KPR and KPDS desuperheater Pump Control in the case of external supply of
electric pumps (to be installed by the installer). For the unit to operate properly, activation of the recovery pump, by the installer, must be
controlled by means of a specific discrete output provided in the board on the unit;
• High-Pressure Prevent function with forced cooling capacity partialisation for a high outdoor temperature;
• the EEO - Energy Efficiency Optimizer function allows unit efficiency to be optimised by acting on the electrical absorption, thereby minimising
consumption. The algorithm identifies the optimal point that minimises the total absorbed power (compressors+fans) of the unit by actuating the
fan rotation speed. The function allows for an increase in seasonal efficiency;
• VPF_R control: (Variable Primary Flow by Rhoss in the main exchanger). VPF_R includes the temperature probs, the inverter management and the
management software of the chiller;
• set-up for serial connection (SS/KRS485, BE/KBE, BM/KBM, KUSB accessory);
• possibility to have a digital input for remote management of double set point (DSP);
• possibility to have a discrete input for total recovery management (CRC100 contact) and desuperheating (CDS contact) (refer to the specific
section for more details);
• possibility to have an analogue input for the shifting Set-point via a 4-20mA remote signal (CS);
• management of time bands and operation parameters with the possibility of daily/weekly functioning programs;
• check-up and monitoring of scheduled maintenance status;
• computer-assisted unit testing;
• self-diagnosis with continuous monitoring of the unit functioning status;
• Master/Slave control of up to 4 units in parallel.
Date: 13.11.2023
Family: FullPOWER EVO - Model: TCAVTZ 2655 Software Release: 20231009/20231009
The certified standard performances and the certified software tool version can be verified in www.eurovent-certification.com
Rhoss Spa - Via Oltreferrovia, 33033 Codroipo (UD) - ITALY
Tel.+39 0432 911611 - Fax +39 0432 911600 - email:
[email protected] - web: http://www.rhoss.com 2/5
CHILLER SELECTION
TECHNİCAL DATA - TCAVTZ 2655
Design parameters
Cooling
External air temperature [°C] 35
External air humidity [%] 50
User side exchanger inlet fluid temperature [°C] 12
User side exchanger outlet fluid temperature [°C] 7
Altitude [m] 0
User side exchanger fluid Water
Fouling factor [m²°C/kW] 0
Performances
At design conditions: Cooling
Capacity (gross) [kW] 668,0
Absorbed power (gross) [kW] 197,0
EER (gross) 3,39
Capacity (UNI EN 14511) [kW] 667,4
EER (UNI EN 14511) 3,35
Functioning limits
User side exchanger
Cooling
Flow rate [m³/h] 114,9
Pressure losses [kPa] 42
Date: 13.11.2023
Family: FullPOWER EVO - Model: TCAVTZ 2655 Software Release: 20231009/20231009
Rhoss Spa - Via Oltreferrovia, 33033 Codroipo (UD) - ITALY
Tel.+39 0432 911611 - Fax +39 0432 911600 - email:
[email protected] - web: http://www.rhoss.com 3/5
CHILLER SELECTION
Pressure losses
Fans
Type: Axial
Fan number 12
Consumption for each [kW] 1,2
Air flow rate [m³/h] 228000
Technical features
Refrigerant: (5) R134a
Amount of refrigerant (6) [kg] 93
Global Warming Potential (GWP) 1450
Equivalent CO 2 [ton] 134,85
Compressors Screw
Oil charge [kg] 38
Number of compressors 2
Number of indipendent circuits 2
Number of compressor steps 25-100%
Noise
Sound Power level (1) [dBA] 99
Sound Pressure level (10m) (2) [dBA] 66,5
Sound Pressure level (1m) (2) [dBA] 78
[Hz] [dB]
63 95
125 95
250 98
500 97
1000 96
2000 88
4000 74
8000 67
Date: 13.11.2023
Family: FullPOWER EVO - Model: TCAVTZ 2655 Software Release: 20231009/20231009
Rhoss Spa - Via Oltreferrovia, 33033 Codroipo (UD) - ITALY
Tel.+39 0432 911611 - Fax +39 0432 911600 - email:
[email protected] - web: http://www.rhoss.com 4/5
CHILLER SELECTION
Electrical data
Cooling
Total electrical power (3) [kW] 197,0
Electrical power supply [V-ph-Hz] 400-3-50
Nominal current (4) [A] 331
Maximum current [A] 459
Starting current [A] 513
Starting current SFS [A] 786
Size and weight
Length [mm] 7150
Height [mm] 2480
Depth [mm] 2260
Empty weight (6) [kg] 4647
User side inlet/outlet connections Ø DN150 VIC
Partial loads
Cooling
Outlet fluid temperature °C 7
External air temperature °C 35
Load % 100 90 80 70 60 50 40 30 20 10
Capacity (GROSS VALUE) kW 668 601,2 534,4 467,6 400,8 334 267,2 200,4 133,6 66,8
EER (GROSS VALUE) 3,39 3,55 3,73 3,67 3,44 3,5 3,62 3,84 3,7 3,25
Capacity (UNI EN 14511) kW 667,4 600,7 534 467,2 400,5 333,7 267 200,2 133,6 66,7
EER (UNI EN 14511) 3,35 3,5 3,67 3,61 3,37 3,42 3,51 3,68 3,54 3,11
Flow rate determined at full load condition
SEER (EN 14825)
Application type LOW LOW
Application temperature [°C] 7 7
Tdesign [°C] 35 35
Water flow FIXED VARIABLE
Pdesignc [kW] 667,4 667,4
SEER 4,68 4,82
Seasonal efficiency (Reg.2016/2281 UE) [%] 184 190
RHOSS reserves the right to make the changes it deems necessary to improve / update the data at any time and without prior notice.
Note
(1) Standard reference UNI EN-ISO 9614
(2) Standard reference UNI EN-ISO 3744
(3) Total absorbed power at selected conditions (compressors, fans if present and pumps if selected)
(4) Referred to nominal conditions: Ta: 35°C Tw:12/7°C
(5) Regulated transport ADR UN 2857
(6) The value is indicative and may be subject to change based on the selected accessories
Date: 13.11.2023
Family: FullPOWER EVO - Model: TCAVTZ 2655 Software Release: 20231009/20231009
Rhoss Spa - Via Oltreferrovia, 33033 Codroipo (UD) - ITALY
Tel.+39 0432 911611 - Fax +39 0432 911600 - email:
[email protected] - web: http://www.rhoss.com 5/5