0% found this document useful (0 votes)
32 views15 pages

Phoenix Contact 2865007 en

This document provides information about the MINI MCR-SL-U-UI-NC signal conditioner from Phoenix Contact. It is a 3-way isolating amplifier used for electrical isolation, conversion, amplification and filtering of analog signals up to 30V. It has configurable input and output ranges that can be set using DIP switches. The signal conditioner has a compact design, low power consumption, and provides basic insulation between the input and output.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
32 views15 pages

Phoenix Contact 2865007 en

This document provides information about the MINI MCR-SL-U-UI-NC signal conditioner from Phoenix Contact. It is a 3-way isolating amplifier used for electrical isolation, conversion, amplification and filtering of analog signals up to 30V. It has configurable input and output ranges that can be set using DIP switches. The signal conditioner has a compact design, low power consumption, and provides basic insulation between the input and output.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 15

MINI MCR-SL-U-UI-NC - Signal conditioner

2865007
https://www.phoenixcontact.com/us/products/2865007

Please be informed that the data shown in this PDF document is generated from our online catalog. Please find the complete data in the user
documentation. Our general terms of use for downloads are valid.

MCR 3-way signal conditioner, with configurable input/output, for electrical isolation and
conversion of analog signals up to 30 V, with screw connection, standard configuration

Product description
The 6.2 mm wide configurable 3-way isolating amplifier MINI MCR-SL-U-UI-... is used for electrical isolation, conversion, amplification and filtering
of standard signals.
The signals 0...24 V and 0...30 V can be processed on the input side.
The analog signals 0...20 mA, 4...20 mA, 0...10 V, 2...10 V, 0...5 V or 1..5 V are available electrically isolated on the output side.
The DIP switches, which can be accessed on the side of the housing, can be used to configure the input and output signal ranges.
Power (19.2 V DC to 30 V DC) can be supplied through connection terminal blocks on the modules or in conjunction with the DIN rail connector.

Your advantages
• Power supply possible via the foot element (TBUS)
• Low power consumption
• Highly-compact isolating amplifier for electrical isolation, conversion, amplification, and filtering of 24 V or
• 30 V DC signals to create standard analog signals
• Up to 12 signal combinations can be configured using DIP switches
• 3-way isolation

Commercial data
Item number 2865007
Packing unit 1 pc
Minimum order quantity 1 pc
Sales key C403
Product key CK1211
Catalog page Page 96 (C-7-2015)
GTIN 4046356046565
Weight per piece (including packing) 87.4 g
Weight per piece (excluding packing) 65.8 g
Customs tariff number 85437090
Country of origin DE

Dec 27, 2023, 9:55 AM Page 1 (15)


MINI MCR-SL-U-UI-NC - Signal conditioner
2865007
https://www.phoenixcontact.com/us/products/2865007

Technical data

Notes

Utilization restriction
EMC note EMC: class A product, see manufacturer's declaration in the
download area

Product properties
Product type Signal conditioner
Product family MINI Analog
No. of channels 1
Configuration DIP switches

Insulation characteristics
Overvoltage category II
Pollution degree 2

Electrical properties
No. of channels 1
Electrical isolation Basic insulation in accordance with EN 61010
Electrical isolation between input and output yes
Limit frequency (3 dB) approx. 100 Hz
Protective circuit Transient protection
Step response (10-90%) approx. 3.5 ms
Maximum temperature coefficient < 0.01 %/K
Temperature coefficient, typical < 0.002 %/K
Maximum transmission error < 0.1 % (of final value)
< 0.4 % (Without adjustment)

Electrical isolation Input/output/power supply


Rated insulation voltage 50 V AC/DC
Test voltage 1.5 kV AC (50 Hz, 60 s)

Supply
Nominal supply voltage 24 V DC
Supply voltage range 19.2 V DC ... 30 V DC (The DIN rail connector (ME 6,2 TBUS-2
1,5/5-ST-3,81 GN, item no. 2869728) can be used to bridge the
supply voltage. It can be snapped onto a 35 mm DIN rail in
accordance with EN 60715)
Max. current consumption < 19 mA (at 24 V DC incl. load)
Power consumption < 450 mW

Input data

Signal: Voltage
Number of inputs 1

Dec 27, 2023, 9:55 AM Page 2 (15)


MINI MCR-SL-U-UI-NC - Signal conditioner
2865007
https://www.phoenixcontact.com/us/products/2865007

Configurable/programmable Yes, unconfigured


Voltage input signal 0 V ... 24 V
0 V ... 30 V
Max. voltage input signal 50 V DC
Input resistance of voltage input approx. 125 kΩ (0 ... 24 V)
approx. 155 kΩ (0 V ... 30 V)

Output data

Signal: Voltage/current
Number of outputs 1
Configurable/programmable Yes, unconfigured
Voltage output signal 0 V ... 10 V
0 V ... 5 V
1 V ... 5 V
2 V ... 10 V
Max. voltage output signal ≤ 12.5 V
Non-load voltage ≤ 12.5 V
Current output signal 0 mA ... 20 mA
4 mA ... 20 mA
Max. current output signal 28 mA
Short-circuit current ≤ 22 mA
Load/output load voltage output > 10 kΩ
Load/output load current output < 500 Ω (at 20 mA)
Ripple < 20 mVPP (at 500 Ω)
< 20 mVPP (at 10 kΩ)

Connection data
Connection method Screw connection
Stripping length 12 mm
Screw thread M3
Conductor cross section rigid 0.2 mm² ... 2.5 mm²
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Conductor cross section AWG 26 ... 12

Dimensions
Dimensional drawing

Width 6.2 mm
Height 93.1 mm

Dec 27, 2023, 9:55 AM Page 3 (15)


MINI MCR-SL-U-UI-NC - Signal conditioner
2865007
https://www.phoenixcontact.com/us/products/2865007

Depth 101.2 mm

Material specifications
Fire protection for rail vehicles (DIN EN 45545-2) R22 HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23 HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24 HL 1 - HL 2
Housing material PBT

Environmental and real-life conditions

Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -20 °C ... 65 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Altitude ≤ 2000 m
Permissible humidity (operation) 5 % ... 95 % (non-condensing)

Approvals

CE
Certificate CE-compliant

UKCA
Certificate UKCA-compliant

UL, USA/Canada
Identification UL 508 Recognized
Class I, Div. 2, Groups A, B, C, D T5

Shipbuilding approval
Certificate DNV GL TAA000020N

DNV GL data
Temperature B
Humidity B
Vibration B
EMC A
Enclosure Required protection according to the Rules shall be provided
upon installation on board

EMC data
Noise immunity EN 61000-6-2
Note When being exposed to interference, there may be minimal
deviations.
Electromagnetic compatibility Conformance with EMC directive
Noise emission EN 61000-6-4

Electrostatic discharge

Dec 27, 2023, 9:55 AM Page 4 (15)


MINI MCR-SL-U-UI-NC - Signal conditioner
2865007
https://www.phoenixcontact.com/us/products/2865007

Standards/regulations EN 61000-4-2

Electrostatic discharge
Comments Safety measures must be taken to prevent electrostatic
discharge.

Electromagnetic HF field
Designation Electromagnetic RF field
Standards/regulations EN 61000-4-3
Typical deviation from the measuring range final value 5%

Fast transients (burst)


Designation Fast transients (burst)
Standards/regulations EN 61000-4-4
Typical deviation from the measuring range final value 5%

Surge current load (surge)


Standards/regulations EN 61000-4-5

Surge current load (surge)


Comments Criterion B

Conducted interference
Designation Conducted interferences
Standards/regulations EN 61000-4-6
Typical deviation from the measuring range final value 5%

Standards and regulations


Electrical isolation Basic insulation in accordance with EN 61010

Mounting
Mounting type DIN rail mounting
Assembly instructions The DIN rail connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, item
no. 2869728) can be used to bridge the supply voltage. It can be
snapped onto a 35 mm DIN rail in accordance with EN 60715.
Mounting position any

Dec 27, 2023, 9:55 AM Page 5 (15)


MINI MCR-SL-U-UI-NC - Signal conditioner
2865007
https://www.phoenixcontact.com/us/products/2865007

Drawings

Block diagram

Sensor / Field IN OUT PLC / DCS

OUT U IN U OUT U, I
1 1 5 5
+ +
US 4-wire active passive
GND 1 GND 2
2 – 2 6 6
GND –

+24V +24V
3 7
+ +

GND 3
4 GND 3
– 8

+24V
GND 3

Dec 27, 2023, 9:55 AM Page 6 (15)


MINI MCR-SL-U-UI-NC - Signal conditioner
2865007
https://www.phoenixcontact.com/us/products/2865007

Dimensional drawing

93,1 6,2
102,5

Dec 27, 2023, 9:55 AM Page 7 (15)


MINI MCR-SL-U-UI-NC - Signal conditioner
2865007
https://www.phoenixcontact.com/us/products/2865007

Application drawing

0...24V 0...10V
1 IN U OUT 5

UPS
2 GND1 GND2 6

Controller
3 UB+ UB + 7

4 GND3 GND3 8

MINI MCR-SL-U-UI 24V

Mains voltage

Signal conversion to uninterruptible power supply (UPS)

Dec 27, 2023, 9:55 AM Page 8 (15)


MINI MCR-SL-U-UI-NC - Signal conditioner
2865007
https://www.phoenixcontact.com/us/products/2865007

Approvals
To download certificates, visit the product detail page: https://www.phoenixcontact.com/us/products/2865007

cUL Recognized
 Approval ID: FILE E 238705

UL Recognized
 Approval ID: FILE E 238705

DNV GL
 Approval ID: TAA000020N

cUL Listed
 Approval ID: FILE E 199827

UL Listed
 Approval ID: FILE E 199827

cULus Recognized

cULus Listed

Dec 27, 2023, 9:55 AM Page 9 (15)


MINI MCR-SL-U-UI-NC - Signal conditioner
2865007
https://www.phoenixcontact.com/us/products/2865007

Classifications

ECLASS
ECLASS-11.0 27210120
ECLASS-12.0 27210120
ECLASS-13.0 27210120

ETIM
ETIM 9.0 EC002653

UNSPSC
UNSPSC 21.0 39121000

Dec 27, 2023, 9:55 AM Page 10 (15)


MINI MCR-SL-U-UI-NC - Signal conditioner
2865007
https://www.phoenixcontact.com/us/products/2865007

Environmental product compliance

REACh SVHC Lead 7439-92-1

China RoHS Environmentally Friendly Use Period = 50 years


For information on hazardous substances, refer to the
manufacturer’s declaration available under “Downloads”

Dec 27, 2023, 9:55 AM Page 11 (15)


MINI MCR-SL-U-UI-NC - Signal conditioner
2865007
https://www.phoenixcontact.com/us/products/2865007

Accessories

ME 6,2 TBUS-2 1,5/5-ST-3,81 GN - DIN rail bus connectors

2869728
https://www.phoenixcontact.com/us/products/2869728

DIN rail connector for DIN rail mounting. Universal for TBUS housing. Gold-
plated contacts, 5-pos.

TC-D37SUB-AIO16-M-PS-UNI - Module carrier

2902934
https://www.phoenixcontact.com/us/products/2902934

Universal termination carrier for connecting 16 MINI Analog signal conditioners


to digital or analog I/O cards, via D-SUB connector, 37-pos. (1:1 connection),
with HART multiplexer connection

Dec 27, 2023, 9:55 AM Page 12 (15)


MINI MCR-SL-U-UI-NC - Signal conditioner
2865007
https://www.phoenixcontact.com/us/products/2865007

TC-D37SUB-ADIO16-M-P-UNI - Module carrier

2902933
https://www.phoenixcontact.com/us/products/2902933

Universal termination carrier for connecting 16 MINI Analog signal conditioners


to digital or analog I/O cards, via D-SUB connector, 37-pos. (1:1 connection)

MINI MCR DKL - Transparent cover

2308111
https://www.phoenixcontact.com/us/products/2308111

Fold up transparent cover for MINI MCR modules with additional labeling option
using insert strips and flat Zack marker strip 6.2 mm

Dec 27, 2023, 9:55 AM Page 13 (15)


MINI MCR-SL-U-UI-NC - Signal conditioner
2865007
https://www.phoenixcontact.com/us/products/2865007

MINI MCR-DKL-LABEL - Marking label

2810272
https://www.phoenixcontact.com/us/products/2810272

Label for extended marking of MINI MCR modules in connection with the MINI
MCR-DKL

MINI MCR-SL-PTB - Power terminal block

2864134
https://www.phoenixcontact.com/us/products/2864134

MCR power terminal block for supplying several MINI Analog modules via the
DIN rail connector, with screw connection, maximum current consumption of up
to 2 A

Dec 27, 2023, 9:55 AM Page 14 (15)


MINI MCR-SL-U-UI-NC - Signal conditioner
2865007
https://www.phoenixcontact.com/us/products/2865007

QUINT4-SYS-PS/1AC/24DC/2.5/SC - Power supply unit

2904614
https://www.phoenixcontact.com/us/products/2904614

Primary-switched power supply, QUINT POWER, screw connection, DIN rail


mounting, supply of devices possible via the TBUS DIN rail connector, protective
coating, input: single-phase, output: 24 V DC/2.5 A

SZS 0,6X3,5 - Screwdriver

1205053
https://www.phoenixcontact.com/us/products/1205053

Actuation tool, for ST terminal blocks, insulated, also suitable for use as a bladed
screwdriver, size: 0.6 x 3.5 x 100 mm, 2-component grip, with non-slip grip

Phoenix Contact 2023 © - all rights reserved


https://www.phoenixcontact.com

Phoenix Contact USA


586 Fulling Mill Road
Middletown, PA 17057, United States
(+717) 944-1300
[email protected]

Dec 27, 2023, 9:55 AM Page 15 (15)