User Manual
ALL
Series
en Ta
Warranty,
2.2 kVA/36 V
1 phase input - 1 phase outputINDEX
WHERE TO FIND
WELCOME
INSTRUCTIONAL ICON
KNOWING YOUR UPS
Description of Front Panel
Description of Back Panel
QUICK INSTALLATION GUIDE
RECOMMENDED APPLICATIONS
PREVENTING MAINTENANCE
DO's & DONT's
OUR RECOMMENDATIONS
WARNING
CAUTION
WARRANTY POLICYUSER MANUAL
FUSION SERIES
WELCOME
Dear Customer,
Congratulations!
Thank you for selecting Su-Kam fusion series
uninterrupted power supply (UPS) Designed to meet
requirements concerning reliability and quality of
electrical supply in the most demanding applications
Su-Kam fusion series is based on DSP Sine Wave PWM
technology. During mains availability, the AC input
voltage is bypass to the load and also converted to the DC
voltage to charge the battery and then reconverted to AC
voltage to supply to the load when mains fail.
This design and product topology is recognized as the
only one able to match the highest requirements of power
reliability for critical applications. High output power
quality, excellent behavior with dynamic load variation;
adequate protections and filtering are some of the most
important features of this UPS.
Regards,
‘Su-Kam Power Systems Ltd
Salient Features of the Product
+ User Selector switch for “Computer application
(UPS)/other electrical appliances (Wide UPS)"
operation.
* User Friendly Graphical Symbol LED display for status
and fault messages.
* Dual selection for “LA Battery/Tubular & SMF Battery”.
+ Run computer along with other appliances.
+ Generator Compatible.
+ Pure Sinewave Output.
+ Great power savings.
* Instant Switchover.INSTRUCTIONAL ICON
Before you start, familiarise yourself with the icons you
will see in this manual
©CfBER BC
£
‘
3
2
"8,
f©or® PH
og
*
Caution/Warning (Read instruction
before use).
Conformity of European Norm.
Manufacturer Logo.
Serial No.
Authorized European Representative.
Start or ON/Stop or OFF.
Temperature Limitation.
Humidity Limitation.
Consult for User Manual.
Warning: To avoid risk of injury from
electric shock, do not open this
enclosure.
Do not use if package damaged.
Keep Dry.
Earthing.
Protect from heat and radioactive
sources.
Audible noise.KNOWING YOUR UPS
In its most basic form, a Fusion series UPS transforms Direct
Current (DC) to Alternating Current (AC). The battery bank
with the UPS acts as a reservoir to ensure continuous supply
of power whenever supply from utility poweris not available.
DESCRIPTION OF FRONT PANEL
od6UcCOlUCOOUlUCOOUCUCOUCO
On the front panel of the UPS there is one ON/OFF "Power
Active" switch with LED and a graphic symbol panel for
indications.
1. MAINS ON : This graphical symbol indicates that
incoming mainsis available display glows continuously.
MCB TRIP : Mains MCB trip when the UPS is operating
‘on mains and the load connected through the UPS
exceeds the specified limits prescribed for the UPS. In
this case, at once, reduce the extra load and restore MCB
in“ON" position given at back to restore the mains line. If
mains MCBtrip then display blinking with buzzer beep.
BACKUP : This graphical symbol indicates that incoming
mains is not available or is out of the specified voltage
range and the outputs from UPS.
BATT. CHARGING / CHARGED : This graphical symbol,
shows that the mains line is coming and side by side the
charging of batteries is also taking place. This graphical
symbol glows intermittently during charging and glows
continuously when battery is charged.
OVERLOAD/OVER TEMPERATURE & SHORT CIRCUIT :
This graphical symbol, when glows indicates that either
Short circuit has occurred or there is overload/over
temperature on the UPS. The UPS resets itself
automatically and makes 8 attempts in case of
overload/over temperature to turn on again, if the
overload/over temperature continues even after these
attempts, it turns off permanently and will turn on only
after ON/OFF "Power Active switch is turned OFF and
then turned ON. If there is short circuit at the output, the
UPS will turn off permanently after 4 attempts. It can be
reset by removing short circuit and then switching off
and on the ‘Power Active" switch.BATTERY LOW : This graphical symbol, when glows
indicates that the battery voltage has gone down to the
lower limit during discharge. After this indication UPS
will shut down automatically after few minutes, During
this the buzzer gives a continuous beep.
SWITCH ACTIVE : This LED glow if power switch is in ON
position,
DESCRIPTION OF REAR PANEL
Battery Charging Selection Switch : You must select the
appropriate charging option (SMF / Tubular / Flate Plate
Flooded Lead Acid) based on the battery connected to
the UPS during the installation through a selector switch
given on the back panel of the system
Selection of Switch for UPS/W-UPS Mode : If you want
to run PC load select the switch to UPS mode.
Other wise keep the switch to W-UPS mode
Output Terminal Block.
Input Terminal Block.
Battery Wires Red & Black
Mains Input MCB : This isolates mains input from
ups.QUICK INSTALLATION GUIDE
Mount the UPS securely in horizontal position in a clean,
dry and ventilated enclosure.
Ensure that the front panel "Power Active" switch and
battery MCB at the rear panel are in OFF position before
you begin the installation.
Connect the positive terminal for the battery to the
positive wire (RED) of the UPS and negative terminal to
negation wire (BLACK) of the UPS. Immediately check
the connections & switch ON Battery MCB.
Now conneetthe Output terminal to the load.
Switch ON the front panel switch and run the load
without AC input Power. Place a load on th UPS and
make sure itworks.
Connect AC input supply to the input terminal such that
Line is connected to the terminal marked "L" Neutral is
connected to terminal marked 'N' and Earth is connected
to the earth terminal marked E.
Switch on the mains MCB & UPS should now show
‘Mains Present Battery Charging ' on the Graphic Display
LED. After the delay for mains synchronization (approx.
30 Sec) The load is connected to mains & Simultaneously
the Battery starts charging.
Now disconnect the AC input power, the UPS should run
the load on the battery backup mode immediately. Back-
up LED should glow.
Install battery as recommended in the diagram.
Install battery type recommended on the “Our
Recommendation" page.
Select the options of battery charging selector switch
and the option of UPS/W-UPS mode switch on the back
panel
REAR PANEL
wlRECOMMENDED APPLICATIONS
FOR 2.2 KVA
+ FAX MACHINE + ROOMCOOLER + PRINTER
+ REFRIGERATOR = + FAN +1
+ TUBE LIGHT + CFL = PC
RECOMMENDED LOAD** ON 2.2 KVA
APPLICATIONS A
COMPUTER
FAN
TUBELIGHT
Vv
CFL(15W)
REFRIGERATOR upto 300 liters
AIR COOLER upto 500VA
NOTE :
+ 19-29 TV
+ CFLOF 15 WATTS
+ Tube light of ow
* Refrigerator upto 300 liters
When PCis running TVis notrecommendable
48mm Ceiling Fan (3 Blades, 1000-1200 mm sweep)
Indicative values only, actual calculation depends on
manufacturer specification.PREVENTING MAINTENANCE
SYMPTOMS, RECTIFICATION
Main Power is | Reduce the load and restore MCB in ON
coming. UPS position given at the rear side of the UPS.
shows mains MCB
trip on its display
panel
Check if low battery LED is glowing, switch
OFF the UPS by “Power Active" switch.
Allow the battery to charge — before
running the UPS on battery again. If
problem arises, please get your batteries
No Power during | checked.
backup mode | Chock
if overload/short circuit LED is
glowing. Reduce load and reset the UPS
by Power Active switch.
UPS does not | Checkthe battery connections.
operate
UPS trips Reduce the load and restart the UPS
frequently at back | through the "Power Active" switch
up mode
‘SYMPTOMS, PROBLEM REMEDY.
There is no output | Low Battery Check condition of
power batteries &
recharge
Loose orcorroded {Check and clean all
battery connections _|connections
Loose AC output |Checkall AC output
connections lconnections
‘System shut Output of UPSis Check the proper
down after 20 sec, | wired backtoits AC input and
Mains on, backup | own input output wiring
& over load LEDs
is glowing
Low/High AC Measuring with the |Meter must bea
output voltage | wrongvoltmeter true RMS reading
meter
Low surge power | Weak batteries or [Refer to cable and
battery cables too {battery
long recommendations
Note: In case of product not performing a function. Please
contact your authorised dealer/customer care.DO's & DONT's
DO's
To reduce risk of electric shock, disconnect all wiring
before cleaning
Provide ventilation to outdoors from the battery
compartment.
Clean the panel at least once in 30 days with the help of
dry cotton cloth.
Ensure that there are no loose contact anywhere in the
utility output powering the home UPS.
Premises is dry and clean.
DON'T
Do not cover your sine wave UPS with any cover or cloth.
Do not expose UPS to rain, liquids of any type. The UPS is
designed for interiors only.
Do not install this UPS on or near flammable materials (
plywood, chemicals, gasoline etc.)
Do not place UPS onan uneven surface.
Do not place UPS under direct sunlight or close to heat
emitting sources.
Do not place UPS power cord in an area where it may get
damaged by heavy objects.
Do not touch the battery terminals as they can have high
risk of electric shock.
Don’t overload UPSOUR RECOMMENDATIONS
Never use Automobiles Batteries With your UPS. They
are not suitable for these applications.
Always use Deep cycle batteries that are best suited for
UPS.
The recommended battery capacity is 120Ah to 200Ah.
The recommended cable for the input & output wiring of
the unit the battery wire are:
Capacity | DC Voltage | Input | Output | Battery Wire
2.2KVA 36 4mm [25mm [12mm
Never disconnect battery wire of switch OFF battery
MCB while UPS or battery chargers operating.
THE BOX CONTAINS :
Product
Battery link cables (0.75 mtrx 2 no's)
DC fuse (2no's)
User manualWARNING
To prevent the risk of fire or electric shock, install the UPS,
in a temperature and humidity controlled room, free of
conductive contaminants.
Operate the UPS properly from a grounded / earthed
AC supply only.
To reduce the risk of electric shock, do not remove the
UPS cover, as it has no user serviceable parts inside.
Some components are live even when AC power is
disconnected. For service contact a Su-Kam engineer.
CAUTION
Although this UPS has been designed and manufactured to
assure personal safety, please observe the following rules :~
+ The Product (UPS) must be used in the recommended
applications only as suggested on page no 8 of the user
manual
The product (UPS) must be disposed off as per country
law of Bio-waste management rules.
The output side of the UPS AC wiring should never be
connected to a generator or incoming utility power. This
condition is far worse than a short circuit. If the unit
survives this condition, it will shut down until correction
ismade.
Never disconnect the battery cables while the UPS is
delivering power or battery charging operation. The
Power Active Switch has no effect on the charger; it
turns off only the power output during backup mode.
To disconnect the batteries for service:
(a) Turn offthe power switch.
(b) Disconnectall AC power.
(c)_ Disconnectall the battery cables.
Warning-risk of Explosive gases
WORKING IN THE VICINITY OF A LEAD ACID BATTERY
MAY BE DANGEROUS. BATTERIES GENERATE
EXPLOSIVE GASES DURING NORMAL OPERATION.
Provide ventilation to outdoors from the battery
compartment.
Remove conductive jewellery such as rings, bracelets,
necklaces and watches when working with a battery. A
battery can produce a short circuit current high enough
to weld a ring or causing severe burns.
In case of accident, abuse, misuse, neglect, improper
installation (if not undertaken by the company or its
representative), fire, flood, or other act of GOD and any
other natural calamities and other unauthorized repairs
done or carried out will have to be borne by the
purchaser.
Su-kam Power system Itd. does not hold any
responsibility for any consequences from: mishandling,
in-proper installation, in-proper transport, in-proper
storage, misuse, abuse, accident, unauthorized repair.WARRANTY POLICY
We thank you for purchasing this Su-Kam product and we are
sure you will enjoy it. In the event of your product requiring
service, please contact the nearest Su-Kam Service Centre. In
case there is no such service centre in your city, please
contact our Toll Free No, 180-102-4423 for assistance. We
advise that you read the Terms and conditions carefully.
Warranty Terms & Conditions
SU-KAM POWER SYSTEMS LIMITED warrant to the
original purchaser provided the product is still in
possession of and used by the original
purchaser from the date of purchase.
The warranty stands on all parts (except LED indications,
switches, fuse and external body) for Commercial UPS
will be for a period of 24 months.
The warranty will be automatically terminate on the
expiry of the warranty period, even in case of the
Commercial UPS no t being in use in the specified
period.
This warranty is valid only if it is duly signed by the
authorized dealer,
The warranty will be invalid if defects arising in
company's opinion by reasons of accident, abuse,
misuse, neglect, improper installation (if not undertaken
by the company or its representative), fire, flood, or other
act of GOD and any other natural calamities and any
other unauthorized repairs done or carried out will have
to be borne by the purchaser. The problem of fuse blown
will not be included in the warranty of the product. The
services given for the same will be paid service
The company will not be held liable in any condition for
any loss or injury or damage caused to life or property or
death and disability caused to any form of life for any
reason whatsoever.
The warranty will not apply if the original seals are found
broken or tampered with.
Free service under the terms of warranty will be provided
only by authorized representatives/dealers of the
company anywhere in India.‘The company expressly denies the right of any person to
incur or assure for it any other liability or obligation in
connection with the sale of Commercial UPS.
Claims if any, to this warranty shall be made only before
courts having jurisdiction in New Delhi.
Now register your product or launch online complaints at
www.su-kam.com for prompt after sales services.