CLICK-DirectLogic CablesPinout
CLICK-DirectLogic CablesPinout
PLC Communications
6
In this Chapter...
Introduction................................................................................................................ 6-2
Available PLC Protocols............................................................................................. 6-2
C-more Micro-Graphic Built-in Port 1........................................................................ 6-3
C-more Micro-Graphic Optional EA-MG-SP1 Port 2.................................................. 6-4
DirectLOGIC PLCs Password Protection.................................................................... 6-5
PLC Compatibility and Connection Charts................................................................ 6-5
AutomationDirect Controllers.................................................................................... 6-5
RS-422A/RS-485A Communications.......................................................................... 6-5
Allen-Bradley:............................................................................................................ 6-6
GE, Mitsubishi, Omron, Modicon and Siemens:........................................................ 6-6
How to use the PLC Compatibility and Connection Charts....................................... 6-7
Example:................................................................................................................... 6-7
Available Purchased Cables...................................................................................... 6-22
Available Purchased Cables – Wiring Diagrams...................................................... 6-24
User Constructed Cables – Wiring Diagrams.......................................................... 6-34
RS-422A/RS-485A Multi-Drop Wiring Diagram Examples....................................... 6-44
Chapter 6: PLC Communications
Introduction
1 The C-more® Micro-Graphic panels are capable of communicating with AutomationDirect
Productivity Series, Do-more, CLICK, SOLO, GS Drives and the entire DirectLOGIC
2 family of PLCs. The panel is capable of communicating using RS232, RS422 and RS485
serial communications and networks. When using the built in RJ12 serial port, designated as
Port 1, on the C-more Micro-Graphic panel to connect with AutomationDirect controllers,
3 your cabling choices are fairly simple.
• DV-1000CBL – connects to Productivity Series, Do-more, CLICK, DL05, DL06, DL105, DL205,
4 D3-350 and D4-450 phone jack.
• D4-1000CBL – connects to all DL405 CPU 15-pin ports.
5 The panel also has the ability to communicate with Allen-Bradley PLCs that support the Allen-
Bradley DF1 and DH485 protocols. Use of the Serial Port with DC Power Adapter module,
EA-MG-SP1, along with the following cables will allow connecting the panel to a majority of
6 Allen-Bradley PLCs.
• EA-MLOGIX-CBL – connects to AB MicroLogix 1000, 1100, 1200, 1400 & 1500
7 • EA-SLC-232-CBL – connects to AB SLC 5/03, /04, /05, ControlLogix, CompactLogix, FlexLogix
• EA-PLC5-232-CBL – connects to AB PLC5
8 • EA-DH485-CBL – connects to AB MicroLogix, SLC500, and any PLC using AB AIC device
The PLC Compatibility and Connection Chart tables on the following pages list the various
9 PLCs and protocols that can be configured. Other third party PLCs include GE, Mitsubishi,
Omron, Modicon and Siemens. The rest of this chapter is devoted to show the pin to pin
connections of available cables plus wiring diagrams that the user can refer to in order to
10 construct their own cables, along with wiring diagrams of cables that are not available for
purchase.
11 Note: A maximum cable length of 10 feet between the Micro-Graphic panel and the PLC is recommended
when powering the panel from the PLC.
12 The Serial Port with DC Power Adapter module, EA-MG-SP1, can be used if the application
13 requires the use of RS-422 or RS-485. The serial port on the adapter, designated as Port 2, can
also be wired for RS-232. The use of the adapter permits greater cable lengths. The panel can
also be connected to more than one PLC by using RS-422 or RS-485 wired in a multi-drop
14 configuration. See the example wiring diagrams at the end of this chapter for details.
PLC Drivers
Available PLC Protocols Serial - port1 or port2 Serial - port2 only*
A AutomationDirect Productivity Series
AutomationDirect Do-more
Allen-Bradley DF1 Half Duplex
Allen-Bradley DF1 Full Duplex
AutomationDirect CLICK Allen-Bradley PLC5 DF1
D technical support group at 770-844-4200. *Note: Use of serial port2 on C-more 3” Micro-Graphic requires the use of EA-MG-SP1
5 Port
2
DL06 PLC
6
C-more to
7 Direct LOGIC
VGA 15-pin port
C-more
Micro Graphic
serial cable Panel
8 p/n EA-2CBL-1
9 Port 2 (optional)
Serial Port w/
10 DC Power Adapter
EA-MG-SP1
PLC 15-pin serial
communications port 2
11
8 1 NOTE: If the DC
15 9 power adapter
is installed on
12 the panel, the
adapter must be
powered.
13
14 Expansion Pin Signal Pin Signal Pin Signal
Connector 1 Frame GND 6 LE 11 TXD+ (422/485)
2 TXD (232C) 7 CTS (232C) 12 TXD– (422/485)
A 3
4
5
RXD (232C)
Supplies +5VDC
Logic GND
8
9
RTS (232C)
RXD+ (422/485)
10 RXD– (422/485)
13 Term. Resistor
14 do not use
15 do not use
NOTE: The panel has one built-in RJ12 serial communications port (Port 1 - RS-232) and the option to add
one 15-pin serial communications port (Port 2 - RS-232/422/485) to the panel by installing the EA-MG-SP1
C module. Only one of the ports can be used with a connected PLC. The programming software allows the
user to select either Comm. Port1 or Comm. Port2 under the Panel Manager dialog box. When using Port
D 2 to communicate with the connected PLC, Port 1 can still be used with the EA-MG-PGM-CBL Software
Programming Cable Assembly to transfer projects between the PC and panel.
RS-422A/RS-485A Communications
14
When using the RS-422A/RS-485A communications capabilities of the C-more Micro-Graphic
Serial Port (Port 2), the termination resistor is placed between the RXD– and RXD+ terminals A
on the PLC side of the connection between the touch panel and PLC. The Termination
Resistor value is based on the characteristic impedance of the cable being used. To enable the B
built-in 120 Ohm Termination Resistor, jumper pin 13 (termination resistor) to pin 9 (RXD+)
on the C-more Micro-Graphic 15-pin PLC communications port.
C
D
®
EA1-MG-USER-M Hardware User Manual, 2nd Ed. Rev. F, 08/18
6-5
Chapter 6: PLC Communications
Allen-Bradley:
As stated in this chapter’s introduction, the panel also has the ability to communicate with
1 Allen-Bradley PLCs that support the Allen-Bradley DF1 and DH485 protocols. Use of the
Serial Port with DC Power Adapter module, EA-MG-SP1, is required. The chart for the
2 various Allen-Bradley PLCs includes recommended cables.
PLC Serial
5 Communications Port 2
6 Serial Port w/
DC Power Adapter
EA-MG-SP1
PLC 15-pin serial
communications port 2
8 1
7 15 9
8
9 Expansion
Connector
Pin
1
Signal
Frame GND
Pin
6 LE
Signal Pin Signal
11 TXD+ (422/485)
2 TXD (232C) 7 CTS (232C) 12 TXD– (422/485)
10 3
4
RXD (232C)
Supplies +5VDC
8
9
RTS (232C)
RXD+ (422/485)
13 Term. Resistor
14 do not use
5 Logic GND 10 RXD– (422/485) 15 do not use
12
13
14
A
B
C
D
®
D2-240
Port 1
RJ12 - 6 pin
K-sequence
DV-1000CBL
K-sequence
DV-1000CBL 12
Port 2 K-sequence, RS-232 K-sequence, RS-232
RJ12 - 6 pin
Port 1
Direct NET
DV-1000CBL
Direct NET
DV-1000CBL
13
Direct LOGIC
DL205 D2-250-1
RJ12 - 6 pin
Port 2
K-sequence,
Direct NET,
RS-232
DV-1000CBL
K-sequence,
Direct NET,
RS-232
DV-1000CBL 14
DB15HD Modbus RTU + FA-15HD Modbus RTU + FA-15HD
(female)
Port 1
RS-232
DV-1000CBL
RS-232
DV-1000CBL
A
RJ12 - 6 pin K-sequence, RS-232 K-sequence, RS-232
D2-260 Port 2 Direct NET,
Modbus RTU
DV-1000CBL Direct NET,
Modbus RTU
DV-1000CBL B
DB15HD + FA-15HD + FA-15HD
(female) RS-232 RS-232
C
D
®
EA1-MG-USER-M Hardware User Manual, 2nd Ed. Rev. F, 08/18
6-7
Chapter 6: PLC Communications
Port3
8 Analog
CPU’s
Terminal block
- 3 pin
Not Available Not Available
RS-232 DV-1000CBL
9 Productivity
all versions
RJ12 - 6 pin
RS-485
AutomationDirect
Productivity3000
RS-232
AutomationDirect
Productivity3000
Not Available
12 SOLO
Temperature all versions Data terminals Not Available Not Available
Controller
13
Port
GS Drives all versions Not Available Not Available
14 RJ12 - 6 pin
* Note: Wiring Diagrams for user constructed cables start on page 6-34.
A
B
C
D
®
Port1
Supported Network Type Supported Network Type 6
RJ12 - 6 pin DV-1000CBL EA-2CBL
CLICK
all versions
Port2
RJ12 - 6 pin Modbus (CLICK)
RS-232
Modbus (CLICK)
RS-232 7
Port3
Analog
CPU’s
Terminal block
- 3 pin
Not Available
* See Diagram 17
RS-232
8
Productivity
all versions
RS-232
RJ12 - 6 pin
RS-485
AutomationDirect
Productivity3000
DV-1000CBL
RS-232
AutomationDirect
Productivity3000
EA-2CBL
RS-232 9
Series Serial Serial * See Diagram 18
Terminal Block
- 3 pin
(P3-550)
Not Available
(P3-550) RS-232 10
Port 2 AutomationDirect DV-1000CBL AutomationDirect EA-2CBL
Do-more all versions
RJ12 - 6 pin Do-more Serial RS-232 Do-more Serial RS-232 11
AutomationDirect
SOLO
Temperature all versions Data terminals Not Available
SOLO
Temperature
* See Diagram 21
RS-485
12
Controller Controller
* See Diagrams
13
Port AutomationDirect
GS Drives all versions
RJ12 - 6 pin
Not Available
GS Drives
19 and 20
RS-485 14
* Note: Wiring Diagrams for user constructed cables start on page 6-34.
A
B
C
D
®
EA1-MG-USER-M Hardware User Manual, 2nd Ed. Rev. F, 08/18
6-9
Chapter 6: PLC Communications
DC Power Adapter
PLC Port Powered
4 Family CPU Port & Type Powered with 5 VDC from the
Powered from an external 24 VDC
source using the DC Power
connected PLC’s comm. port. Adapter, EA-MG-P1.
6 Port 1
RJ12 - 6 pin
Supported
K-sequence,
Network Type
DV-1000CBL
Supported
K-sequence,
Network Type
DV-1000CBL
all versions Direct NET, Direct NET,
7 Port 2
RJ12 - 6 pin
Modbus RTU
RS-232
Modbus RTU
RS-232
A Direct LOGIC
DL105
all versions
Port 1
RJ12 - 6 pin K-sequence
DV-1000CBL
RS-232
K-sequence
DV-1000CBL
RS-232
B
C
D
®
Port 1
Supported
K-sequence,
Network Type Supported
K-sequence,
Network Type
6
RJ12 - 6 pin DV-1000CBL EA-2CBL
all versions Direct NET, Direct NET,
Port 2
RJ12 - 6 pin
Modbus RTU
RS-232
Modbus RTU
RS-232
7
Port 1 DV-1000CBL EA-2CBL
Direct LOGIC
DL05
RJ12 - 6 pin RS-232 K-sequence,
Direct NET,
RS-232
EA-2CBL-1 8
K-sequence, RS-232
Modbus RTU
D0-DCM Port 2
DB15HD
Direct NET,
Modbus RTU
DV-1000CBL
+ FA-15HD
* See Diagram 1
RS-422 9
(female) RS-232 * See Diagram 2
Modbus RTU RS-485
Modbus only 10
Port 1 DV-1000CBL EA-2CBL
RJ12 - 6 pin RS-232 K-sequence,
Direct NET,
RS-232
EA-2CBL-1 11
K-sequence, RS-232
Modbus RTU
all versions Port 2
DB15HD
Direct NET,
Modbus RTU
DV-1000CBL
+ FA-15HD
* See Diagram 1
RS-422 12
(female) RS-232 * See Diagram 2
Direct LOGICDL06
Modbus RTU RS-485
Modbus only 13
Port 1 DV-1000CBL EA-2CBL
RJ12 - 6 pin RS-232 K-sequence,
Direct NET,
RS-232
EA-2CBL-1 14
K-sequence, RS-232
D0-DCM Port 2
DB15HD
Direct NET,
Modbus RTU
DV-1000CBL
+ FA-15HD
Modbus RTU * See Diagram 1
RS-422
A
(female) RS-232 * See Diagram 2
Modbus RTU RS-485
Modbus only
B
Direct LOGIC Port 1 DV-1000CBL EA-2CBL
DL105
all versions
RJ12 - 6 pin K-sequence
RS-232
K-sequence
RS-232 C
* Note: Wiring Diagrams for user constructed cables start on page 6-34.
D
®
EA1-MG-USER-M Hardware User Manual, 2nd Ed. Rev. F, 08/18
6-11
Chapter 6: PLC Communications
A
B
C
D
®
Family CPU Port & Type Powered from an external 24 VDC source using the
4
Serial Port with DC Power Adapter, EA-MG-SP1.
Using panel’s RJ12 port 1
Using adapter’s serial Port 2
DB 15-pin - female
5
Protocol(s) Components & Protocol(s) Components &
D2-230
Port 1
Supported
K-sequence
Network Type
DV-1000CBL
Supported
K-sequence
Network Type
EA-2CBL
6
RJ12 - 6 pin RS-232 RS-232
Port 1
RJ12 - 6 pin
K-sequence
DV-1000CBL
K-sequence
EA-2CBL
7
D2-240
RS-232 RS-232
Port 2
RJ12 - 6 pin
K-sequence,
Direct NET
K-sequence,
Direct NET 8
Port 1 DV-1000CBL EA-2CBL
RJ12 - 6 pin
K-sequence,
RS-232
K-sequence,
RS-232 9
EA-2CBL-1
D2-250-1 Direct NET, Direct NET,
Port 2
DB15HD Modbus RTU
DV-1000CBL
+ FA-15HD Modbus RTU
RS-232
* See Diagram 1
10
(female) RS-232
Direct LOGIC
Port 1 DV-1000CBL
RS-422
EA-2CBL
11
DL205
RJ12 - 6 pin RS-232 RS-232
K-sequence,
K-sequence,
Direct NET, EA-2CBL-1 12
Modbus RTU RS-232
D2-260 Direct NET,
Port 2
DB15HD Modbus RTU
DV-1000CBL
+ FA-15HD
* See Diagram 1
RS-422 13
(female) RS-232 * See Diagram 2
Modbus RTU RS-485
Modbus only 14
EA-4CBL-2
Port 1 K-sequence,
D2-DCM DB 25 pin
(female)
Direct NET,
Modbus RTU
* See Diagram 3
RS-232
Direct NET
RS-232
* See Diagram 6 A
RS-422
WINPLC
Port 1
RJ12 - 6 pin
Modbus RTU
DV-1000CBL
RS-232
Modbus RTU
EA-2CBL
RS-232
B
* Note: Wiring Diagrams for user constructed cables start on page 6-34.
C
D
®
EA1-MG-USER-M Hardware User Manual, 2nd Ed. Rev. F, 08/18
6-13
Chapter 6: PLC Communications
14
A
B
C
D
®
Family CPU Port & Type Powered from an external 24 VDC source using the
4
Serial Port with DC Power Adapter, EA-MG-SP1.
Using panel’s RJ12 port 1
Using adapter’s serial Port 2
DB 15-pin - female
5
Protocol(s) Components & Protocol(s) Components &
D3-232-DCU
Supported Network Type
* See Diagram 3
Supported Network Type
EA-4CBL-2
6
DB 25 pin Direct NET Direct NET
D3-330 or
D3-340
(female)
D3-422-DCU
RS-232 RS-232
7
* See Diagram 6
DB 25 pin Not Possible Direct NET
(female)
Port 1
RS-422
8
Direct NET Direct NET
D3-340
RJ11 - 4 pin
Port 2 Direct NET,
OP-3CBL-1
RS-232 Direct NET,
EA-3CBL
RS-232 9
Direct LOGIC RJ11 - 4 pin Modbus RTU Modbus RTU
DL305
Port 1 K-sequence, DV-1000CBL K-sequence, EA-2CBL 10
RJ12 - 6 pin Direct NET RS-232 Direct NET RS-232
D3-350 Port 2
DB 25 pin
K-sequence,
Direct NET,
* See Diagram 3
K-sequence,
Direct NET,
EA-4CBL-2
RS-232
11
RS-232 * See Diagram 4
(female)
Port 1
Modbus RTU
K-sequence,
Modbus RTU
RS-422
EA-4CBL-2
12
D3-DCM * See Diagram 3 RS-232
D3-350 only
DB 25 pin
(female)
Direct NET,
Modbus RTU
RS-232
Direct NET
* See Diagram 6
RS-422
13
* Note: Wiring Diagrams for user constructed cables start on page 6-34.
14
A
B
C
D
®
EA1-MG-USER-M Hardware User Manual, 2nd Ed. Rev. F, 08/18
6-15
Chapter 6: PLC Communications
* Note: Wiring Diagrams for user constructed cables start on page 6-34.
C
D
®
Family CPU Port & Type Powered from an external 24 VDC source using the
4
Serial Port with DC Power Adapter, EA-MG-SP1.
Using panel’s RJ12 port 1
Using adapter’s serial Port 2
DB 15-pin - female
5
Protocol(s) Components & Protocol(s) Components &
Port 0
Supported Network Type
D4-1000CBL
Supported Network Type
6
or DV-1000CBL EA-4CBL-1
D4-430
DB 15 pin
(female)
K-sequence
& FA-CABKIT
RS-232
K-sequence
RS-232
7
EA-4CBL-2
Port 1
DB 25 pin
K-sequence,
Direct NET
DV-1000CBL
& FA-CABKIT
K-sequence,
Direct NET
RS-232
* See Diagram 4
8
(female) RS-232
RS-422
Port 0
D4-1000CBL
or DV-1000CBL EA-4CBL-1
9
DB 15 pin K-sequence K-sequence
& FA-CABKIT RS-232
D4-440
(female)
RS-232
EA-4CBL-2
10
Port 1 DV-1000CBL
K-sequence, K-sequence, RS-232
DB 25 pin
(female)
Direct NET
& FA-CABKIT
RS-232
Direct NET * See Diagram 4
RS-422
11
Direct LOGIC D4-1000CBL
DL405
Port 0
DB 15 pin K-sequence
or DV-1000CBL
& FA-CABKIT
K-sequence
EA-4CBL-1
RS-232
12
(female)
RS-232
Port 1 K-sequence, DV-1000CBL K-sequence,
EA-4CBL-2
RS-232
13
DB 25 pin Direct NET, & FA-CABKIT Direct NET,
* See Diagram 4
D4-450 (female)
Port 3
Modbus RTU RS-232 Modbus RTU
K-sequence,
RS-422 14
* See Diagram 5
DB 25 pin Not Possible Direct NET,
(female) Modbus RTU
RS-422
A
Port 2 K-sequence, DV-1000CBL K-sequence, EA-2CBL
RJ12 - 6 pin Direct NET RS-232 Direct NET RS-232
EA-4CBL-2
B
Port 1 K-sequence,
D4-DCM DB 25 pin
(female)
Direct NET,
Modbus RTU
* See Diagram 3
RS-232
Direct NET
RS-232
* See Diagram 6 C
RS-422
* Note: Wiring Diagrams for user constructed cables start on page 6-34.
D
®
EA1-MG-USER-M Hardware User Manual, 2nd Ed. Rev. F, 08/18
6-17
Chapter 6: PLC Communications
Allen-Bradley PLCs
Panel Powered via PLC’s Port or EA-MG-P1, Port 1 Communications
1
PLC Compatibility & Connection Chart
2 PLC C-more Micro-Graphic Panel
Panel to PLC Cabling Components Required for
3 Specific Port and Protocol being used.
11 Allen-Bradley
FlexLogix
all
9-pin
D-sub port
12 Allen-Bradley
all
25-pin
D-sub port
PLC5 RJ45 8-pin
13 phone plug
14
A
B
C
D
®
Allen-Bradley PLCs
Panel Powered via EA-MG-SP1, Port 1 or Port 2 Communications
1
PLC Compatibility & Connection Chart
PLC C-more Micro-Graphic Panel 2
Panel to PLC Cabling Components Required for
Specific Port and Protocol being used. 3
Serial Port with DC Power Adapter
Family CPU Port & Type Powered from an external 24 VDC source using the
4
Serial Port with DC Power Adapter, EA-MG-SP1.
Using panel’s RJ12 port 1
Using adapter’s serial Port 2
DB 15-pin - female
5
Protocol(s) Components & Protocol(s) Components &
1000, 1100,
8-pin
Supported Network Type Supported Network Type
DF1 Full Duplex, EA-MLOGIX-CBL
6
Allen-Bradley mini-din port DF1 Half Duplex RS-232
MicroLogix
1200, 1400,
1500
RJ45 8-pin
phone plug
DH485/AIC/AIC+ EA-DH485-CBL 7
5/03, 5/04, 9-pin DF1 Full Duplex, EA-SLC-232-CBL
Allen-Bradley
SLC500
5/05
5/01, 5/02,
D-sub port
RJ45 8-pin
DF1 Half Duplex
DH485/AIC/AIC+
RS-232
EA-DH485-CBL
8
5/03 phone plug
Allen-Bradley
all
9-pin DF1 Full Duplex, EA-SLC-232-CBL 9
ControlLogix D-sub port
Not Possible
DF1 Half Duplex RS-232
Allen-Bradley
all
9-pin DF1 Full Duplex, EA-SLC-232-CBL 10
CompactLogix D-sub port DF1 Half Duplex RS-232
Allen-Bradley
all
9-pin DF1 Full Duplex, EA-SLC-232-CBL 11
FlexLogix D-sub port DF1 Half Duplex RS-232
Allen-Bradley 25-pin
EA-PLC5-232-CBL
RS-232
12
all DF1 Full Duplex
PLC5 D-sub port ** See Diagram 16
RS-422 13
** Note: Wiring Diagrams for user constructed cables start on page 6-34.
14
A
B
C
D
®
EA1-MG-USER-M Hardware User Manual, 2nd Ed. Rev. F, 08/18
6-19
Chapter 6: PLC Communications
90/30, 90/70
D-sub port
7 RJ45
GE Micro 90, Port 1
8 VersaMax
Micro
15-pin
D-sub port
Port 2
9 25-pin
D-sub port
Melsec
10 Mitsubishi FX Series
8-pin
mini-din port
11 C200
(Adapter),
25-pin Not Possible Not Possible
D-sub port
12 Omron
C500
CJ1, CS1,
25-pin
CQM1,
D-sub port
13 CPM1
984 CPU,
Quantum
14 Modicon
113 CPU,
AEG varies
Modicon
A Micro Series
110 CPU
9-pin
B Siemens
S7-200
CPU
D-sub port
0 or 1
C
D
®
Family CPU
PLC Port & 4
Type Powered from an external 24 VDC source.
15-pin
Supported Network Type Supported Network Type
EA-90-30-CBL
6
90/30, 90/70
D-sub port RS-422
RJ45 ** See Diagram 12
7
GE Micro 90, Port 1 SNPX RS-232
VersaMax
Micro
15-pin
D-sub port
EA-90-30-CBL
8
RS-422
Port 2
25-pin EA-MITSU-CBL 9
Melsec D-sub port RS-422
FX Series 8-pin
mini-din port
CPU Direct
EA-MITSU-CBL-1
RS-422
10
Mitsubishi 9-pin
D-sub port
** See Diagram 14
RS-232C
11
Q / QnA Q / QnA
6-pin
mini-din port Not Possible
** See Diagram 15
RS-232C 12
C200 (Adapter),
C500
25-pin
D-sub port
Host Link
EA-OMRON-CBL
RS-232 13
Omron CJ1, CS1,
CQM1, CPM1, 9-pin Host Link
** See Diagram
7&8
14
CPM2 D-sub port FINS
RS-232
C200 CPU
984 CPU,
A
Quantum
Modicon
113 CPU, AEG
Modicon
varies Modbus RTU
** See Diagram
9, 10 & 11 B
RS-232
Micro Series
110 CPU C
9-pin
S7-200 ** See Diagram 13
Siemens CPU
D-sub port
0 or 1
PPI
RS-485 D
** Note: Wiring Diagrams for user constructed cables start on page 6-34.
®
EA1-MG-USER-M Hardware User Manual, 2nd Ed. Rev. F, 08/18
6-21
Chapter 6: PLC Communications
14
A
B Part No. EA-2CBL Part No. EA-2CBL-1 Part No. EA-3CBL
C
D
Part No. EA-4CBL-1 Part No. EA-4CBL-2
A
B
C
Part No. EA-MITSU-CBL Part No. EA-MITSU-CBL-1 Part No. EA-OMRON-CBL
D
®
EA1-MG-USER-M Hardware User Manual, 2nd Ed. Rev. F, 08/18
6-23
Chapter 6: PLC Communications
7
TXD RXD 13 = do not use
3 = RXD 3 2 5 = Logic GND 12 = do not use
4 = TXD RXD TXD
4 = do not use 11 = do not use
5 = do not use GND 1 5 3 = RXD (232C) 10 = do not use
123456
6 = do not use
8 shield 1 2 = TXD (232C)
1 = Frame GND
1 9 = do not use
Note: Use the above wiring diagram if you need to make your own cable. We recommend using 22 AWG shielded cable.
9 Note: Only one C-more Micro-Graphic panel can be powered by an AutomationDirect PLC. If connecting
C-more Micro-Graphic panels to more than one port on and AutomationDirect PLC, the additional panel
10 must use an external power supply.
13 15-pin
HD D-sub
Wiring Diagram 15-pin
D-sub
TXD 2 3 RXD
(male)
14 8 = do not use 15 = do not use 8 = do not use (male) 15 = do not use
RXD 3 2 TXD
7 = Sig GND 15 14 = do not use 7 = do not use 15 14 = do not use
6 = do not use 13 = do not use GND 7 5 6 = donot use 13 = do not use
5 = CTS 12 = do not use 4 5 = Logic GND 12 = do not use
A 4 = RTS
3 = RXD
2 = TXD
1 6
11 = do not use
9 = do not use
RTS
10 = do not use CTS 5
4 = do not use
3 = RXD (232C)
2 = TXD (232C) 1
11 = do not use
10 = do not use
9 = do not use
1 = +5 VDC - N/C 1 1 = Frame GND
shield
B HD = High Density
Note: Use the above wiring diagram if you need to make your own cable. We recommend using 22 AWG shielded cable.
C
D
®
7
8
9
10
11
12
13
14
A
B
C
D
®
EA1-MG-USER-M Hardware User Manual, 2nd Ed. Rev. F, 08/18
6-25
Chapter 6: PLC Communications
3 Wiring Diagram
4 TXD 2 3 RXD
15-pin 3 2 15-pin
RXD TXD
D-sub D-sub
8 = YOM Sense (male) 15 = Logic GND online 4 5 8 = do not used (male) 15 = do not use
5 7 = CTS
6 = do not use
5 = do not use
15
14 = Logic GND
13 = Logic GND
12 = do not use
GND 13
GND 14
7 = do not used
6 = do not used
5 = Logic GND
15
14 = do not use
13 = do not use
12 = do not use
4 = Online 11 = do not use 4 = do not used 11 = do not use
GND 15
6 3 = RXD (232C)
2 = TXD (232C)
1 = YOP Sense 1
10 = do not use
9 = do not use YOP
CTS
1
7
3 = RXD (232C)
2 = TXD (232C) 1
1 = Frame GND
10 = do not use
9 = do not use
8
7
See PLC user manual YOM
for pin out details.
shield 1
Note: Use the above wiring diagram if you need to make your own cable. We recommend using 22 AWG shielded cable.
8
9 Direct LOGIC: EA-4CBL-2
To PLC Direct Logic PLC 25-pin D-sub port: DL405, D3-350, To C-more Micro-Graphic
11 Wiring Diagram
25-pin 15-pin
12 11 = do not use
D-sub
13 = do not use (male) 25 = do not use TXD 2
12 = do not use 25 24 = do not use
23 = do not use RXD
3
3 RXD 8 = do not use
2 TXD 7 = do not use
D-sub
(male) 15 = do not use
14 = do not use
15 13 = do not use
10 = do not use 6 = do not use
22 = do not use GND 7 5
13 9 = do not use
8 = do not use
7 = Signal GND
21 = do not use
20 = do not use RTS 4
5 = Logic GND
4 = do not use
3 = RXD (232C)
12 = do not use
11 = do not use
10 = do not use
6 = do not use 19 = do not use CTS 5 2 = TXD (232C) 1 9 = do not use
14 5 = CTS
4 = RTS
3 = RXD
18 = do not use
17 = do not use
16 = do not use
shield 1
1 = Frame GND
B
C
D
®
6
4 = TXD +5 V +5 V 4 = TXD
5 = not used GND 1 6 GND 5 = +5 VDC
6 = Sig GND 6 = Sig GND
123456 123456
7
Note: Only one C-more Micro-Graphic panel can be powered by an AutomationDirect PLC. If connecting
C-more Micro-Graphic panels to more than one port on and AutomationDirect PLC, the additional panel
must use an external power supply.
8
9
Direct LOGIC: OP-3CBL-1
To PLC
Direct Logic PLC RJ11 port: D3-340 Port 1 & 2
RS-232C (p/n OP-3CBL-1)
To C-more
Micro-Graphic
10
RJ11 Port Serial Port 1
11
RJ11 4-pin RJ12 6-pin
Phone Plug
(4P4C) Wiring Diagram
Phone Plug
(6P6C) 1 = Sig GND
2 = not used
12
1 = RXD RXD 1 4 TXD 3 = RXD
2 = TXD
3 = do not use
4 = Sig GND
TXD
GND
2
4
3
1
RXD 4 = TXD
5 = +5 VDC
6 = Sig GND
13
1234 123456
Note: Use the above wiring diagram if you need to make your own cable. We recommend using 22 AWG shielded cable. 14
A
B
C
D
®
EA1-MG-USER-M Hardware User Manual, 2nd Ed. Rev. F, 08/18
6-27
Chapter 6: PLC Communications
3
15-pin
4 1 = do not use
2 = Sig GND
Mini Din
8-pin Male Wiring Diagram 8 = do not use
7 = do not use
D-sub
(male) 15 = do not use
14 = do not use
3 = do not use TXD 7 3 RXD 6 = do not use 15 13 = do not use
0.290”
5 4 = RXD 6 7 8
3 4 5 4 2 5 = Logic GND 12 = do not use
5 = do not use RXD TXD
1 2 4 = do not use 11 = do not use
6 = do not use GND 2 5 3 = RXD (232C) 10 = do not use
0.35”
7 = TXD DIA. Nonstandard 1 2 = TXD (232C) 1 9 = do not use
shield
6 8 = do not use keying 1 = Frame GND
Note: Use the above wiring diagram if you need to make your own cable. We recommend using 22 AWG shielded cable.
7 EA-SLC-232-CBL
To PLC
Allen-Bradley SLC 5-03/04/05, ControlLogix, CompactLogix, To C-more Micro-Graphic
EA-MG-SP1 Serial Port
8 9-Pin Port FlexLogix, DF1, RS-232C (p/n EA-SLC-232-CBL) with DC Power Adapter
9 9-pin
D-sub
15-pin
D-sub
(female) Wiring Diagram 8 = do not use (male) 15 = do not use
10 1 = do not use 1
2 = RXD
6 = do not use TXD
7 = do not use
3
2
3
2
7 = do not use
RXD 6 = do not use
5 = Logic GND
15
14 = do not use
13 = do not use
12 = do not use
3 = TXD 8 = do not use RXD TXD
4 = do not use 11 = do not use
11 4 = do not use
5 = Signal GND 9
9 = do not use GND 5
shield
5
1
3 = RXD (232C)
2 = TXD (232C) 1
1 = Frame GND
10 = do not use
9 = do not use
12 Note: Use the above wiring diagram if you need to make your own cable. We recommend using 22 AWG shielded cable.
EA-PLC5-232-CBL
13 To PLC
25-Pin Port
Allen-Bradley PLC5, DF1, To C-more Micro-Graphic
EA-MG-SP1 Serial Port
RS-232C (p/n EA-PLC5-232-CBL) with DC Power Adapter
14
A 25-pin
D-sub
13 = do not use (male) 25 = do not use TXD 2
Wiring Diagram
Wiring Diagram
3
1 = TXD/RXD+
RJ45 8-pin
Phone Plug
(8P8C)
13 Term.
15-pin
D-sub
4
2 = TXD/RXD– TXD/RXD+ 1 9 RD+ 8 = do not use (male) 15 = do not use
3 = do not use
4 = Signal GND
5 = LE
TXD/RXD– 2 10
11
RD–
SD+
7 = do not use
6 = LE
5 = Logic GND
15
14 = do not use
13 = Termination
12 = SD– (RS485)
5
6 = do not use 12 4 = do not use 11 = SD+ (RS485)
7 = Signal GND
8 = do not use LE * 5
4
6
SD–
LE *
3 = do not use
2 = do not use 1
1 = Frame GND
10 = RD– (RS485)
9 = RD+ (RS485) 6
GND
GND 7
shield
5
1
* Note: The LE signal is wired in the cable
as shown, but not required for
point-to-point communications.
7
Note: Use the above wiring diagram to make your own cable. We recommend AutomationDirect p/n L19954 shielded cable or equivalent.
Allen-Bradley SLC500™, 5/01, /02, /03 DH-485/AIC to Multiple C-more Micro-Graphic Panels
8
RS-485A (using C-more cable p/n EA-DH485-CBL)
Allen-Bradley
SLC 500 Modular
DH-485 Link
(See manufacturer’s litature for details.)
9
PLC Controller
DH-485
Peripheral
J2
DH-485
Peripheral
J2
10
Channel 1 must be
set to DH485.
CPU
J1
Power
CPU
J1
Power 11
AB 1747-AIC AB 1747-AIC
DH485 Link Coupler DH485 Link Coupler
12
AB 1747-C11 A
13
Cable
14
A
B
C-more C-more
Micro-Graphic Micro-Graphic
Panel Panel
C-more
EA-DH485-CBL
C-more
EA-DH485-CBL
C
Cable Cable
Note: The above diagram shows connecting multiple C-more Micro-Graphic panels to an Allen-Bradley DH485/AIC network
using the AB DH485 Link Coupler, p/n 1747-AIC. Select the “Allen-Bradly DH485/AIC SLC500 MircroLogix” driver in the
C-more Micro Programming Software when starting the project. Also, set the AB channel configuration for DH485.
D
®
EA1-MG-USER-M Hardware User Manual, 2nd Ed. Rev. F, 08/18
6-29
Chapter 6: PLC Communications
3 Allen-Bradley
SLC 5/03 Modular
DH-485 Link
(See manufacturer’s litature for details.)
PLC Controller
4
5 Channel 0 must be
set to DH485.
AB 1761-NET-AIC AB 1761-NET-AIC
6 AIC + Advanced
Interface Converter
AIC + Advanced
Interface Converter
C-more
Serial Port w/
7
Serial Port w/ EA-MLOGIX-CBL
DC Power Adapter DC Power Adapter Cable
EA-MG-SP1 EA-MG-SP1
AB 1747-CP3
RS-232 Cable
8 To additional
C-more
9 C-more
Micro-Graphic
C-more
Micro-Graphic
Touch Panel
Panel Panel
10
11 C-more
EA-MLOGIX-CBL
Cable
C-more
EA-SLC-232-CBL
Cable
12 Note: The above diagram shows connecting multiple C-more Micro-Graphic panels to an Allen-Bradley DH485/AIC network using the
AB AIC+ Advanced Interface Converter, p/n 1761-NET-AIC. Select the “Allen-Bradly DH485/AIC SLC500 MircroLogix” driver
in the C-more Micro Programming Software when starting the project. Also, set the AB channel configuration for DH485.
13
14
A
B
C
D
®
5
6 = do not use 13 = SD(B) 15
5 = +5V 12 = SD(A) RD(B’) 11 11 SD+ 6 = do not use 13 = Termination
5 = Logic GND 12 = SD– (RS422)
4 = do not use 11 = RD(B’) RD(A’) 10 12 SD– 4 = do not use 11 = SD+ (RS422)
3 = do not use 10 = RD(A’) 7 5 3 = do not use 10 = RD– (RS422)
6
2 = do not use 9 = do not use GND
2 = do not use 1 9 = RD+ (RS422)
1 = do not use 1 CTS(B’) 8
1 = Frame GND
CTS(A’) 15
7
+5V 5
shield 1
Note: Use the above wiring diagram to make your own cable. We recommend AutomationDirect p/n L19853 shielded cable or equivalent.
8
9
10
11
12
13
14
A
B
C
D
®
EA1-MG-USER-M Hardware User Manual, 2nd Ed. Rev. F, 08/18
6-31
Chapter 6: PLC Communications
3
Wiring Diagram
4 13 = do not use
12 = do not use
25-pin
D-sub
(male) 25 = do not use SD+ 3
13 Term.
9 RD+
15-pin
D-sub
8 = do not use (male) 15 = do not use
25 24 = do not use SD– 16 10 RD– 7 = do not use
11 = do not use 14 = do not use
5
23 = do not use 15
10 = do not use 22 = do not use RD+ 2 11 SD+ 6 = do not use 13 = Termination
9 = do not use 21 = do not use RD– 15 5 = Logic GND 12 = SD– (RS422)
8 = do not use 12 SD–
20 = do not use 4 = do not use 11 = SD+ (RS422)
7 = Signal GND 7 5 3 = do not use 10 = RD– (RS422)
6 6 = do not use
5 = do not use
4 = Signal GND
19 = do not use GND
18 = do not use GND 4
17 = do not use
shield 1
2 = do not use 1
1 = Frame GND
9 = RD+ (RS422)
7 2 = RD+ (RS422) 1
1 = do not use
15 = RD– (RS422)
14 = do not use
Note: Use the above wiring diagram ito make your own cable. We recommend AutomationDirect p/n L19853 shielded cable or equivalent.
8
9 EA-MITSU-CBL-1
To C-more Micro-Graphic
Mitsubishi FX Series 8-pin MINI-DIN, EA-MG-SP1 Serial Port
10 To PLC
8-Pin Port
RS-422A (p/n EA-MITSU-CBL-1) with DC Power Adapter
11 Mini Din
8-pin Male
Wiring Diagram 13 Term. 15-pin
D-sub
1 = RD– (RS-422) 7 9
SD+ RD+ 8 = do not use (male) 15 = do not use
12 2 = RD+ (RS-422)
3 = Sig GND
4 = SD– (RS-422) 3
6
4
7
5
8
SD–
RD+
4
2
10
11
RD–
SD+
7 = do not use
6 = do not use
5 = Logic GND
15
14 = do not use
13 = Termination
12 = SD– (RS422)
5 = do not use 1 2
1 12 4 = do not use
13 6 = do not use RD– SD– 11 = SD+ (RS422)
3 5 3 = do not use 10 = RD– (RS422)
7 = SD+ (RS-422) GND 2 = do not use 9 = RD+ (RS422)
8 = do not use 1 1
shield 1 = Frame GND
14 Note: Use the above wiring diagram ito make your own cable. We recommend AutomationDirect p/n L19853 shielded cable or equivalent.
A
B
C
D
®
13 = do not use
12 = do not use
25-pin
D-sub
(male) 25 = do not use TXD 2 3 RXD 8 = do not use
15-pin
D-sub
(male) 15 = do not use
4
25 24 = do not use 3 2 7 = do not use 14 = do not use
11 = do not use 23 = do not use RXD TXD
5
6 = do not use 15 13 = do not use
10 = do not use 22 = do not use GND 7 5
9 = do not use 5 = Logic GND 12 = do not use
21 = do not use 4 4 = do not use 11 = do not use
8 = do not use
7 = Signal GND 20 = do not use RTS 3 = RXD (232C) 10 = do not use
19 = do not use CTS 5
6 = do not use
5 = CTS
4 = RTS
18 = do not use
17 = do not use shield 1
2 = TXD (232C) 1
1 = Frame GND
9 = do not use
6
3 = RXD 16 = do not use
2 = TXD
1 = do not use
1 15 = do not use
14 = do not use
Note: Use the above wiring diagram if you need to make your own cable. We recommend using 22 AWG shielded cable.
7
8
9
10
11
12
13
14
A
B
C
D
®
EA1-MG-USER-M Hardware User Manual, 2nd Ed. Rev. F, 08/18
6-33
Chapter 6: PLC Communications
3 To 15-pin HD
PLC Port
RS-232 RXD
To C-more Micro-Graphic
4 TERMINATE
RS-232 TXD
+5V
Wiring Diagram
5
EA-MG-SP1 Serial Port
with DC Power Adapter
SIGNAL GND 15-pin
5 ZL-CMA15L
RXD
RS-422/485 RX–
RS-422/485 TX–
Pair 1
12
11
SD–
SD+
8 = do not use
7 = do not use
D-sub
(male) 15 = do not use
14 = do not use
10 15
TXD RS-422/485 RX+ RD– 6 = do not use 13 = Termination
6 RS422/485 232
RS-422/485 TX+
Pair 2 9
RD+
5 = Logic GND
4 = do not use
12 = SD– (RS422)
TX+
RX+
TXD
RXD
+5V
11 = SD+ (RS422)
TX-
RX-
SG
Note: Use the above wiring diagram to make your own cable. We recommend AutomationDirect p/n L19853 shielded cable or equivalent.
8
9 Diagram 2 User Constructed
10 Direct LOGIC DL06, D2-250, D2-250-1, D2-260 using ZIPLink ZL-CMA15L Adapter Module
(all Port 2) RS-485A
11 To 15-pin HD
PLC Port
RS-232 RXD
12
To C-more Micro-Graphic
RS-232 TXD Wiring Diagram EA-MG-SP1 Serial Port
+5V with DC Power Adapter
TERMINATE
13 ZL-CMA15L
RXD
RS-422/485 RX–
RS-422/485 TX–
12
11
SD–
SD+
8 = do not use
7 = do not use
D-sub
(male) 15 = do not use
14 = do not use
10 15
6 = do not use
14 TXD RS-422/485 RX+ RD– 13 = Termination
RS422/485 232 9 5 = Logic GND 12 = SD– (RS485)
RS-422/485 TX+ RD+ 4 = do not use
TX+
RX+
TXD
RXD
+5V
11 = SD+ (RS485)
TX-
RX-
SG
B
C NOTE: The RS-422 and RS-485 wiring diagrams shown above are not for multi-drop networks involving
connecting more than one PLC to a panel. Refer to the wiring diagram examples starting on page 6-40 if
3
25-pin Wiring Diagram
13 = do not use
12 = do not use
D-sub
(male) 25 = do not use TXD
25 24 = do not use
2 3 RXD RJ12 6-pin
Phone Plug
4
3 4 TXD 1 = Sig GND
11 = do not use 23 = do not use RXD (6P6C)
10 = do not use
9 = do not use
8 = do not use
22 = do not use GND 7
21 = do not use
20 = do not use RTS
4
6 2 = do not use
3 = RXD
4 = TXD
5
7 = Signal GND 5 = +5 VDC
19 = do not use CTS 5
6 = +5 VDC
5 = CTS
4 = RTS
18 = do not use +5 V 6
17 = do not use
shield
5 +5 V
123456
6 = Sig GND
6
3 = RXD 16 = do not use
7
2 = TXD 1 15 = do not use
1 = do not use 14 = do not use
Note: Use the above wiring diagram if you need to make your own cable. We recommend using 22 AWG shielded cable.
10
13 = do not use
25-pin
D-sub
(male) 25 = do not use TXD+ 14
Wiring Diagram 13
9
Term.
RD+
15-pin
D-sub 11
12 = do not use 24 = do not use 8 = do not use (male) 15 = do not use
16 10
11 = CTS+
10 = RXD–
(RS422)
25 23 = CTS–
22 = do not use
21 = do not use
TXD–
RXD+ 9
10
11
12
RD– 7 = do not use
SD+
6 = do not use
5 = Logic GND
15
14 = do not use
13 = Termination
12 = SD– (RS422)
12
9 = RXD+ RXD– SD– 4 = do not use 11 = SD+ (RS422)
20 = do not use
7=0V
(RS422)
8 = do not use
6 = do not use
19 = RTS+
18 = RTS–
17 = do not use
0V
RTS–
7
18
5 3 = do not use
2 = do not use 1
1 = Frame GND
10 = RD– (RS422)
9 = RD+ (RS422) 13
CTS– 23
5 = do not use 16 = TXD–
4 = do not use
3 = do not use
2 = do not use
1
(RS422)
15 = do not use
14 = TXD+
RTS+
CTS+
19
11
14
1 = do not use (RS422) 1
A
shield
Note: Use the above wiring diagram to make your own cable. We recommend AutomationDirect p/n L19853 shielded cable or equivalent.
B
NOTE: The RS-422 wiring diagram shown above is not for multi-drop networks involving connecting more
than one PLC to a panel. Refer to the wiring diagram examples starting on page 6-40 if more than one PLC
C
will be connected to a panel.
D
®
EA1-MG-USER-M Hardware User Manual, 2nd Ed. Rev. F, 08/18
6-35
Chapter 6: PLC Communications
3
4 13 = TXD–
(RS422)
25-pin
D-sub
(male)
25 = RXD–
(RS422) TXD+ 12
Wiring Diagram 13
9
Term.
RD+
8 = do not use
15-pin
D-sub
(male)
24 = RXD+ 15 = do not use
12 = TXD+ 13 10
5 RD– 7 = do not use 14 = do not use
25 TXD–
(RS422) (RS422) 15
24 11 6 = do not use 13 = Termination
11 = do not use 23 = do not use RXD+ SD+
10 = do not use 5 = Logic GND 12 = SD– (RS422)
22 = do not use RXD– 25 12 SD– 4 = do not use
9 = do not use 21 = do not use 11 = SD+ (RS422)
6 8 = do not use
7=0V
6 = do not use
20 = do not use
19 = do not use
18 = do not use
0V 7
shield
5
1
3 = do not use
2 = do not use 1
1 = Frame GND
10 = RD– (RS422)
9 = RD+ (RS422)
5 = do not use
17 = do not use
7 4 = do not use
3 = do not use
2 = do not use
1 = do not use
1
16 = do not use
15 = do not use
14 = do not use
8 Note: Use the above wiring diagram to make your own cable. We recommend AutomationDirect p/n L19853 shielded cable or equivalent.
10 25-Pin Port
RS-422A
EA-MG-SP1 Serial Port
with DC Power Adapter
13 9 = do not use
8 = do not use
7=0V
20 = do not use
19 = do not use
18 = do not use
RXD–
0V
16
7
12
5
5 = Logic GND
SD– 4 = do not use
3 = do not use
12 = SD– (RS422)
11 = SD+ (RS422)
10 = RD– (RS422)
6 = do not use 2 = do not use 1 9 = RD+ (RS422)
17 = RXD+ 11
14 5 = do not use
4 = do not use
3 = do not use
2 = do not use
(RS422)
16 = RXD–
(RS422)
RTS–
CTS– 13
10
1 = Frame GND
B Note: Use the above wiring diagram to make your own cable. We recommend AutomationDirect p/n L19853 shielded cable or equivalent.
C NOTE: The RS-422 wiring diagrams shown above are not for multi-drop networks involving connecting more
than one PLC to a panel. Refer to the wiring diagram examples starting on page 6-40 if more than one PLC
9-pin 15-pin
10
D-sub D-sub
1 = do not use
(male)
9
6 = do not use TXD 3
Wiring Diagram
3 RXD
8 = do not use
7 = do not use
6 = do not use
(male)
15
15 = do not use
14 = do not use
13 = do not use
11
2 = RXD 7 = do not use 5 = Logic GND 12 = do not use
12
3 = TXD 2 2
8 = do not use RXD TXD 4 = do not use 11 = do not use
4 = do not use 9 = do not use GND 5 5 3 = RXD (232C) 10 = do not use
5 = Signal GND 1 2 = TXD (232C) 9 = do not use
1 1 = Frame GND 1
13
shield
Note: Use the above wiring diagram to make your own cable. We recommend using 22 AWG shielded cable.
14
A
B
C
D
®
EA1-MG-USER-M Hardware User Manual, 2nd Ed. Rev. F, 08/18
6-37
Chapter 6: PLC Communications
3
9-pin 15-pin
4 D-sub
(male) Wiring Diagram
D-sub
8 = do not use (male)
7 = do not use
15 = do not use
14 = do not use
1 = do not use 9 3 3
6 = DSR TXD RXD 6 = do not use 15 13 = do not use
5 2 = RXD
3 = TXD
4 = DTR
7 = RTS
8 = CTS
9 = do not use
RXD
GND
2
5
2
5
TXD
5 = Logic GND
4 = do not use
3 = RXD (232C)
12 = do not use
11 = do not use
10 = do not use
5 = Signal GND 1 2 = TXD (232C) 1
4 9 = do not use
6 DTR
DSR 6
7
1 = Frame GND
RTS
7 CTS 8
shield 1
Note: Use the above wiring diagram to make your own cable. We recommend using 22 AWG shielded cable.
14
A
B
C
D
®
3
1 = do not use
2 = do not use
RJ45 8-pin
Phone Plug
(8P8C) TXD 3
Wiring Diagram
3 RXD
8 = do not use
15-pin
D-sub
(male) 15 = do not use
4
RXD 4 2 TXD 7 = do not use
5
3 = TXD 15 14 = do not use
4 = RXD GND 5 5 6 = donot use 13 = do not use
5 = Logic GND 6 5 = Logic GND 12 = do not use
6 = RTS RTS 4 = do not use 11 = do not use
7
7 = CTS
8 = do not use
CTS
shield 1
3 = RXD (232C)
2 = TXD (232C) 1
1 = Frame GND
10 = do not use
9 = do not use 6
Note: Use the above wiring diagram to make your own cable. We recommend using 22 AWG shielded cable.
7
Diagram 12 User Constructed 8
To C-more Micro-Graphic
GE VersaMax Micro Port 1
To PLC
RJ45 Port 1
RS-232C
EA-MG-SP1 Serial Port
with DC Power Adapter 9
RJ45 8-pin
10
15-pin
Phone Plug
1 = RTS
2 = CTS
3 = RXD
(8P8C)
TXD 4
Wiring Diagram
3
8 = do not use
RXD 7 = do not use
D-sub
(male)
15
15 = do not use
14 = do not use
11
4 = TXD RXD 3 2 TXD 6 = donot use 13 = do not use
5 = DCD
6 = DTR
7 = +5V
GND 8
shield
5
1
5 = Logic GND
4 = do not use
3 = RXD (232C)
12 = do not use
11 = do not use
10 = do not use
12
8 = GND 2 = TXD (232C) 1 9 = do not use
1 = Frame GND
Note: Use the above wiring diagram to make your own cable. We recommend using 22 AWG shielded cable.
13
14
A
B
C
D
®
EA1-MG-USER-M Hardware User Manual, 2nd Ed. Rev. F, 08/18
6-39
Chapter 6: PLC Communications
3
Wiring Diagram
4 9-pin
D-sub
(male)
RS-485
Signal B
3
13
9
Term.
RD+
15-pin
D-sub
8 = do not use (male) 15 = do not use
9 11 SD+ 7 = do not use 14 = do not use
5
1 = Logic Com 6 = +5 VDC 15
2 = Logic Com RS-485 8 10 6 = do not use 13 = Termination
7 = +24 VDC RD–
3 = RS485 Sig B Signal A 5 = Logic GND 12 = SD– (RS485)
8 = RS485 Sig A 12 SD– 4 = do not use
4 = do not use 11 = SD+ (RS485)
9 = do not use Logic 5 5 3 = do not use 10 = RD– (RS485)
6 5 = Logic Com 1 Common
shield 1
2 = do not use 1
1 = Frame GND
9 = RD+ (RS485)
Note: Use the above wiring diagram to make your own cable. We recommend AutomationDirect L19954 shielded cable or equivalent.
7
Diagram 14 User Constructed
8 Mitsubishi Q / QnA Serial PLC To C-more Micro-Graphic
To PLC EA-MG-SP1 Serial Port
9-Pin Port QJ71C24N
9 RS-232C
with DC Power Adapter
10 1
Wiring Diagram
CD
11
9-pin 4 15-pin
D-sub DTR D-sub
(female) DSR 6 8 = do not use (male) 15 = do not use
1 7 7 = do not use 14 = do not use
1 = CD 6 = DSR RS
12
6 = do not use 15 13 = do not use
2 = RXD 7 = RS 8
CS 5 = Logic GND 12 = do not use
3 = TXD 8 = CS 3 3 4 = do not use 11 = do not use
4 = DTR 9 = do not use TXD RXD
3 = RXD (232C) 10 = do not use
5 = Signal GND 9 2 2
13 RXD
GND 5
shield
5
1
TXD 2 = TXD (232C)
1 = Frame GND
1 9 = do not use
14 Note: Use the above wiring diagram if you need to make your own cable. We recommend using 22 AWG shielded cable.
A
B
C
D
®
1 = RXD (232C)
Mini Din
6-pin Male Wiring Diagram 8 = do not use
D-sub
(male) 15 = do not use
4
2 = TXD (232C) 7 = do not use 15 14 = do not use
2 3
5
3 = Logic GND TXD RXD 6 = donot use 13 = do not use
4 = do not use 5 6 RXD 1 2 TXD 5 = Logic GND 12 = do not use
5 = do not use 4 = do not use 11 = do not use
3 4 GND 3 5
3 = RXD (232C) 10 = do not use
6 = do not use
1 2
shield 1 2 = TXD (232C)
1 = Frame GND
1 9 = do not use
Note: Use the above wiring diagram to make your own cable. We recommend using 22 AWG shielded cable.
6
7
Diagram 16 User Constructed
8
To PLC Allen Bradley PLC5 DF1 To C-more Micro-Graphic EA-MG-SP1
9
25-Pin Port
RS-422 Serial Port with Power Adapter
2 CLICK
Com Port 3 Analog CPU
RS-485
EA-MG-SP1 Serial Port
with DC Power Adapter
4 RS-485 Signal A +
RS-485
Signal A
3
Term.
9
11
RD+
SD+ 7 = do not use
D-sub
8 = do not use (male) 15 = do not use
14 = do not use
15
RS-485 8 10 6 = do not use 13 = Termination
5 RS-485 Signal B
Logic Ground
-
LG
Signal B
Logic 5
12
5
RD–
SD–
5 = Logic GND
4 = do not use
3 = do not use
12 = SD– (RS485)
11 = SD+ (RS485)
10 = RD– (RS485)
Ground 2 = do not use 1 9 = RD+ (RS485)
6 shield 1 1 = Frame GND
Note: Use the above wiring diagram to make your own cable. We recommend AutomationDirect p/n L19954 shielded cable or equivalent.
Use 120 ohm resistors as termination resistors (Term.)
7
Diagram 18 User Constructed
8 Removable Connector
AutomationDirect Productivity PAC
RS-485
To C-more Micro-Graphic
EA-MG-SP1 Serial Port
included with with DC Power Adapter
9
Productivity3000 CPU
10 TXD+ / RXD+ 3
Wiring Diagram 13
9
Term.
RD+
15-pin
D-sub
(male)
8 = do not use 15 = do not use
11
11 TXD+ / RXD+ + Term. SD+ 7 = do not use 14 = do not use
15
8 10 6 = do not use 13 = Termination
TXD- / RXD- - TXD- / RXD- RD–
5 = Logic GND 12 = SD– (RS485)
12 SD– 4 = do not use
Ground G 11 = SD+ (RS485)
12 Ground 5
shield
5
1
3 = do not use
2 = do not use 1
1 = Frame GND
10 = RD– (RS485)
9 = RD+ (RS485)
13 Note: Use the above wiring diagram to make your own cable. We recommend AutomationDirect p/n L19954 shielded cable or equivalent.
Use 120 ohm resistors as termination resistors (Term.)
C 4: SG + SD+
RD+
shield TERM
D EA-COMCON-3
Note: Use the above wiring diagram to make your own cable. We recommend AutomationDirect p/n L19772 shielded cable or equivalent.
12
11 12
A
DATA –
1
RS-485
2
DATA +
Note: Use the above wiring diagram to make your own cable. We recommend AutomationDirect p/n L199772 shielded cable or equivalent. B
C
D
®
EA1-MG-USER-M Hardware User Manual, 2nd Ed. Rev. F, 08/18
6-43
Chapter 6: PLC Communications
RXD
(Slave)
Cable Adapter
5
TXD
RS422/485 232
TX+
RX+
TXD
RXD
+5V
TX-
RX-
SG
(ZL-CMA15L shown)
Port 2
6 ZL-CMA15L
(Slave)
Shielded Cable
When connecting to a DirectLogic PLC
RXD
Cable Adapter
7
TXD
TXD
RXD
+5V
TX-
RX-
SG
(ZL-CMA15L shown)
Shielded Cable
8
9
10 Notes: 1. We recommend Belden 8103 shielded cable or equivalent.
2. Wiring Diagram for this example, ZL-CMA15(L)
RXD+
RXD–
RXD–
TXD+
TXD+
RTS+
CTS+
RTS+
CTS+
TXD–
TXD–
RTS–
CTS–
RTS–
CTS–
GND
GND
12 7 10 9 6
*
13 11 14 12 15 7 10 9 6 13 11 14 12 15
13 15-pin
HD D-sub
8 = do not use (male) 15 = CTS–
7 = Sig GND 14 = CTS+
8
7
6 = RXD– 15 13 = RXD+ 6
A RXD+
HD = High Density
RXD+
RXD– RXD–
B TXD+
TXD–
TXD+
TXD–
C
Signal GND Signal GND
shield
* Termination resistors required at both ends of the
network receive data signals to match the impedance
of the cable (between 100 and 500 ohms).
TXD
RXD
+5V
TX-
RX-
SG
Shielded Cable
When connecting to a DirectLogic PLC
use connector ZL-CMA15L or ZL-CMA15
8
9
Notes: 1. We recommend Belden 8103 shielded cable or equivalent.
2. Wiring Diagram for this example, ZL-CMA15(L) 10
To C-more Micro-Graphic Serial Port
To DL06 PLC port 2
used as example
w/ DC Power Adapter EA-MG-SP1.
11
Term.
RXD+
RXD–
TXD+
RTS+
CTS+
TXD–
RTS–
CTS–
SHD
RD+
RD–
SD+
GND
SD–
GND
*
7 10 9 6 13 11 14 12 15 5 10 9 12 11 13 1
12
15-pin
7 = Sig GND
HD D-sub
8 = do not use (male) 15 = CTS–
14 = CTS+
15-pin
8 = do not use D-sub 15 = do not use
13
7 = do not use (male)
6 = RXD– 15
13 = RXD+ 14 = do not use
15
14
5 = do not use 12 = RTS- 6 = do not use 13 = Termination
4 = do not use 11 = RTS+ 5 = Logic GND 12 = SD– (RS422)
3 = do not use 1 10 = TXD– 4 = do not use 11 = SD+ (RS422)
2 = do not use 6 9 = TXD+ 3 = do not use 10 = RD– (RS422)
1 = do not use 2 = do not use 1 9 = RD+ (RS422)
HD = High Density
RXD+
1 = Frame GND
RXD+
A
RXD– RXD–
TXD+
TXD–
TXD+
TXD–
B
C
Signal GND Signal GND
shield shield
* network
Termination resistors required at both ends of the
receive data signals to match the impedance
of the cable (between 100 and 500 ohms). Jumper pin
Typical RS-422 Multi-Drop Wiring Diagram (cont’d)
using DirectLogic pin numbers to illustrate
13 to 9 on the C-more 6” Micro-Graphic Serial Port2
15-pin connector to place the 120 internal resistor
into the network. If the cable impedance is different,
D
then use an external resistor matched to the cable
impedance.
®
EA1-MG-USER-M Hardware User Manual, 2nd Ed. Rev. F, 08/18
6-45
Chapter 6: PLC Communications
3
Port 2
4 (Slave) ZL-CMA15L
RXD
(Slave)
ZL-CMA15 or
TXD
5
RS422/485 232
TX+
RX+
TXD
RXD
+5V
TX-
RX-
SG
ZL-CMA15L
Port 2
6 ZL-CMA15L
RXD
Shielded Cable
Cable Adapter
TXD
When connecting to a DirectLogic PLC
7
use connector ZL-CMA15L or ZL-CMA15
RS422/485 232
TX+
RX+
TXD
RXD
+5V
TX-
RX-
SG
(ZL-CMA15L shown)
Shielded Cable
8
9
10 Notes: 1. We recommend Belden 9842 shielded cable or equivalent.
2. Wiring Diagram for this example, ZL-CMA15(L)
12
RXD+
RXD+
RXD–
RXD–
TXD+
RTS+
CTS+
TXD+
RTS+
CTS+
TXD–
RTS–
CTS–
TXD–
RTS–
CTS–
GND
GND
7 6 10 13 9 11 14 12 15 7 6 10 13 9 11 14 12 15
13 *
15-pin
HD D-sub
8 = do not use (male) 15 = CTS– 8
14 7 = Sig GND
6 = RXD–
5 = do not use
15
14 = CTS+
13 = RXD+
12 = RTS-
7
6
5
4 = do not use 11 = RTS+ 4
A
3 = do not use 1 10 = TXD– 3
2 = do not use 6 9 = TXD+ 2
1 = do not use 1
HD = High Density
B TXD+ / RXD+
TXD– / RXD–
TXD+ / RXD+
TXD– / RXD–
Signal GND Signal GND
shield
C * Termination resistors required at both ends of
the network to match the impedance of the cable
(between 100 and 500 ohms).
Typical RS-485 Multi-Drop Wiring Diagram
D using DirectLogic pin numbers to illustrate
RXD
Cable Adapter
C-more 3”
Micro-Graphic
Panel
6
(ZL-CMA15L shown)
TXD
7
RS422/485 232
TX+
RX+
TXD
RXD
+5V
TX-
RX-
SG
Shielded Cable
When connecting to a DirectLogic PLC
use connector ZL-CMA15L or ZL-CMA15
8
9
Notes: 1. We recommend Belden 9842 shielded cable or equivalent.
2. Wiring Diagram for this example, ZL-CMA15(L)
10
To DL06 PLC port 2
used as example
To C-more Micro-Graphic Serial Port
w/ DC Power Adapter EA-MG-SP1.
11
Term.
12
RXD+
RXD–
TXD+
RTS+
CTS+
TXD–
RTS–
CTS–
SHD
RD+
RD–
SD+
GND
GND
SD–
*
7 6 10 13 9 11 14 12 15 5 10 12 9 11 13 1
15-pin
HD D-sub
13
8 = do not use (male) 15 = CTS– 15-pin
7 = Sig GND
6 = RXD–
5 = do not use
4 = do not use
15
14 = CTS+
13 = RXD+
12 = RTS-
11 = RTS+
8 = do not use D-sub 15 = do not use
7 = do not use (male) 14 = do not use
6 = do not use
5 = Logic GND
15 13 = Termination
12 = SD– (RS485)
14
3 = do not use 1 10 = TXD– 4 = do not use 11 = SD+ (RS485)
2 = do not use
1 = do not use
6 9 = TXD+
HD = High Density
3 = do not use
2 = do not use 1
1 = Frame GND
10 = RD– (RS485)
9 = RD+ (RS485) A
TXD+ / RXD+
TXD– / RXD–
Signal GND
TXD+ / RXD+
TXD– / RXD–
Signal GND
B
shield shield
*network
Termination resistors required at both ends of the
receive data signals to match the impedance
C
of the cable (between 100 and 500 ohms). Jumper pin
Typical RS-485 Multi-Drop Wiring Diagram (cont’d)
using DirectLogic pin numbers to illustrate
13 to 9 on the C-more 6” Micro-Graphic Serial Port2
15-pin connector to place the 120 internal resistor
into the network. If the cable impedance is different,
then use an external resistor matched to the cable
D
impedance.
®
EA1-MG-USER-M Hardware User Manual, 2nd Ed. Rev. F, 08/18