EDC-DTS-MV005 - Overhead Conductors and Accessories

This document provides technical specifications for overhead conductors and accessories used by Electricite Du Cambodge (EDC). It includes specifications for bare aluminum conductors, covered conductors, and various accessories like dead end grips, ties, joints, lugs and clamps. The document establishes testing standards, ambient condition requirements, and provides detailed technical data sheets for approved conductor and accessory types. It is intended to guide the selection and use of overhead line components that meet EDC's standards for safety, reliability and performance.

Uploaded by

Joe biloute
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
57 views78 pages

EDC-DTS-MV005 - Overhead Conductors and Accessories

This document provides technical specifications for overhead conductors and accessories used by Electricite Du Cambodge (EDC). It includes specifications for bare aluminum conductors, covered conductors, and various accessories like dead end grips, ties, joints, lugs and clamps. The document establishes testing standards, ambient condition requirements, and provides detailed technical data sheets for approved conductor and accessory types. It is intended to guide the selection and use of overhead line components that meet EDC's standards for safety, reliability and performance.

Uploaded by

Joe biloute
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 78

KINGDOM OF CAMBODIA

NATION RELIGION KING

ELECTRICITE DU CAMBODGE

TECHNICAL SPECIFICATION

EDC-DTS-MVOOS
Overhead Conductors and Accessories
November 2017
ELECTRICITE DU CAMBODGE

Version Date Techincal Specification Name Authorized by :

1.0 November, 2017


f
EDC-DTS-MVOOS- Overhead Conductors and Accessories

Version Drafted/reviewed by Verified by Approved by Date


Draftl AD
Draft 2 AD
FINAL 2 AD/EDC

Page3/77
EDC-DTS-MVOOS- Overhead Conductors and Accessories

[Blank]

Page 4 / 77

!
EOC-OTS-MV005- Overhead Conductors and Accessories

Content
1 Scope 9
2 Standards 9

3 Testing and Inspection 9


3.1 General Notes for Test 9
3.2 Conductors Type Tests 10
3.3 Conductors Routine Tests 10
3.4 Conductors SpecialTests 11
3.5 Bare Conductors AccessoriesTests 11
3.5.1 Preformed ties for Insulators 11
3.5.2 Mid Span Full Tension Joint 11
3.5.3 Terminal Lugs 12
3.5.4 Cable clamp (PGclamps) 12
3.6 Covered Conductor's AccessoriesTests 12
4 Quality Management 12
5 Ambient Conditions 12
6 Bare Conductors 13
6.1 Constitution and CrossSections 13
6.2 Outer Area 13
6.3 Layers 14
6.4 Jointing 14
6.5 Grease 14
7 Accessories for Bare Conductors 14
7.1 Preformed Dead EndGrips for Bare Conductors 14
7.1.1 Functional Characteristics 14
7.1.2 Markings 15
7.2 Metallic Preformed Ties 15
7.2.1 Markings 16
7.3 Mid-span Full Tension Joints 16
7.3.1 Markings 16
7.4 Terminal Lugs 17

7.5
7.5.1
7.5.2

Page 5/77
EDC-DTS-MVOOS- Overhead Conductors and Accessories

7.5.3 Markings 19
8 MV Covered Conductors 19
8.1 General 19
8.2 Breaking Strength 19
8.3 Core of Conductor 20
8.4 Longitudinal Water Tightness 20
8.5 Covering 20
8.6 Maximum Permissible Temperatures 21
8.7 Markings 21
9 Accessoriesfor Covered Conductors 21
9.1 General 21
9.2 Tie-Termination Anchor Sleeve 22
9.2.1 Functional Characteristics 22
9.2.2 Markings 22
9.3 Mid-span Full Tension Joints 22
9.3.1 Functional Characteristics 22
9.3.2 Markings 23
9.4 Pin Branch Joint 23
9.4.1 Markings 24
9.5 Pin Connector 24
9.5.1 Functional Characteristics 24
9.5.2 Markings 25
9.6 Terminal Lugsfor Covered Conductors 25
9.6.1 Functional Characteristics 25
9.6.2 Markings 26
9.7 Insulation Piercing Connectors 26
9.8 Insulating Ties 27
9.9 Sample Goods 27
10 Technical Data Sheets 28
10.1 Bare conductors 28
10.2 Preformed Dead End Grips for Bare Conductors 33
10.3 Metallic Preformed Ties 36
-span Full Tension Joints 38

Terminal Lug 44
................................................................................................................................47

Page6/77
EDC-DTS-MVOOS- Overhead Conductors and Accessories

10.8 Covered Conductors 49

10.9 Tie Termination Anchor Sleeve 55

10.10 Mid-span Full Tension Joints for Covered Conductors 58

10.11 Pin Branch Joint 61

10.12 Pin Connector 65

10.13 Aluminium Terminal Lug for Covered Conductor 69

10.14 Bi-metallic Terminal Lug for Covered Conductors 72


10.15 IPC for Covered Conductors 75

Page 7/77
EDC-DTS-MV005- Overhead Conductors and Accessories

[Blank]

+-
Page8/77
f
EDC-DTS-MV005- Overhead Conductors and Accessories

Overhead Conductors and Accessories

1 Scope

This specification covers the design, manufacturing, testing, supply, delivery and performance
requirements of overhead conductors and accessoriesfor MV overhead lines used on 35 and 22 kV
networks of Electriclte du Cambodge.

2 Standards

The equipment shall comply with the latest editions and amendments of standards/specifications
listed below:

IEC : International Electromechanical Commission

IEC60104 : Aluminium-magnesium-silicon alloy wires for overhead line conductors

IEC60889 : Hard Drawn Aluminium wires for overhead line conductors

IEC61089 : Round wire concentric lay overhead electrical stranded conductors

EN European Standard CENElEC

EN50182 : Conductors for overhead lines -Round wire concentric lay stranded
conductors

EN 50183 : Conductors for overhead lines- Aluminium-magnesium-silicon alloy wires

EN 50397 : Covered conductors for overhead lines and the related accessoriesfor rated
voltages above 1 kV AC and not exceeding 36 kV AC

ISO : International Standard Organization

ISO/IEC17025 : General requirements for the competence of testing and calibration


laboratories

ISO9001 : Quality management systems - Requirements

The Bidder may propose alternative standards, provided it is demonstrated that they give an
equivalent degree of quality asthe referenced standard. Acceptability of any alternative standard is at
the discretion of EDC.

3 Testing and Inspection

3.1 General Notes for Test

Conductors and accessoriesmay be inspected at the manufacturer's factory by EDC'srepr

The inspection and routine tests shall be carried out in accordance with the provision
IECor national recommendations. In the absence of IECstandards, the inspection

Page9/77
EDC-DTS-MVOOS- Overhead Conductors and Accessories

carried out in such a manner as to be at least equivalent to conditions, provisions and definitions set
out in one of the standards listed in this specification.

The conductors and all accessoriesshall be subjected to test as specified below.

3.2 Conductors Type Tests

All type tests required by the relevant IEC bare conductors and EN for covered conductors and
accessoriesshall be carried out.

Type test reports shall be carried out by internationally recognized electrical testing laboratories.

Full copies of type test reports shall be submitted within the bid of the manufacturer/supplier. Type
test reports older than 15 years will not be accepted.

If the manufacturer is certified by EDC,it is not necessaryto submit type test reports for the considered
equipment.

Nevertheless, in case the testing laboratory is not internationally recognized, the testing laboratory
shall be mandatorily accredited ISO/IEC 17025 by an international or national accreditation body
specialized in testing laboratories accreditation/acceptance. In that case, the testing laboratory shall
prove mandatorily its capability/capacity to carry out all type tests mentioned in the type tests reports
by suppling: Full description of all tests the laboratory can carry out, list of testing equipment with full
characteristics, drawing of testing rooms with location of testing equipment etc., supported by pictures
and copy of the ISO/IEC17025 accreditation certificate.

Acceptability of any accredited testing laboratory is at the discretion of the EDC.

3.3 Conductors Routine Tests

EDC Representative may call for routine tests to be carried out at the Manufacturer's Works and
witnessed by EDC or their Inspecting Engineers. Such tests would be on random samples at the
discretion of EDCRepresentative and failure to meet the conditions of tests could result in the rejection
of a complete batch of conductor.

Routine tests shall be carried out on all the conductors in a particular order, and shall be free of charge
to EDC.

Before stranding, tests shall be carried out on samples of wire, selected from not less than 10% of the
individual lengths of wire to be included in anyone consignment. Each sample shall be of sufficient
length to provide one test specimen for each of the appropriate tests.

After stranding, tests shall be carried out on samples selected from every drum in the consignment.
Eachsample shall be sufficient length to provide one test specimen for each of the appropriate tests.

If any sample fails to pass anyone of the tests nominated for that conductor or wire, then samples
shall be taken from every drum in the consignment and any drum length from which a sample proves
defective shall be rejected. On no account shall any rejected material be again presented for test unless
with the written approval of, and under conditions determined by, the purchaser.

r measurement

Page 10/77
EDC-DTS-MVOOS- Overhead Conductors and Accessories

• Tensile strength measurement


• Resistancetest
• Wrapping test

For each complete conductor sample:

• Lay ratio of each layer to be measured.


• Dimensions (diameters, thickness, etc...),
• Tensile strength of complete conductor to be measured. Alternatively, the tensile strength
may be calculated from the results of tests on individual wires using the method of IEC
61089.
• Resistivity of complete conductor to be measured as applied to individual aluminium or
aluminium allow wires. Alternatively, the resistivity may be calculated from the results of
tests on individual wires, using the method of IEC61089.

The following routine tests shall also be included:

• Electrical resistance of conductors.


• covering spark test (covered conductors)

3.4 Conductors Special Tests


Special tests shall be carried out at EDC'sdiscretion on a number of conductor samples selected by
EDCfrom the contract consignment. The tests shall be carried out on one randomly selected sample
of the production batch of the conductor type and cross section.

The following special tests shall be included:

• Conductor examination
• Checkof dimensions
• Resistancetest
• Rate tensile strength
• Voltage and leakage test (covered conductors)
• Hot set test for XLPEinsulation (covered conductors)

3.5 Bare Conductors Accessories Tests

3.5.1 Preformed ties for Insulators

In absence of IECtest standard, any ENor national test standard could be applied. As a minimum, the
following type test reports shall be supplied:

• Tensile strength test for attaching ties


• Breaking load type test for dead end grips and anchorage

The Routine tests carried out on accessories by the manufacturer shall be backed by routine test
reports which are signed by the factory's quality control department.

3.5.2 Mid Span Full Tension Joint

In absence of IECtest standard, any ENor national test standard could be applied. As
following type test reports shall be supplied:

• Tensile strength test


• Electrical resistance measurements test

Page 11 / 77
EDC-DTS-MVOOS- Overhead Conductors and Accessories

The Routine tests carried out on accessories by the manufacturer shall be backed by routine test
reports which are signed by the factory's quality control department.

3.5.3 Terminal Lugs

In absence of IECtest standard, any national test standard could be applied. As a minimum, the
following type test reports shall be supplied:

• Electrical resistance measurement test

The Routine tests carried out on accessories by the manufacturer shall be backed by routine test
reports which are signed by the factory's quality control department.

3.5.4 Cable clamp (PG clamps)

In absence of IECtest standard, any national test standard could be applied. As a minimum, the
following type test reports shall be supplied:

• Electrical resistance measurement test

The Routine and sample tests carried out on accessories by the manufacturer shall be backed by
routine test reports which are signed by the factory's quality control department.

3.6 Covered Conductor's Accessories Tests

All covered conductor's accessories shall be type tested according the requirements of EN 50397-2
standard. Full type tests report shall be provided.

The Routine and sample tests carried out on accessories by the manufacturer shall be backed by
routine test reports which are signed by the factory's quality control department.

4 Quality Management

Design, development and production of the proposed equipment shall be ISO9001 certified. The ISO
9001 certificate shall be submitted within the bid.

5 Ambient Conditions

Conductors and accessoriesshall be suitable to operate in the ambient conditions described here after:

Altitude Sealevel to 1,000 meters

Climate Tropical

Annual Rainfall 1,300 mm. 140 days

Monsoon Period June to November

Ambient Air Temperatures:

27SC

inimum

Page 12/77
EDC-DTS-MVOOS- Overhead Conductors and Accessories

Maximum 40SC

Relative Air Humidity 65-100%

Soil Thermal Resistivity:

Average 1.20c m/W

Maximum 3.00c m/W

Solar Emissivity 0.8

Solar absorption 0.8

Wind Velocity:

Average 37 km/h (10.3 m/s)

Maximum 72 km/h (20 m/s)

6 Bare Conductors

6.1 Constitution and Cross Sections

The bare conductors shall be made of Aluminium-magnesium-silicon alloy wires (AAAC).

The cross sections of bare conductors to be supplied are 240 rnrn", 185 rnrn", 150 mm/, 70 mrrr' and
35 mrrr'.
Depending of international and national standards, approximate cross section areas shall be accepted.

The minimal characteristics of bare conductors shall be as follows:

AAACConductor

Approximate crosssection Minimum Modulus of Coefficient of Conductivity


breaking elasticity linear expansion % lACS
strength N/mm2 per·C x 10-6
KN

240 rnrn? ± 5 mrrr' 74 57000 23 52.9%

185 mrrr' ± 3 rnrn? 58 57 000 23 52.9%

150 rnrrr' ± 3 rnrn? 47 60 000 23 52.9%

70 mrrr' +5/-1 mrrr' 23 62 000 23 52.9%

35 mrrr' +2/-1 rnrrr' 10 62 000 23

6.2 Outer Area

The area shall be longitudinally identical; the stranded wires shall not be overlap
defect; there shall be bandagesto keep the ends of conductor coil fixed.

Page 13 / 77
EDC-DTS-MVOOS- Overhead Conductors and Accessories

6.3 Layers

All the layers shall be stranded securely. The direction of lay of two consecutive layers shall be
different; the outmost layer of wires shall be right-hand direction.

6.4 Jointing

Welding on aluminium allow wire is tolerated but if we consider all the wires, a distance of 50 meters
between 2 consecutives welding is requested, in all casesthe table below shall be respected.

Jointing shall be performed by butt-welding. There shall be not more than 5 joints within any wire of
the outer layer. The distance between two consecutive joints among different wires shall be different.

Number of Maximum number of welding


layers acceptable per section of 1500 m

1 2
2 3
3 4
4 5

6.5 Grease

In order to protect wires from the corrosion, the conductors shall be greased: The internal core and all
aluminium alloy layers excluding outer layer will be greased.

The grease used shall be high temperature melting point grease of more than 70°(.

7 Accessories for Bare Conductors

7.1 Preformed Dead End Grips for Bare Conductors

This preformed dead end grips shall be used for bare conductor anchorage on the strain insulators.

7.1.1 Functional Characteristics

Page 14/77
EDC-DTS-MV005- Overhead Conductors and Accessories

Dead end grips shall be used with the following conductors:

Conductor type Cross Section [rnm"]

AAC(existing network) 35, 70 and 150

AAAC 35, 70, 150, 185 and 240

ACSR(existing network) 35, 70, 150 and 185

These terminations shall guarantee mechanical features at least equivalent to those of the conductor
on which they are installed and shall be protected against corrosion.

When installed on the conductor, no conductor failure shall appear next to the dead end grip and no
conductor slip shall appear at tensile load below the nominal breaking load value of the conductor.

7.1.2 Markings
Each individual Preformed Dead End Grip shall be marked by colour code depending the associated
conductor cross sections.

7.2 Metallic Preformed Ties


These preformed ties shall be used for attaching/fixing the bare conductors onto the 35 kV and 22 kV
line post insulators.

Preformed ties shall be used with the following conductors:

Conductor type Cross Section [mm"]


AAC (existing network) 35, 70 and 150

AAAC 35, 70, 150, 185 and 240

ACSR(existing network) 35, 70, 150 and 185

Side or top preformed ties shall be supplied according the conductor location on the line post insulator.

All preformed ties shall be supplied with a neoprene pad for insertion over th
rests in the insulator top or side groove.

Page 15/77
EDC-DTS-MV005- Overhead Conductors and Accessories

7.2.1 Markings

Each individual preformed tie shall be marked by colour code depending the associated conductor
cross sections.

7.3 Mid-span Full Tension Joints

This equipment is intended to ensure mechanical and electrical connection between two lengths of
same cross section of bare conductors under mechanical strength.

Eachmid-span full tension joint comprises:

• One aluminium alloy sleeve allowing the hexagonal compression on conductor core for
aluminium and aluminium alloy conductors
• One steel sleeve and one aluminium alloy sleeve and eventually aluminium insert tubes
allowing the hexagonal compression on conductor core for ACSRconductors.

Mid-span full tension joints shall be used with:

Conductor type Cross Section (mm2)


AAC (existing network) 35, 70 and 150
AAAC 35, 70, 150 and 185 and 240
ACSR(existing network) 35, 70, 150 and 185

Mid-span full tension joints shall be of regular hexagonal compression type. These joints shall
guarantee mechanical and electrical features at least equivalent to those of the conductor on which
they are installed.

They shall include internal barer for correct insertion of the conductor.

When in use, no conductor failure shall appear next to the mid-span full tension joints and no
conductor slip shall occur at tensile load below the nominal breaking load value of the conductor.

This accessory shall be delivered with necessarygrease inside and both ends shall be capped.

7.3.1 Markings

Eachindividual Mid-span full tension joint shall have the range of permanent embossed markings listed
below,

wing the places of compression.

Page 16/77
EDC-DTS-MVOOS- Overhead Conductors and Accessories

7.4 Terminal Lugs

The compression terminal lugs are intended to connect overhead network apparatuses (LBS,Auto-
Recloser, Transformer, etc.) to a bridge constituted by a non-stretched linking conductor.

Eachterminal lug comprises:

• One tube to be compressed on the conductor.


• One palm with a hole to connect the lug onto the network apparatus.

Terminal lugs shall be used with:

Conductor type Cross Section [mrn"]


AAC (existing network) 35, 70 and 150

AAAC 35, 70, 150 and 185 and 240

ACSR(existing network) 35, 70, 150 and 185

Terminal lugs for conductors shall be filled with high quality oxide inhibiting compound.

The carrying capacity of the terminal lugs shall be at least equal to the capacity of the conductor.

Two types of lugs shall be supplied:

• Aluminium terminal lug for connection of AAC,or AAAC,or ACSRconductors on aluminium


terminals.
• Bi-metallic Aluminium/copper terminal lug for connection of AAC, or AAAC or ACSR
conductors on copper terminals.

Bi-metallic terminal lugs shall be made of:

• One aluminium or aluminium alloy tube


• One copper palm.

These two components shall be a not dissociable assembly.

Page 17/77
EDC-DTS-MVOOS- Overhead Conductors and Accessories

Friction welding between aluminium tube and copper palm of bi-metallic lugs is not accepted for
reason of too short lifespan under daily OHLvibrations.

The minimum hole diameter of palm of each kind of lug shall be:

• 13 mm for bi-metallic terminal lug and for copper terminal lug.

• 15 mm for aluminium terminal lug.

The lugs shall be supplied with a bolt in accordance with the metal of the connecting palm and fitted
with bolt, nut and washers.

These accessoriesshall be delivered with necessarygrease inside and both ends shall be capped.

7.4.1 Markings
Eachindividual terminal lug shall have the range of permanent embossed markings listed below,

• Manufacturer's identification.
• Type of conductor.
• Crosssection of conductor.
• Compression die reference.
• Reference of lot including the last two digits of manufacture Year.
• Marks showing the places of compression.

7.5 CableClamps(PG)
Bolted cable clamps shall be used for connecting two conductors or for fixing connection stirrup on
tight conductors.

These cable clamps shall be of bolted type with parallel grooves (PG).

7.5.1 ClampBody
The clamp body shall be made of high corrosion resistance aluminium alloy.

7.5.2 Bolts
number of tightening bolts per cable clamps shall be suitable for cross section of

Page 18/77
EDC-DTS-MV005- Overhead Conductors and Accessories

7.5.3 Markings
Each individual parallel groove clamp shall have the range of permanent embossed markings listed
below,

• Manufacturer's identification.
• Crosssection range.
• Reference of lot including the last two digits of manufacture Year.

8 MV Covered Conductors
This specification applies to 22 kV insulated, unscreened, Water Blocking Covered Conductors. The
conductor shall be made of compacted aluminium alloy wire (Aluminium - Magnesium - Silicon) of
AL4 type as per EN50183 standard, and of compacted Aluminium for 35 mrn", stranded in layers.

Covered conductors consist of a compacted conductor surrounded by a covering made of insulating


material as protection against accidental contacts with other covered conductors and with grounded
parts such as tree branches, etc. In comparison with insulated conductors, this covering has reduced
properties, but is able to withstand the phase-to-earth voltage temporarily.

Since covered conductors are unscreened, they are not touch-proof, i.e. they must be treated as bare
conductors with respect to electric shock.

The covered conductor's networks implementation shall be similar to the bare conductor
implementation.

Depending of international and national standards, approximate section areas shall be accepted.

The 35 rnm! cross section Covered Conductor is specifically dedicated for Pole Mounted distribution
substation wiring.

The life expectancy of covered conductor and accessoriesshall be not lessthan 30 years.

8.1 General
System voltage: 12.7/22 (24) kV

Conductor rated voltage (U) : 24 kV

Full type test reports carried out in accordance with the requirement of EN50397 shall be supplied.

8.2 BreakingStrength
The minimal breaking strength of MV covered conductors core shall be as follows:

Page 19/77
EDC-DTS-MVOOS- Overhead Conductors and Accessories

Minimum breaking Modulus of Coefficient of


Crosssection strength elasticity expansion
(kN) hbar per "C x 10-6
CC185 mrn! ± 3 rnm' 54 6000 23
CC150 mrn" ± 3 rnrn" 43 6000 23
CC95 rnrrf ± 3 rnrn' 27 6000 23
CC70 rnm' +5/-1 mrn" 23 6200 23
CC50 rnrrr' +5/-1 rnm' 14 6200 23
CC35 rnm?+5/-1 rnm' 5 7000 23

The covered conductor comprises:

• Circular aluminium alloy stranded compacted conductor or aluminium stranded conductor


for 35 rnrrr'.
• Watertight system for longitudinal water tightness.
• XLPEcovering sheath.

A semi- conductive layer could be inserted between core and insulation.

8.3 Coreof Conductor


The core of covered conductor shall be made of compacted AL4 (EN 50183) Aluminium alloy
(aluminium-magnesium-silicium) wires for 185 mrrr', 150 mrn", 95 rnrn! and 50 rnrrr' cross section
conductor and Aluminium for 35mm2 cross section conductor. It is a stranded conductor with a circular
cross section.

The 35 rnm" shall be used for wiring of pole mounted substations.

8.4 LongitudinalWaterTightness
The stranded conductor shall be longitudinally watertight by means of adequate measures ase.g. filling
with an adequate mass, water blocking fibber or powder etc ... The filling mass or other materials for
obtaining the longitudinal water tightness, shall be compatible with the conductor material and the
material of the covering to prevent the migration of water inside the covered conductor which
guarantees the long performance required.

This water blocking mass shall not migrate into the core of the conductor. It shall not deteriorate
mechanical and electrical characteristics of accessoriesthereafter. No specific tool and no solvent shatl
have to be used to prepare the contact between conductors and accessories.

The water blocking mass used shall be safe for the environment. This shall be proved by supplying
relevant tests and certificates within the offer.

th is a black UV stabilized and weather resistant extruded XLPEwhich resists all

Page20/77
EDC-DTS-MVOOS- Overhead Conductors and Accessories

within the offer as well as all type tests. Failure to supply type tests as requested will result in the
rejection of the offer.

It shall be possible to remove the covering without damage to the conductor.

8.6 Maximum Permissible Temperatures

The maximum permissible temperatures shall be as follow:

• 90°C during normal operation,


• 120° C under a short duration overload (a total of 24 hours a year in separate periods of 3
hours at the most),
• 250°C under short circuit (max 5 seconds)

These temperatures are based on the intrinsic properties of the insulating materials. These values can
only be used for calculating permissible current ratings.

8.7 Markings

Each individual conductor shall have the range of markings listed below, embossed on the insulation
surface at one meter intervals. The letters and figures shall be raised on the insulation surface, thus it
does not damage the insulation.

• Manufacturer'sidentification
• Year of manufacture : Four digits
• Conductor type : CC;
• Covering material : S (for semi-conductive conductor screen, if any),

: X (for cross-linked polyethylene),

• Conductor material and cross-section : AL4 .....


• Conductor design : W (for watertight),

: K (for compacted);

• Rated voltage Um in kV : 24 kV
• Supplier name : XXXX

The markings shall be made in the sequence indicated above. Thus if the manufacturer is XY,the
core of AL4 and the cross section is 150 rnrn", without semi conductive layer, the cable was
manufactured in 2015, the markings would be: XV 2015 CCX150-AL4 WK 24kV - XXXX

9 Accessories for Covered Conductors

9.1 General

The above accessories shall be used with watertight covered conductors without removing the
covering with exception of hexagonal compression accessories for which the covering (if any) shall
have the same basic insulation properties as the conductor covering.

All proposed accessories shall be specially manufactured or adapted for covered c

shall be the origin of radio influence, corona, electrical field stresses and tracking

Page 21 / 77
EDC-DTS-MVOOS- Overhead Conductors and Accessories

9.2 Tie-Termination Anchor Sleeve

This Tie-Termination anchor sleeve shall be installed on strain insulators.

9.2.1 Functional Characteristics

EachTie-Termination anchor sleeve is used to:

• Anchor the covered conductor by hexagonal compression on covered conductor core.


• Connect with the strain insulator by a clevis with a breaking load of 70 kN.
• Connect with a branch or a jumper through a diameter 25 mm pin connector
• Prevent the penetration of water into the covered conductor
• Short circuiting and earthing of covered conductor

Tie-Termination shall be used with the following covered conductors: 185 rnrrr', 150 rnrrr', 95 mrn' and
50 rnrrr'.

These terminations guarantee mechanical and electrical features at least equivalent to those of the
conductor core on which they are installed.

When using, no covered conductor failure shall appear next to the Tie - Termination anchor sleeve and
no conductor slip shall appear at tensile load below the nominal breaking load value ofthe conductor.

9.2.2 Markings

Eachindividual Tie - Termination shall have the range of permanent embossed markings listed below:

• Manufacturer's identification.
• Type of conductor.
• Crosssection of conductor.
• Compression die reference.
• Reference of lot including the last two digits of manufacture Year.
• Marks showing the places of compression.

9.3 Mid-span Full Tension Joints

This equipment is intended to ensure mechanical and electrical connection between two length of
same cross section of stretched bare conductors.

9.3.1 Functional Characteristics

-span full tension joint comprises:

inium alloy sleeve allowing the hexagonal compression on conductor core.


r tightening system (gasket, cap, sleeve) to prevent the penetration of water into
c ~r d conductor and reconstitute the conductor covering.
o
~
C~
Page 22 / 77
EDC-DTS-MVOOS- Overhead Conductors and Accessories

Mid-span full tension joints shall be used with the following covered conductors: 185 mrrr'. 150 rnrrr',
95 rnrrr' and 50 mrn".

Mid-span full tension joints shall be hexagonal compression type. These joints shall guarantee
mechanical and electrical features at least equivalent to those of the conductor on which they are
installed.

When in use, no covered conductor failure shall appear next to the mid-span full tension joints and no
conductor slip shall appear at tensile load below the nominal breaking load value of the conductor.

9.3.2 Markings
Each individual Mid-span full tension joint shall have the range of permanent embossed markings listed
below,

• Manufacturer's identification.
• Type of conductor.
• Crosssection of conductor.
• Compression die reference.
• Reference of lot including the last two digits of manufacture Year.
• Marks showing the places of compression.

9.4 Pin Branch Joint

These joints are intended to connect a covered, non-cut, stretched line conductor with a cut covered
conductor. This connection is made with a branch associated pin and a pin connector defined after.

5.4.1 Functional Characteristics

Eachpin branch joint for Covered Conductor comprises:

• One or two insulation piercing connectors with water-tightness system (gasket, cap...) to
prevent the penetration of water into the covered conductor.
• One 25 mm diameter aluminium alloy tap pin to connect a jumper with a pin connector.
• One pin or device allowing short circuiting and earthing of covered conductor

Pin branch joints for Covered Conductors shall be used with the following covered
---~
mrrr': 150 rnrrr': 95 mrn! and 50 mm".

The carrying capacity of pin branch joints shall be at least equal to the one of
indifferently line or tap conductor.

Page 23 / 77
EDC-DTS-MVOOS- Overhead Conductors and Accessories

The insulation piercing connector (s) shall not have components that are liable to be lost during
installation. The housing shall be made entirely of mechanical and resistant plastic insulation material
and no metallic part outside the housing is acceptable except for the tightening system. The housing
shall be an integral part of the connector. The bolts tightening torque shall be controlled by shear head
screws without the need of any special tool.

The number and the length of the teeth shall be adequate enough to penetrate the relevant covered
conductor covering to establish proper contact without any contract resistance and without the need
to strip the covered conductor insulation. To achieve the required water tightness a special rubber seal
be provide around the teeth of the present connector. The bolts and washers shall be of corrosion
resistant type.

9.4.1 Markings

Eachindividual pin branch joint shall have the range of permanent embossed markings listed below:

• Manufacturer's identification.
• Type of conductor
• Crosssection range of conductor.
• Reference of lot including the last two digits of manufacture Year.

9.5 Pin Connector

These connectors are intended to connect Tie-Termination anchor sleeve and pin branch joints to a
bridge constituted by a non-stretched linking bare or covered conductor. This connector is to be used
on a 25 mm diameter pin.

9.5.1 Functional Characteristics

Each pin connector comprises:

One body made of aluminium alloy including a tightening system. This body shall permit the electrical
connection on the 25 mm diameter pin of the tie-termination or the pin branch joints.

One tube welded on the body. On site, this tube shall be hexagonally compressed onto the conductor.

conductor and a special device to confirm the correct

Page 24/77
EDC-DTS-MV005- Overhead Conductors and Accessories

All tube connectors shall be filled with high quality oxide inhibiting compound.

The carrying capacity of the connectors shall be at least equal to the capacity of the compressed
conductor.

The tightening bolts shall include an over-torque shear head made of suitable material which allows a
clamping torque in conformity with the recommendation of the manufacturer, without the need of
any special tool. This head shall be hexagonal head type.

A ring shall be accessibleafter breaking of the first head to allow disconnection of pin connector from
a pin with hook stick for future hot line working.

According the cross sections, dies used to hexagonal compression of the tube of pin connectors shall
be same as the dies used for compression of pin dead end tension joints and mid-span full tension
joints.

9.5.2 Markings
Each individual pin connector shall have the range of permanent embossed markings listed below,

• Manufacturer's identification.
• Type of conductor.
• Crosssection of conductor.
• Compression die reference.
• Reference of lot including the last two digits of manufacture Year.
• Marks showing the places of compression.

9.6 Terminal Lugsfor Covered Conductors


The compression terminal lugs are intended to connect overhead network apparatuses to a bridge
constituted by a non-stretched linking covered conductor. Those lugs shall be identical to the bare
conductor lugs with exception of a water-tightness system for preventing penetration of water inside
the covered conductor.

9.6.1 Functional Characteristics


Each terminal lug comprises:

• One tube to be compressed on the conductor.


• One palm with a hole to connect the lug on the network apparatus.

The tube shall include a water-tightness system (gasket, cap...) to prevent the penetration of water
into the covered conductor.

Terminal lugs shall be used with the following conductors: 185 mrrr': 150 rnrrr': 95 mrn", 50 rnrrr' and
35 rnrn?covered conductors.

Terminal lugs for conductors shall be filled with high quality oxide inhibiting compound.

The carrying capacity of the terminal lugs shall be at least equal to the capacity of the conductor.

Two types of lugs shall be supplied:

• Aluminium terminal lug for connection of covered conductors on alum


• Bi-metallic Aluminium/copper terminal lug for connection of
copper terminals.

Page 25 / 77
EDC-DTS-MVOOS- Overhead Conductors and Accessories

Bi-metallic terminal lugs shall be made of:

• One aluminium or aluminium alloy tube


• One copper palm.

These two components shall be an in dissociable assembly.

Friction welding between aluminium tube and copper palm of bi-metallic lugs is not accepted for
reason of too short lifespan under daily OHLvibrations.

The minimum hole diameter of palm of each kind of lug shall be:

• 13 mm for bi-metallic terminal lug and for copper terminal lug.


• 15 mm for aluminium terminal lug.

The lugs shall be supplied with a bolt in accordance with the metal of the connecting palm and fitted
with bolt, nut and washers.

9.6.2 Markings

Eachindividual terminal lug shall have the range of permanent embossed markings listed below,

• Manufacturer's identification.
• Type of conductor.
• Crosssection of conductor.
• Compression die reference.
• Reference of lot including the last two digits of manufacture Year.
• Marks showing the places of compression

9.7 Insulation Piercing Connectors

These insulation-piercing connectors are intended to connect two covered conductors with the same
or different cross section between them without possibility of disconnection latter. They shall be of
not reusable type. The main conductor should be stretched or not. The tap conductor shall be a bridge
constituted by a not stretched linking covered conductor.

The insulation piercing connector shall not have components that are liable to be lost during
installation. The housing shall be made entirely of mechanical and resistant plastic insulation material
and no metallic part outside the housing is acceptable except for the tightening system. The housing
shall be an integral part of the connector. The bolts tightening torque shall be controlled by shear head
screws without the need of any special tool.

The number and the length of the teeth shall be adequate enough to penetrate the relevant covered
conductor covering to establish proper contact without any contract resistance and without the need
to strip the covered conductor insulation. To achieve the required water tightness a special rubber seal
be provide around the teeth of the present connector. The bolts and washers shall be of corrosion
resistant type.

The piercing of insulation shall be simultaneous on main and tap conductor when tightening the bolts.

ng connector shall accept the following cross section covered conductors:

Page26/77
EDC-DTS-MV005- Overhead Conductors and Accessories

Main covered conductor cross Tap covered conductor cross


section (mrrr') section (mrrr')

185, 150,95, 50 and 35 185, 150,95,50 and 35

As example, it could be requested a connector with the following cross section capacity: Main 185 mrn!
and Tap 35 rnrrr'.

This means that different connectors shall be supplied for covering all connection capacities.
Nevertheless, the number of connectors for covering all possibilities shall be reduce to a minimum.

9.8 Insulating Ties


Insulating ties will be used for attaching 22 kV covered conductors onto line post insulators.

The insulating ties for 22 kV covered conductor shall be single material plastic ties of the highest
integrity type, no metal parts are allowed. Ties shall be used without removing the sheath of covered
conductors.

They shall combine the necessarymechanical holding function with protection of the conductor sheath
from long term deterioration caused by electrical stress. The electrical integrity of covered conductor/
line post insulator system shall be maintained.

Insulating ties shall be used with the following covered conductors: 185 rnrrr', 150 rnrn", 95 mrn", 50
rnrn" and 35 rnrn' and they shall be of weather and UV resistant type.

9.9 Sample Goods


Two (2) samples of each type of accessoriesand two (2) pieces (50 cm) of each cross section of the
proposed covered conductor shall be submitted to EDCwithin the offer.

Page 27/77
EDC-DTS-MVOOS- Overhead Conductors and Accessories

10 Technical Data Sheets

10.1 Bare conductors

No. Description Unit Requirements Supplier's Offer


1 Country to be specified

2 Manufacturer to be specified

3 Manufacturer's Reference to be specified

4 Applicable Standards IEC60104

IEC60889

IEC61089

EN50182

EN50183

5 Full type tests reports supplied Yes,as per IECand EN


requirements

Conductors made of: Aluminium-magnesium-


silicon alloy wires (AAAC)

6 Aluminium alloy origin To be specified

7 Crosssections mm! 0 240


0 185
0 150
0 70
0 35

8 Realcross section of:

0 240 mm! ± 5 rnrn!


0 185 rnrrr' ± 3 mm'
rnrn? To be specified
D 150 rnrn" ± 3 rnrn"
0 70 mrn' +5/-1 rnm!
D 35 rnrn' +2/-1 mm!

Conductor diameter

D 240 mrrf

/!,~
D 185 mrrr'
mm To be specified

Vi ~~omm' mm'
~ ~.~ '*'
*1
~
~~ ~~
%J: ·r",
1;; rnm?

J?/C i7-'E'6~ Page 28/77


EDC-DTS-MVOOS- Overhead Conductors and Accessories

9 Minimum breaking strength

D 240 rnrrf 74

D 185 mrn? 58

D 150 rnm" kN 47

D 70mm2 23

D 35 rnrrr' 10

10 Conductivity % 52.9%
lACS

11 Modulus of elasticity

240 mrn! and 185 mm" 57000


N/mm2
150 mrrr' 60000
70 mm' and 35 rnm? 62000

12 Coefficient of linear expansion

per °Cx 10-6 23

13 Nominal carrying capacity

20°C in air without wind

D 240 mrrf ~485

D 185 rnm' ~ 415

D 150 mrn? A ~ 365

D 70mm2 ~ 230

D 35 rnm' ~ 145

14 Minimal linear resistance 20°C

D 240 mrrf s 0.146


D 185 mm' s 0.183
O/km
D 150 mrrr' s 0.224
D 70 rnm? s 0.440
D 35 rnm! s 0.958

15 Number of wires

D 240 mrrr'

D 185 mrrr'

D 150 rnrrr' To be specified

Page 29 / 77
EDC-OTS-MVOOS- Overhead Conductors and Accessories

D 70mm2

D 35 mrrr'

16 Diameter of wires

D 240 mrrf

D 185 rnrn! To be specified

D 150 rnm?

D 70 rnrn'

D 35 rnrn'

17 Number of layers

D 240 mrrr'
D 185 mrn' To be specified

D 150 mrrr'

D 70mm2

0 35 rnm'
18 Outer area

The area shall be longitudinally Yes


identical;

The stranded wires shall not be Yes


overlapped,

not have any defect Yes

19 Layers

All the layers shall be stranded


securely
Yes
The direction of lay of two
consecutive layers shall be
different Yes

the outmost layer of wires shall


be right-hand direction
Yes

20 Jointing

Yes

Yes

Page30/77
EDC-DTS-MVOOS- Overhead Conductors and Accessories

No more than 5 joints within


any wire of the outer layer.
Yes
The distance between two
consecutive joints among
different wires is different. Yes

Maximum number of welding


acceptable per section of
1500m
2
One layer
3
Two layers
4
Three layers
S
Four layers

21 Grease

The internal core and all


aluminium alloy layers
Yes
excluding outer layer are
greased.

Grease melting point >70

22 Packing

Material of Drum (Non- Steel/Timber


returnable)

Length of Cable per Drum m

3000± Sm

> 70 mrn! 2000 ± Sm

23 Drum Marking:

Manufacturer's name Yes

Month and Year of


manufacture Yes

Batch number Yes

Total gross weight Yes

Net weight Yes

Distributor's name Yes

Length of conductor m Yes

Yes

Page 31 / 77
EDC-OTS-MV005- Overhead Conductors and Accessories

24 Technicaldrawings, Must be provided


Catalogue,full technical
If not the offer is not
information, etc...
considered.

Supplier's offer column must be properly filled with the right figures. "Compliant, Yes, ", V, etc..." are not accepted.

Deviation from the technical specification:

The bidder shall list point after point and explain here in after all deviation from the
requested technical specification.

1/
2/

Full technical information shall be supplied within the bid.

Bidder signature:

Page32/77
EDC-DTS-MVOOS- Overhead Conductors and Accessories

10.2 Preformed Dead End Grips for Bare Conductors

No. Description Unit Requirements Supplier's Offer

1 Country to be specified

2 Manufacturer to be specified

3 Manufacturer's Reference to be specified

4 Applicable Standard to be specified

5 Full type tests reports supplied Breaking load type test

6 Used for bare conductor


anchorage on strain insulators
Yes
without cut of the conductor.

7 Connect with the strain


insulator by a clevis thimble
Yes
with a breaking load of not less
than 70 kN

8 AAC conductors mrrr' D 35


D 70
D 150

9 AAACconductors mrn! D 35
D 70
D 150
D 185
D 240

10 ACSRconductors mrn" D 35
D 70
D 150
D 185

11 Mechanical features at least


equivalent to those of the
Yes
conductor on which they are
installed.

lla Breaking load To be specified

llb Length To be specified

llc Number of wires To be specified


Ai ft ..~
12 When installed on the
conductor, no conductorfailure
Yes
1~~LIt\~
1*1 ~
"~~
Page 33/77
-
"(/
EDC-DTS-MV005- Overhead Conductors and Accessories

appears next to the dead end


grip

13 no conductor slip shall appear


at tensile load below the
Yes
nominal breaking load value of
the conductor

14 Colour code:
AACconductors
D 35 mrrf
D 70mm2
D 150 mm'

AAACconductors
D 35 rnm!
D 70 mrn"
D 150 mrn"
to be specified
D 185 rnm"
D 240 mrrr'

ACSRconductors
D 35 mm'
D 70 mrn"
D 150 mrrf
D 185 mrn'

15 Constitution of preformed to be described


dead end grips

16 Packing

Cardbox or bag of 10 pes Yes

17 Packing Marking:
Manufacturer's name Yes
Month and Year of Yes
manufacture Yes
Batch number Yes
Total gross weight Yes
Distributor's name Yes
Reference of dead end Yes
Type of conductor Yes
Min and Max cross section
18

»:
a..l.
~
V
_
tt
Technical drawings,
__~_C...a~talogue,full technical
e
-!:!
IJIfO! ation, etc...
...
,~
¥'
Must be provided

If not, the offer is not


.
considered.
EDC-DTS-MV005- Overhead Conductors and Accessories

Deviation from the technical specification:

The bidder shall list point after point and explain here in after all deviation from the
requested technical specification.

1/
2/

Full technical information shall be supplied within the bid.

Bidder signature:

Page35 / 77
EDC-DTS-MVOOS- Overhead Conductors and Accessories

10.3 Metallic Preformed Ties

No. Description Unit Requirements Supplier's Offer

1 Country to be specified

2 Manufacturer to be specified

3 Manufacturer's Reference to be specified

4 Applicable Standard to be specified

5 Full type tests reports supplied Tensile strength test

6 Used for bare conductor fixing Yes


on line post insulators

7 AAC conductors mrrr' D 35


D 70
D 150

8 MAC conductors rnrrr' D 35


D 70
D 150
D 185
D 240

9 ACSR conductors rnrn? D 35


D 70
D 150
D 185

10 Conductor position on line post D Side (neck)


insulator D Top

11 Supplied with a neoprene pad


for insertion over the
Yes
conductor where it rests in the
insulator top or side groove.

12 Colour code:
AAC conductors
D 35 mrrf
D 70mm2
D 150 rnm"

AAAC conductors
D 35 rnm? to be specified
;:;~i If
V--- " ~ D 70 mm?

~
Ir(' Ii ~
'" ~p!~~~ )~
* D 150 mrn!
D 185 rnrn"

~~ ~Q
~~
:tClr~e~
"' ~- ~(/JO
Page 36/77
&/II--
EDC-DTS-MVOOS- Overhead Conductors and Accessories

o 240 mrn?

ACSRconductors
D 35 rnm'
D 70 rnrn?
D 150 rnm!
D 185 rnm!

13 Constitution of preformed to be described


ties

14 Packing

Cardbox or bag of 10 pcs Yes

15 Packing Marking:
Manufacturer's name Yes
Month and Year of
Yes
manufacture
Yes
Batch number
Yes
Total gross weight
Yes
Distributor's name
Yes
Reference of tie
Yes
Top or side tie
Yes
Type of conductor
Yes
Min and Max cross section
Yes
Min and max insulator
diameter
16 Technical drawings, Must be provided
Catalogue, full technical
If not the offer is not
information, etc ...
considered.

Supplier's offer column must be properly filled with the right figures. "Compliant, Yes, ", V , etc ..." are not accepted.

Deviation from the technical specification:

The bidder shall list point after point and explain here in after all deviation from the requested technical
specification.

1/
2/
Full technical information shall be supplied within the bid.

Bidder signature:

Page 37/77
EDC-DTS-MV005- Overhead Conductors and Accessories

10.4 Mid-span Full Tension Joints

No. Description Unit Requirements Supplier's Offer

1 Country to be specified

2 Manufacturer to be specified

3 Manufacturer's Reference to be specified

4 Applicable Standard to be specified

5 Full type tests reports supplied Tensile strength test


(as a minimum)
Electrical resistance
measurements test

6 Used to ensure mechanical and


electrical connection between
Yes
two lengths of same cross
section of bare conductors
under mechanical strength.

7 AAC conductors rnrn' 0 35


0 70
0 150
8 AAAC conductors rnrn" 0 35
0 70
0 150
0 185
0 240
9 ACSR conductors mrrr' 0 35
0 70
0 150
0 185
10 One aluminum alloy sleeve
allowing the hexagonal Yes
compression on conductor
core for AAC and AAAC

lOa Diameter of conductor hole mm

0 35 mrrr' To be specified
0 70mm2
0 150 rnrn'

-s=
0 185 mrrr'
~ 0 240 rnm'
Yes
, fltbn,~.. correct
~v. ~iO of conductor
~ ~ .. ~

1*1~'i~lg\
~~ (lh I.'" ..~
W.& elf-
~/CIT~ \.J Page 38/77
-
EDC-DTS-MVOOS- Overhead Conductors and Accessories

10c Supplied with internal grease Yes


and Two caps

11 One steel sleeve and one


aluminum alloy sleeve and
Yes
eventually aluminum insert
tubes allowing the hexagonal
compression on steel core for
ACSRconductors.

12 Guarantee mechanical and


electrical features at least
equivalent to those of the
conductor on which they are Yes
installed

12 a Breaking strength kN To be specified

12b Length mm To be specified

12c No conductor failure appears


next to the mid-span full
Yes
tension joints. and

13 No conductor slip occurs at


tensile load below the nominal Yes
breaking load value of the
conductor.
14 Regular hexagonal Yes
compression type.
15 Regular hexagonal dies mm
references
AACconductors

0 35 rnrrr' 12.0
0 70 rnm? 14.0
0 150 mrrf 23.0

AAACconductors

0 35 rnm' 12.0
0 70mm2 14.0
0 150 rnm" 23.0
0 185 rnrn! 25.0
28.0
0 240 mrrf

ACSRconductors

0 35 rnrrr' 7.2 and 14.0


0 70 mrrr' 12.0 and 23.0
0 150 mm' 12.0 and 23.0
0 185 rnrrf ... and 25.0

Page 39/77
EDC-DTS-MVOOS- Overhead Conductors and Accessories

16 Marking
Manufacturer's identification.

Type of conductor.

Crosssection of conductor.

Compression die reference (s).


Yes
Reference of lot including the
last two digits of manufacture
Year.

Marks showing the places of


compression

17 Packing

Cardbox or bag of 10 pes Yes

18 Packing Marking:

Manufacturer's name Yes

Month and Year of


manufacture Yes

Batch number Yes

Total gross weight Yes

Reference of mid span joint Yes

Type of conductor Yes

Crosssection Yes

19 Technical drawings, Must be provided


Catalogue, full technical
If not the offer is not
information, etc...
considered.

Supplier's offer column must be properly filled with the right figures. "Compliant, Yes, ", V, etc ..." are not accepted.

Deviation from the technical specification:


The bidder shall list point after point and explain here in after all deviation from the requested technical
specification.

1/

~.
s. *
~--~
.., i......
r.
m.~#
2/
Full technical information shall be supplied within the bid.

~
Bidder signature:

~~ a~~._!II
~(
~ -.~~
«'0
7'I?IC~
7.l!lJHI.~'"

/'~
I~
0
v"/ Page40 / 77
EDC-DTS-MVOOS- Overhead Conductors and Accessories

10.5 Aluminium Terminal Lug

No. Description Unit Requirements Supplier's Offer

1 Country to be specified

2 Manufacturer to be specified

3 Manufacturer's Reference to be specified

4 Applicable Standard to be specified

5 Full type tests reports supplied Electrical resistance


(as a minimum) measurements test

6 For connection of AAC,or


AAAC,or ACSRnot stretch
Yes
conductors on aluminium
terminals.

7 AACconductors mrrr' 0 35
0 70
0 150
8 AAACconductors mm' 0 35
0 70
0 150
0 185
0 240
9 ACSRconductors mrrr' 0 35
0 70
0 150
0 185
10 One aluminum alloy sleeve
allowing the hexagonal Yes
compression on conductor and
one aluminum palm

lOa Diameter of conductor hole

0 35 rnrrr' mm To be specified
0 70 mm!
0 150 mm!
0 185 rnrrr'
0 240 mrn?
lOb Internal grease and cap Yes

11 Guarantee electrical features


at least equivalent to those of
Yes
the conductor on which they
are installed

'r I .
, ,
~,

Page41 / 77
~7'rE'
EDC-DTS-MVOOS- Overhead Conductors and Accessories

12 No conductor failure appears Yes


next to the lug

13 Palm hole diameter mm 15

14 Regular hexagonal Yes


compression type.
15 Regular hexagonal dies
references
mm
0 35 mm' 12.0
0 70 rnm' 14.0
0 150 rnm' 23.0
0 185 rnrrr' 25.0
0 240 rnrrr' 28.0
16 Marking
Manufacturer's identification.

Crosssection of conductor.

Compression die reference

Reference of lot including the Yes


last two digits of manufacture
Year.

Marks showing the places of


compression

17 M14 x 50 mm aluminium bolt Supplied


and two aluminium washers

18 Packing

Cardbox or bag of 10 pcs Yes

19 Packing Marking:
Manufacturer's name Yes
Month and Year of
Yes
manufacture
Yes
Batch number
Yes
Total gross weight
Yes
Reference of lug
Yes
Type of conductor
Yes
Crosssection

~ 20 Technical drawings,
cr~~ataIOgu~i'full technical
ation, etc...
Must be provided

If not the offer is not

S
~ i4
~ ~c:, considered.

ee .,,~ ~uejter'~~~,olumn must be properly filled with the right figures. "Compliant, Yes, ", V, etc ..." are not accepted.

1*1 ~ ("~ g
~~rt/~
~C • , 'W +-- lfNl
J'J(ICIl'E. V'" V Page42 / 77
EDC-DTS-MVOOS- Overhead Conductors and Accessories

Deviation from the technical specification:

The bidder shall list point after point and explain here in after all deviation from the requested technical
specification.

1/
2/
Full technical information shall be supplied within the bid.

Bidder signature:

Page43 /77
EDC-DTS-MVOOS- Overhead Conductors and Accessories

10.6 Bi-metallic Terminal Lug

No. Description Unit Requirements Supplier's Offer

1 Country to be specified

2 Manufacturer to be specified

3 Manufacturer's Reference to be specified

4 Applicable Standard to be specified

5 Full type tests reports supplied Electrical resistance


(as a minimum) measurements test

Climatical ageing test

6 For connection of AAC,or


AAAC,or ACSRnot stretch
Yes
conductors on copper
terminals.

7 AACconductors rnrn? D 35
D 70
D 150
8 AAACconductors rnrrr' D 35
D 70
D 150
D 185
D 240
9 ACSRconductors mrrf D 35
D 70
D 150
D 185
10 One aluminum alloy sleeve
allowing the hexagonal Yes
compression on conductor and
one copper palm

lOa Diameter of conductor hole mm

D 35 mrrr' To be specified
D 70mm2
D 150 mm'
D 185 mrn?
D 240 mrn'
;:;:,r\1

:.t
~r.::~. ~* II ~~e

.,- lW .l
electricalfeatures
equivalentto those of Yes

I I~~
'* ~~ )C>
Q
0
~-~~
~
~C'J:
~/CITE Q~
IuJ -r Page 44 / 77
EDC-DTS-MV005- Overhead Conductors and Accessories

the conductor on which they


are installed

12 No conductor failure appears Yes


next to the lug

13 Method of aluminum/copper To be described


connection and corrosion
protection

14 Palm hole diameter mm 13

15 Regular hexagonal Yes


compression type.
16 Regular hexagonal dies
references
mm
0 35 rnrrf 12.0
0 70 mrrr' 14.0
0 150 rnm? 23.0
0 185 rnrrf 25.0
0 240 rnrrr' 28.0
17 Marking
Manufacturer's identification.

Cross section of conductor.

Compression die reference

Reference of lot including the Yes


last two digits of manufacture
Year.

Marks showing the places of


compression

18 M12 x 50 mm copper or
stainless steel bolt and two
Supplied
copper or stainless steel
washers

19 Packing

Cardbox or bag of 10 pcs Yes

20 Packing Marking:

Manufacturer's name Yes

Month and Year of


manufacture Yes
.. ,.;;.;,.. --.,

Batch number Yes ~'i I'I~'"

Total gross weight Yes

Page4S /77
~ , fJAr,
A~~1f¬ ~~
EDC-DTS-MVOOS- Overhead Conductors and Accessories

Reference of lug Yes

Type of conductor Yes

Crosssection Yes

21 Technical drawings, Must be provided


Catalogue, full technical
If not the offer is not
information, etc ...
considered.

Supplier's offer column must be properly filled with the right figures. "Compliant, Yes, ", V, etc ..." are not accepted.

Deviation from the technical specification:

The bidder shall list point after point and explain here in after all deviation from the requested technical
specification.

1/
2/

Full technical information shall be supplied within the bid.

Bidder signature:

Page46 / 77
EDC-DTS-MVOOS- Overhead Conductors and Accessories

10.7 PG Clamp

No. Description Unit Requirements Supplier's Offer

1 Country to be specified

2 Manufacturer to be specified

3 Manufacturer's Reference to be specified

4 Applicable Standard to be specified

5 Full type tests reports supplied Electrical resistance


(as a minimum) measurements test

6 Parallel grooves type Yes

7 For connection of AAC,or Yes


AAAC,or ACSR

8 Main conductors rnrrr' 0 35


0 70
0 150
0 185
0 240
9 Tap conductors mrrr' 0 35
0 70
0 150
0 185
0 240
10 The clamp body shall be made
of high corrosion resistance Yes
aluminum alloy.

11 Minimum number of 2
tightening bolts

12 Number and diameter of bolts To be specified


according cross section range

13 Bolts screwed in one half of Yes


the PGclamp.

14 Bolts made of aluminum alloy


or stainless steel and fitted
Yes
with one locking nut.

15 Markings

Manufacturer's identification. Yes ~!_ft~ :;'1


Cross section range.
~rtJ ~
'\'"1 --,: *
. ,

Page 47 / 77
W
EDC-DTS-MVOOS- Overhead Conductors and Accessories

Reference of lot including the


last two digits of manufacture
Year.
16 Packing

Cardbox or bag of 10 pcs Yes

17 PackingMarking:

Manufacturer's name Yes

Month and Year of


manufacture Yes

Batch number Yes

Total gross weight Yes

Reference of PGclamp Yes

18 Technicaldrawings, Must be provided


Catalogue,full technical
If not the offer is not
information, etc...
considered.

Supplier's offer column must be properly filled with the right figures. "Compliant, Yes, ", V, etc ..." are not accepted.

Deviation from the technical specification:

The bidder shall list point after point and explain here in after all deviation from the requested technical
specification.

1/
2/

Full technical information shall be supplied within the bid.

Bidder signature:

Page48/77
EDC-DTS-MVOOS- Overhead Conductors and Accessories

10.8 Covered Conductors

No. Description Unit Requirements Supplier's Offer

1 Country to be specified

2 Manufacturer to be specified

3 Manufacturer's Reference to be specified

4 Applicable Standard EN50397

EN50183

5 Full type tests reports supplied Yesas per EN50397


requirements

6 Rated Voltage (Um) kV 24 kV

7 Voltage withstand one minute kV 30 kV

8 Conductors core made of:

185 mrrr', 150 mm", 95 rnrrr', AL4 Aluminium alloy


70 mm", 50 mrn", 35 rnrn".
(EN 50397)

9 Compacted cores Yes

10 Aluminium (35 rnrn/] and To be specified


Aluminium alloy AL4 origin

11 Core Crosssections mrrr' 0 185


0 150
0 95
0 70
0 50
0 35

12 Real core cross section:

0 185 rnrrr' ± 3 mrn'


0 150 rnrrr' ± 3 mrrr'

0 95 rnm' ± 3 mrn'
0 70 rnrn" +5/-1 rnrn' mrrr' To be specified
0 50 rnrn" +5/-1 rnrrr'

0 35 mrrr' +2/-1 mrn'

12a Core diameter of:

0 185 mm'
0 150 rnrn!
mm To be specified ¢i If-:a~
"'t'J
0 95 rnrn' :/~~ 1*
~~L
Page 49 / 77
:'_'Uif~~
EDC-DTS-MV005- Overhead Conductors and Accessories

0 70 mrn'
0 50 rnrrr'
0 35 mrn"

Diameter over covering of:

0 185 mm' mm
0 150 rnrn"
To be specified
0 95 rnrrr'
0 70 rnm'
0 50mm2
0 35 rnrn'

13 Number of wires of :

0 185 mm!
0 150 mm'
0 95 mrn!
To be specified
0 70mm2
0 50mm2
0 35 mrn?

14 Diameter of wires

0 185 rnrn' mm
0 150 mm! To be specified
0 95 mrrr'
0 70mm2
0 50mm2
0 35 mm!

15 Number of layer

0 185 rnrrf
0 150 mm' To be specified
0 95 mm'
0 70mm2
0 50mm2
0 35 rnrn"

16 Minimum breaking strength of


complete covered conductor
kN
0 185 mm! 54

0 150 rnm' 43

0 95 rnm? 27

4~ft~
~~r;"~
I
r ~
,..1 C!)
0 70mm2

0 50 rnrn'
24

14

*'1f
«
«'c ~I
"l?tCI
CJ~ ". Page50/77
EOC-OTS-MV005- Overhead Conductors and Accessories

0 35 rnrn" 5

17 Conductivity % 52.9%
lACS

18 Modulus of elasticity hbar

185, 150 and 95 mm' 6000


70 and 50 rnrrr' 6200
35 rnrn' 7000

19 Coefficient of linear expansion

per·C x 10-6 23

20 Minimal carrying capacity

20·C in air without wind To be specified

0 185 mrrf 390

0 150 mrrr' 340

0 95 rnrn" 280

0 70mm2 A 200

0 50 rnrn! 150

0 35 mrn' 130

21 Minimal linear resistance 20·C

0 185 rnrn'

0 150 rnm'

0 95 rnrrr'
O/km
0 70mm2 To be specified

0 50mm2

0 35 mrrr'

22 Core water tightness

The stranded conductor shall


Yes
be longitudinally watertight
To be described
Means for water tightness

The filling mass or other


materials for obtaining the
longitudinal water tightness,
shall be compatible with the Yes
conductor material and the
material of the covering to

Page 51 / 77
EDC-DTS-MV005- Overhead Conductors and Accessories

prevent the migration of water


inside the covered conductor

This water blocking massshall


not migrate into the core of
the conductor.

It shall not deteriorate Yes


mechanical and electrical
characteristics of accessories
thereafter. Yes
No specific tool and no solvent
shall have to be used to
prepare the contact between
conductors and accessories.
Yes
The water blocking mass used
shall be safe for the
environment. This shall be
proved by supplying relevant
tests and certificates.
Yes

23 Core semi conductive layer Yes/No

24 Covering sheath

Made of black UVstabilized and


weather resistant extruded Yes
XLPE

Covering thickness, consistent Yes


with minimum cost and
satisfactory performance

Minimum thickness mm 2.5

Thickness of covering

o 185 rnrn" mm To be specified

o 150 rnrrr' mm To be specified

o 95 rnrrr' mm To be specified

o 70 rnrn' mm To be specified

o 50 mrrr' mm To be specified

o 35 rnm? mm To be specified

compound in
ce with the EN 50397 Yes
ents.

Page52 / 77
EDC-DTS-MV005- Overhead Conductors and Accessories

XLPECompound tests supplied. Yes

Possible to remove the


covering without damage to
Yes
the conductor.

25 Maximum Temperatures

normal operation °C 90

short duration overload °C 120

Under short circuit (5 sec) °C 250

26 Marking

Embossed Yes

Manufacturer's identification Yes

Year of manufacture Yes


Conductor type CC
Covering material 5 (for semi-conductive
conductor screen, if any) X (for
cross-linked polyethylene),

Conductor material AL4 or AL

Cross-section Yes

Conductor design W (for watertight), : K (for


compacted);

Rated voltage Um kV 24

Supplier name To be mentioned

27 Packing

Material of Drum (Non- Steel/Timber


returnable)

Length of Cable per Drum m 1000 ± 5m

28 Drum Marking:
Manufacturer's name Yes

Month and Year of Yes


manufacture Yes
Type and cross section Yes
Batch number Yes

Page53 / 77
EDC-DTS-MV005- Overhead Conductors and Accessories

Total gross weight Yes


Net weight m Yes
Distributor's name Yes
Length of conductor Yes
18 Technical drawings, Must be provided
Catalogue, full technical
If not the offer is not
information, etc ...
considered.

2 samples of 50 cm length of the offered covered conductor to be supplied within the bid

Supplier's offer column must be properly filled with the right figures. "Compliant, Yes, ", V, etc. .." are not accepted.

Deviation from the technical specification:

The bidder shall list point after point and explain here in after all deviation from the
requested technical specification.

1/
2/
Full technical information shall be supplied within the bid.

Bidder signature:

Page54/77
EDC-OTS-MV005- Overhead Conductors and Accessories

10.9 Tie Termination Anchor Sleeve

No. Description Unit Requirements Supplier's Offer

1 Country to be specified

2 Manufacturer to be specified

3 Manufacturer's Reference to be specified

4 Applicable Standard to be specified

5 Full type tests reports supplied Yes

6 Used to

-Anchor the covered conductor


by hexagonal compression on
Yes
covered conductor core.

-Connect with the strain


insulator by a clevis with a Yes
breaking load of 70 kN.

-Connect with a branch or a


Yes
jumper through a diameter 25
mm pin connector

-Prevent the penetration of Yes


water into the covered
conductor

-Short circuiting and earthing Yes


of covered conductor

7 Compression tube inside


diameter

D 185 rnrn!
mm To be specified
D 150 rnrrr'

D 95 rnm!

D 70 mrrr'

D 50 mrn"

8 Cross section mm

D 185 rnrn'
to be specified
D 150 rnm?

D 95 rnm'

Page 55/77
EDC-DTS-MV005- Overhead Conductors and Accessories

D 70 mrrr'

D 50mm2

D 35 rnrn'

9 Guarantee mechanical and


electrical features at least
equivalent to those of the Yes
conductor core on which they
are installed.

10 No covered conductor failure


shall appear next to the Tie - Yes
Termination anchor sleeve

11 No conductor slip shall appear


at tensile load below the
Yes
nominal breaking load value of
the conductor.

12 Regular Hexagonal Yes


compression type

13 Compression dies sizes of:

D 185 rnrrr' mm 25

D 150 rnrrr' mm 23

D 95 rnrn! mm 17.3

D 70mm2 mm 17.3

D 50mm2 mm 14

13a Grease filled and capped Yes

14 Markings

Manufacturer's identification. Yes

Type of conductor. Yes

Cross section of conductor. Yes

Compression die reference. Yes

Reference of lot including the Yes


last two digits of manufacture
Year.

~ ~~ng the placesof Yes

IS:
~( ~
~
~~~"
~.

~\
.

~tyJ -. Page56/77 +-
EDC-DTS-MV005- Overhead Conductors and Accessories

Cardbox or bag of 10 pcs Yes

16 Packing Marking:

Manufacturer's name Yes

Month and Year of


manufacture Yes

Batch number Yes

Total gross weight Yes

Reference and cross section of Yes


equipment

17 Technical drawings, Must be provided


Catalogue, full technical
If not the offer is not
information, etc ...
considered.

2 samples of the offered equipment to be supplied within the bid

Supplier's offer column must be properly filled with the right figures. "Compliant, Yes, ", V ,etc ..." are not accepted.

Deviation from the technical specification:

The bidder shall list point after point and explain here in after all deviation from the requested technical
specification.

1/
2/

Full technical information shall be supplied within the bid.

Bidder signature:

Page57/77
EDC-DTS-MV005- Overhead Conductors and Accessories

10.10 Mid-span Full Tension Joints for Covered Conductors

No. Description Unit Requirements Supplier's Offer

1 Country to be specified

2 Manufacturer to be specified

3 Manufacturer's Reference to be specified

4 Applicable Standard To be specified

5 Full type tests reports supplied Tensile strength test


(as a minimum)
Electrical resistance
measurements test

6 Ensure mechanical and


electrical connection between
Yes
two lengths of same cross
section of stretched bare
conductors.

7 Eachmid-span full tension joint


comprises:

One aluminium alloy sleeve


allowing the hexagonal
Yes
compression on conductor
core.

One water tightening system


(gasket, cap, sleeve) to prevent
the penetration of water into Yes
the covered conductor and
reconstitute the conductor
covering.

8 Crosssections of covered o 185 mrrf


conductors
o 150 rnrn'

o 95 rnrn!

o 70 mrn?

o 50 mrn!

Page58/77
EDC-DTS-MV005- Overhead Conductors and Accessories

o 150 rnrrr' mm To be specified


o 95 mm"
o 70 rnm'
o 50 rnm'

8b Grease filled and capped Yes

9 Guarantee mechanical and


electrical features at least
equivalent to those of the
covered conductor on which Yes
they are installed

10 No conductor failure appears


next to the mid-span full
Yes
tension joints. and

11 No conductor slip occurs at


tensile load below the nominal Yes
breaking load value of the
covered conductor.
12 Regular hexagonal Yes
compression type.
13 Regular hexagonal dies
references
o 50 rnrn?
14
o 70 rnm? mm 70
o 95 rnm! 17.3
o 150 mrn' 23
o 185 mrn' 25

14 Marking
Manufacturer's identification.

Type of conductor.

Cross section of conductor.

Compression die reference (s).


Yes
Reference of lot including the
last two digits of manufacture
Year.

Marks showing the places of


compression

15 Packing

Cardbox or bag of 10 pes Yes

16 Packing Marking:

Page 59/77
EDC-DTS-MVOOS- Overhead Conductors and Accessories

Manufacturer's name Yes

Month and Year of


manufacture Yes

Batch number Yes

Total gross weight Yes

Reference of mid span joint Yes

Type of conductor Yes

Crosssection Yes

17 Technical drawings, Must be provided


Catalogue, full technical
If not the offer is not
information, etc...
considered.

2 samples of the offered equipment to be supplied within the bid

Supplier's offer column must be properly filled with the right figures. "Compliant, Yes, ", V r etc ..." are not accepted.

Deviation from the technical specification:

The bidder shall list point after point and explain here in after all deviation from the requested technical
specification.

1/
2/

Full technical information shall be supplied within the bid.

Bidder signature:

Page 60/77
EDC-DTS-MVOOS- Overhead Conductors and Accessories

10.11 Pin Branch Joint

No. Description Unit Requirements Supplier's Offer

1 Country to be specified

2 Manufacturer to be specified

3 Manufacturer's Reference to be specified

4 Applicable Standard EN50397-2

5 Full type tests reports supplied According EN50397-2

6 Used to connect a covered,


non-cut, stretched line
Yes
conductor with a cut covered
conductor

7 Eachpin branch joint for


Covered Conductor comprises:

One or two insulation piercing


connectors with water-
tightness system (gasket, Yes
cap...) to prevent the
penetration of water into the
covered conductor.

One 25 mm diameter
aluminum alloy tap pin to
connect a jumper with a pin Yes
connector.

One pin or device allowing


short circuiting and earthing of
covered conductor Yes

8 To be used with the following rnm!


covered conductors 0 185
0 150
0 95
0 70
0 50
9 The carrying capacity of pin
branch joints shall be at least
equal to the one of the bigger Yes
cross section indifferently line
or tap conductor

Page 61 / 77
EDC-DTS-MVOOS- Overhead Conductors and Accessories

Carrying capacity of :

0 185 mrn!
0 150 rnrrr'
A To be specified
0 95 mm!
0 70 rnrn'
0 50 rnrn"
10 insulation piercing connector

Not have components that are


Yes
liable to be lost during
installation.

The housing made entirely of


mechanical and resistant Yes
plastic insulation material

No metallic part outside the


housing is acceptable except
Yes
for the tightening system.

The housing is an integral part


of the connector. Yes

The bolts tightening torque are


controlled by shear head Yes
screws without the need of
any special tool.

The number and the length of


the teeth are adequate enough
to penetrate the relevant Yes
covered conductor covering to
establish proper contact
without any contract
resistance and without the
need to strip the covered
conductor insulation.

To achieve the required water


tightness a special rubber seal Yes
be provide around the teeth of
the present connector.

The bolts and washers are of


Yes
corrosion resistant type.

Page 62 / 77
EDC-DTS-MVOOS- Overhead Conductors and Accessories

11 Pin

Metal To be specified

Diameter To be specified

Length To be specified

lla EarthingPin

Metal To be specified

Diameter To be specified

Length To be specified

12 IPCcross section range To be specified for each


type of IPC

14 Markings
Manufacturer's identification. Yes
Type of conductor. Yes
Crosssection range of Yes
conductor. Yes
Reference of lot including the Yes
last two digits of manufacture
Year.

15 Packing
Cardbox or bag of 10 pcs Yes

16 PackingMarking:
Manufacturer's name Yes
Month and Year of
Yes
manufacture
Yes
Batch number
Yes
Total gross weight
Yes
Reference and cross section of
equipment
17 Technicaldrawings, Must be provided
Catalogue,full technical
If not the offer is not
information, etc...
considered.

2 samplesof the offered equipment to be supplied within the bid

Supplier's offer column must be properly filled with the right figures. "Compliant, Yes, ", V ,etc ..." are not accepted.

Page63 / 77
EDC-OTS-MV005- Overhead Conductors and Accessories

Deviation from the technical specification:

The bidder shall list point after point and explain here in after all deviation from the requested technical
specification.

1/
2/

Full technical information shall be supplied within the bid.

Bidder signature:

Page64/77
EDC-DTS-MV005- Overhead Conductors and Accessories

10.12 Pin Connector

No. Description Unit Requirements Supplier's Offer

1 Country to be specified

2 Manufacturer to be specified

3 Manufacturer's Reference to be specified

4 Applicable Standard To be specified

5 Full type tests reports supplied Yes

6 Used to connect Tie-


Termination anchor sleeve and
Yes
pin branch joints to a bridge
constituted by a non-stretched
linking bare or covered
conductor

7 To be installed on a 25mm Yes


diameter pin.

8 To be used with the following rnrn"


AAAC bare conductors D 240
D 185
D 150
D 70
D 35
8a Compression tube inside
diameter

D 240 mrrr'
mm To be specified
D 185 rnm'
D 150 rnm?
D 70mm2
D 35 rnrrf

9 To be used with the following mrn? D 185


covered conductors D 150
D 95
D 70
D 35 -..c-.

9a Compression tube inside


diameter
&t-~~
Page 65/77

-,
EDC-OTS-MVOOS- Overhead Conductors and Accessories

o 185 rnm!
o 150 mrrr'
mm To be specified
o 95 mrrr'
o 70 rnrrr'
o 50 mrrf

10 A Pin connector comprises:

• One body made of


aluminum alloy including a
Yes
tightening system.
• This body allows the
electrical connection on
Yes
the 25mm diameter pin of
the tie-termination or the
pin branch joints
• One tube welded on the Yes
body
• For covered conductors,
the tube shall include a Yes
water-tightened system
(gasket, cap ...) to prevent
the penetration of water
into the covered conductor
and a special device to
confirm the correct
penetration of the
conductor in the tube

11 All tube are filled with high


quality oxide inhibiting Yes
compound and capped

12 On site, the tube is hexagonally


compressed onto the Yes
conductor

13 The carrying capacity of the


connectors is at least equal to Yes
the capacity of the compressed
conductor

14 Tightening system onto the


pin

The tightening bolts include an


~ c r-torque shear head made
.A~Ii i' .Jfs ble material which
t~'V\ al s.j. lam ping torque in
L .Ji>nf
~r/)~8
1% 7 .~ ~ rmt with the
Yes

*1 ~l
~ f)'l1
.w~"~
~C/'1:1 ----
'T/CITE \)v
,\
j ~

(J
Page66 / 77

-
EDC-DTS-MVOOS- Overhead Conductors and Accessories

recommendation of the
manufacturer, without the
need of any special tool.
Yes
This head shall be hexagonal
head type.

A ring is accessibleafter
breaking of the first head to
allow disconnection of pin Yes
connector from a pin with
hook stick for future hot line
working.

15 Tube of Regular hexagonal Yes


compression type.
16 Regular hexagonal dies
references
0 35 rnrrr' 12
0 50mm2 mm 14
0 70mm2 17.3
0 95 rnrrr' 17.3
0 150 mrn' 23
0 185 rnm' 25
0 240 mm? 28

17 Markings

Manufacturer's identification. Yes

Type of conductor. Yes

Cross section Yes

Reference of lot including the Yes


last two digits of manufacture
Year.

18 Packing

Cardbox or bag of 10 pcs Yes

19 Packing Marking:

Manufacturer's name Yes

Month and Year of


manufacture Yes

Batch number Yes

Total gross weight Yes

Yes

Page 67/77
EDC-DTS-MVOOS- Overhead Conductors and Accessories

Reference and cross section of


equipment

20 Technical drawings, Must be provided


Catalogue, full technical
If not the offer is not
information, etc ...
considered.

2 samples of the offered equipment to be supplied within the bid

Supplier's offer column must be properly filled with the right figures. "Compliant, Yes, ", V, etc ..." are not accepted.

Deviation from the technical specification:

The bidder shall list point after point and explain here in after all deviation from the requested technical
specification.

1/
2/

Full technical information shall be supplied within the bid.

Bidder signature:

Page68 / 77
----------------------_ ~---. ~

EDC-DTS-MVOOS-
Overhead Conductors and Accessories

lO.13Aluminium Terminal Lug for Covered Conductor

No. Description Unit Requirements Supplier's Offer

1 Country to be specified

2 Manufacturer to be specified

3 Manufacturer's Reference to be specified

4 Applicable Standard to be specified

5 Full type tests reports supplied Electrical resistance


(as a minimum) measurements test

6 For connection covered


conductors onto aluminum
Yes
terminals.

7 Covered conductors for D 35


D 50
D 70
D 95
D 150
D 185
8 One aluminum alloy tube
allowing the hexagonal Yes
compression on conductor and
one aluminum palm

8a Compression tube inside


diameter

D 185 rnrrr'
mm To be specified
D 150 rnm'
D 95 rnrrr'
D 70 mm?
D 50 mrn?

9 One gasket of system avoiding


penetration of water inside the Yes
covered conductor

10 Guarantee electrical features


at least equivalent to those of
the conductor on which they
are installed Yes

11 No covered conductor failure Yes -7~~


~-i II-;~
~
L___---'--_ap_p_e_a_rs_n_e_x_t
_to_t_h_e_IU_g _L_ __ L__ __L __ !~!O._f--j~ ~ ..!
._'_.q
m' (!)

"'A ~
Page 69/77 ~~
i9ICafe \) ~
EDC-DTS-MVOOS- Overhead Conductors and Accessories

12 Palm hole diameter mm 15

13 Regular hexagonal Yes


compression type.
14 Regular hexagonal dies
references
0 35 mrn! 12.0
0 50 rnrn' 14.0
0 70 mrrr' 17.3
95 rnm? mm
0 17.3
0 150 mm? 23.0
0 185 mrn!
25.0
15 Marking
Manufacturer's identification.

Crosssection of conductor.

Compression die reference

Reference of lot including the Yes


last two digits of manufacture
Year.

Marks showing the places of


compression

16 M14 x 50 mm aluminium bolt Supplied


and two aluminium washers

17 Packing

Cardbox or bag of 10 pes Yes

18 Packing Marking:

Manufacturer's name Yes

Month and Year of


manufacture Yes

Batch number Yes

Total gross weight Yes

Reference of lug Yes

Type of conductor Yes

Crosssection Yes

~ ~Chnical drawings, Must be provided


~ ~ fl f.ta~ gue, full technical
t~~~..}
:,: '('. ~
r~ tion, etc ...
uJ
If not the offer is not
considered.

*' -~~J8 o
\~ , ~
(" . ~f'~
<"C .Jf.fL.? ~
Page70/77
EDC-DTS-MVOOS- Overhead Conductors and Accessories

2 samples of the offered equipment to be supplied within the bid

Supplier's offer column must be properly filled with the right figures. "Compliant, Yes, ", V, etc ..." are not accepted.

Deviation from the technical specification:

The bidder shall list point after point and explain here in after all deviation from the requested technical
specification.

1/
2/
Full technical information shall be supplied within the bid.

Bidder signature:

Page 71/77
EDC-DTS-MVOOS- Overhead Conductors and Accessories

10.14 Bi-metallic Terminal Lug for Covered Conductors

No. Description Unit Requirements Supplier's Offer

1 Country to be specified

2 Manufacturer to be specified

3 Manufacturer's Reference to be specified

4 Applicable Standard to be specified

5 Full type tests reports supplied Electrical resistance


(as a minimum) measurements test

Climatical ageing test

6 For connection of covered


conductors on copper
Yes
terminals.

7 Covered conductors 0 35
0 50
0 70
mrn' 0 95
0 150
0 185
8 One aluminum alloy sleeve
allowing the hexagonal Yes
compression on conductor and
one copper palm

8a Compression tube inside


diameter

0 185 mrrr'
mm
0 150 rnrn?
0 95 mrrr' To be specified
0 70 rnrrr'
0 50 mrrf
0 35 rnrn"

9 Guarantee electrical features


at least equivalent to those of
Yes

Vl ~ ~r
the conductor on which they

-
S~le
are installed

I <:*e system avoiding


at n of water inside the
Yes
~ r'rr 11§'e~f~ ductor

I*I~
~ ~
. CJ'tf
1b1fE O\} Page 72 / 77
EDC-DTS-MVOOS- Overhead Conductors and Accessories

11 No conductor failure appears Yes


next to the lug

12 Method of aluminum/copper To be described


connection and corrosion
protection

13 Palm hole diameter mm 13

14 Regular hexagonal Yes


e.
15 Regular hexagonal dies
references
0 35 rnrrr'
12.0
0 50 mm' mm 14.0
0 70mm2 17.3
0 95 rnm' 17.3
0 150 rnm? 23.0
0 185 rnrrr' 25.0

16 Marking
Manufacturer's identification.

Crosssection of conductor.

Compression die reference

Reference of lot including the Yes


last two digits of manufacture
Year.

Marks showing the places of


compression

17 M12 x 50 mm copper or
stainless steel bolt and two
Supplied
copper or stainless steel
washers

18 Packing

Cardbox or bag of 10 pcs Yes

19 Packing Marking:

Manufacturer's name Yes

Month and Year of


manufacture Yes

Batch number Yes

Total gross weight Yes

Reference of lug Yes

Page 73/77
EDC-DTS-MVOOS- Overhead Conductors and Accessories

Type of conductor Yes

Crosssection Yes

20 Technical drawings, Must be provided


Catalogue, full technical
If not the offer is not
information, etc...
considered.

2 samples of the offered equipment to be supplied within the bid

Supplier's offer column must be properly filled with the right figures. "Compliant, Yes, ", V, etc ..." are not accepted.

Deviation from the technical specification:

The bidder shall list point after point and explain here in after all deviation from the requested technical
specification.

1/
2/

Full technical information shall be supplied within the bid.

Bidder signature:

Page74/77
EDC-DTS-MV005- Overhead Conductors and Accessories

lO.15IPC for Covered Conductors

No. Description Unit Requirements Supplier's Offer

1 Country to be specified

2 Manufacturer to be specified

3 Manufacturer's Reference to be specified

4 Applicable Standard EN 50397-2

5 Full type tests reports supplied As per requirements of


EN 50397-2

6 Used to connect two covered


conductors with the same or
Yes
different cross section
between them without
possibility of disconnection
latter.

7 They are of not reusable type. Yes

8 The main conductor is


stretched or not. Yes

9 The tap conductor is a bridge


constituted by a not stretched Yes
linking covered conductor.

10 To be used with the following rnm" D 185


covered conductors on main D 150
D 95
D 70
D 35
11 To be used with the following rnrn? D 185
covered conductors on Tap D 150
D 95
D 70
D 35
12 Cross section ranges (Main and rnrn? To be specified
tap) for each IPCsupplied

13 The carrying capacity of pin


branch joints shall be at least
equal to the one of the bigger Yes
cross section indifferently main
or tap conductor
~'~

*1
~~~~
.w *
~w(!)
tn! LI.
~.
Cl)).
8
9:)
Page75 / 77 I?/c:, ':-OU
,_,_ .
EDC-OTS-MVOOS- Overhead Conductors and Accessories

Carrying capacity
To be specified
o 185 rnm' A
o 150 rnm'
o 95 rnrn!
o 70 rnm!
o 50 mrn'
o 35 mrn?

14 Not have components that are


liable to be lost during
installation. Yes

The housing made entirely of


mechanical and resistant
plastic insulation material
Yes
No metallic part outside the
housing is acceptable except
for the tightening system.
Yes
The housing is an integral part
of the connector.

The bolts tightening torque are Yes


controlled by shear head
screws without the need of
any special tool. Yes

The number and the length of


the teeth are adequate enough
to penetrate the relevant
covered conductor covering to Yes
establish proper contact
without any contract
resistance and without the
need to strip the covered
conductor insulation.

To achieve the required water


tightness a special rubber seal
Yes
be provide around the teeth of
the present connector.

The bolts and washers are of


corrosion resistant type. Yes

Yes

Yes

Page 76/77
EDC-DTS-MVOOS- Overhead Conductors and Accessories

Min/max Crosssection on Yes


main and tap
Yes
Reference of lot including the
last two digits of manufacture
Year.

Yes

16 Packing

Cardbox or bag of 10 pcs Yes

17 PackingMarking:

Manufacturer's name Yes

Month and Year of


manufacture Yes

Batch number Yes

Total gross weight Yes

Reference and cross section of Yes


equipment

18 Technicaldrawings, Must be provided


Catalogue,full technical
If not the offer is not
information, etc...
considered.

2 samplesof the offered equipment to be supplied within the bid

Supplier's offer column must be properly filled with the right figures. "Compliant, Yes, ", V etc ..." are not accepted.
t

Deviation from the technical specification:

The bidder shall list point after point and explain here in after all deviation from the requested technical
specification.

1/
2/
Full technical information shall be supplied within the bid.

Bidder signature:

Page 77 / 77