LAB MANUAL FOR 8 EXPERIMENTS D
LAB MANUAL FOR 8 EXPERIMENTS D
Location of the Lab: Room No: 018 & 019, New Academic Building
Page | 1
DEPARTMENT OF ELECTRICAL ENGINEERING
Experiment No.: 01
STUDY OF VARIOUS SYSTEM FAULTS USING A DC ANALYZER
Page | 2
TITLE: Study of various system faults using a DC analyzer.
OBJECTIVE: To simulate the following system in a DC network analyzer and calculate the fault
current in different parts of the system for i) 3-phase fault ii) S.L.G fault iii) L.L fault iv) D.L.G fault.
Apparatus List:
System Diagram:
11KV 6.6KV
132KV
Line
Tr - 1 Tr - 2
Page | 3
Positive sequence reactance = 5%
Positive sequence reactance = 2%
Zero sequence reactance = 1%
Procedure:
1. Convert all the data to per unit quantities choosing 100MVA base.
2. Draw sequence box connections for above faults, and check it with the help of teacher-in-charge.
3. Simulate the network with proper interconnection on the analyzer, taking a scale factor of
1 p.u volt = 10 volts
1 p.u Ohm = 1 KΩ Determine the scale factor for current.
4. Note the current value in p.u. in all parts of the system.
Single line diagram and their equivalent 𝑍𝑝.𝑢
G1
G3
G2 Tr - 1 Tr - 2
𝑆𝑏𝑎𝑠𝑒 𝑀𝑉𝐴
𝑍𝑝.𝑢 = 𝑍𝑎𝑐𝑡𝑢𝑎𝑙 ∗ ( 2 ) = 𝑍𝑎𝑐𝑡𝑢𝑎𝑙 ∗
𝑉𝑏𝑎𝑠𝑒 𝐾𝑉 2
𝑆 (𝑀𝑉𝐴)
𝑍𝑝.𝑢.𝑛𝑒𝑤 = 𝑍𝑝.𝑢.𝑜𝑙𝑑 *( 𝑆𝑏𝑎𝑠𝑒 𝑛𝑒𝑤
) = 𝑍𝑝.𝑢.𝑜𝑙𝑑 ∗ ( (𝑀𝑉𝐴)𝑛𝑒𝑤 )
𝑏𝑎𝑠𝑒 𝑜𝑙𝑑 𝑜𝑙𝑑
Page | 4
+VE SEQUENCE: 𝑍𝑝.𝑢 = (0.132 x 66) x (100/1322) = 0.05
+VE SEQUENCE, -VE SEQUENCE and ZERO SEQUENCE p.u. reactance: 0.1
V a = Vb = V c = ( I a + I b + I c ) Z f
I f = I a + I b + I c = E a (Z 1 + Z f )
+ve sequence
1 0 0 1 0 0 2 0 0 5 0 0 1 0V
1 0 0 5 0 1 0 0
F
I LF I RF
IF
Page | 5
Observation Table: -
Va = Z f I a , Ib = Ic = 0
I 1a = I a2 = I a0 = E a ( Z 1 + Z 2 + Z 0 + 3Z f )
I f = I a = 3I 1a
+ve sequence
1 0 0 1 0 0 2 0 0 5 0 0
1 0 0 5 0 1 0 0
F1
I L F1 I R F1
I F1
-ve sequence
5 0 5 0 1 0 0 2 0 0 1 0V
1 0 0 5 0 F2 1 0 0
I LF2 I RF2
IF2
zero sequence 5 0 0
4 0 4 0 1 0 0
5 0
1 0 0 1 0 0 F0 1 0 0
I LF0 I RF0
I F0
Page | 6
Observation Table: -
I f = 3I 1F = 8 6 . 2 2m A
Vb − V c = I b Z f , Ib + Ic = 0 , Ia = 0
I a0 = 0 , I 1a = − I a2 = E a ( Z 1 + Z 2 + Z f )
I f = I b = − I c = (a 2 − a ) I 1a = − j 3I 1a
Page | 7
P
+ve sequence
1 0 0 1 0 0 2 0 0 5 0 0
1 0 0 5 0 1 0 0
F1
I L F1 I R F1
I F1
1 0V
-ve sequence
5 0 5 0 1 0 0 2 0 0
1 0 0 5 0 F2 1 0 0
I LF2 I RF2
IF2
Observation Table: -
If = 3I 1F = 8 8 . 8 0m A
Page | 8
4. Double Line to Ground (LLG) Fault
Vb = V c = ( I b + I c ) Z f , I a = I 1a + I a2 + I a0 = 0
Z 2 ( Z 0 + 3Z f ) Ea − I a Z 1 1
E −I Z 1 1
V a1 = V a2 , I 1a = E a {Z1 + } , I a2 = − 2
, I a0 = − a a
2 0
Z + Z + 3Z f Z Z 0 + 3Z f
I f = I b + I c = 3I a0
+ve sequence
1 0 0 1 0 0 2 0 0 5 0 0
1 0 0 5 0 1 0 0
F1
I L F1 I R F1
I F1
1 0V
-ve sequence
5 0 5 0 1 0 0 2 0 0
1 0 0 5 0 F2 1 0 0
I LF2 I RF2
IF2
zero sequence 5 0 0
4 0 4 0 1 0 0
5 0
1 0 0 1 0 0 F0 1 0 0
I LF0 I RF0
I F0
Page | 9
Observation Table: -
I f = 3I F0 = 6 5 . 3 4m A
Page | 10
DEPARTMENT OF ELECTRICAL ENGINEERING
Experiment No.: 02
SYMMETRIC & ASYMMETRIC FAULTS IN TRANSMISSION LINE
Page | 11
Title: Study of the symmetric & asymmetric faults in transmission line.
Objective: To study the symmetrical and asymmetrical faults on the transmission line ‘T
‘model and understand the concept of symmetrical and asymmetrical faults:
Apparatus used:
6) Current transformer
7) Variac/Dimmer
The most extreme but also common, series fault in the open circuit, this occur for
example, when a circuit breaker or isolator is opened or when a line is broken (but does
not touch the ground).
4) Three phase short circuit (L-L-L) fault: It is symmetrical fault that affects the three
phases of the power system. This is the most severe short circuit fault.
5) Three phase to ground (L-L-L-G) fault: It is symmetrical fault, all three phases are
grounded.
L-G, L-L & L-L-G are the unsymmetrical faults while L-L-L, L-L-L-G are symmetrical
faults. In case of symmetrical faults, the system remains balanced even after the faults.
For unsymmetrical faults the voltages and currents becomes unbalanced after the fault.
Procedure:
To create L-G, L-L, L-L-G, L-L-L & L-L-L-G faults on medium length transmission line
T model.
VS VR
ISR 10ohm 0.15H 0.15H
R 10ohm IRR
R
0.15H 0.15H
ISY 10ohm 10ohm IRY
Y EMT34A EMT34B Y
0.15H 0.15H
B ISB 10ohm 10ohm IRB B
1¢Aux supply
Dimmer EMT4A
415V AC EMT1 3 phase EMT34A ON/OFF
3¢ supply breaker
1¢Aux supply
R VR
Y EMT38 Tx line VS
B EMT34B panel (T model)
N
1) Make the wiring connection as per wiring schedule for any fault say R to G (L-G).
Keep the dimmer at minimum position & switch on EMT4A at FWD position.
2) Here EMT34A will read sending end voltage, current, power factor etc. and EMT34B
will read receiving end voltage, current, power factor etc.
3) Here note that we have shorted R phase of transmission line to neutral at EMT34B.
4) Make on three phase supply and now increase dimmer slowly to 230volt AC observing
voltage on EMT34A & monitoring current on EMT34B.
5) Now take the readings of sending and receiving end voltage & current as per table
given below.
Page | 14
Observation table for faults on T model:
Sr. Type of fault Sending end (On EMT34A) Receiving end (On EMT34B)
No.
𝑉𝑆𝑅 𝑉𝑆𝑌 𝑉𝑆𝐵 𝐼𝑆𝑅 𝐼𝑆𝑌 𝐼𝑆𝐵 𝑉𝑅𝑅 𝑉𝑅𝑌 𝑉𝑅𝐵 𝐼𝑅𝑅 𝐼𝑅𝑌 𝐼𝑅𝐵
1 L-G
2 L-L
3 L-L-G
4 L-L-L
5 L-L-L-G
Conclusion:
IRR
System R
RECEIVING Y
IRY
END
IRB B IF
IRR
System R
RECEIVING Y
IRY
END
IRB B
IF
Page | 17
DEPARTMENT OF ELECTRICAL ENGINEERING
Experiment No.: 03
STUDY OF POWER TRANSFER THROUGH A TRANSMISSION SYSTEM
Page | 18
TITLE: Study of power transfer through a transmission system.
List of Items:
OBJECT:
To plot the power angle diagram of a transmission system under steady state condition and to
study the effect of resistance of the line on the power transfer characteristics.
Page | 19
Fig.1 Connection diagram for power transfer experimental set-up
PROCEDURE:
The front view of the power transfer cubicles, and the detail circuit diagram and connection
diagrams are shown in figure 1 and 2 respectively.
1) Connect the 3-phase power cable with neutral at the desired terminals provided in the power
supply Transformer [i.e. 400-415/ 110-120 V (10A)] cubicle.
Page | 20
Fig.2 Power Transfer through Transmission System
2) Now connect the 110 or 120 V secondary to the 3-phase Variac and the main Power Transfer Kit
Cubicle’s left hand/ Sending End (SE) side through the cable entry grommet
[110 V (line-to-line) single phase only].
3) Then connect the output of the Variac to the Phase Shifter input while connecting its output to the
Isolation transformer [i.e. 110V/110V, 2A transformer].
4) Connect the output of the Isolation Transformer (single phase, the same phases as connected to
the sending end only.) to the main Power Transfer Kit cubicle’s right hand/Receiving End (RE)
side through the cable entry grommet [110V (line-to-line) single phase on the RE side.]
5) Lastly connect the single phase Variac plug to the power plug socket present on the left hand side
of the Main Power transfer cubicle while connecting the Variac outputs to the SE of the Main
Power transfer cubicle.
6) Connect the Voltmeter, Ammeter, Wattmeter and the Phase-angle meters as shown in the diagram
with the terminals on Main Power transfer cubicle.
Page | 21
7) Switch on the 3-phase, ON/OFF switch (on the Power Supply Transformer) to the ‘ON’ position
and observe that the three indicator lamps glow.
8) Set SE voltage (ES) and RE voltage (ER) at a constant value of about 100V by the corresponding
Variac. The AC voltages will show the actual value of ES and ER by throwing the single pole two
way switch in either left-ward or right-ward directions.
9) Set the phase angle to zero degree by adjusting the Variac used for adjusting the phase angle. The
6-pole 6-way course phase shift adjust switch should be in POS-1.
10) Under that condition ammeter reading, wattmeter reading and phase angle meter reading
should be zero.
RUN 1
Take ammeter and wattmeter readings at ends for ES leading with respect to ER from 0° to 180°
in steps of 20° interval. This can be done by adjusting the phase shifter.
OBSERVATION TABLE
Sl. No. Angle (°) ES(V) ER(V) IS(A) WS(W) WR(W) QS(VAR) QR(VAR)
To be To be
calculated calculated
THEORY
To measure the active power transfer, we are keeping the sending and receiving end voltage
constant while varying the phase angle to change the power output.
Known Parameters
1. Angle ‘δ’ in degrees
2. ES – Sending end voltage
3. ER – Receiving end voltage
4. I – Current magnitude in small transmission network in amps
5. WS – Sending end power in watts
6. WR – Receiving end power in watts
Unknown Parameters
1. QS – Sending end VAr
2. QR – Receiving end VAr
3. WL – Line loss in Watts
4. Angle γ – of current I
5. ZS S = rs + jx s – the value of the reactor
Page | 22
CALCULATION
Line loss = WS – WR = I2rs (1)
From equation (1),
W − WR
rs =
I2
(Volt Amp)2 = (Active Power)2 + ( Reactive Power)2 (2)
(ESI)2 = WS2 + QS2 (3)
Hence |QS| is known for every observation.
Also,
(ERI)2 = WR2 + QR2 (4)
Hence |QR| is known for every observation.
Now,
W − jQ
I = S * S
ES
WS − jQ S
I = (Taking ES as a reference Phasor) (5)
ES
From equation (5) I can be determined for every set of observation.
Again,
E S 0 − E R −
= Z S S (6)
I
From equation (6) ZSS will be known for every set of observation.
Again,
ZSS = rs+jxs (7)
From equation (7) ZSS and rs are known so xs will be known for every set of
observation.
Page | 23
DEPARTMENT OF ELECTRICAL ENGINEERING
Experiment No.: 04
Study of power transfer through a transmission system
Page | 24
TITLE: Study of power transfer through a transmission system.
List of Items:
Apparatus Range Maker
1. Ammeter 0-2 A
2. Voltmeter 0-150/300/600 V
3. Digital Phase-angle meter (0-360°)
0-150/230 V,
I (0-10) A
4. 3-phase, 6-pole, 6 position rotary
switch
5. Low Power Factor Wattmeter 0-150/300 V,
1A /2 A
6. Three pole ON/OFF switch
7. Single Phase Variac 0-250 V, 5 A
8. Isolation Transformer (3-phase) 110/110 V, 2 A
9. Power Supply Transformer 400-415 V/ 110-120 V
(3- phase) (10 A),
Star/ Delta
10. Single pole two way switch 230 V, 5 A
11. Indicating Lamps 0-230 V (AC)
12. 0-2 A Fuses
13. Induction Motor type Phase
Sequence Indicator
14. Single Pole two way Switch 230 V, 5 A
15. An Inductor (Linear air gap type) 250/300/500 mh, 2 A
(It represents a short transmission
system)
16. Sheet metal cubicle housing
different equipment mentioned
above
Page | 25
Objective:
To plot the power angle diagram of a transmission system under steady state
condition and to study the effect of resistance of the line on the power transfer
characteristics.
1) Connect the 3-phase power cable with neutral at the desired terminals provided in
the power supply Transformer [i.e. 400-415/ 110-120 V (10A)] cubicle.
Page | 26
2)
3) Fig.2 Power Transfer through Transmission System
4) Now connect the 110 or 120 V secondary to the 3-phase Variac and the main Power
Transfer Kit Cubicle’s left hand/ Sending End (SE) side through the cable entry
grommet
5) [110 V (line-to-line) single phase only].
6) Then connect the output of the Variac to the Phase Shifter input while connecting
its output to the Isolation transformer [i.e. 110V/110V, 2A transformer].
7) Connect the output of the Isolation Transformer (single phase, the same phases as
connected to the sending end only.) to the main Power Transfer Kit cubicle’s right
hand/Receiving End (RE) side through the cable entry grommet [110V (line-to-
line) single phase on the RE side.]
Page | 27
8) Lastly connect the single phase Variac plug to the power plug socket present on
the left hand side of the Main Power transfer cubicle while connecting the Variac
outputs to the SE of the Main Power transfer cubicle.
9) Connect the Voltmeter, Ammeter, Wattmeter and the Phase-angle meters as shown
in the diagram with the terminals on Main Power transfer cubicle.
10) Switch on the 3-phase, ON/OFF switch (on the Power Supply Transformer)
to the ‘ON’ position and observe that the three indicator lamps glow.
11) Set SE voltage (ES) and RE voltage (ER) at a constant value of about 100V
by the corresponding Variac. The AC voltages will show the actual value of ES and
ER by throwing the single pole two way switch in either left-ward or right-ward
directions.
12) Set the phase angle to zero degree by adjusting the Variac used for adjusting
the phase angle. The 6-pole 6-way course phase shift adjust switch should be in
POS-1.
13) Under that condition ammeter reading, wattmeter reading and phase angle
meter reading should be zero.
RUN 2
The value of ES from 30V to 100V in steps of 10V keeping E R=50V and phase
angle at 20° fixed and take ammeter and wattmeter readings.
OBSERVATION TABLE
THEORY
To measure the reactive power transfer, we are keeping receiving end voltage and
phase angle constant while varying the sending end voltage to change the power output.
Known Parameters
7. Angle ‘δ’ in degrees
8. ES – Sending end voltage
Page | 28
9. ER – Receiving end voltage
10.I – Current magnitude in small transmission network in amps
11.WS – Sending end power in watts
12.WR – Receiving end power in watts
Unknown Parameters
6. QS – Sending end VAR
7. QR – Receiving end VAR
8. WL – Line loss in Watts
9. Angle γ – of current I
10. ZSS = rs + jx s – the value of the reactor
CALCULATION
Line loss = WS – WR = I2rs (1)
From equation (1),
W − WR
rs =
I2
(Volt Amp)2 = (Active Power)2 + (Reactive Power)2 (2)
(ESI)2 = WS2 + QS2 (3)
Hence |QS| is known for every observation.
Also,
(ERI)2 = WR2 + QR2 (4)
Hence |QR| is known for every observation.
Now,
WS − jQ S
I = *
ES
WS − jQ S
I = (Taking ES as a reference Phasor) (5)
ES
From equation (5) I can be determined for every set of observation.
Again,
E S 0 − E R −
= Z S S (6)
I
From equation (6) ZSS will be known for every set of observation.
Again,
ZSS = rs+jxs (7)
Page | 29
From equation (7) ZSS and rs are known so xs will be known for every set of
observation.
Page | 30
DEPARTMENT OF ELECTRICAL ENGINEERING
Experiment No.: 05
STUDY OF IDMT OVER CURRENT RELAY
Page | 31
TITLE: Study of IDMT over current relay.
APPARATUS USED:
THEORY:
It finds its application from the fact that in the event of fault the current increases to a value several
times greater than maximum load current. A relay that operates or picks up when its current exceeds
a predetermined value (setting value) is called Over-current Relay. Over-current relay protects
electrical power systems against excessive currents caused due to faults. Over-current relays can be
used to protect practically any power system elements, i.e. transmission lines, transformers,
generators, or motors. For feeder protection, there would be more than one over-current relay to
protect different sections of the feeder. These over-current relays need to coordinate with each other
such that the relay nearest to the fault operates first.
The IDMT relay is widely used by the utilities in the field. Initially, the characteristics of the relay
follows inverse law, and thereafter, when the current becomes very high, it follows definite minimum
operating time pattern. This is because of the constant operating torque due to the saturation of flux
at a high value of current in the electromechanical relay. The mathematical relation between the
current and operating time of IDMT characteristics can be written as,
0.14 (𝑇𝑀𝑆)
𝑡𝑜𝑝 =
(𝑃𝑆𝑀)0.02 − 1
Where PSM is the plug-setting multiplier and TMS is the time multiplier setting of the relay.
Page | 32
The various important terms used in connection with over-current relays are as follows,
(i) Pick-up current. It is the minimum current in the relay coil at which the relay starts to
operate. So long as the current in the relay is less than the pick-up value, the relay does not
operate and the breaker controlled by it remains in the closed position. However, when the
relay coil current is equal to or greater than the pickup value, the relay operates to energize
the trip coil which opens the circuit breaker.
(ii) Current setting. It is often desirable to adjust the pick-up current to any required value. This
is known as current setting and is usually achieved by the use of tappings on the relay
operating coil. The taps are brought out to a plug bridge. The plug bridge permits to alter the
number of turns on the relay coil. This changes the torque on the disc and hence the time of
operation of the relay. The values assigned to each tap are expressed in terms of percentage
full-load rating of C.T. with which the relay is associated and represents the value above
which the disc commences to rotate and finally closes the trip circuit.
(iii) Plug-setting multiplier (PSM). It is the ratio of fault current in relay coil to the pick-up
current i.e.
PROCEDURE:
Page | 33
1. According to the above figure make all the connections of the relay study kit.
2. Set the variac to 230 V.
3. Set PSM=1.
4. Set a particular TSM (=0.5) in the IDMT over current relay.
5. Switch on the green push button.
6. Increase the load.
7. Once the relay start operating note down the fault currents and relay tripping times.
8. Set other TSM (=0.9) in the IDMT over current relay.
9. Repeat step 6-7.
10. Plot the fault current (A) vs. operating time (s) curves for TSM=0.5 and TSM=0.9.
COMMENTS/ DISCUSSIONS:
Write your comments on the results obtained and discuss the discrepancies, if any.
PRECAUTIONS:
Page | 34
DATA SHEET
Experimental Data:-
____________________________
Page | 35
DEPARTMENT OF ELECTRICAL ENGINEERING
Experiment No: 06
STUDY OF DIRECTIONAL OVER CURRENT RELAY
Page | 36
TITLE: Study of Directional Over Current Relay
APPARATUS USED:
THEORY:
In plain radial feeder, the non-directional relays are used as they operate when the CT secondary
current exceeds the threshold value of pickup setting in relays. Here, no directional features are used
to avoid cost issues regarding both line current and bus voltage data extraction in directional relays.
But to obtain fault zone discrimination in case of the protection of parallel feeders and ring main
systems, the directional features are necessary. By introducing the directional features in relays,
interrupted supply can be made possible at all load points connected in the parallel/ring system.
A B C D
1 3 5
Gen R1 F R3 R5
In the plain radial feeder shown in Fig. 1, if the breaker 1 trips because of any abnormalities in the
section between bus A and bus B, it will interrupt the power supply at the buses B, C and D. Thus,
because of the tripping of the first breaker, the load connected to the other buses will not receive any
power supply. In case of the same radial feeder is fed from both the ends with the necessary
modification in the protection scheme using the directional feature, at relay point R2, R3, R4 and R5
as shown in Fig. 2.
A B C D
1 2 3 4 5 6
Gen-1 R1 R2 R3 R4 R5 R6 Gen-2
F
Page | 37
In the event of any abnormalities (e.g. faults) in the section between bus A and bus B, the breaker 1
and 2 will isolate the faulty section, without interrupting the supply to the load connected at the buses
A, B, C and D. Hence, to discriminate the faulty section, the relay R2 should be direction sensitive
so that it operate only in the direction indicated by the arrows as shown in Fig. 2. So the directional
relays should operate when the current flows away from the bus where the relay is located and restrain
if the current flows towards the bus.
Another power system network containing parallel feeders are shown in Fig. 3. In case a fault
occurs on line 1 at point F, the fault is fed from both the buses (A and B) because line 2 is in healthy
condition. If the directional feature is provided to the relay R3 (and R4), only relays R1 and R3 trip
the respective breakers of line 1 for a fault at F. The relay R2 is graded with the relay R3 in such way
the R2 provides backup to R3, if the relay R3 fails to clear the fault on line 1. Similarly, R1 is to be
graded with the relay R4.
A B
Line-1
1 3
Load
R1 F R3
Load
Gen Line-2
2 4
R2 R4
CONNECTION DIAGRAM:
Page | 38
PROCEDURE:
1) According to the above figure make all the connections of the relay study kit.
2) Adjust the plug setting.
3) Before power switch on keep the variac in zero position.
4) Now make on the MCBs, AC switch.
5) Switch on green push button for contactor.
6) Rotate the variac and keep the set current value between 2 to 4 times of the plug setting
value.
7) If it does not trips, no problem.
8) Now push the red push button, rotates the variac to zero.
9) Change the direction of current.
10) Follow step 5-6.
11) If trips push the red push button, keep the variac to previous position and again switch
on green push button.
12) Note down the trip time.
13) Change the polarity.
14) Follow step 10-12.
15) Change the phase angle.
16) Follow step 10-12.
COMMENTS/ DISCUSSIONS:
Write your comments on the results obtained and discuss the discrepancies, if any.
PRECAUTIONS:
Page | 39
DATA SHEET
Experimental Data:-
Sl. No. Plug setting Set current (A) Phase angle (0) Trip time (s)
Sl. No. Plug setting Set current (A) Phase angle (0) Trip time (s)
Sl. No. Plug setting Set current (A) Phase angle (0) Trip time (s)
_________________________
Experiment No: 07
STUDY AND APPLICATION OF NUMERICAL TYPE OVER
CURRENT RELAY FOR DISTRIBUTION LINE PROTECTION
Page | 41
TITLE: Study and application of numerical type over current relay for distribution
line protection.
OBJECTIVE: To study the characteristics of numerical type over current relay and its application for
protection of distribution lines experimentally.
APPARATUS USED:
THEORY:
An over current relay has a current coil when normal current flows through it the magnetic field
generated is not sufficient to move the restraining coil as restraining torque is greater than operating
torque
In case of abnormal conditions fault current i.e. I > Ith, generated magnetic field effect produce
deflecting torque which is greater than restraining coil torque hence change in constant position in
relay.
Numerical over current relay is a microprocessor-based relay which follows certain inbuilt
algorithm for its operating time by changing TSM as well as operating current by adjusting PSM.
80 ∗ 𝑇𝑀𝑆
𝑡𝑜𝑝 =
𝐹𝑎𝑢𝑙𝑡 𝑐𝑢𝑟𝑟𝑒𝑛𝑡 2
[( ) − 1]
𝑃𝑖𝑐𝑘 𝑢𝑝 𝐶𝑢𝑟𝑟𝑒𝑛𝑡
Page | 42
CONNECTION DIAGRAM:
Start
Compute input
Compute Ipms
Compute Iratio
I0 > Ipms
Set F
Start timer
Yes No
If type = std
inverse
Trip
Compute time Compute time
Trip Trip
PROCEDURE:
Page | 43
1) According to the above figure make all the connections of the relay study kit.
2) Adjust the plug setting.
3) Before power switch on keep the variac in zero position.
4) Now make on the MCBs, AC switch.
5) Switch on green push button for contactor.
6) Rotate the variac and keep the set current value between 2 to 4 times of the plug setting value.
7) Note down the trip time.
8) Follow step 6-7.
9) Draw the graph for operating characteristics of over current
COMMENTS/ DISCUSSIONS:
Write your comments on the results obtained and discuss the discrepancies, if any.
PRECAUTIONS:
Page | 44
DATA SHEET
TITLE: Study and application of numerical type over current relay for distribution line protection.
Experimental Data:-
Sl. No. Fault Voltage (V) Operating Time (ms) Calculated Time (ms)
____________________________
Experiment No: 08
STUDY OF NUMERICAL TYPE DIFFERENTIAL RELAY
Page | 46
TITLE: Study of numerical type differential relay
APPARATUS USED:
THEORY:
The schematic diagram of the percentage (biased) differential relay is shown in Figure 1. This relay
has two coils. One coil is known as restraining coil or bias coil which restrains the operation of the
relay. Another coil is the operating coil which produces the operating torque for the relay. When the
operating torque exceeds the restraining torque, the relay operates. The operating coil is connected
to the mid-point of the restraining coil as show in the Figure 1. Nr and N0 are the total number of turns
of the restraining coil and the operating coil, respectively. Since the restraining coil is tapped at the
centre, it forms two sections with equal number of turns, Nr/2. The restraining coil is connected in
the circulating current path in such a way that current I1s flows through one section of Nr/2 turns and
I2s flows through the another section of Nr/2, so that the complete restraining coil of Nr turns receives
the through fault current of (I1s+I2s)/2. The operating coil, having N0 number of turns, is connected
in the difference path, so that it receives the differential current, (I1s - I2s).
The operating condition of the percentage differential relay can be derived as follows:
The relay operates if the operating torque produced by the operating coil is more that the restraining
torque produced by the restraining coil. As the torque is proportional to the ampere-turns (AT), the
relay will operate when the ampere-turns of the operating coil (ATO), will be greater that ampere-
turns of the restraining coil, (ATR).
Page | 47
Protected zone
CT1 CB CB CT2 I2
Protected
equipment
I1S I2S
Restraining coil
I1S
I1S I2S
(I1S – I2S)
I1S I2S
Percentage
differential relay
𝑁𝑟
Ampere-turns of the right-hand section of the restraining coil = 𝐼2𝑆
2
𝑁𝑟
Total ampere-turns of the restraining coil, ATR = (𝐼1𝑆 + 𝐼2𝑆 )
2
(𝐼1𝑆 +𝐼2𝑆 )
= 𝑁𝑟 2
Thus it can be assumed that the entire 𝑁𝑟 turns of the restraining coil carries a current (I1s+I2s)/2. The
current (I1s+I2s)/2 which is the average of the secondary currents of the CTs (CT1 and CT2) is known
as the ‘through current’ or restraining current, IR, Hence
IR = (I1s+I2s)/2
Page | 48
𝑁 (𝐼1𝑆 +𝐼2𝑆 )
Or (I1s - I2s) > 𝑁𝑟
0 2
Or 𝐼𝐷 > 𝐾𝐼𝑅
Where, 𝐼𝐷 = (I1s - I2s) is the differential current through the operating coil. Hence it is also called
the differential operating current.
Or 𝐼𝐷 > 𝐾𝐼𝑅
Thus, at the threshold of operation of the relay, the ratio of the differential operating current (𝐼𝐷 ) to
the restraining current (𝐼𝑅 ) is a fixed percentage; and for operation of the relay the differential
operating current must be greater than this fixed percentage of the restraining (through fault) current.
Hence, this relay is called ‘percentage differential relay’. The percentage differential relay is also
known as ‘bias differential relay’. The operating characteristics of this relay is shown in Figure 2.
Id = (I1S – I2S)
Trip
Ipick-up = KS Block
( I 1S + I 2 S )
Ir =
2
Figure 2. Operating characteristic of percentage differential relay
Page | 49
EXPERIMENTAL SETUP:
PROCEDURE:
𝐼𝐷 = 𝐼1 – 𝐼2 , 𝐼𝑅 = ( 𝐼1 + 𝐼2 )/2
Page | 50
COMMENTS/ DISCUSSIONS:
Write your comments on the results obtained and discuss the discrepancies, if any.
PRECAUTIONS:
Page | 51
DATA SHEET
Experimental Data:-
Test Points
Sl. I1 I2 Trip Status Trip Status
No. Idiff Ibias (A) (A) (Practical) (Theoretical)
(A) (A)
____________________________
Page | 52