Product datasheet
Specifications
soft starter for asynchronous motor,
Altistart 22, control 230V, 230 to
440V, 39 to 55kW
ATS22C11Q
Main
Range Of Product Altistart 22
Product Or Component Type Soft starter
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Product Destination Asynchronous motors
Product Specific Application Pumps and fans
Component Name ATS22
Network Number Of Phases 3 phases
[Us] Rated Supply Voltage 230...440 V - 15...10 %
Motor Power Kw 39 kW 230 V
55 kW 400 V
55 kW 440 V
Factory Setting Current 100 A
Power Dissipation In W 73 W for standard applications
Utilisation Category AC-53A
Type Of Start Start with torque control (current limited to 3.5 In)
Icl Starter Rating 110 A for connection in the motor supply line for standard applications
Ip Degree Of Protection IP20
Complementary
Assembly Style With heat sink
Function Available Internal bypass
Supply Voltage Limits 195…484 V
Supply Frequency 50...60 Hz - 10...10 %
Network Frequency 45...66 Hz
Device Connection In the motor supply line
To the motor delta terminals
[Uc] Control Circuit Voltage 230 V - 15...10 % 50/60 Hz
Control Circuit Consumption 20 W
Discrete Output Number 2
Discrete Output Type Relay outputs R1 230 V running, alarm, trip, stopped, not stopped, starting, ready C/
O
Relay outputs R2 230 V running, alarm, trip, stopped, not stopped, starting, ready C/
O
Minimum Switching Current 100 mA at 12 V DC (relay outputs)
Dec 13, 2023 1
AD
Maximum Switching Current 5 A 250 V AC resistive 1 relay outputs
5 A 30 V DC resistive 1 relay outputs
2 A 250 V AC inductive 0.4 20 ms relay outputs
2 A 30 V DC inductive 7 ms relay outputs
Discrete Input Number 3
Discrete Input Type (LI1, LI2, LI3) logic, 5 mA 4.3 kOhm
Discrete Input Voltage 24 V <= 30 V
Discrete Input Logic Positive logic LI1, LI2, LI3 at State 0: < 5 V and <= 2 mA at State 1: > 11 V, >= 5 mA
Output Current 0.4...1 Icl adjustable
Ptc Probe Input 750 Ohm
Communication Port Protocol Modbus
Connector Type 1 RJ45
Communication Data Link Serial
Physical Interface RS485 multidrop
Transmission Rate 4800, 9600 or 19200 bps
Installed Device 31
Protection Type Phase failure: line
Thermal protection: motor
Thermal protection: starter
Marking CE
Type Of Cooling Forced convection
Operating Position Vertical +/- 10 degree
Height 356 mm
Width 150 mm
Depth 229.5 mm
Net Weight 18 kg
Motor Power Range Ac-3 30…50 kW at 200…240 V 3 phases
55…100 kW at 380…440 V 3 phases
Motor Starter Type Soft starter
Environment
Electromagnetic Compatibility Conducted and radiated emissions level A conforming to IEC 60947-4-2
Damped oscillating waves level 3 conforming to IEC 61000-4-12
Electrostatic discharge level 3 conforming to IEC 61000-4-2
Immunity to electrical transients level 4 conforming to IEC 61000-4-4
Immunity to radiated radio-electrical interference level 3 conforming to IEC 61000-4-3
Voltage/current impulse level 3 conforming to IEC 61000-4-5
Standards EN/IEC 60947-4-2
Product Certifications UL
CSA
GOST
C-Tick
CCC
Vibration Resistance 1 gn (f= 13…200 Hz) conforming to EN/IEC 60068-2-6
1.5 mm (f= 2…13 Hz) conforming to EN/IEC 60068-2-6
Shock Resistance 15 gn for 11 ms conforming to EN/IEC 60068-2-27
Noise Level 56 dB
Pollution Degree Level 2 conforming to IEC 60664-1
Relative Humidity 0…95 % without condensation or dripping water conforming to EN/IEC 60068-2-3
2 Dec 13, 2023
AD
Ambient Air Temperature For -10…40 °C (without derating)
Operation 40…60 °C (with current derating 2.2 % per °C)
Ambient Air Temperature For -25…70 °C
Storage
Operating Altitude <= 1000 m without derating
> 1000...< 2000 m with current derating of 2.2 % per additional 100 m
Packing Units
Unit Type Of Package 1 PCE
Number Of Units In Package 1 1
Package 1 Height 25.000 cm
Package 1 Width 33.000 cm
Package 1 Length 41.000 cm
Package 1 Weight 12.744 kg
Unit Type Of Package 2 P06
Number Of Units In Package 2 4
Package 2 Height 75.000 cm
Package 2 Width 60.000 cm
Package 2 Length 80.000 cm
Package 2 Weight 64.472 kg
Contractual warranty
Warranty 18 months
Dec 13, 2023 3
AD
Sustainability
Green PremiumTM label is Schneider Electric’s commitment to delivering products with best-in-
class environmental performance. Green Premium promises compliance with the latest regulations,
transparency on environmental impacts, as well as circular and low-CO2 products.
Guide to assessing product sustainability is a white paper that clarifies global eco-label
standards and how to interpret environmental declarations.
Well-being performance
Mercury Free
Rohs Exemption Information Yes
Reach Regulation REACh Declaration
Eu Rohs Directive Pro-active compliance (Product out of EU RoHS legal scope)
EU RoHS Declaration
China Rohs Regulation China RoHS declaration
Weee The product must be disposed on European Union markets following specific waste
collection and never end up in rubbish bins
4 Dec 13, 2023
AD
Product datasheet ATS22C11Q
Dimensions Drawings
Frame Size C
Dimensions
Dec 13, 2023 5
AD
Product datasheet ATS22C11Q
Mounting and Clearance
Precautions
Standards
The Altistart 22 soft starter is compliant with pollution Degree 2 as defined in NEMA ICS1-1 or IEC 60664-1.
For environment pollution degree 3, install the Altistart 22 soft starter inside a cabinet type 12 or IP54.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
ATS22 soft starters are open devices and must be mounted in a suitable enclosure.
Failure to follow these instructions will result in death or serious injury.
Air Circulation
Leave sufficient free space to help the air required for cooling purposes to circulate from the bottom to the top of the
unit.
Overheating
To avoid the soft starter to overheat, respect the following recommendations:
• Mount the Altistart 22 Soft Starter within ± 10° of vertical.
Do not locate the Altistart 22 Soft Starter near heat radiating elements.
• Electrical current through the Altistart 22 Soft Starter will result in heat losses that must be dissipated into the
• ambient air immediately surrounding the soft starter. To help prevent a thermal fault, provide sufficient
enclosure cooling and/or ventilation to limit the ambient temperature around the soft starter.
• If several soft starters are installed in a control panel, arrange them in a row. Do not stack soft starters. Heat
generated from the bottom soft starter can adversely affect the ambient temperature around the top soft
starter.
6 Dec 13, 2023
AD
Product datasheet ATS22C11Q
Mounting
Connection Between the Fan and the Altistart 22 Soft Starter
1 Altistart 22 Soft Starter
2 Fan
Dec 13, 2023 7
AD
Product datasheet ATS22C11Q
Wall mounted or Floor-standing Enclosure with IP 23 Degree of protection
Introduction
To help proper air circulation in the soft starter, grilles and forced ventilation can be installed.
Ventilation Grilles
Forced Ventilation Unit
8 Dec 13, 2023
AD
Product datasheet ATS22C11Q
Connections and Schema
Power Terminal
Bar Style
b 20 mm (0.79 in)
Bar a 5 mm (0.2 in)
Bolt M8 (0.31 in)
Size 95 mm²
Power supply and output to motor
Gauge 250 MCM
Cable and protective cover Protective cover LA9F702
18 N.m
Tightening torque
157.5 lb.in
Power connections, minimum required wiring section
IEC cable UL cable
mm² (Cu 70°C/158°F) (1) AWG (Cu 75°C/167°F) (1)
35 1/0
Dec 13, 2023 9
AD
Product datasheet ATS22C11Q
230 Vac control, logic Inputs (LI) 24 Vdc, 3-wire control
With Line Contactor, Freewheel or Controlled Stop
10 Dec 13, 2023
AD
Product datasheet ATS22C11Q
230 Vac control, logic Inputs (LI) 24 Vdc, 2-wire control,freewheel stop
Dec 13, 2023 11
AD
Product datasheet ATS22C11Q
Connection in the motor delta winding in series with each winding
Wiring
ATS22 soft starters connected to motors with the delta connections can be inserted in series in the motor windings.
The following wiring requieres particular attention. It is documented in the Altistart 22 Soft start - soft stop unit user
manual. Please contact Schneider Electric commercial organisation for further informations.
Example
A 400 V - 110 kW motor with a line current of 195 A (nominal current for the delta connection). The current in each
winding is equal to 195/1.5 or 130 A. The rating is determined by selecting the soft starter with a permanent nominal
current (ICL) just above this current.
12 Dec 13, 2023
AD
Product datasheet ATS22C11Q
Performance Curves
Motor Thermal Protection - Cold Curves
Curves
A Class 10
B Class 20
C Class 30
Trip time for a Standard Application (Class 10)
3.5 ln
32 s
Trip time for a Severe Application (Class 20)
Dec 13, 2023 13
AD
Product datasheet ATS22C11Q
3.5 ln
63 s
Trip time for a Severe Application (Class 30)
3.5 ln
95 s
14 Dec 13, 2023
AD
Product datasheet ATS22C11Q
Motor Thermal Protection - Warm Curves
Curves
A Class 10
B Class 20
C Class 30
Trip time for a Standard Application (Class 10)
3.5 ln
16 s
Trip time for a Severe Application (Class 20)
3.5 ln
Dec 13, 2023 15
AD
Product datasheet ATS22C11Q
32 s
Trip time for a Severe Application (Class 30)
3.5 ln
48 s
16 Dec 13, 2023
AD