Distance Relay
Distance Relay
6
6.1 INTRODUCTION
Distance protection is a widely used protective scheme for the protection of high
and extra high voltage (EHV) transmission and sub-transmission lines. This scheme
employs a number of distance relays which measure the impedance or some com-
ponents of the line impedance at the relay location. The measured quantity is pro-
portional to the line-length between the location of the relay and the point where the
fault has occurred. As the measured quantity is proportional to the distance along
the line, the measuring relay is called a distance relay. Overcurrent relays have been
found unsuitable for the protection of transmission lines because of their inherent
drawbacks of variable reach and variable operating time due to changes in source
impedance and fault type. Distance relays have been developed to overcome the
problems associated with the use of overcurrent relays for the protection of transmis-
sion lines.
Modern distance relays provide high speed fault clearance. They are used where
overcurrent relays become slow, and there is difficulty in grading time-overcurrent
relays for complicated networks. They are used for the protection of transmission
and subtransmission lines at 220 kV, 132 kV, 66 kV, and 33 kV. Sometimes, they are
also used at 11 kV. For 132 kV and 220 kV systems, the recent trend is to use carrier
current protection. The relaying units used in carrier current protection are distance
relays. They operate under the control of carrier signals. In case of the failure of car-
rier signal, they act as back-up protection.
A distance protection scheme is a non-unit system of protection. A single scheme
provides both primary and back-up protection.
The most important and versatile family of relays is the distance-relay group. It
includes the following types:
(i) Impedance relays
(ii) Reactance relays
(iii) MHO relays
(iv) Angle impedance relays
(v) Quadrilateral relays
(vi) Elliptical and other conic section relays
250 Power System Protection and Switchgear
+ve Torque
X
region Operating
characteristic
Z
I Block
– ve Torque f
region Trip R
F
V
Fig. 6.1 Operating characteristic of an Fig. 6.2 Operating characteristic of an
impedance relay impedance relay on the R-X diagram
A more useful way is to draw a distance relay characteristic on the R-X diagram.
Figure 6.2 shows an impedance relay characteristic on the R-X diagram, where Z =
K represents a circle and Z < K indicates the area within the circle. Thus, it is seen
that the zone within the circle is the operating zone of the relay. Its radius is Z = K,
which is the setting of the relay. K is equal to the impedance of the line which is to be
protected. f is the phase angle between V and I. As the operating characteristic is a
circle, the relay operation is independent of the phase angle f. The operation depends
on the magnitude of Z. If a fault point is on the protected section of the line, it will
lie within the circle. For this condition, the relay will operate and send a tripping
signal to the circuit breaker. The region
outside the circle is the blocking zone. If a
fault point lies in this zone, i.e. it is beyond
Operating time
impedance relays and a directional unit are employed. Their characteristics are shown
in Fig. 6.4. The directional unit is connected in series with the impedance relays as
shown in Fig. 6.5(a). Figure 6.5(b) shows connections if only one measuring unit is
employed. In such a scheme zone II and zone III are set by adjusting ohmic reach of
the relay after appropriate delay.
Z3
e
Zon
+ve Torque III Z2
one t3
IIZ e Z1 t t2
Z on 1
I a
–ve Torque
Directional
relay
+
Directional unit Directional unit Zone 2
ohmic
Seal-in Z2 Seal-in reach
relay Z1 T2 relay Z1 T2
Z3 Zone 3
ohmic
reach
Seal-in T3 Seal-in T3
relay coil relay coil
Flags Timing Flags
Timing
Trip coil unit Trip coil unit
Fig. 6.5 (a) Connections of impedance relays (b) Connections of one measuring unit
The directional unit has a straight line characteristic as shown in the figure. It
allows impedance relays to see only in the forward direction. The torque equation of
the directional unit is given by T = KVI cos (f – a), neglecting spring-effect. Here, f
is the angle between V and I, and a is the angle of maximum torque. For the opera-
tion of the relay, T should be positive and hence,
KVI cos (f – a) > 0
or cos (f – a) > 0 or (f – a) < ± 90°
Distance Protection 253
The directional relay employs two pairs of contacts, one pair is placed in series
with the contacts of the impedance relay. The other pair is connected to energise an
auxiliary relay. The contacts of the auxiliary relay, when deenergised, short circuit
the current coil of the impedance relay. The contacts of the auxiliary relay are opened
when a fault occurs in the forward direction. This type of a control is essential to
avoid a contact race between the impedance relay and the directional relay in inter-
connected or double circuit lines. See details in Ref. 5.
possible to use three measuring units for the 3 zones of protection. In a modern dis-
tance protective system, only one measuring unit is employed for all the three zones
of protection. The ohmic reach is progressively increased by the timing unit to obtain
the distance settings for the II and III zones. Sometimes two units can be employed,
one unit for the I and II zone and a separate unit for the III zone. The distance setting
for the II zone is done by the timing unit.
Operating time
should be set to reach beyond
the end of the longest adjoining B2
line section under the conditions
of maximum underreach which A1 B1
may arise due to arcs, interme- A B C
diate current sources and errors
Distance
in CT, VT and measuring units.
This is achieved with addi- Fig. 6.7 Second zone adjustment with additional
tional time delay, as shown in time for selectivity with relay of a very
Fig. 6.8. Compare Fig. 6.8 with short adjoining line
Fig. 6.6 which is for normal
selectivity of the III zone unit.
The reach of any unit should not A3
be so long as to cause the relay
Operating time
A1 B1
6.2.7 Electromechanical
A B
Impedance Relay
Induction cup type construc-
tion is used to realise an imped- Distance
ance relay characteristic. This Fig. 6.8 Third zone adjustment with additional
construction is compact and time to provide back-up protection for
robust. It produces nonvibrat- adjoining line
ing torque. It is less affected
by dc transients and possesses high speed and sensitivity. It gives a perfect circular
V
characteristic. For such an impedance relay, __ £ K. IZr is to be compared with V if
I
an amplitude comparator is used. But the induction
cup construction is a phase comparator and hence, Zr
(I + V) and (I – V) are used as the actuating quanti-
ties, as shown in Fig. 6.9. With the introduction of (I – V )
V
Zr in the voltage circuit, the current flowing in this
circuit is VZr.
S
( ) V
Therefore, I + __ is the polarising quantity and
Zr
(I + V )
I
(I – V/Zr) is the operating quantity. The polarising
quantity produces one of the fluxes. In case of Fig. 6.9 Induction cup type
phase comparators it provides reference for phase impedence relay
angle measurement.
256 Power System Protection and Switchgear
IX X
Zr
IXr IZr (IZr – V )
(Zr – Z)
V Z
IRr I IR R
(a) (b)
Fig. 6.11 (a) Phasor diagram showing V, I and voltage drops (b) Impedance diagram
Now, a circle with radius Zr is drawn, as shown in Fig. 6.12. Since NM is the
diameter of the circle, NO = Zr and phasor NP = Zr + Z. The angle between (Zr + Z)
(Zr – Z) is q. If the point P lies within the circle, q is less than 90°. If P falls outside
the circle, q is greater than 90°. Thus, to realise an impedance characteristic, the
phase angle between (Zr + Z) and (Zr – Z) is to be compared with ± 90°. If we multi-
ply these impedance phasors by I the resulting phasors are
I(Zr + Z) and I(Zr – Z)
or (IZr + IZ) and (IZr – IZ)
or (IZr + V) and (IZr – V)
Therefore, to realise an impedance relay characteristic using a phase comparator,
the phase angle q between (IZr + V) and (IZr – V) is compared with ± 90°. If q is less than
± 90°, the point lies within the characteristic circle. (IZr + V) is the polarising input and
(IZr – V) is the operating input.
Distance Protection 257
X
Block M
Zr (Zr – Z )
q
Z P
Trip
Z)
+
R
r
(Z
0
achieved by introducing an additional voltage into the voltage supply circuit of the
relay. The torque equation of a modified impedance relay is as follows.
T = K1I2 – K2 (V + IR)2
where R is a resistance.
The modified impedance relay has a greater tolerance for fault resistance as com-
pared to the impedance relay, as shown in Fig. 6.13. Such a characteristic is not as
effective or accurate as the reactance relay characteristic explained in the next sec-
tion. Moreover, they are more affected by power surges.
(a) (b)
pole. The flux in the right-hand side pole is out of phase with that in the upper and
lower poles because of the secondary winding which is closed through a phase shift-
ing circuit and is placed on the right-hand side pole. The interaction of the polarising
flux and the flux in the right-hand side pole produces an operating torque K1I2. The
winding placed on the left-hand side pole produces a flux which interacts with the
polarising flux to produce a restraining torque. There is a phase-angle adjustment
circuit connected in series with the voltage coil. The restraining torque is propor-
tional to VI cos (90 – f). The angle between the actuating quantities which are pro-
portional to V and I can be changed to realise the desired characteristic. In this case,
the angle between the actuating quantities is kept (90 – f). The relay operates when
K1I2 > K2VI sin f, neglecting K3 which is a constant for the spring’s torque. Thus, we
have
V
__ K1
sin f < ___
I K2
or Z sin f < K or X < K
The characteristic of the reactance relay on the R-X diagram is shown in
Fig. 6.14(a). It will operate when the measured value of the reactance is less than
the predetermined value K. It is a non directional relay as it will also operate for the
negative values of X. The negative value of X means that the fault is behind the relay
location, i.e. in the reverse direction. A directional unit, having a circular character-
istic is used in conjunction with reactance relays. The directional unit also acts as
the III unit of the distance scheme. The I and II units are reactance units as shown in
Fig. 6.14(b). The I unit is a high speed unit to protect 80% to 90% of the protected
line. The II unit protects up to 50% of the adjacent line. The III unit is a back-up unit
to protect the whole of the adjacent line. The time-distance characteristic is a stepped
characteristic, as shown in Fig 6.6
Why the directional unit used with reactance relays should have a circular char-
acteristic needs further explanation. Under normal conditions, with a load of high
power factor, the reactance measured by the reactance relay may be less than its
setting. Such points have been shown in Fig. 6.14(b) by P1 lying in the I zone of
protection and P2 in the II zone of protection. To prevent false trippings under such
conditions, the reactance relay should be +
supervised by a fault-detecting unit (start- M Starting unit
ing unit) which limits its area on the R-X Seal-in X2
relay X1 T2
diagram. Hence, its characteristic should
be a circular one. A directional unit with
a straight line characteristic, as used with Seal-in T3
an impedance relay cannot be used in this relay coil
case. With this type of a directional unit, Flags Timing
Trip coil unit
the reactance relay will not trip under con-
ditions of a high power factor load. CB Auxiliary
switch
The starting unit detects faults and also –
serves the function of the III zone unit. Its Fig. 6.16 Connections of reactance relay
connection is shown in Fig. 6.16.
260 Power System Protection and Switchgear
| || |V V
I – ___ > ___
2Xr 2Xr
Multiplying both sides by 2Xr, we
2Xr
+
get,
+
|2IXr – V| > |V| R
Dividing both sides by I, we get
| V
||| V
2Xr – __ > __ or |2Xr – Z| > |Z|
I I +
where Xr is the reactance of the line to Fig. 6.17 Static reactance relay
be protected.
When the above condition is satisfied, the characteristic realised is a reactance
relay characteristic. Proof of this will be given later on while discussing the angle
impedance relay as the reactance relay is a special case of an angle impedance
relay.
M
IXr L N
(IZr – V ) Zr (Zr – Z)
r
IZ
q q
V P
Z
IRr I IR K R
(a) (b)
torque K1VI cos (f – a). The angle a can be adjusted by varying resistance in the
phase shifting circuit placed on the left pole (not shown in the figure). The right-hand
side pole is energised by voltage. The flux produced by the right side pole interacts
with the polarising flux to produce a restraining torque K2V2.
The relay will operate when
1 K2
K1VI cos (f – a) > K2 V2 or __ cos (f – a) > ___
V K1
K2 1
or Y cos (f – a) > ___ or ___________ <K
K1 Y cos (f – a)
Z
_________
or <K or M<K
cos (f – a)
| |
V
I > __ – I
Zr
R
+
| | V
|Zr| > __ – Zr or |Zr| > |Z – Zr|
I
X
q q
P
V Z
Z
R
IRr I IR R
Output
teristic. The inputs to the phase com-
parator are (IZr – V) and V. A phase –V
comparator circuit using an opera-
tional amplifier has been shown in
Fig. 6.27. Its operating principle has
already been explained in the Section
2.3.5(c), Fig. 2.29. V
6.4.4 Polarising Quantity
Fig. 6.26 Recti ier bridge phase comparator
For MHO and reactance relays, three
inputs are used, though the comparator employed is a two-input comparator. These
are (i) operating input (current I), (ii) restraining input (voltage V) and (iii) polarising
input. The polarising input is current in the case of a reactance relay, and voltage in
the case of a MHO relay. The relay uses the first two quantities for impedance (or a
component of the impedance) measurement, which are derived from the current and
voltage associated with the fault. The third quantity, i.e. the polarising quantity is a
reference for determining the phase-sense of the operating current. If a terminal fault
occurs, the voltage at the relay location becomes zero. In case of a reactance relay,
the polarising input is current and hence, the relay operates even though the terminal
voltage is zero. The restraining quantity V is zero. This will not prevent the operation
of the relay. On the other hand, in case of a MHO relay, the polarising input is V. If
it is derived from the faulty phase, it will become zero in case of a terminal fault.
Therefore, the MHO relay will fail to operate for terminal faults. To overcome this
difficulty, the polarising input may be derived from the healthy phases, as discussed
in the next section.
op-amp
IZr – V
Sine to square
Coincidence op-amp Level
wave converter
circuit detector Trip
op-amp Integrator
V
Sine to square
wave converter
In the last two methods, when Vp is derived either fully or partly from the healthy
phases, the relay fails to operate if a three-phase terminal fault occurs. In such a situ-
ation, the fault is cleared by an offset MHO relay which is used as a back-up relay.
An offset MHO relay, which has current bias in the voltage circuit, operates even in
case of three-phase terminal faults, (see Section 6.4.6). In a number of cases, high-
set overcurrent relays have been used to clear three-phase terminal faults at a high
speed.
If Vp is derived from the faulty phase, the relay is said to be a self-polarised relay.
If it is derived from the healthy phases, it is called a cross-polarised relay. Fully
cross-polarised means that Vp is fully derived from the healthy phases.
In the first method in which Vp is derived from the faulty phase, it is possible, by
using memory, to maintain the polarising input for a short time even after the occur-
rence of the fault. Therefore, when a terminal fault occurs, the polarising input is
maintained sufficiently long to cause the operation of the relay. In this method, the
polarising current does not maintain the constant phase relation with respect to the
faulty phase voltage. The phase angle of the faulty phase voltage changes when a
fault occurs but the phase angle of the current of the memory circuit is maintained
at the original value. The change in the phase-shift is negligible. The phase-angle
shift also occurs due to the variation in the supply frequency. The supply frequency
may vary from 47 c/s to 51 c/s but the resonant circuit resonates at a fixed frequency.
To minimise the error, the memory is restricted to about three cycles at the most.
Therefore, the relay must be very fast. The most serious drawback of this method
is that this method is not effective when the line is energised. This drawback can be
removed by the supply using voltage from the busbar instead of the line.
6.4.6 Offset MHO Relay
Figure 6.29 shows an offset MHO characteristic. A rectifier bridge type amplitude
comparator, as shown in Fig. 6.23 can be used to realise the offset MHO characteris-
tic. The actuating quantities to be compared are I and (V/Zr – nI). Only a fraction of
the CT output current is injected into the restraint circuit. Thus n is fraction, i.e. n <
1. The relay operates when
| |
V
|I| > __ – nI or |IZr| > |V – nIZr|
Zr
X
or
|V
|Zr| > __ – nZr
I | or |Zr| > |Z – nZr| Z
In case of a reactance relay, a = 90°. But in the case of an angle impedance relay,
it may have any value which governs the inclination of the characteristic with respect
to the R-axis (see Fig. 6.31).
| || |
V V
I – ___ > ___
2Zr 2Zr
or |2IZr – V| > |V|
or
| V V
2Zr – __ > __
I I||| or |2Zr – Z| > |Z|
Block
V
P
Z
Trip
IRr I IR R
(a) (b)
V
__ V V
Impedance I I – __ I + __
Zr Zr Zr
V V V
Directional I + __ __ –I I __
Zr Zr Zr
V V V
Reactance I – ___ ___ I I – __
2Xr 2Xr Xr
2V
___ V V
MHO I –I I – __ __
Zr Zr Zr
Offset MHO (
V
Zr Z0
V
2I – __ + __ ) V __
__ –
Zr Z0
V V
I – __
Zr
V
__
Zo
–I
V V V
Angle Impedance 2I – __ __ I I – __
Zr Zr Zr