CGTest Report for RTcc Automatic Public Authoy tor o s i n a
Contract No Voltage Regulator Relay Customer : PAHW
Project Name
Systema PAHW/C/1428/2020-2021 MUTLA *1D" 132/11kV S/S
Author | Prepared 30MVA Power Transformer
No. Page/No.of pagess
T&C Dept Resp. Dept. Date Lang. NCC Rev. Doc.kind
-
2
TR Page 1 of
MEW 0
2ol212e2 En
1. Protection Device:
Make MR
Serial No
Model 2341gb6
:TAPCON 230BASIC
VT Ratio : 11.5KVN3 / 110V/N3
2. Settings:
11 KV
Desired Voltage Level (DVL)- 1
2.00%
Bandwidth
25 Sec
Delay Time-1
Off
Delay Time-2
110%
Over Voltage V>
80%
Under Voltage V<
11.5 KV
Primary Transformer Voltage
110
Secondary Transformer Voltage
3. Voltage Regulation Test:
Calculated Pick Up Actual Pick Up
Calculated Pick Up Actual Pick Up Volatge for Lower
Volatge for Raise Volatge for Lower
Volatge for Raise
Bandwidth
Command (V) Command (V)
Command (V) Command (V)_
107.34 1O7 4
2.00%
103.10
o3-1
inside the Bandwidth Zone.
(Lower/Raise) Checked
Relay Non-Operation
4.Timing Test:
MEW Witnessed By MEW Approved By
NCC Tested By
Name
Page 1 of 2
Signature
NCC Test Report for RTCC Automatic ubic Authority for Housina welfere
Voltage Regulator Relay Customer : PAHW
Contract No
System PAHW/C/1428/2020-2021
30 MVA Power
Project Name
Author / Prepared Transformer No. MUTLA "1D" 132/11KV 8/S
T&C Dept Resp. Dept. Date |Lang.| NCC Rev. Doc.kind Page/No.of pages_
MEW TR
Page 2 of2
En
Actual Delay
Set Delay Actual Delay Actual Delay Actual Delay
(Sec)Time-1Set Delay Time-2
Time for Second
Time for Time for Second Time for
(Sec) First Raisee Raise Command First Lower Lower
25.00 Command (Sec) (Sec) Command (Sec)_ Command (Sec)
OFF
ds8S 29-9o 25 26
Actual Delay Actual Delay Actual Delay Actual Delay
Set Delay Time-1Set Delay Time-2 Time for Second
Time1 for Time for Second Time for
(Sec) (Sec) First Raise Raise Command First Lower Lower
Command (Sec) (Sec) Command (Sec)_ Command (Sec)
25.00 5.00
2638 :16 25:93 S4S
5. Limit Values Check:
Calculated Actual Calculated Over Actual
Under Voltage Over Voltage
Under Voltage Under Voltage Voltage Pick up Over Voltage
Setting Setting
Pick up (V Pick up (V) (V)_ Pick up (V
80% of DVL 84.17 84.1 110% of DVL 115.73
lis.8
Under Voltage Blocking Checked.
Over Voltage Continous High Speed Lower Checked.
6. Checklistt
a) Case earth installed--
b) Test block connections checked--
c)Watchdog contact checked--.
d) Auto/Manual mode operation checked.-
e) Below 30V Relay function checked. - - - - - - - - - - - - . - - - - - . - - . = a a =
7.Test Equipments Used:
Equipment Make&Model Serial No Cal.Due
Sl.no
1
Secondary Injection Tester OMICRON CMC 256 Plus 2A bo 8g | 2o-S8P 252
NCC Tested By MEW Witnessed By MEW Approved By
Name
Signature
Page 2 of 2