User Manual
Rennertronic Plus Touch
Before starting the controller, read and follow the manual
25282_EN_18239
carefully!
RENNER GmbH Kompressoren
Emil-Weber Str. 32
D-74363 Güglingen
Tel: +49 (0)7135 931 93 0
Fax: +49 (0)7135 931 93 50
[email protected] www.renner-kompressoren.de
EN
User Manual
Contents
1. Safety 9
2. User Interface 10
2.1. Buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.2. Main View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.2.1. Net pressure tile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.2.2. System pressure tile + BLCO status . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.2.3. Time and date tile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.2.4. State of miscellaneous compressor functions tile . . . . . . . . . . . . . . . . . . . . 13
2.2.5. Compressor information additional fields tile . . . . . . . . . . . . . . . . . . . . . . . 14
2.2.6. Compressor state tile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
2.2.7. Status bar . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
2.2.8. Sliding menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
2.3. Statistics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
2.3.1. Fault memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
2.3.2. Utilisation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
2.3.3. Error counter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
2.3.4. Charts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
2.3.5. Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
2.4. BLCO (Network operation menu) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
2.5. Main settings menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
2.5.1. Pressure settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
2.5.2. Operation parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
2.5.2.1. System pressure related . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
2.5.2.2. Control timings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
2.5.2.3. Drain configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
2.5.2.4. Fan configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
2.5.2.5. Dryer configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
2.5.2.6. Frost protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
2.5.3. Schedule . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
2.5.4. Baseload Changeover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
2.5.5. Remote control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
2.5.6. Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
2.5.6.1. Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
2.5.6.2. Time and Date . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
2.5.6.3. Language . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
2.5.7. Service data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
2.5.7.1. General Maintenance settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
2.5.7.2. Counter settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
2.5.8. I/O configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Rennertronic Plus Touch 2 18239 24th April 2020
User Manual
2.5.8.1. Digital input configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
2.5.8.2. Digital output configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
2.5.8.3. Analog input configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
2.5.8.4. Analog output configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
2.5.9. Network settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
2.5.10. Frequency converter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
2.5.11. Factory settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
2.5.11.1. Temperatures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
2.5.11.2. Pressure settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
2.5.11.3. Frequency converter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
2.5.11.4. Running hour counter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
2.5.11.5. Compressor data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
2.5.11.6. IO Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
2.5.11.7. Backup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
2.5.11.8. PIN codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
2.5.12. Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
2.6. Notifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
3. Faults and warnings 62
3.1. Critical faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
3.2. FC critical faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
3.3. Non-critical faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
3.4. Recoverable faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
3.5. Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
4. Operation theory 65
4.1. Start prerequisites . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
4.2. Challenge response code authorization system . . . . . . . . . . . . . . . . . . . . . . . . . . 65
5. Function setup 69
5.1. Frequency converter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
5.1.1. Analog frequency converter setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
5.1.1.1. Analog frequency converter configuration - setup VFD type . . . . . . . . . . . . 69
5.1.1.2. Analog frequency converter configuration - DI setup . . . . . . . . . . . . . . . . 69
5.1.1.3. Analog frequency converter configuration - DO setup . . . . . . . . . . . . . . . 70
5.1.1.4. Analog frequency converter configuration - AO setup . . . . . . . . . . . . . . . 70
5.1.1.5. Analog frequency converter configuration - VFD parameter modification . . . . . 71
5.1.2. Modbus frequency converter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
5.1.2.1. Modbus frequency converter - setup VFD type . . . . . . . . . . . . . . . . . . . 71
5.1.2.2. Modbus frequency converter - serial configuration . . . . . . . . . . . . . . . . . 73
5.1.2.3. Analog frequency converter - setup VFD type . . . . . . . . . . . . . . . . . . . . 74
5.2. BLCO setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
5.2.1. BLCO Master configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Rennertronic Plus Touch 3 18239 24th April 2020
User Manual
5.2.1.1. BLCO Master serial port configuration . . . . . . . . . . . . . . . . . . . . . . . . 75
5.2.1.2. BLCO Master pressure control input configuration . . . . . . . . . . . . . . . . . 76
5.2.1.3. BLCO Master BLCO net configuration . . . . . . . . . . . . . . . . . . . . . . . . 76
5.2.1.4. BLCO Master BLCO slave configuration . . . . . . . . . . . . . . . . . . . . . . . 77
5.2.2. BLCO Slave configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
5.2.2.1. BLCO Slave serial configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
5.2.2.2. BLCO Slave pressure control selection . . . . . . . . . . . . . . . . . . . . . . . 79
5.3. Schedule . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
5.4. Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
5.5. Fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
5.6. Dryer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
5.7. Frost protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
5.8. Build up monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
5.9. Software update . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
5.9.1. HMI update . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
5.9.1.1. Fallback HMI updater . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
5.9.2. Main Controller update . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
5.9.2.1. Fallback Main controller update . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
List of Tables
1 Miscellaneous symbols descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2 Compressor state list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
2 Compressor state list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3 Compressor service status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
4 Pressure settings parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
5 System pressure related settings parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
5 System pressure related settings parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
6 Control timings parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
7 Control timings parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
8 Drain configuration parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
9 Fan configuration parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
10 Dryer configuration parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
11 Frost protection configuration parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
12 Baseload Changeover settings 1/3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
13 Baseload Changeover settings 2/3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
14 Baseload Changeover settings 3/3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
15 Remote control - start parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
16 Remote control - Pressure control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
17 Remote control - auto restart parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
18 Date and time parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Rennertronic Plus Touch 4 18239 24th April 2020
User Manual
19 General maintenance parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
20 Digital input configuration parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
20 Digital input configuration parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
21 Digital output configuration parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
21 Digital output configuration parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
22 Analog input 4-20mA configuration parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
23 Analog input RTD configuration parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
24 Analog input RTD configuration parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
25 Internal serial configuration parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
25 Internal serial configuration parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
26 Serial 2 configuration parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
27 Address configuration parameter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
28 Frequency converter parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
29 Factory settings temperature parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
30 Factory settings pressure parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
31 Factory settings frequency converter parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
32 Factory settings frequency converter parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
33 Factory settings frequency converter parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
34 Factory settings hour counters parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
35 Factory settings compressor data parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
36 Backup menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
36 Backup menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
37 List of critical faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
38 List of FC critical faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
39 List of non-critical faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
40 List of recoverable faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
41 List of warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
41 List of warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
42 HMI Update messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
42 HMI Update messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
43 Main Controller Update messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
44 Main Controller Update messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
List of Figures
1 Rennertronic Plus Touch main screen view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2 Net pressure tile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3 Net pressure diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4 System pressure tile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
5 Time and date tile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
6 Time and date tile with scheduler active . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Rennertronic Plus Touch 5 18239 24th April 2020
User Manual
7 Miscellaneous functions tile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
8 Compressor additional parameter fields . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
9 Compressor additional parameter menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
10 Main view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
11 Compressor state tile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
12 Status bar in the main view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
13 Status bar when a menu is active . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
14 Compressor status pop-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
15 Sliding menu open . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
16 Statistics menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
17 Fault memory menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
18 Utilisation menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
19 Error counter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
20 Charts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
21 Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
22 Network menu with example devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
23 Password input dialog . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
24 Main menu 1/2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
25 Main menu 2/2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
26 System pressure settings menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
27 Operation parameters menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
28 System pressure related settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
29 Control timings menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
30 Control timings data input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
31 Drain configuration menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
32 Fan configuration menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
33 Dryer configuration menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
34 Frost protection configuration menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
35 Schedule menu 1 / 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
36 Schedule menu 2 / 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
37 Schedule menu - setting for channel 7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
38 Schedule menu - priorities for channel 7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
39 Baseload Changeover menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
40 Baseload Changeover menu setup 1/2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
41 Baseload Changeover menu setup 2/2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
42 Baseload Changeover menu - setting for slave 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
43 Remote control menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
44 Remote control - Start control settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
45 Remote control menu - Pressure control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
46 Remote control - Auto restart settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
47 Display menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Rennertronic Plus Touch 6 18239 24th April 2020
User Manual
48 Units configuration menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
49 Date and time configuration menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
50 Language selector menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
51 Service counter menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
52 General maintenance menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
53 Counter setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
54 IO Configuration menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
55 Digital inputs configuration menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
56 Digital output configuration menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
57 Analog input configuration menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
58 Analog output configuration menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
59 Network settings configuration menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
60 Network settings / serial parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
61 Network settings / serial parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
62 Network settings addres configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
63 Frequency converter menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
64 Factory settings menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
65 Factory settings temperature menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
66 Factory settings pressure menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
67 Factory settings frequency converter menu 1/3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
68 Factory settings frequency converter menu 2/3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
69 Factory settings frequency converter menu 3/3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
70 Factory settings - Work counters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
71 Factory settings - Compressor Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
72 Factory settings - IO Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
73 Backup menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
74 Factory settings - PIN codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
75 Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
76 Example notification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
77 Challenge response with hidden code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
78 Challenge response with example code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
79 Challenge response with permmission granted . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
80 Challenge response with bad response . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
81 Factory settings - Deauthorization button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
82 Analog frequency converter type setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
83 Analog frequency converter Digital Input menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
84 Analog frequency converter Digital Output menu . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
85 Analog frequency converter Analog Output menu . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
86 Modbus frequency converter type setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
87 Modbus frequency converter serial port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
88 Modbus frequency converter model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Rennertronic Plus Touch 7 18239 24th April 2020
User Manual
89 Modbus frequency converter ID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
90 Modbus frequency converter on internal serial . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
91 Device Modbus address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
92 BLCO Master communication setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
93 BLCO Device modbus address setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
94 BLCO Master pressure source . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
95 Baseload changeover setup 1 / 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
96 Baseload changeover setup 2 / 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
97 BLCO Master slave 1 configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
98 Network settings / Serial menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
99 Network settings / Address configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
100 Remote control / Pressure control menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
101 Schedule menu 1 / 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
102 Schedule menu 2 / 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
103 Schedule menu - settings for channel 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
104 Schedule menu - BLCO priorities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
105 Schedule menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
106 Main view with active sheduler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
107 Drain configuration menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
108 Drain digital output configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
109 Fan configuration menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
110 Fan digital output configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
111 Fan analog output configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
112 Dryer configuration menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
113 Drain digital output configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
114 Drain digital input configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
115 Frost protection configuration menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
116 Heater digital output configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
117 System pressure related menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
118 Information menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
119 Update process . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Rennertronic Plus Touch 8 18239 24th April 2020
User Manual
1. Safety
The person installing the controller should read the following manual and
warranty information. Improper installation and handling of the controller
voids the warranty.
Any connection and mounting work can be performed only when the supply
voltage is disconnected.
The controller should be installed only by an authorized service or author-
ized personnel.
To comply with safety standards, the PE terminal of the controller should be
connected to a protective conductor or dedicated grounding.
Using the controller without the enclosure is forbidden as it might result in
an electric shock.
The device should not be exposed to water or excessive humidity which
may cause damage.
Before switching on check the electrical connections according to the con-
nection diagram in the operating manual.
Before starting the controller, make sure that the power supply meets the
requirements in the operating manual.
Any repairs can be done only by the manufacturer’s service. A repair done
by an unauthorized person voids the warranty.
Rennertronic Plus Touch 9 18239 24th April 2020
User Manual
2. User Interface
2.1. Buttons
The HMI provides two physical buttons: start and stop. Any function and device configuration is carried out
using the touch screen interfaces.
2.2. Main View
Figure 1: Rennertronic Plus Touch main screen view
Main display view is divided into tiles representing a specific function (as seen from left to right and from top to
bottom):
1. Net pressure
2. Oil temperature
3. System pressure
4. Time and date
5. State of miscellaneous compressor functions
6. Compressor information additional fields
7. Compressor state
8. Slider menu
Most of the tiles can be tapped to reveal additional information. The functions and operation of the specific
fields are described in the following subsections.
Rennertronic Plus Touch 10 18239 24th April 2020
User Manual
2.2.1. Net pressure tile
Figure 2: Net pressure tile
Pressure tile presents the following information:
1. Net pressure value
2. Pressure max (cut-out)
3. Pressure min (cut-in)
4. Pressure band indicator
5. Bar graph
Bar graph displays the pressure level between the active band’s cut-in and cut-out pressures. If the current
pressure is above the cut-out level the bar graph is black and if the pressure is below the cut-in level the bar
graph is white.
The pressure shows the active pressure band that is currently active. The user can define four different pressure
bands that can be selected using Modbus communication, digital input selector or with scheduler.
The default color of pressure tile is gray when the compressor is deactivated. During compressor operation
pressure tile changes color to:
1. Green - the pressure is in the allowed region - between max and min pressure value (+/- 0.1).
2. Yellow - the pressure exceeded the minimum/maximum pressure value.
3. Red - the pressure exceeded minimum/maximum alert value.
When the tile is tapped, the net pressure diagram is displayed.
Rennertronic Plus Touch 11 18239 24th April 2020
User Manual
Figure 3: Net pressure diagram
2.2.2. System pressure tile + BLCO status
Figure 4: System pressure tile
System pressure tile displays current internal pressure value. On the right side of the panel the BLCO active
icon is displayed if the BLCO is active.
The tile changes color to red if the sensor fails.
2.2.3. Time and date tile
Figure 5: Time and date tile
The tile displays current date and time. All the relevant settings are described in the section 2.5.6.2.
Rennertronic Plus Touch 12 18239 24th April 2020
User Manual
Figure 6: Time and date tile with scheduler active
If at least one scheduler is active, the tile displays the scheduler icon. For more information and setting de-
scriptions refer to section 5.3.. When the tile is tapped, the scheduler settings menu will be displayed.
2.2.4. State of miscellaneous compressor functions tile
Figure 7: Miscellaneous functions tile
The tile can display up to four miscellaneous compressor functions. The appropriate icons indicate the status
of the selected functions. If the specific icon has a dark gray background, the function is currently active/in
operation. If the icon is shown only as an outline, the function is inactive.
Table 1: Miscellaneous symbols descriptions
Description Symbol Description symbol Description symbol
Water injec-
Fan Dryer
tion
Network op-
Drain Heater
eration
Rennertronic Plus Touch 13 18239 24th April 2020
User Manual
2.2.5. Compressor information additional fields tile
Figure 8: Compressor additional parameter fields
The tile can display up to three additional compressor information. To select the visible information tap the tile
and choose the parameter from the menu.
Figure 9: Compressor additional parameter menu
Main view with Free air delivery parameter on.
Rennertronic Plus Touch 14 18239 24th April 2020
User Manual
Figure 10: Main view
2.2.6. Compressor state tile
Figure 11: Compressor state tile
Tile displays current state of the compressor.
Table 2: Compressor state list
Compressor state name Description
DEACTIVATED The compressor is not allowed to start.
STARTING The compressor is active and motor is starting.
COMPRESSION DELAY The start procedure has been completed and com-
pressor is waiting to load.
COMPRESSION The compressor is on load.
IDLE The pressure has reached pressure max level and
the motor is idling until pressure drops below pres-
sure min or idle time elapses.
DEACTIVATION STOPPING Stopping procedure was activated by a stop com-
mand and a stop procedure will be ended when all
conditions to stop have been met.
FAULT CONDITION An fault has occurred, the compressor stops or has
stopped and is waiting for the user to acknowledge
the faults or the fault cause disappears.
READY TO START The compressor is active and the pressure is above
the pressure min. When pressure drops down below
pressure min, compressor starts automatically.
Rennertronic Plus Touch 15 18239 24th April 2020
User Manual
Table 2: Compressor state list
Compressor state name Description
STOP-START DELAY COUNTING The stop-start delay is active. Compressor waits un-
til the counter reaches the desired value. The de-
sired start/stop delay can be modified in the ”opera-
tion parameters / control timings menu”.
NOT READY TO START The compressor is not ready to start - at least one
of the conditions preventing the compressor start is
active.
SYSTEM PRESSURE TOO HIGH System pressure is too high. When the pressure
drops below ”maximum system pressure to start”,
compressor starts automatically.
OIL TEMPERATURE TOO LOW Oil temperature is too low. When oil temperature ex-
ceeds min oil temperature, compressor starts auto-
matically.
MOTOR START COUNTER The motor was started more times than allowed by
the maximum starts per hour counter.
IDLE STOPPING Stopping procedure was activated by a idle timer,
but at least one of the conditions preventing the com-
pressor stop is active.
DEACTIVATION (KEEP POWER) There is a frequency converter fault active, the com-
pressor is not allowed to start.
AUTO-RESTART The compressor has activated auto restart proced-
ure after power fail.
2.2.7. Status bar
Status bar is always visible, regardless of what is displayed in the user interface. When the main HMI view is
displayed, the status bar contains elements:
1. MENU button
2. Service status icon
Figure 12: Status bar in the main view
When any other UI view is displayed, the status bar displays additional information - compressor status and
the current pressure.
Figure 13: Status bar when a menu is active
In any moment, the status bar displays the service status of the compressor. The icon changes colour depend-
ing on the compressor status.
Rennertronic Plus Touch 16 18239 24th April 2020
User Manual
Table 3: Compressor service status
Description Symbol
Normal operation
Active warning
Active warning and
error
Active error
By pressing the icon in any menu, the user can request the display of a pop-up with a summary of the active
messages, warnings and errors, together with the current counter statuses.
If an event or error occurred, the user can acknowledge the event by pressing the confirmation button. If the
event is currently inactive, this will allow the compressor to resume normal operation.
Figure 14: Compressor status pop-up
Rennertronic Plus Touch 17 18239 24th April 2020
User Manual
2.2.8. Sliding menu
When the MENU is pressed, the sliding menu opens, allowing the user to enter the specific menus.
Figure 15: Sliding menu open
From the sliding menu the user has access to following menu entries:
• Statistics menu
• Sensors
• BLCO (Network operation menu) [If BLCO is active]
• Main settings menu
• Information about compressor and the software
2.3. Statistics
Statistics menu entry contains four submenus:
1. Events history
2. Utilisation
3. Error counter
4. Charts
Rennertronic Plus Touch 18 18239 24th April 2020
User Manual
Figure 16: Statistics menu
2.3.1. Fault memory
Figure 17: Fault memory menu
Event history menu stores all errors and warnings that have occurred during compressor operation. All the
registered events are displayed
Rennertronic Plus Touch 19 18239 24th April 2020
User Manual
2.3.2. Utilisation
Figure 18: Utilisation menu
Utilisation menu displays counters related to aggregation of compressor operation time:
1. Working hours - counts total time of the motor being on.
2. Under load hours - counts total time of the compression time when the valve is on.
3. Average utilisation - this parameter shows ratio between ”working hours” and ”under load hours”.
4. Motor power cycles - counts total cycles of the motor being on.
2.3.3. Error counter
Figure 19: Error counter
Rennertronic Plus Touch 20 18239 24th April 2020
User Manual
2.3.4. Charts
The Charts show the values of selected parameters over time.
Figure 20: Charts
The time period can be set to:
1. hour,
2. day,
3. week,
4. 30 days.
The parameter can be selected between:
1. Net pressure,
2. System pressure,
3. Oil temperature,
4. Free air delivery.
Rennertronic Plus Touch 21 18239 24th April 2020
User Manual
2.3.5. Sensors
Figure 21: Sensors
2.4. BLCO (Network operation menu)
Figure 22: Network menu with example devices
2.5. Main settings menu
To access the main settings menu the user must provide a correct access password after pressing the Main
Menu icon. Depending on the password entered, the user will be granted a different access. In lower access
levels some parameters can be invisible or read only.
To get full access to compressor configuration, the user must obtain the unique access code, more information
in section 4.2..
Rennertronic Plus Touch 22 18239 24th April 2020
User Manual
While entering the password, the user can preview the already entered characters by pressing the View icon.
Figure 23: Password input dialog
Figure 24: Main menu 1/2
Rennertronic Plus Touch 23 18239 24th April 2020
User Manual
Figure 25: Main menu 2/2
Main settings menu is divided into following parameter lists:
1. Pressure settings - section 2.5.1.
2. Operation parameters - section 2.5.2.
3. Schedule - section 2.5.3.
4. BLCO - section 2.5.4.
5. Remote control - section 2.5.5.
6. Display - section 2.5.6.
7. Service data - section 2.5.7.
8. IO configuration - section 2.5.8.
9. Network settings - section 2.5.9.
10. Frequency converter - section 2.5.10.
11. Factory settings - section 2.5.11.
12. Diagnostics - section 2.5.12.
2.5.1. Pressure settings
Pressure settings allows the user to define four independent pressure bands.
Rennertronic Plus Touch 24 18239 24th April 2020
User Manual
Figure 26: System pressure settings menu
Table 4: Pressure settings parameters
Parameter Description Access level
Net pressure max alert If pressure rises above this level, high pressure warning Customer
occurs. Range [Net pressure max + 0.2 bar - Net pressure
faul value - 0.2 bar]
Net pressure max Upper switching point for pressure control. Range [Pres- Customer
sure setpoint + 0.2 bar - Net pressure max alert - 0.2 bar]
Net pressure min Lower switching point for pressure control. Range [Net Customer
pressure min + 0.2 bar - Net pressure max - 0.2 bar]
Net pressure min alert If pressure falls below this level, low pressure warning oc- Customer
curs. Range [Net pressure min alert + 0.2 bar - Pressure
setpoint - 0.2 bar]
2.5.2. Operation parameters
Operation parameters menu contains subgroups related to compressor control algorithm and additional com-
pressor functions.
Rennertronic Plus Touch 25 18239 24th April 2020
User Manual
Figure 27: Operation parameters menu
2.5.2.1. System pressure related
Figure 28: System pressure related settings
Table 5: System pressure related settings parameters
Parameter Description Access level
Maximum system If system pressure rises above this level, the motor start is Service
pressure to start prohibited.
Idle stop system pres- If system pressure is higher than this level, the motor stop Service
sure limit is prohibited.
User stop system If system pressure is higher than this level, user stop with Service
pressure limit a push button is prohibited.
Rennertronic Plus Touch 26 18239 24th April 2020
User Manual
Table 5: System pressure related settings parameters
Parameter Description Access level
Pressure build up Time after which the system pressure is checked during Service
monitoring time compresson for the pressure build up.
Build up minimum Level of system pressure that must be reached after build Service
pressure up delay.
2.5.2.2. Control timings
Figure 29: Control timings menu
Table 6: Control timings parameters
Parameter Description Access level
Stop-start delay Time between consecutive stops and starts of the motor to Service
allow the compressor to discharge.
Main power delay Delay between switching the main power relay on and the Service
start relay on
Startup time Delay for motor start in star-delta mode. Service
Compression delay Delay to switch the valve on after start up time. Service
Idling time Delay between reaching pressure cut-off level and switch- Service
ing the motor off
Soft stop delay Delay between receiving stop command and stopping the Service
motor
Rennertronic Plus Touch 27 18239 24th April 2020
User Manual
Figure 30: Control timings data input
Table 7: Control timings parameters
Parameter Description Access level
Stop mode time Time between pressing the stop button and the motor stop. Service
Star delta switch delay Time between star relay disable and delta relay enable. Highest permis-
Time count in ms. sion level
2.5.2.3. Drain configuration
Figure 31: Drain configuration menu
Rennertronic Plus Touch 28 18239 24th April 2020
User Manual
Table 8: Drain configuration parameters
Parameter Description Access level
Period time Length of the drain function operation period Customer
Drain duty cycle Time of active ouput during operation period. Customer
Drain function active Activation or deactivation of the drain function Customer
2.5.2.4. Fan configuration
Figure 32: Fan configuration menu
Table 9: Fan configuration parameters
Parameter Description Access level
Fan function active Activation or deactivation of the fan function Service
Fan off When the temperature drops below this level fan turns off. Service
Fan on When the temperature rises above this level fan turns on. Service
Must be higher than fan off temperature.
Fan max speed tem- When the temperature reaches this level the analog fan Service
perature control reaches max value. Must be higher than fan off
temperature.
Rennertronic Plus Touch 29 18239 24th April 2020
User Manual
2.5.2.5. Dryer configuration
Figure 33: Dryer configuration menu
Table 10: Dryer configuration parameters
Parameter Description Access level
Pre-run dryer Activation or deactivation of the dryer function Service
Pre run time Time that prohibits the start of the compressor if the dryer Service
reaches the working condition
2.5.2.6. Frost protection
Figure 34: Frost protection configuration menu
Rennertronic Plus Touch 30 18239 24th April 2020
User Manual
Table 11: Frost protection configuration parameters
Parameter Description Access level
Modbus heater active Activation or deactivation of the heater function Service
Heater activation tem- When the temperature drops below this level heater turns Service
perature on.
Heater deactivation When the temperature rise above this level heater turns off. Service
temperature
Modbus motor heating Activation or deactivation of the motor heationg function Service
active
Motor heating activa- When the temperature drops below this level motor heating Service
tion temperature turns on.
Motor heating deactiv- When the temperature rise above this level motor heating Service
ation temperature turns off.
2.5.3. Schedule
Figure 35: Schedule menu 1 / 2
Rennertronic Plus Touch 31 18239 24th April 2020
User Manual
Figure 36: Schedule menu 2 / 2
Figure 37: Schedule menu - setting for channel 7
Rennertronic Plus Touch 32 18239 24th April 2020
User Manual
Figure 38: Schedule menu - priorities for channel 7
2.5.4. Baseload Changeover
Figure 39: Baseload Changeover menu
Rennertronic Plus Touch 33 18239 24th April 2020
User Manual
Figure 40: Baseload Changeover menu setup 1/2
Table 12: Baseload Changeover settings 1/3
Parameter Description Access level
BLC Master If set to ’yes’ compressor works as master, if set to ’no’ Service
compressor works as a slave
Number of slaves Number of connected slave devices Service
Changing time Time between consecutive base load and compressor Service
switch order changes.
Start up delay Time of switching on additional compressors when the Service
pressure remains below cut-in level. If the pressure rises
above cut-in level during this time start of next compressor
is prohibited.
Switch off delay Time of switching off additional compressors when the Service
pressure remains above cut-in level. If the pressure falls
below cut-in level during this time stop of the next com-
pressor is prohibited.
Switch on over The value of motor speed in percent above which the next Service
compressor is switched on.
Rennertronic Plus Touch 34 18239 24th April 2020
User Manual
Figure 41: Baseload Changeover menu setup 2/2
Table 13: Baseload Changeover settings 2/3
Parameter Description Access level
Switch off below The value of motor speed in percent below which one of Service
the working compressors is switched off.
Delay time switching Time between consecutive starts and stops of a com- Service
on/off over/under pressor with a VFD, related to VFD switch on setpoint and
VFD switch off setpoint parameters.
Internal hours offset Number added to work counter to equalize work hours to Service
rest of the slaves.
Figure 42: Baseload Changeover menu - setting for slave 1
Rennertronic Plus Touch 35 18239 24th April 2020
User Manual
Table 14: Baseload Changeover settings 3/3
Parameter Description Access level
Slave 1 master Select the serial port to which the slave is connected. Service
selector
Slave 1 address Select Modbus ID for this device. Service
Slave 1 hours offset Number added to work counter to equalize work hours to Service
rest of the slaves.
For other slaves the configuration process is similar and is carried out in next tabs.
2.5.5. Remote control
Figure 43: Remote control menu
Rennertronic Plus Touch 36 18239 24th April 2020
User Manual
Figure 44: Remote control - Start control settings
Table 15: Remote control - start parameters
Parameter Description Access level
Start source Local or external start source. Service
Figure 45: Remote control menu - Pressure control
Rennertronic Plus Touch 37 18239 24th April 2020
User Manual
Table 16: Remote control - Pressure control
Parameter Description Access level
Pressure control mode Local - the controller utilizes load/unload signal derived Service
from internal pressure sensor. BLCO - the controller util-
izes load/unload signal from BLCO master. BLCO option
is required for BLCO operation. External - the controller
utilizes load/unload signal from digital input.
Pressure band select Local - Bands can be changed only by schedule. Digital Service
mode input - Every pressure band has a digital input for activating
a band.
Pressure setting No - Option is deactivated. Modbus - it is possible to Service
change max/min pressure value by modbus registers.
Figure 46: Remote control - Auto restart settings
Table 17: Remote control - auto restart parameters
Parameter Description Access level
Service
Auto restart function Auto restart function active. / inactive. Customer
active
Auto restart delay Delay for the auto restart procedure. Customer
Rennertronic Plus Touch 38 18239 24th April 2020
User Manual
2.5.6. Display
Figure 47: Display menu
Menu is a group of settings concerning the UI display.
2.5.6.1. Units
Figure 48: Units configuration menu
Rennertronic Plus Touch 39 18239 24th April 2020
User Manual
2.5.6.2. Time and Date
Figure 49: Date and time configuration menu
Table 18: Date and time parameters
Parameter Description Access level
Set time Change current time Customer
Set date Change current date Customer
Time format Switch between 24h and 12h clock Customer
Activate automatic Select if the controller is to automatically change time Customer
summer/winter time based on Daylight Saving Time
switch
Rennertronic Plus Touch 40 18239 24th April 2020
User Manual
2.5.6.3. Language
Figure 50: Language selector menu
The manu allows the user to change the display language.
2.5.7. Service data
Figure 51: Service counter menu
The menu groups service counter subsystem settings and annual maintenance counter. Main view of the menu
lists all the available counters.
Each counter is represented as a tile with the counter’s name and status. Status indicates how many hours
are left until the counter expires. If the counter reaches 0, the expiry is indicated with a warning symbol and
Rennertronic Plus Touch 41 18239 24th April 2020
User Manual
the status shows how many hours are left until error occurs (if error function is enabled - see 2.5.7.2.).
2.5.7.1. General Maintenance settings
Figure 52: General maintenance menu
General maintenance function allows the user to set the date of the yearly general maintenance.
Table 19: General maintenance parameters
Parameter Description Access level
Annual maintenance Confirm that the maintenance has just been performed and Service
schedule the maintenance in one year.
Shutdown after main- Enable or disable the fault that occurs if minimum one of Service
tenance exceeded the service counters has reached fault level and the main-
tenance has not been performed after operating more than
the number of hours defined in the parameter ”Time range
after exceeded” after the counter expiry.
Time range after ex- Number of hours of operation for service counters before Service
ceeded the fault occurs if the maintenance was not performed in
the designated time.
Rennertronic Plus Touch 42 18239 24th April 2020
User Manual
2.5.7.2. Counter settings
Figure 53: Counter setup
To enter the counter setup menu, press the tile with a corresponding counter name.
The menu allows the user to change the number of hours after which the counter elapses. All counters count
to zero from that value. Entering the number of hours enables the counter. To disable the counter, press the
”DISABLE COUNTER” button.
2.5.8. I/O configuration
Figure 54: IO Configuration menu
I/O configuration menu groups the settings associated with the controller’s inputs and outputs.
Rennertronic Plus Touch 43 18239 24th April 2020
User Manual
2.5.8.1. Digital input configuration
Figure 55: Digital inputs configuration menu
The menu allows the user to assign functions to digital inputs. The controller allows the user to define the
function of each available input, both in the master Main Controller and the Main Controller defined as an I/O
expander.
Table 20: Digital input configuration parameters
Parameter Description Access level
Free No function assigned to the input Factory
Motor Current High Digital input. When active it triggers current overflow fault. Factory
Fault frequency con- It is digital input for FC fault Factory
verter
Fan fault It is digital input for fan fault Factory
Phase rotation fault It is digital input for phase rotation fault Factory
Fault The function allows the input to trigger a fault. Can be as- Factory
signed to all digital inputs.
Uncritical fault The function allows the input to trigger uncritical fault. Can Factory
be assigned to all digital inputs.
Recoverable fault The function allows the input to trigger recoverable fault. Factory
Can be assigned to all digital inputs.
Warning The function allows the input to trigger a warning. Can be Factory
assigned to all digital inputs.
External Start-Stop The function allows the compressor to be started from di- Factory
gital input. It can be assigned only to a single input.
External Load-Unload External load-unload signal for the compressor. Factory
100% setpoint If set, the maximum speed for motor is selected even if Factory
pressure value is above the setpoint level.
Minimum speed 2 If set, the second minium speed for motor is selected. Factory
Dryer ready Digital input signal for dryer to indicate that dryer does not Factory
work properly. If this input is active the compressor turns
off. Behaviour is similar to recoverable fault.
Band 2 Selector Digital input to change active band to band 2. Factory
Rennertronic Plus Touch 44 18239 24th April 2020
User Manual
Table 20: Digital input configuration parameters
Parameter Description Access level
Band 3 Selector Digital input to change active band to band 3. Factory
Band 4 Selector Digital input to change active band to band 4. Factory
Scheduler On-Off Digital input for Scheduler on-off. Factory
2.5.8.2. Digital output configuration
Figure 56: Digital output configuration menu
The menu allows the user to assign functions to digital outputs. The controller allows the user to define the
function of four available outputs, both in the master Main Controller and the Main Controller defined as an I/O
expander. First four digital outputs are reserved and used in solenoid control and star-delta control.
Table 21: Digital output configuration parameters
Parameter Description Access level
Free No function assigned to the output Factory
Drain Control of the condensate drain Factory
FC Enable Start stop signal for frequency converter. Factory
Fan Control of the cooling fan. Factory
Dryer Control of the refrigerator dryer. Factory
Heater Control of the heater. Factory
Warning Digital output indicating that a warning has occurred. Factory
Fault Digital output indicating that a fault has occurred. Factory
Ready Digital output indicating that compressor is ready to start. Factory
Running Digital output indicating that motor is running. Factory
On Load Digital output indicating that compressor is on load. Factory
Warning / Fault Digital output indicating that warning or fault has occurred. Factory
Scheduler channel 1 Digital output indicating that scheduler channel 1 is active. Factory
Scheduler channel 2 Digital output indicating that scheduler channel 2 is active. Factory
Scheduler channel 3 Digital output indicating that scheduler channel 3 is active. Factory
Scheduler channel 4 Digital output indicating that scheduler channel 4 is active. Factory
Rennertronic Plus Touch 45 18239 24th April 2020
User Manual
Table 21: Digital output configuration parameters
Parameter Description Access level
Scheduler channel 5 Digital output indicating that scheduler channel 5 is active. Factory
Scheduler channel 6 Digital output indicating that scheduler channel 6 is active. Factory
Scheduler channel 7 Digital output indicating that scheduler channel 7 is active. Factory
Scheduler channel 8 Digital output indicating that scheduler channel 8 is active. Factory
Any shceduler Digital output indicating that any scheduler is active. Factory
Maintenance Digital output for control maintenance. Factory
BLCO Ready Digital output indicating that BLCO is ready. Factory
2.5.8.3. Analog input configuration
Figure 57: Analog input configuration menu
The menu allows the user to assign functions to analog inputs, both the 4-20mA inputs and the RTD inputs.
Table 22: Analog input 4-20mA configuration parameters
Parameter Description Access level
Free No function assigned to the output Factory
Net pressure sensor Input for net pressure sensor Factory
System pressure Input for system pressure sensor Factory
sensor
Table 23: Analog input RTD configuration parameters
Parameter Description Access level
Free No function assigned to the output Factory
Temperature Input for oil temperature sensor Factory
Motor temperature Input for motor temperature sensor Factory
Rennertronic Plus Touch 46 18239 24th April 2020
User Manual
2.5.8.4. Analog output configuration
Figure 58: Analog output configuration menu
Table 24: Analog input RTD configuration parameters
Parameter Description Access level
Free No function assigned to the output Factory
Setpoint frequency Speed setpoint for frequency converter Factory
converter
Fan Speed setpoint for fan. Factory
Rennertronic Plus Touch 47 18239 24th April 2020
User Manual
2.5.9. Network settings
Figure 59: Network settings configuration menu
Tiles with ”Serial 1 configuration”, ”Serial 2 configuration” and ”Serial 3 configuration” are enabled only if external
serial communication modules are installed correctly.
Figure 60: Network settings / serial parameters
Table 25: Internal serial configuration parameters
Parameter Description Access level
Baudrate Buad rate of the internal RS-485 interface (Default: 19200) Service
Parity Parity bit for the communication on the internal RS-485 in- Service
terface (Default: Even)
Rennertronic Plus Touch 48 18239 24th April 2020
User Manual
Table 25: Internal serial configuration parameters
Parameter Description Access level
Stop bits Stop bit for the communication on the internal RS-485 in- Service
terface (Default: one)
Function Serial function of the internal interface. None - no function Service
assigned to the internal serial, BLCO Slave - internal serial
works as BLCO slave, Modbus Master - internal serial
works as Modbus master
RTU master timeout Time of wait for the response for the communication on the Service
internal RS-485 interface. (Default: 200)
Figure 61: Network settings / serial parameters
Table 26: Serial 2 configuration parameters
Parameter Description Access level
Baudrate Baud rate of the internal RS-485 interface (Default: 19200) Service
Parity Parity bit for the communication on the internal RS-485 in- Service
terface (Default: Even)
Stop bits Stop bit for the communication on the internal RS-485 in- Service
terface (Default: two)
Function Serial function of the internal interface. None - no function Service
assigned to the Serial 2, BLCO Slave - Serial 2 works as
BLCO slave, Modbus Master - Serial 2 works as Modbus
master
RTU master timeout Time of wait for the response for the communication on the Service
internal RS-485 interface. (Default: 200)
For serials 1 and 3 there is the same configuration in the next tabs.
Rennertronic Plus Touch 49 18239 24th April 2020
User Manual
Figure 62: Network settings addres configuration
Table 27: Address configuration parameter
Parameter Description Access level
Modbus address Modbus slave ID for the device. All Modbus serials use the Customer
assigned ID.
2.5.10. Frequency converter
Figure 63: Frequency converter menu
Rennertronic Plus Touch 50 18239 24th April 2020
User Manual
Table 28: Frequency converter parameters
Parameter Description Access level
Minimum speed 1 Default lower motor speed limit Service
Minimum speed 2 Lower motor speed limit Service
Maximum speed Highest motor speed limit Service
2.5.11. Factory settings
Figure 64: Factory settings menu
The menu groups the parameters that can only be changed by the manufacturer.
Rennertronic Plus Touch 51 18239 24th April 2020
User Manual
2.5.11.1. Temperatures
Figure 65: Factory settings temperature menu
Table 29: Factory settings temperature parameters
Parameter Description Access level
Overtemperature fault Value of the oil temperature readout that stops the com- Factory
pressor and triggers fault if the temperature is above the
value
Overtemperature Value of the oil temperature readout that triggers warning Factory
warning if the temperature is above the value
Minimum start temper- Value of the oil temperature readout that stops the com- Factory
ature pressor and triggers fault if the temperature is below the
value
Rennertronic Plus Touch 52 18239 24th April 2020
User Manual
2.5.11.2. Pressure settings
Figure 66: Factory settings pressure menu
Table 30: Factory settings pressure parameters
Parameter Description Access level
Net pressure fault Value of the net pressure readout that stops the com- Factory
maximum value pressor and triggers fault if the pressure is above the value.
Range [Net pressure max alert + 0.2 bar - 16 bar]
System pressure fault Enable or disable of system pressure fault. Factory
enable
System pressure fault Value of the system pressure readout that stops the com- Factory
maximum value pressor and triggers fault if the pressure is above the value.
System pressure Enable or disable of system pressure warning. Factory
warning enable
System pressure Value of the system pressure readout that triggers warning Factory
warning maximum if the pressure is above the value.
value
Rennertronic Plus Touch 53 18239 24th April 2020
User Manual
2.5.11.3. Frequency converter
Figure 67: Factory settings frequency converter menu 1/3
The menu contains all the settings that are associated with the frequency converter control algorithm.
Table 31: Factory settings frequency converter parameters
Parameter Description Access level
Frequency converter Select compressor operation mode. Factory
• OFF - compressor in star-delta configuration
• Analog - compressor in frequency converter mode
with I/O control
FC Modbus master Select serial bus for frequency converter. Factory
FC Modbus protocol Set the type of Modbus device. Factory
FC Modbus slave ad- Set device Modbus ID for frequency converter. Factory
dress
FC communication er- Timeout for fault communication. Factory
ror timeout
Proportional gain PI parameter which determines influence of proportional Factory
coefficient for regulation
Rennertronic Plus Touch 54 18239 24th April 2020
User Manual
Figure 68: Factory settings frequency converter menu 2/3
Table 32: Factory settings frequency converter parameters
Parameter Description Access level
Integral gain PI parameter which determines influence of Integral coef- Factory
ficient for regulation
Absolute minimum Lowest motor speed limit Factory
speed
Change minimum Time after which the speed limit is changed from minimum Factory
speed after 1 to speed limit minimum 2.
Speed limit start pres- Pressure level on which speed reduction starts. Factory
sure
Speed limit pressure Dependency between presssure and speed setpoint re- Factory
gradient duction.
Speed limit start tem- Temperature level on which speed reduction starts. Factory
perature
Rennertronic Plus Touch 55 18239 24th April 2020
User Manual
Figure 69: Factory settings frequency converter menu 3/3
Table 33: Factory settings frequency converter parameters
Parameter Description Access level
Speed limit temperat- Dependency between temperature and speed setpoint re- Factory
ure gradient duction.
2.5.11.4. Running hour counter
Figure 70: Factory settings - Work counters
Rennertronic Plus Touch 56 18239 24th April 2020
User Manual
Table 34: Factory settings hour counters parameters
Parameter Description Access level
Running hours Work hours counter setup Factory
Load hours Compressor under load counter setup. Factory
2.5.11.5. Compressor data
Figure 71: Factory settings - Compressor Data
Table 35: Factory settings compressor data parameters
Parameter Description Access level
Serial number Unique number for the compressor, created by the manu- Factory
facturer
Free air delivery Nominal value of free air delivery. Factory
Maximum startups If the number of compressor starts is equal with number Factory
per hour declared in the parameter, compressor can’t start.
Vendor It’s used to change the vendor logo on the main view. Factory
Rennertronic Plus Touch 57 18239 24th April 2020
User Manual
2.5.11.6. IO Calibration
Figure 72: Factory settings - IO Calibration
2.5.11.7. Backup
Figure 73: Backup menu
Table 36: Backup menu
Parameter Description Access level
Dump settings Records encrypted settings to USB Factory
Override factory Remembers the current settings in the internal memory. Factory
settings The stored settings are then restored with factory reset.
Rennertronic Plus Touch 58 18239 24th April 2020
User Manual
Table 36: Backup menu
Parameter Description Access level
Dump factory settings Records encrypted settings to USB and a public file to view Factory
stored settings
Factory reset Restores the settings stored in the internal memory using Factory
override factory settings
Restore settings Restore the settings from the flash drive. There must be Factory
an encrypted file on the USB, created with Dump settings
or Dump factory settings.
Dump sensor history Record to USB file with sensors measurement history Factory
2.5.11.8. PIN codes
Figure 74: Factory settings - PIN codes
Rennertronic Plus Touch 59 18239 24th April 2020
User Manual
2.5.12. Diagnostics
Figure 75: Diagnostics
2.6. Notifications
While the compressor is running, notifications may appear in the system. Notifications are shown as red pop
up windows in the middle of the screen. Below is a example notification.
Figure 76: Example notification
List of messages:
• Connecting ...
• Main controller not detected ...
• Updating HMI. Do not turn off the power supply!
Rennertronic Plus Touch 60 18239 24th April 2020
User Manual
• UPDATE SUCCEED. REBOOTING...
• UPDATE FAILED!
• There was detected more than one updatable file on the data storage. Remove additional files and restart
update.
• There is no file with the .update extension present on the data storage in the /update folder.
• Updating Main Controller: starting update
• Updating Main Controller: step 1 of 3
• Updating Main Controller: step 2 of 3
• Updating Main Controller: step 3 of 3
• No main controller for update available
• Performing enforced update of the main controller
• Reset DIP switch 1 to continue
• No data storage detected
• MAINTENANCE. DO NOT POWER OFF THE DEVICE. The display may flicker or temporarily switch off.
• Collecting data: step 1 of 5
• Collecting data: step 2 of 5
• Collecting data: step 3 of 5
• Collecting data: step 4 of 5
• Collecting data: step 5 of 5
• Saving data to storage failed
• Collecting settings
• Restoring settings
• Processing ...
• Disable the compressor to be able to change parameters
• Factory access not authenticated.
• Database clear
• Events and sensor history clear
• Factory access blocked.
• Wrong code. Retries: 3
• New code generated!
• Do you want to leave without resetting the annual maintenance counter?
• Lack of proper permissions. You can see some parameters that cannot be changed
• The password must be 4 digits, please try entering new password again.
Rennertronic Plus Touch 61 18239 24th April 2020
User Manual
3. Faults and warnings
Faults are divided into groups:
1. Critical faults - faults that stop the compressor immediately
2. Non-critical faults - faults that stop the compressor using a stop procedure
3. Recoverable faults - faults that stop the compressor using a stop procedure and resume the compressor
operation after the fault cause ceases dissapears.
3.1. Critical faults
Table 37: List of critical faults
Critical fault Description
No oil temperature sensor Oil temperature sensor not attached or incorrect connection to the
sensor.
Short circuit of oil temperature Oil temperature may be shorted, damaged or the wire may be
sensor shorted.
Overtemperature fault Oil temperature above fault level. If the temperature rises above
the fault level, the compressor stops.
Can be changed in Factory settings / temperature menu. See
2.5.11.1.
Short circuit of net pressure Net pressure sensor may be shorted, damaged or the wire may
sensor be shorted.
High net pressure fault Net pressure above the fault level.
Can be changed in Factory settings / temperature menu. See
2.5.11.1.
No system pressure sensor System pressure not attached or incorrect connection to the
sensor.
Short circuit of system pressure System pressure sensor may be shorted, damaged or the wire
sensor may be shorted.
High system pressure fault System pressure above the fault level.
Can be changed in Factory settings / Pressure menu. See
2.5.11.2. Not in UI
Generic fault Generic fault assigned to a digital input. See 2.5.8.1.
Emergency stop Emergency stop button was pressed.
3.2. FC critical faults
Table 38: List of FC critical faults
FC critical Fault Description
Frequency converter fault
Frequency converter communic- Communication with frequency converter was lost.
ation fault
Frequency converter trip fault Trip faults can be reset using the automatic reset function in fre-
quency converter.
Frequency converter trip lock Alarms that are trip locked offer additional protection, meaning
fault that the mains supply must be switched off before the alarm can
be reset. After having been switched back on, the frequency con-
verter is no longer blocked and can be reset as described in fre-
quency converter manual.
Rennertronic Plus Touch 62 18239 24th April 2020
User Manual
3.3. Non-critical faults
Table 39: List of non-critical faults
Non-critical fault Description
Air filter service counter fault Air filter service counter has reached fault value.
Oil filter service counter fault Oil filter service counter has reached fault value.
Oil change service counter fault Oil change service counter has reached fault value.
Oil separator service counter Oil separator service counter has reached fault value.
fault
Belt change service counter fault Belt change service counter has reached fault value.
Generic non-critical fault Generic non-critical fault assigned to a digital input. See 2.5.8.1.
System pressure build up fault System pressure does not rise after start up.
Motor temperature too high Motor temperature above fault level. If the temperature rises
above the fault level, the compressor stops.
3.4. Recoverable faults
Table 40: List of recoverable faults
Recoverable Fault Description
Generic recoverable fault Generic recoverable fault assigned to a digital input. See 2.5.8.1.
Low oil temperature fault Oil temperature below fault level.
Can be changed in Factory settings / temperature menu. See
2.5.11.1.
No net pressure sensor Net pressure sensor not attached or incorrect connection to the
sensor.
Power failure fault Power supply was turned off.
Dryer not ready Dryer does not work properly. If the fault occurs the compressor
turns off, similar to recoverable fault.
3.5. Warnings
Table 41: List of warnings
Warning message Description
High oil temperature Oil temperature above the warning level.
Warning level can be changed in the Factory settings / Temper-
atures menu
High net pressure warning Net pressure above the warning level.
Warning level can be changed in Pressure settings menu
Low net pressure warning Net pressure below the warning level
Warning level can be changed in Pressure settings menu
High system pressure warning System pressure below the warning level
Warning level can be changed in Pressure settings menu
Not in UI
Maintenance counter warning General maintenance was not performed in a required period.
Air filter service counter warning Air filter service counter elapsed.
Oil filter service counter warning Oil filter service counter elapsed.
Oil change service counter Oil change service counter elapsed.
warning
Oil separator service counter Air filter service counter elapsed.
warning
Belts change service counter Belts change service counter elapsed.
Rennertronic Plus Touch 63 18239 24th April 2020
User Manual
Table 41: List of warnings
Warning message Description
Counter warning Warning after a counter has elapsed.
Generic warning Generic warning assigned to one of the digital inputs. See 2.5.8.1.
Frequeny converter warning There is a frequency converter fault active. Description of the
warning provides information on warning type. For details see
chapter 3.2.
Rennertronic Plus Touch 64 18239 24th April 2020
User Manual
4. Operation theory
4.1. Start prerequisites
This section describes the conditions that must be fulfilled to start / stop the compressor. Depending on the
start / stop signal source, the prerequisites differ.
1. Start / stop source: automatic start / stop
• System pressure must fall below ”Idle stop system pressure limit”. It can be changed in Operation
parameters / System pressure related settings, this can prevent problem with next compressor start.
• If pressure drops soon next start will be possible without violating ”Maximum startups per hour”. It
can be changed in Factory settings / Compressor Data.
2. Start / stop source: user request
• System pressure must fall below ”User stop system pressure limit”. It can be changed in Operation
parameters / System pressure related settings, this can prevent this problem with next compressor
start. This is usually set higher than ”Idle stop system pressure limit”.
3. Start / stop source: fault
• When the compressor stops because a fault was detected, no conditions are checked.
If compressor can not start, it is necessary to check:
• System pressure level must be lower than level set in Operation parameters / System pressure related /
Maximum system pressure to start.
• Oil temperature level must be higher than 5 degrees Celsius.
• Motor will not start soon after stop. It can be changed in Operation parameters / Control timings / Stop-start
delay.
• Motor is not permitted to start more than number of times per hour as set in Factory settings / Compressor
Data / Maximum startups per hour.
• If dryer is enabled it’s output must be enabled for some time before proceeding. It is set in Operation
parameters / Dryer configuration.
4.2. Challenge response code authorization system
Challenge response code authorization system protects the compressor from changes made by not-authorized
user. To get the full configuration access to the compressor controller, the authorization is carried out as follows:
1. Enter Main settings menu, press the icon with padlock symbol
2. When 9-digit code will appear, contact the compressor manufacturer and provide the generated code
3. The manufacturer will provide the user with a 9-digit response code
4. Enter the generated code in the authorization menu
5. • If the entered code is correct, the main system menu is open and full permissions will be granted for
24 hours.
• If the entered code is incorrect, the system will generate a new challenge code and the code gener-
ation procedure is to be retried.
Rennertronic Plus Touch 65 18239 24th April 2020
User Manual
Figure 77: Challenge response with hidden code
Figure 78: Challenge response with example code
Rennertronic Plus Touch 66 18239 24th April 2020
User Manual
Figure 79: Challenge response with permmission granted
Figure 80: Challenge response with bad response
After the modifications requiring full access are finished, it is necessary to de-authorize. In main settings menu,
enter Factory settings and PIN codes and press the ”Deauth” button. Full configuration access is revoked. To
perform additional, changes, the challenge-response procedure is to be performed again.
Rennertronic Plus Touch 67 18239 24th April 2020
User Manual
Figure 81: Factory settings - Deauthorization button
Rennertronic Plus Touch 68 18239 24th April 2020
User Manual
5. Function setup
This section describes how to enable and setup some of the controller functions.
5.1. Frequency converter
The controller supports two frequency converter control methods:
• Analog frequency converter, controlled using digital and analog input/outputs,
• Modbus frequency converter, controlled using serial port with Modbus RTU.
5.1.1. Analog frequency converter setup
To setup the analog frequency converter, the following parameters must be changed:
1. VFD type
2. IO assignment for VFD control signals
3. VFD operation parameters
5.1.1.1. Analog frequency converter configuration - setup VFD type
From settings menu, enter Factory settings / Frequency converter and set the converter type to ”Analog” in
parameter ”Frequency converter”.
Figure 82: Analog frequency converter type setup
5.1.1.2. Analog frequency converter configuration - DI setup
From settings menu, enter IO configuration / Digital input menu and assign Fault frequency converter function
to one of the digital inputs.
Rennertronic Plus Touch 69 18239 24th April 2020
User Manual
Figure 83: Analog frequency converter Digital Input menu
5.1.1.3. Analog frequency converter configuration - DO setup
From settings menu, enter IO configuration / Digital output menu and assign an FC enable function to one of
the relay outputs.
Figure 84: Analog frequency converter Digital Output menu
5.1.1.4. Analog frequency converter configuration - AO setup
From settings menu, enter IO configuration / Analog output menu and assign a Setpoint frequency converter
to one of the analog outputs.
Rennertronic Plus Touch 70 18239 24th April 2020
User Manual
Figure 85: Analog frequency converter Analog Output menu
5.1.1.5. Analog frequency converter configuration - VFD parameter modification
If all the steps were done correctly, the Analog frequency converter should work properly. If required, enter
Factory settings / Frequency converter menu and modify the converter parameters:
1. Minium FC speed
2. Maximum FC speed
3. PID parameters
4. Speed reduction functions
From settings menu, enter Frequency converter and if necessary modify speed limits.
5.1.2. Modbus frequency converter
To setup the Modbus-controlled frequency converter, the following parameters must be changed:
1. VFD type
2. Serial interface type for VFD control
3. VFD operation parameters
5.1.2.1. Modbus frequency converter - setup VFD type
From settings menu, enter Factory settings / Frequency converter and set the converter type to ”Modbus” in
parameter ”Frequency converter”.
Rennertronic Plus Touch 71 18239 24th April 2020
User Manual
Figure 86: Modbus frequency converter type setup
Set the ”FC Modbus master” to the interface (serial port) to which the frequency converter is connected to.
Figure 87: Modbus frequency converter serial port
Set the ”FC Modbus protocol” to the type of the FC.
Rennertronic Plus Touch 72 18239 24th April 2020
User Manual
Figure 88: Modbus frequency converter model
Set the FC Modbus slave address.
Figure 89: Modbus frequency converter ID
The parameter ”FC communication error timeout” can be adjusted if the controller reports communication errors
too early.
5.1.2.2. Modbus frequency converter - serial configuration
From settings menu, enter Network settings and enter the configuration menu for the interface that the FC is
connected to. Set all the communication parameters according to the VFD settings in ”Internal serial function”.
The example below shows the configuration for the Danfoss VFD on the internal serial.
Rennertronic Plus Touch 73 18239 24th April 2020
User Manual
Figure 90: Modbus frequency converter on internal serial
From settings menu, enter Network settings and Address configuration. Choose the ”Modbus address” refers
to the address of the master interface and not the VFD ID.
Figure 91: Device Modbus address
5.1.2.3. Analog frequency converter - setup VFD type
If all the steps were done correctly, the Modbus frequency converter should work properly. If required, enter
Factory settings / Frequency converter menu and modify the converter parameters:
1. Minium FC speed
2. Maximum FC speed
3. PID parameters
4. speed reduction functions
Rennertronic Plus Touch 74 18239 24th April 2020
User Manual
From settings menu, enter Frequency converter and if necessary modify speed limits.
5.2. BLCO setup
5.2.1. BLCO Master configuration
To configure BLCO master, the following parameters must be changed on the master controller:
1. Serial port used for BLCO
2. Pressure control input
3. BLCO configuration
4. Individual slave configuration
5.2.1.1. BLCO Master serial port configuration
From settings menu, enter Network settings on the chosen serial port (Internal / Serial 1 / Serial 2 / Serial
3) which will be using for BLCO Network. Set the communication parameters to reflect the communication
parameters that the BLCO net uses.
The following example is for Serial 3.
Figure 92: BLCO Master communication setup
Parameter ”Function” must be set to Modbus master, the rest of the parameters must be the same as on BLCO
slave devices.
From settings menu, enter Network setting and Address configuration and set ”Modbus address” - this is the
interface Modbus master ID.
Rennertronic Plus Touch 75 18239 24th April 2020
User Manual
Figure 93: BLCO Device modbus address setup
5.2.1.2. BLCO Master pressure control input configuration
From settings menu, enter Remote control / Pressure control and set the pressure control mode to ”BLCO” if
the master compressor is to be used and controlled by BLCO.
Figure 94: BLCO Master pressure source
5.2.1.3. BLCO Master BLCO net configuration
From settings menu, enter Baseload changeover / Baseload changeover setup
Parameters required to enable BLCO master:
1. ”Master enable” - set to yes
Rennertronic Plus Touch 76 18239 24th April 2020
User Manual
2. ”Slave count” - set to the number of slaves in the BLCO net. If this value is wrong, the network will be
slower.
3. Rest of the parameters do not affect BLCO communication but influence the BLCO algorithm behaviour
Figure 95: Baseload changeover setup 1 / 2
Figure 96: Baseload changeover setup 2 / 2
5.2.1.4. BLCO Master BLCO slave configuration
From settings menu, enter Baseload changeover. There the user can configure each of the slaves in their
respective menu.
For each of the slaves, configure:
1. Slave serial port to which the slave is connected
Rennertronic Plus Touch 77 18239 24th April 2020
User Manual
2. Device address
3. Hours offset
Figure 97: BLCO Master slave 1 configuration
5.2.2. BLCO Slave configuration
To configure BLCO slave, the following parameters must be changed on the slave controller:
1. Serial port used for BLCO
2. Pressure control input
5.2.2.1. BLCO Slave serial configuration
From settings menu, enter Network settings on the chosen serial port (Internal / Serial 1 / Serial 2 / Serial
3) which will be using for BLCO Network. Set the communication parameters to reflect the communication
parameters that the BLCO net uses.
The following example is for Serial 3.
Rennertronic Plus Touch 78 18239 24th April 2020
User Manual
Figure 98: Network settings / Serial menu
Parameter ”Function” must be set to BLCO slave, the rest of the parameters must be the same as on BLCO
master device.
From settings menu, enter Network setting and Address configuration and set ”Modbus address” - this is the
interface Modbus master ID.
Figure 99: Network settings / Address configuration
5.2.2.2. BLCO Slave pressure control selection
From settings menu, enter Remote control / Pressure control and set the pressure control mode to ”BLCO” if
the master compressor is to be used and controlled by BLCO.
Rennertronic Plus Touch 79 18239 24th April 2020
User Manual
Figure 100: Remote control / Pressure control menu
5.3. Schedule
Scheduler allows to configure up to eight channels that can modify certain compressor operation parameters.
From settings menu, enter Schedule and select the channel which settings are to be modified.
Figure 101: Schedule menu 1 / 2
Rennertronic Plus Touch 80 18239 24th April 2020
User Manual
Figure 102: Schedule menu 2 / 2
Figure 103: Schedule menu - settings for channel 1
Schedule configuration options for each of the channels:
1. Channel function: ”Compressor active” or ”Output active” or ”Compressor and output active”
2. Days on which the selected channel is active
3. Channel activation and deactivation times
4. Pressure band if the compressor is active during the active scheduler channel
If the scheduler is modified on the BLCO master device, slave device priorities can be adjusted.
Rennertronic Plus Touch 81 18239 24th April 2020
User Manual
Figure 104: Schedule menu - BLCO priorities
To enable the scheduler, click on the ”Scheduler is turned off” tile. After successful activation, the text changes
to ”Scheduler is active”.
Figure 105: Schedule menu
In the main view, the scheduler can be enabled and disabled by pushing the time and date tile. The calendar
icon indicates that the scheduler is active.
Rennertronic Plus Touch 82 18239 24th April 2020
User Manual
Figure 106: Main view with active sheduler
In order for the scheduler to be active, the compressor must be in enabled stage (the user must press the green
start button).
5.4. Drain
From settings menu, enter Operation parameters / Drain configuration. To enable the function, set ”Drain
function active” to ON.
Figure 107: Drain configuration menu
Drain configuration options:
1. Drain period time - Length of the drain function operation period
2. Drain duty cycle - How long in the operation period the drain output is active
Rennertronic Plus Touch 83 18239 24th April 2020
User Manual
If drain is activated, it is necessary to set one of the digital outputs to drain function. In order to do this, from
settings menu enter IO configration / Digital outputs configuration and set one of the outputs as a drain function.
Figure 108: Drain digital output configuration
5.5. Fan
From Operation parameters, enter Fan configuration. To enable the function, set ”Fan function active” to ON.
Figure 109: Fan configuration menu
Fan configuration options:
1. Fan off temperature - When the temperature drops below this level fan turns off.
Rennertronic Plus Touch 84 18239 24th April 2020
User Manual
2. Fan on temperature - When the temperature rises above this level fan turns on. Must be higher than fan
off temperature.
3. Fan max speed temperature - When the temperature reaches this level the analog fan control reaches
max value. Must be higher than fan off temperature.
If fan is activated, it is necessary to set one of the digital outputs to fan function. In order to do this, from settings
menu enter IO configration / Digital outputs configuration and set one of the outputs as a fan function.
Figure 110: Fan digital output configuration
When a digital output is set, the next step is to setup the analog output. In order to do this, from settings menu
enter IO configration / Analog outputs configuration and set one of the outputs as a fan function.
Figure 111: Fan analog output configuration
Rennertronic Plus Touch 85 18239 24th April 2020
User Manual
5.6. Dryer
From Operation parameters, enter Dryer configuration and set parameter ”Dryer function active” to ON.
Figure 112: Dryer configuration menu
Dryer configuration options:
1. Pre run time - Time that prohibits the start of the compressor if the dryer reaches the working condition.
If dryer is activated, it is necessary to set one of digital output to dryer function. To do this, go to IO configuration
enter digital output configuration choose output and set to dryer function.
Figure 113: Drain digital output configuration
The user can optionally set the ”Dryer ready” input. This input is used to indicate that the dryer does not work
correctly. If this input is active the compressor turns off.
Rennertronic Plus Touch 86 18239 24th April 2020
User Manual
To enable the signal, enter Settings menu / IO Configuration / Digital inputs and select the input to be used as
a dryer ready input.
Figure 114: Drain digital input configuration
5.7. Frost protection
From Operation parameters, enter Frost protection configuration. To enable the function, set ”Heater active” to
ON.
Figure 115: Frost protection configuration menu
Frost protection configuration options:
1. Heater active - Activation or deactivation of the heater function.
Rennertronic Plus Touch 87 18239 24th April 2020
User Manual
2. Heater activation temperature - When the temperature drops below this level heater turns on.
3. Heater deactivation temperature - When the temperature rise above this level heater turns off.
4. Motor heating active - Activation or deactivation of the motor heationg function.
5. Motor heating activation temperature - When the temperature drops below this level motor heating turns
on.
6. Motor heating deactivation temperature - When the temperature rise above this level motor heating turns
off.
If Frost protection is activated, it is necessary to set one of the digital outputs to heater function. In order to
do this, from settings menu enter IO configration / Digital outputs configuration and set one of the outputs as a
Heater function.
Figure 116: Heater digital output configuration
5.8. Build up monitor
From settings menu, enter Operation parameters / System pressure related and setup the parameters according
to the requirements.
Rennertronic Plus Touch 88 18239 24th April 2020
User Manual
Figure 117: System pressure related menu
Build up monitor configuration options:
1. Pressure build up monitoring time - Time after which system pressure will be checked in compressing
state for the pressure build up.
2. Build up minimum pressure - Level of system pressure that must be reached after build up delay.
If the compressor does not reached the ”build up minimum pressure” level after the ”build up delay”, the fault
occurs and the compressor stops.
5.9. Software update
The update process consists of two steps:
1. HMI update - initiated by the user
2. Main controller update - performed automatically after the HMI update
5.9.1. HMI update
To begin the update process, plug the USB key with the update file located in the update/ directory to the USB
port on the HMI. From the bottom sliding menu, enter Information menu and press the ”Update” button.
Rennertronic Plus Touch 89 18239 24th April 2020
User Manual
Figure 118: Information menu
The update procedure starts. Do not turn off the power supply during the update process.
Figure 119: Update process
During the update process the diagnostic information will be displayed.
Table 42: HMI Update messages
Update message Details / suggested action
Updating HMI. Do not turn off the The update is in progress.
power supply!
Update succeess. Rebooting The HMI update was completed and the device is rebooting.
Rennertronic Plus Touch 90 18239 24th April 2020
User Manual
Table 42: HMI Update messages
Update message Details / suggested action
There was detected more than On the USB key’s update directory, there is more than one file
one file with .update extension with the update package.
on the removable drive. Re- To fix the issue:
move additional files and restart
update. 1. Disconnect the USB key from the HMI
2. Plug the USB key back to the HMI
3. Retry the update
4. If problem persists, connect to PC and verify if the update
package was uploaded to the USB key properly
There is no file with .update ex- On the USB key’s update directory, there isno file with the update
tension present on the remov- package.
able drive in the update foder. To fix the issue:
1. Disconnect the USB key from the HMI
2. Plug the USB key back to the HMI
3. Retry the update
4. If problem persists, connect to PC and verify if the update
package was uploaded to the USB key properly
5. If the update package exists in the update directory, verify if
it is a proper update file for a device
6. Disconnect the USB key from the PC and retry the update
UPDATE FAILED Generic error.
To fix the issue:
1. Retry the update
2. Disconnect the USB key from the HMI
3. Plug the USB key back to the HMI
4. Retry the update
5. If problem persists, connect to PC and verify if the update
package was uploaded to the USB key properly
6. If the update package exists in the update directory, verify if
it is a proper update file for a device
7. Disconnect the USB key from the PC and retry the update
8. If problem persists, try updating the HMI using the fallback
update method.
5.9.1.1. Fallback HMI updater
If the HMI update fails or the user cannot enter the Information menu, there is a possibility to update the software
system using the fallback updater.
To use a fallback updater:
1. Connect the USB key with a update package to the HMI USB port
2. Power off the HMI
3. Power on the HMI
4. When the splash screen is shown, press a 0 button several times and wait for the fallback updater to
display the messages.
Rennertronic Plus Touch 91 18239 24th April 2020
User Manual
5.9.2. Main Controller update
In order for the Main Controller software to be updated, it needs to be connected to the HMI and powered on.
After successful connection to the Main Controller, HMI detects if the software version on the Main Controller is
the same as on the HMI and initiates the update if necessary. During the Main Controller update, the diagnostic
information will be displayed.
Table 43: Main Controller Update messages
Update message Details / suggested action
Updating Main Controller: start- The update has started
ing update
Updating Main Controller: step 1 The update is in progress
of 3
Updating Main Controller: step 2 The update is in progress
of 3
Updating Main Controller: step 3 The update is in progress
of 3
Updating Main Controller failed The update has failed and will be retried
5.9.2.1. Fallback Main controller update
If updating the Main Controller fails it is possible to eneble the emergency updater and force the update.
In order to carry out the emergency update procedure, it is required to enable the switch position 1 on the
main controller and restart the controller. The emergency update procedure starts and HMI will display the
notification about updating the MC using the emergency updater. Possible notifications:
Table 44: Main Controller Update messages
Update message Details / suggested action
Emergency updating Main Con- The update has started
troller: starting update
Emergency updating Main Con- The update is in progress
troller: step 1 of 3
Emergency updating Main Con- The update is in progress
troller: step 2 of 3
Emergency updating Main Con- The update is in progress
troller: step 3 of 3
Toggle a switch to proceed Toggle the switch position 1 on the main controller to ”off” and wait
for the procedure to end.
Rennertronic Plus Touch 92 18239 24th April 2020