0% found this document useful (0 votes)
157 views61 pages

Example For User Manaul ImageIII-2

This document provides an overview and instructions for using the screens and functions of an Image IIII controller. It includes brief explanations of key terms and the purpose of screens such as Heater, Silo, Light, Air Inlets, Cool, and others. The screens allow the user to monitor and control various climate parameters, alarms, equipment, feeding, and more for indoor agricultural applications.

Uploaded by

Ansell Jaya
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
157 views61 pages

Example For User Manaul ImageIII-2

This document provides an overview and instructions for using the screens and functions of an Image IIII controller. It includes brief explanations of key terms and the purpose of screens such as Heater, Silo, Light, Air Inlets, Cool, and others. The screens allow the user to monitor and control various climate parameters, alarms, equipment, feeding, and more for indoor agricultural applications.

Uploaded by

Ansell Jaya
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 61

Image IIII

Program version KIS179901E


09/11/2022
Program version KIS179901E

Contents
Overview .................................................................................................................................... 8
The System............................................................................................................................. 8
Main Unit ............................................................................................................................... 8
The Relay Box ....................................................................................................................... 8
Unit- Front Panel........................................................................................................................ 9
The Keyboard............................................................................................................................. 9
Cursor Focus ............................................................................................................................ 10
Glossary of terms ..................................................................................................................... 11
Side Damper / Inlet .............................................................................................................. 11
Tunnel / Cool curtain ........................................................................................................... 11
Minimum or cycle ventilation .............................................................................................. 11
Cross Ventilation ................................................................................................................. 11
Tunnel ventilation ................................................................................................................ 11
Static Pressure (negative pressure) ...................................................................................... 11
Main Screen ............................................................................................................................. 12
Menu Screen ............................................................................................................................ 13
Menu icon ............................................................................................................................... 14
Show Alarm History ........................................................................................................ 14
Alarm\Par column ............................................................................................................ 15
Date column: .................................................................................................................... 15
Time column..................................................................................................................... 15
Grow Day column ............................................................................................................ 15
Alarms column ................................................................................................................. 15
Disable column ................................................................................................................ 15
Alarm 2 column................................................................................................................ 15
Disable column ................................................................................................................ 15
Requested Temperature column: ..................................................................................... 15
In Temperature column: ................................................................................................... 15
Humidity column:............................................................................................................. 15
Weight column: ................................................................................................................ 15
Help icon .................................................................................................................................. 17
ImageIIII controller screens ..................................................................................................... 18
Heater Screen ........................................................................................................................... 18
Diff Set On ....................................................................................................................... 18

www.agrologic.com Page 2 of 61 [email protected]


Program version KIS179901E

Diff Set Off ...................................................................................................................... 18


Heat Sensor Allocation .................................................................................................... 18
Daily On / Total On ......................................................................................................... 18
Silo Screen ............................................................................................................................... 19
Current Weight Silo 1 / 2 ................................................................................................. 19
Silo last fill 1 / 2 ............................................................................................................... 19
Silo State .......................................................................................................................... 19
Zero Cal Screen.................................................................................................................... 19
Weight Cal Screen ............................................................................................................... 20
Silo Constants Screen .......................................................................................................... 21
Light Screen ............................................................................................................................. 21
Dimmer minimum............................................................................................................ 21
Dimmer delay................................................................................................................... 21
On / Off ............................................................................................................................ 22
Calculated ON and Off Times ......................................................................................... 22
Light Graph .......................................................................................................................... 22
Static Pressure Screen .......................................................................................................... 23
Pressure Gap: ................................................................................................................... 23
Pressure Cal: .................................................................................................................... 23
Pressure Delay Measure ................................................................................................... 23
Press Step ......................................................................................................................... 23
Press Delay....................................................................................................................... 23
Feed Screen .......................................................................................................................... 24
Feedline / Auger ............................................................................................................... 24
History Screen ...................................................................................................................... 25
Air Inlets Screen 1 ............................................................................................................... 25
Maximum Flaps Move Time ........................................................................................... 25
Air Inlets 2 ........................................................................................................................... 26
Air inlet synchronization position level ........................................................................... 26
Number of air inlet movements to activate flap synchronization .................................... 26
Minimum-maximum ........................................................................................................ 26
Cool Screen / Fogger ........................................................................................................... 27
Temperature Offset .......................................................................................................... 27
On Time ........................................................................................................................... 27
Maximum Off Time ......................................................................................................... 27
Minimum Off Time.......................................................................................................... 27
Cool Pad Screen ................................................................................................................... 28

www.agrologic.com Page 3 of 61 [email protected]


Program version KIS179901E

Temperature Offset .......................................................................................................... 28


Humidity Level To Stop Cooling .................................................................................... 28
Cooling Start / End Time ................................................................................................. 28
Cool Curtain Open in Cool State ..................................................................................... 28
Ventilation Screens .................................................................................................................. 29
Temperature Stages .............................................................................................................. 30
Temperature On ............................................................................................................... 30
Temperature Off............................................................................................................... 30
Fans 1-5 ............................................................................................................................ 30
Fans 6-9 ............................................................................................................................ 30
Fan 10............................................................................................................................... 30
Fans 11-13 ........................................................................................................................ 30
Humidity Control ................................................................................................................. 31
Humidity Level To Add Fan Stage .................................................................................. 31
Humidity control to cutoff temp ...................................................................................... 31
CO2 Control ............................................................................................................................. 31
CO2 Control Setup 1 Screen ................................................................................................ 31
CO2 level to add fan stage ............................................................................................... 31
CO2 Margin Level ........................................................................................................... 31
CO2 Control Cutoff Temperature .................................................................................... 32
CO2 Control Setup 2 Screen ................................................................................................ 32
CO2 Average Time .......................................................................................................... 32
Average Timer ................................................................................................................. 32
CO2 Startup Delay ........................................................................................................... 32
CO2 Control Enable\Disabled ......................................................................................... 32
Minimum Vention.................................................................................................................... 33
Cycle Time ....................................................................................................................... 33
Minimum On Time .......................................................................................................... 33
Number of Birds .............................................................................................................. 33
Current Weight................................................................................................................. 33
Duty Cycle ....................................................................................................................... 33
Minimum cube air kilogram screen ................................................................................. 34
Outside Temperature Above and Below .......................................................................... 34
Volume Air/Hour Per Kg ................................................................................................. 34
Current Weight Gain Table;................................................................................................. 35
Grow Day Column ........................................................................................................... 35
Weight Gain Column ....................................................................................................... 35

www.agrologic.com Page 4 of 61 [email protected]


Program version KIS179901E

First Day Weight .............................................................................................................. 35


Weight increase graph...................................................................................................... 36
Ventilation Setup ..................................................................................................................... 37
Ventilation Setup 1 .............................................................................................................. 37
Ventilation State Delay .................................................................................................... 37
Fan Stage To Stop Minimum Ventilation ........................................................................ 37
First tunnel stage fan ........................................................................................................ 37
Fan State in transition mode ............................................................................................ 37
Minimum and Initial Positions......................................................................................... 37
Ventilation Setup 2 .............................................................................................................. 38
Tunnel Cold Ventilation ...................................................................................................... 38
Maximum outside temperature ........................................................................................ 38
Stage To Open Tunnel Curtain ........................................................................................ 38
The dampers will open to the percent set in Minimum Damper Postion......................... 38
Maximum Ventilation Stage ............................................................................................ 38
Minimum Damper Position.............................................................................................. 38
In cold tunnel ventilation, when the Stage To Open Tunnel Curtain is reached, the
dampers will automatically open to the percent set here. ................................................ 38
Stir Fan ..................................................................................................................................... 39
Stir Fan On When Heater Is On ....................................................................................... 39
Stir Fan On In Cross Ventilation ..................................................................................... 39
Stir Fan Operation Mode ................................................................................................. 39
Operation Temperature .................................................................................................... 39
Constant Operation Temperature Difference ................................................................... 39
Set here the number of degrees above the Operation Temperature that will cause the stir
fan to run nonstop. ........................................................................................................... 39
Sensors Select .................................................................................................................. 39
On Time ........................................................................................................................... 39
Off Time........................................................................................................................... 40
Setup Screens ........................................................................................................................... 40
Setup Screen 1...................................................................................................................... 40
Set Date ............................................................................................................................ 40
Time ................................................................................................................................. 40
Grow Day ......................................................................................................................... 40
Net Name ......................................................................................................................... 40
Reset Time ....................................................................................................................... 40
Screen Time ..................................................................................................................... 40

www.agrologic.com Page 5 of 61 [email protected]


Program version KIS179901E

Required Temperature ..................................................................................................... 41


Water Multiplier............................................................................................................... 41
State Delay; ...................................................................................................................... 41
PC Communication Setup ................................................................................................ 41
Setup Screen 2...................................................................................................................... 42
Average Temperature Setup ............................................................................................ 42
Temperature Sensors Measure Delay .............................................................................. 42
UPS Mode Setup .............................................................................................................. 42
UPS Mode ........................................................................................................................ 42
Fan Groups ON In Power Outage .................................................................................... 42
Input Delay....................................................................................................................... 43
Temperature Reduction Table.............................................................................................. 43
Grow Day Column ........................................................................................................... 43
Temperature Difference Column ..................................................................................... 43
Calculated temperature Column ...................................................................................... 43
Grow Day ......................................................................................................................... 43
Room Temperature Reduction Graph .............................................................................. 44
Setup Screen 3 Setup Screen 4 ............................................................................... 45
Timer Screen ............................................................................................................................ 45
Daily Data Screen .................................................................................................................... 46
Alarm Screens .......................................................................................................................... 46
Alarm Screen 1 .................................................................................................................... 47
Panel Alarm (#9) .............................................................................................................. 47
Clearing the Panel Alarms ............................................................................................... 48
Disabling Panel Alarms ................................................................................................... 48
Static Pressure Alarm Screen ............................................................................................... 48
High Pressure Alarm ........................................................................................................ 48
Low Pressure Alarm ........................................................................................................ 48
Temperature Alarm Screens ................................................................................................ 49
Hot Alarm temp offset-day time ...................................................................................... 49
Night start time and end time ........................................................................................... 49
Hot Alarm temp offset-night time.................................................................................... 49
Time period for temp change ........................................................................................... 49
Max. temp change in period............................................................................................. 50
Cold Alarm........................................................................................................................... 50
Cold Alarm Temp Offset ................................................................................................. 50
Time period for temp. change .......................................................................................... 50

www.agrologic.com Page 6 of 61 [email protected]


Program version KIS179901E

Max. temp change in period............................................................................................. 50


Water Alarms ........................................................................................................................... 52
Water Consumption Table ....................................................................................................... 53
CO2 Alarm ............................................................................................................................... 53
High CO2 Alarm Level .................................................................................................... 53
High CO2 Alarm Delay ................................................................................................... 53
Low CO2 Alarm Level .................................................................................................... 53
Low CO2 Alarm Delay .................................................................................................... 53
Alarm Log Screen .................................................................................................................... 54
Basic installation ...................................................................................................................... 54
Main Unit ............................................................................................................................. 54
230V power connection ................................................................................................... 54
Power supply .................................................................................................................... 54
Main Unit – Relay Box ........................................................................................................ 55
Mother Board to Relay Box ................................................................................................. 55
Power supply to relay box.................................................................................................... 55
Temperature sensors ............................................................................................................ 56
Temperature Sensors ............................................................................................................ 56
Fast analog inputs ................................................................................................................ 57
FS1 Current Sensor .............................................................................................................. 57
8/16/24/32 modular relay box .................................................................................................. 58
Connection Table ..................................................................................................................... 60
Relay Setup .............................................................................................................................. 61

This manual may contain mistakes and or printing errors.


We accept no liability for technical mistakes, printing errors or their consequence's.

www.agrologic.com Page 7 of 61 [email protected]


Program version KIS179901E

Overview

The Image III is a standalone climate control computer with optional connection to a central
Windows operated personal computer or internet connection for central management.

The Image III can be ordered with various software programs to suit any type of poultry
house.

The Image III operates all systems installed in the modern poultry house. Heating, cooling,
ventilation, all flap motors, feed and augur motors, lighting systems and more, all controlled
from one main unit.

The System

The Image III consists of two parts, Main unit and Relay box.

Main Unit

The main unit (see photo below) is the brain of the Image III. It makes all the calculations
needed to adequately control the house climate and operates all equipment in the house. The
main unit controls the relay box. The main unit panel enables the user to program all
parameters needed to maintain the best conditions in the house.

Main Unit

The Relay Box


The relay box holds up to 32 dry contact change-over relays. The relay box is controlled by
the main unit. The 32 lights located on the relay box front panel indicate which relays are
active.
Note: 2 relay boxes can be connected for a total number of relays of 64.

Relay Box

www.agrologic.com Page 8 of 61 [email protected]


Program version KIS179901E

Unit- Front Panel

Display screen – The Image III display screen is a 7" full color, LCD touch sensitive
screen.
Navigation to other screens is done from the display screen or the
keyboard.
(editing and setup is done with the keyboard).

Display screen

Numerical Keyboard
Directional arrows
keys and spin wheel
USB connector
connector ESC key
Star key

Enter key Menu key

The Keyboard

The keyboard is used to enter data, setup and navigate through the screens.
Following is a description of all keyboard functions:

Numerical Keyboard – The 0 to 9 keys are used to enter the values of the parameters and to
choose a function within a menu.

ESC key – The ESC key has several functions;

• The ESC key is used to exit Edit boxes without saving.


• The ESC key is used to return to the pervious screen.
• The ESC key is used to close popup windows and menus.

STAR key – The STAR key has several functions;

• The STAR key is used when programming the Temperature Reduction & Weight Increase
Graphs.
• The STAR key is used to bring up the graph menu when the history graph is displayed.
• The STAR key is used to open the calendar window in the Setup screen (see Set Date in
the first Setup screen).
• The STAR key is used to bring up the Help window when the cursor focus is in an Edit
box.

www.agrologic.com Page 9 of 61 [email protected]


Program version KIS179901E

• The STAR key is used to close popup windows.

MENU key –The MENU key is used to jump to the Menu screen .

• When the Menu screen is displayed, the MENU key is used to jump to the Main screen.

Remove space ENTER key – The ENTER key is used to store parameter values to the internal
memory. The ENTER key is also used to activate the action corresponds with an Icon.

Directional arrows keys

The Up, Down, Left and Right arrows keys have several functions:

• They are used to move the cursor focus around the screen between the different Edit
Boxes and Icons.
• The Up and Down keys are used to change the value of a parameter.
• The Up and Down keys are used to select an item from a menu.

Spin wheel– to use the spin wheel, move your finger in circular direction inside the wheel,
either in clockwise or counter-clockwise direction. The spin wheel has several functions:

• It is used to move the cursor focus around the screen.


• It is used to change the value of a parameter.

USB connector – The USB connector is a standard USB connector. It is compatible with all
USB memory sticks. It is used for backing up all programmed parameters, uploading
previous programmed parameters and to update the panel program and screens. To use these
features your memory stick must contain the RunMe program.

Cursor Focus

The cursor focus moves between the Edit boxes and Icons.
There are three ways to move the cursor focus around within the display screen:

1. Directional arrows – use the directional arrows to move the cursor focus around the
screen.
2. Spin Wheel – spin the Spin Wheel to move the cursor focus around the screen
3. Touch screen – use your finger as a pointer. Tap on the Edit box where you would like the
cursor focus to be.

www.agrologic.com Page 10 of 61 [email protected]


Program version KIS179901E

Glossary of terms

Side Damper / Inlet


The side damper is usually located on the side walls of the house. It is used to bring fresh air
into the house. The side Damper is used mostly during minimum ventilation. The fresh air is
coming into the house near the ceiling where it is mixing with the warm air and absorbing
humidity. The side dampers are used to regulate the house static pressure during minimum
and cross ventilation.

Tunnel / Cool curtain


The tunnel curtain is located at the end of the house and is usually opposite the tunnel fans.
The cool air curtain is opening together with the tunnel fans and during tunnel ventilation the
tunnel curtain is used to regulate the house static pressure.
The tunnel curtain is always open when the outside cooling system runs.

Minimum or cycle ventilation


Minimum ventilation mode is the ventilation mode that is used by the controller to supply the
minimum amount of air needed per kilo per hour. Normally this is done by using the cross-
ventilation fans together with the side dampers to bring fresh air into the house.
The fans are running in a cycle mode as calculated according to the current bird weight,
current amount of birds in the house and the minimum air per kilo according to the outside
temperature. Minimum ventilation generally does not reduce the temperature in the house.
During the minimum ventilation mode the dampers will open to a preset opening before the
cross ventilation fans come into operation. Once the fans have finished their on cycle, they go
off and the dampers will close.

Cross Ventilation
Cross ventilation is the mode that is used by the controller once the house starts to heat up
and the cycle ventilation is no longer enough. Once the set point for the cross fans is reached
they will leave the cycle mode and run nonstop.

Tunnel ventilation
The controller converts to this mode of operation from the minimum or cross ventilation
modes when the temperature in the house is too high. When the set point for the first tunnel
fan group is reached the unit will go into tunnel ventilation.

There are two modes for tunnel ventilation.


o Cold tunnel ventilation.
Cold tunnel ventilation is when the control unit goes into tunnel ventilation mode but
the outside temperature is too cold to open the tunnel curtain. The tunnel fans come
on and work opposite the side dampers.
o Regular tunnel ventilation.
Regular tunnel ventilation is where the tunnel fans are running, the side dampers are
closed and the tunnel curtain is open and is controlling the static pressure for the
house.

Static Pressure (negative pressure)


Static pressure refers to the pressure difference that exists between the inside and outside of
the house. This pressure difference is the result of running Fans in the walls. The air that they
exhaust enters the house through various types of

www.agrologic.com Page 11 of 61 [email protected]


Program version KIS179901E

air inlet openings. In the Minimum ventilation mode the dampers is where the vast majority
of the air enters. In the Tunnel Mode, the tunnel curtain at the end of the house is where the
air enters. The pressure drops due to the resistance to the air flowing through the dampers, is
the reason a static pressure difference exists. If the dampers are all the same size, the same
amount of air will enter through each damper.
When the incoming air is cooler than the inside air, it will tend to drop down onto the
birds before it is warmed up. Adequate static pressure brings the air into the house
high and fast so that it heats up before it can fall.

Main Screen

The main screen (photo below) is the first screen that is displayed when the Image III starts
up.
The main screen contains basic information on the current house climate, recorded daily
water and feed consumption and feed silo weight. To reach the main screen from any screen,
the keyboard MENU key has to be pressed twice.

The main screen contains;


Average Temperature
Current measured inside average temperature in the house.

In normal conditions the average temperature reading will be Black.


When the Hot or Cold alarm is activated; the average temperature text will be Red.

Humidity
The current house humidity level is displayed here.

Pressure
Shows the current static pressure reading in the house.

CO2
The current house CO2 level is displayed here.

Required Temperature
The current required temperature for the house as calculated in the Temperature Reduction
table are shown here.

Grow Day

www.agrologic.com Page 12 of 61 [email protected]


Program version KIS179901E

A display of the current grow day. Age (grow day) will change each day after both midnight
and Reset Time have passed.

Water
This is a display of the current daily water consumption. The display is reset to zero at reset
time.

Feed
This is a display of the current daily feed consumption. The display is reset to zero at reset
time.

Side Inlets and Cool Curtain Status


Shown here is the current position in percentage for the side inlets and cooling curtains. The
readout is from 0 to 100. 0 = fully closed, 100 = fully open.

T1-T7/ outside temperature


This is a display of the current temperature readout for each of the six inside temperature
sensors and the one outside sensor.

Feel Temperature
Shows the front and rear feel temperature in the house, based on the wind chill factor.

Opening screens from within the Main screen


From the main screen, it is possible to open other screens by tapping on certain action
pictures.
➢ To open the alarm screen, tap on the Alarm Horn action picture.
➢ To open the ventilation screen, tap on one of the Fan action pictures.
➢ To open the heater screen, tap on one of the Heater action picture.
➢ To open the light screen, tap on the Light action picture.

Menu Screen

By pressing on the MENU button located on the front board of the Image III, the following
screen will appear.

The menu screen contains icons that link to other screens that contain information for
programming the unit.

www.agrologic.com Page 13 of 61 [email protected]


Program version KIS179901E

Navigate the cursor focus to the icon subject of your choice, to open press the ENTER button
on the front panel.

Menu icon

The Menu screen enables you to view the alarm history and make eight more actions (Press
on the Menu icon in the Menu screen to bring up the menu window).
This popup screen contains 8 menu items:
1: Show alarm history.
2: Start photo mode.
3: Stop photo mode.
4: Copy photos to memory stick.
5: Copy the data files to memory stick.
7: Start diagnostics mode.
8: Stop diagnostics mode.

To choose one of the items, use the UP and DOWN arrows to move the yellow cursor to the
desired item and then press on the ENTER key. Another way to choose an item is to press on
its number using the keyboard. For example: press the ‘1’ key to choose the first item.

Here is a description of each menu item:

Show Alarm History


This item brings up the Alarm/Event history table. This table displays up to 500 last alarms
and other events that have occurred.
The total number of events that can be viewed is displayed above the table.
Use the navigation arrows to move the yellow marker.
Use the UP arrow to return to the previous row, DOWN arrow to move to the next row, the
LEFT arrow to return to the previous column and the RIGHT arrow to move to the next
column.

Following is a list of the columns and a short explanation.

Alarm Type List


➢ Alarm On: alarm turned on. When the cursor is moved to any of the parameters
opposite the Alarm On type, they will be in Red text.

➢ Alarm Off: Alarm turned off. When the cursor is moved to any of the parameters
opposite the Alarm Off type, they will be in Green text.

➢ Start-up (power returned): The control unit has restarted. When the cursor is moved to
any of the parameters opposite the Start-up type, they will be in Blue text

➢ Shut-down (power outage): The control unit shuts down (power outage). When the
cursor is moved to any of the parameters opposite the Start-down type, they will be in
Blue text.

www.agrologic.com Page 14 of 61 [email protected]


Program version KIS179901E

➢ Parameter: Any changes in the Current weight or Requested room temperature will be
logged. When the cursor is moved to any of the parameters opposite the Parameter
type, they will be in Blue text.

Alarm\Par column
➢ This column displays the alarm number and type (type 1, 2, panel, weight or
Requested temperature).

Date column:
➢ This column displays the date the alarm or parameter change occurred.

Time column
➢ This column displays the time the alarm or parameter change occurred.
Grow Day column
➢ This column displays the grow day the alarm occurred or the grow day as changed.

Alarms column

➢ This column displays the numerical list of the alarms types (alarm type 1).

Disable column
➢ This column displays the numerical list of alarm type 1 which were disabled at the
time of the alarm.

Alarm 2 column
➢ This column displays the numerical list of alarm 2 types.

Disable column
➢ This column displays the numerical list of alarm type 2 which were disabled at the
time of the alarm.

Requested Temperature column:


➢ This column displays the Requested temperature at the time of the alarm.

In Temperature column:
➢ This column displays the house average temperature at the time of the alarm.

Humidity column:
➢ This column displays the house humidity at the time of the alarm.

Weight column:

▪ This column displays the current weight at the time of the alarm.
Use the ESC key to exit the Alarm History screen.

The Alarm History table cannot be cleared or modified.

www.agrologic.com Page 15 of 61 [email protected]


Program version KIS179901E

3. Start Photo Mode


This item is used to take screen photos of your Image III screens. Use this item to enter the
Photo mode. Once entered, the Photo Mode message will appear at the bottom of the Image
III screen for two seconds.

Working with the Photo-Mode


Once in Photo-Mode you can take (capture) screen photos. Go to the screen you want to
capture, be sure that the cursor is not in an edit box. Press on the keyboard zero key to take a
photo of the screen. At the bottom of the Image III screen will appear the photo number and
how many photos have been taken. A maximum of 30 photos can be taken. To take more
than 30 photos you first must download the photos using the Menu option 5 Copy photos to
memory stick option or by using the RunMe program.

4. Stop Photo-Mode
Use this option to exit the Photo-Mode.

5. Copy the photos to the memory stick


This option is not accessible (greyed out in the menu) until a memory stick is inserted into the
USB connector.
This item is used to copy all photos taken using the Photo Mode. You will need a standard
memory stick.
Insert the memory stick into the USB connector, at the bottom of the screen will appear the
word USB. Open the Menu option window and choose item 5 Copy photos to memory stick.
All photos will be copied over to the memory stick. The photos are stored on the memory
stick
under ImageIIII\Photos.
Once copied over, the photos will be erased for the controller.

6. Copy the data files to the memory stick


This item is used to copy all data files from the Image III to the memory stick.
At present time, this information can only be processed by Agrologic. In the future, you will
be able to import the data into a program to view history or transfer the data to a different
house.
The data files are stored on the memory stick under ImageIIII\Files.

8. Start Diagnostics-Mode
This item should be used only by certified AgroLogic technical personnel.

9. Stop Diagnostics-Mode
This item should be used only by certified Agrologic technical personnel.

www.agrologic.com Page 16 of 61 [email protected]


Program version KIS179901E

Help icon

Your Image III includes internal help files. This Icon is used to enable the help mode which
will show help information of all statuses and editable parameters.
To turn the Help feature on, click on the Help Icon in the Menu screen. It will receive a
yellow outline indicating that the help feature is on.

Help feature off Help feature on

There are 2 types of help. One is for Status information; the second for editable parameters.

Status Help
To bring up help for a Status display, tap on the value you would like to see the help for.
A yellow window will appear containing the help text. Use the ESC or STAR key, or tap on
the yellow window to close it (photo 3).

Status Help

Help for editable parameters


To bring up help for an editable parameter, move the cursor focus to the edit box you want to
edit. The edit box will have a yellow background. Press on the STAR key, or start to enter a
number with the numerical keyboard. The edit window will open. The edit box contains two
areas. The top blue area contains the edit box value (photo 4); the bottom yellow area
contains the help text. To save any changes made and close the edit/help window, press on
the ENTER key. To close without saving, use the ESC key or simply tap on the edit window
with your finger.

www.agrologic.com Page 17 of 61 [email protected]


Program version KIS179901E

Editable Parameters Help

ImageIIII controller screens

Heater Screen

Diff Set On
Enter a temperature offset to be used by each heating group.
This temperature offset is set below the required house temperature.
Once the heater group temperature reaches this level, the heaters will turn on.

Diff Set Off


Enter a temperature offset to be used by each heating group.
This temperature offset is set below the required house temperature, but above the Diff Set On
setting.
Once the heater group temperature reaches this level, the heaters will turn off.
Heat Sensor Allocation
Set the temperature sensor or sensors used to for the heating group temperature reading.
Enter 1 for sensor 1, 12 for sensors 1&2. You can use up to 4 sensors.

Daily On / Total On
Displayed here is the daily ON time for each heater group displayed in Hours and Minutes.
This is reset at Reset Time (see Setup Screen 1 on page 40).

www.agrologic.com Page 18 of 61 [email protected]


Program version KIS179901E

Silo Screen

Current Weight Silo 1 / 2


This is the current weight in kilogram for silo 1 & 2

Silo last fill 1 / 2


This is the last filling for silo 1 & 2

Silo State
Normal; All is in order with the feeding system.
Detecting Fill; the feeding system has detected an increase of 300 kg or more in the feed silo
weight. The program reacts to this as if the feed silo is being filled with feed.
Fill; the feed silo is being filled. The program will not allow the feed auger to run while it’s
in the Fill detect state.
Zero Calibration; the feed silo is being calibrated to zero.
Weight Calibration; the feed silo is being calibrated to a known weight.
Calibration Error; the calibration process did not succeed.
Unused; the feeding system is in this state while between batch times.

Zero Cal Screen

In order for the Image III to weigh properly, first the system must be calibrated.
The A/D junction box is measuring the input from the load cells and converting it to a
number that is transmitted to the Image III for processing.

www.agrologic.com Page 19 of 61 [email protected]


Program version KIS179901E

When the silo is empty, this number is related to the ZERO weight, lets call it Z.
The load cell constant is the multiplier that must be used to display the correct weight, lets
call it M.

The weight displayed on the Image III is calculated by the following formula:
(X-Z)*M where X is the output from the junction box.
When X=Z then the silo is empty, and the display is 0000.
In order to have a calibrated system; we must calculate Z and M. This can be done as
follows:

Make sure the silo is empty.

To start the zero-calibration process for silo 1, press on the Zero Cal 1 icon. To start the zero-
calibration process for silo 2, press on the Zero Cal 2 icon
This calculates the Zero (Z) number automatically and stores it in the memory.
This number is constant for the installation. If it is changed for some reason, you can reenter
it manually in the Constant Screen.

Please record and save this number for future reference.

After the Zero (Z) data has been set, the multiplier (M) data must be set.
Fill the silo with an accurate known weight. Enter this weight in the FULL CALIBRATION
screen. The more exact the weight, the more precise the silo weighing will be.

Weight Cal Screen

Once the zero calibration has been done, it is important to run a weight calibration as well. To
get the best and most accurate results in this calibration, we need to define the exact weight,
which we are certain of, so the controller will have a unified and standard reference of full
weight.

Enter weight and press to start calibration of silo 1/2:


Enter here the weight in KG that has been put in or on the feed silo.

To start the Full calibration process, click on the Silo 1 Cal or silo Cal 2 icon ( for silo 1 and
silo 2 respectively).

www.agrologic.com Page 20 of 61 [email protected]


Program version KIS179901E

Silo Constants Screen

The Zero and load cell constant numbers are recorded here.
If for some reason the silo weighting program goes into an error alarm, check the zero and
load cell constants. If they have changed you can re-enter them manually here.

Copy these numbers and save them for future reference.

Light Screen

Your program contains a sunrise-sunset mode.


The program contains a light graph which can be setup for the entire flock.

Dimmer minimum
Enter here a percentage between 0-100. This is the minimum light intensity when the lights
are on.

Dimmer delay
This is the length of time in minutes and seconds that it takes the lights to go from minimum
to maximum intensity or from maximum to minimum intensity.

www.agrologic.com Page 21 of 61 [email protected]


Program version KIS179901E

On / Off
These on off time setting are used to add extra light times.
These times will override the time setting in the Light Graph screen below.

Calculated ON and Off Times


Displays the current on and off times as calculated in the light graph.

Light Graph

The screen has 3 columns.


• Day; the day column represents the target grow day for the light change.
• Start; start is the set time for the lights to go on. This ON time will be used with the
target day setting. The start time will change in a linear fashion between target days (see
example Error! Reference source not found.Error! Reference source not
found.Error! Bookmark not defined. ).
• Stop; stop is the set time for the lights to go off. This OFF time will be used with the
target day setting. The stop time will change in a linear fashion between target days (see
example Error! Bookmark not defined.).
• Grow day; this is the current grow day.
• Calc start; this is the calculated time the lights will go on.
• Calc stop; this is the calculated time the lights will go off.

Example;
Day 1;
Start = 06:00
Off = 05:00
Dimmer minimum = 10
Dimmer maximum = 100
Dimmer delay = 02:00
The lighting system will come on at 06:00 at an intensity of 10% (dimmer minimum). Over
the next 2 minutes (dimmer delay) the lights will increase in intensity from 10% to 100%. At
05:00 the light intensity will start to decrease going from 100% to 10% over a two minute
time period (dimmer delay). Once the 10% is reached the lights will go off.

Between day one and day seven, the On time will be shorted in a liner fashion. By day seven
the lights will go on at 06:00 and off at 03:00.
By day 25, the light will go on at 06:00 and off at 23:00

www.agrologic.com Page 22 of 61 [email protected]


Program version KIS179901E

Static Pressure Screen

Pressure Gap:
The value entered here will be the difference above and below the desired static pressure in
which the controller will not attempt to change the position of the damper or cool flap.

Pressure Cal:
Enter here the required number for pressure calculation.
This setting can be changed to help calibrate the sensor.
If you use an external sensor to compare readings, you can change the Pressure Cal to create
the same reading as your sensor.
Advised setting; 4.0

Pressure Delay Measure


This is the time delay used before measuring the static pressure.
Enter here a time between ¼ of a second to 2 seconds.
1 means a quarter of a second. 2 is a half of a second. 3 is three quarters of a second.
Maximum delay is 8 which is two seconds.

Press Step
Enter here a value in percentage. This is the step size for the damper / cool curtain that is
taken while trying to regulate the static pressure in the house.

Press Delay
Enter here a time period in minutes and seconds. This is the time delay the controller will
wait between each pressure step while trying to adjust the static pressure.

Try entering 0 for the both Press Step and Delay. Let the controller calculate its steps and
delay automatically.
If you see after a trial period that the controller is unable to keep a steady pressure reading for
the house, you can use the Press step and delay to help it out.

www.agrologic.com Page 23 of 61 [email protected]


Program version KIS179901E

Static pressure according to outside temperatures;


There are three outside temperature settings. For each temperature setting, there is a different
required static pressure setting.

Example:

Outside temperature Required static pressure


Lower than 7.0° 25
Between 20
Higher than 28.0° 10

In this example, if the outside temperature is less than 7° the required static pressure for the
house will be 25 pascal.
If the outside temperature is between 7° - 25° the required static pressure will be 20 pascal.
If the outside temperature rises above 28° then the required static pressure will be 10 pascal.

Feed Screen

Feedline / Auger
The feedline / Auger have 12 Start and Stop times throughout the day.
Example:
Feedline Start: 06:00 - Feedline Stop: 10:00
Feedline Start: 13:00 - Feedline Stop: 17:00
Feedline Start: 20:00 - Feedline Stop: 23:00
In this example, the feedline will start running at 06:00 and stop at 10:00
The lines will start again at 13:00 and run to 17:00
The lines will start up again at 20:00 and go off at 23:00

Do not use 00:00 as a time setting.

www.agrologic.com Page 24 of 61 [email protected]


Program version KIS179901E

History Screen

The Image III stores both information collected over a 24 hour time period on an hour by
hour basis and information stored as flock information on a day by day basis. This
information can be viewed in a graph or table format. The data that has been recorded over an
hour by hour basis is collected over the last 30 growing days. The data that has been recorded
over a day by day basis is collected over the last 365 growing days.
The history screen contains links to both 24 hour and flock graphs.

At the beginning of a new flock, click on the Clear History icon to erease all history.

Air Inlets Screen 1

In order for the unit to properly control the Damper and Cool Flap, they first need to be
calibrated. Click on one of the calibration buttons to start the calibration. The damper or cool
flap being calibrated will first close to 0%, then open to 100%. After that it will return to its
proper position according to the ventilation mode.

-8888 will appear when the flap is calibrating to 0%


8888 will appear when the flap is calibrating to 100%
9999 will appear if the flap has lost calibration.

Maximum Flaps Move Time


This is the maximum allowed move time for the inlet or curtain. If they move for longer than
this set time, the controller will assume there is a problem and will stop the calibration.
The alarm relay will be active.
This time is set in minutes and seconds.

www.agrologic.com Page 25 of 61 [email protected]


Program version KIS179901E

Air Inlets 2

Air inlet synchronization position level


Set here a value in percentage. This value will determine the behavior of the inlets and
curtain during synchronization (either open to 100% or close completely). If it is time for
synchronization and the inlets or curtains position at that time is equal or higher to the value
set here, then they will open to 100% during the synchronization process. If at the time for
synchronization, their position is lower than the value set here, then they will close during
synchronization.

Number of air inlet movements to activate flap synchronization


Normal- Set here a value reflecting the number of movements of the inlet or curtain, without
reaching one of the end points (fully open or fully closed). If the air inlet has moved the
number of times set here, the synchronization process will begin.

Minimum-maximum
Set here a value reflecting the number of movements of the air inlet. If the air inlet has not
reached its minimum/maximum opening position at the movement that is stated here, then a
synchronization process will begin (in the example above, if at its 15th move, the air inlet will
not be at its minimum/maximum opening position, then there will be a synchronization).

Synchronization is necessary to help the controller know the current position of the inlet or
curtain.

www.agrologic.com Page 26 of 61 [email protected]


Program version KIS179901E

Cool Screen / Fogger

Temperature Offset
Set as a temperature offset above the required house temperature.
When reached, the fogger system will start to run.
The system will run in a cycle mode as set in the On Time, Maximum Off Time and Minimum
Off Times.

On Time
Set in minutes and seconds.
The is the on time for the foggers.

Maximum Off Time


Set in minutes and seconds.
This is the maximum time the fogger system will be off once the Temperature Offset is
reached.

Minimum Off Time


Set in minutes and seconds.
This is the minimum time the fogger system will be off once the Temperature Offset is
reached.

Example:
Required house temperature is 20°
Temperature offset is 6°
On Time is 01:00
Max Off time is 10:00
Min Off time is 01:00
When the average house temperature reached 26°, the fogger system will start to run.
The system will in a cycle time of one minute on, 20 minutes off.
For every one-degree temperature increase, the Off time will be reduced by two minutes.
At 27° the cycle time will be one minute on, 18 minutes off.
At 28° the cycle time will be one minutes on 16 minutes off.
The minimum off time will be as set in Minimum Off Time, one minute.

www.agrologic.com Page 27 of 61 [email protected]


Program version KIS179901E

Cool Pad Screen

The Cooling pads run in an On Off-cycle.

Temperature Offset
Set as a temperature offset above the required house temperature.
When reached, the cooling pad pump will start to run.
The system will run in a cycle mode as set in the On Time and Off times.

Humidity Level To Stop Cooling


Set here the maximum allow humidity for the house. If this level is passed, the cooling
system will not run.

Cooling Start / End Time


Enter here in a 24-hour time mode a time frame for the cooling systems. The systems will
operate only within this time frame.

Cool Curtain Open in Cool State


The cooling pad mode has two modes that the cool curtain can operate in.
If zero (0) is entered here, the cool air curtain will open to 100% when the cooling system is
running. No static pressure control will take place.
If one (1) is entered, the cool air curtain will operate in the static pressure mode. It will open
and close according to the static pressure reading.

www.agrologic.com Page 28 of 61 [email protected]


Program version KIS179901E

Ventilation Screens

There are 4 ventilation modes.


1. Minimum ventilation mode in which the fans work in an on-off cycle to bring in
adequate amount of air according to the number and the size of the birds and the
outside temperature. This mode occurs when the temperature in the house is close or
below the required temperature. In this mode the air comes into the house through the
dampers. The settings of this mode are done in the Minimum Ventilation screen (see
below).
2. Cross ventilation mode in which the fans work according to the temperature
difference settings. Once a fan group is added, the previous fan groups keeps on
working as well. In the Ventilation screen and air goes into the house through the
dampers. In this mode, the minimum on-off fan groups keep working.
3. Tunnel cold ventilation mode in which the fans work according to the temperature
difference settings in the Ventilation screen and air goes into the house through the
dampers or through the dampers and the cool curtains. In this mode, the minimum on-
off fan groups are turned off. The tunnel cold mode is used when it is cold outside.
4. Tunnel ventilation mode in which the fans work according to the temperature
difference settings in the Ventilation screen and air goes into the house through the
cool curtains. In this mode, the minimum on-off fan groups are turned off. This tunnel
mode is used when it is not cold outside.

Table: Summery of Ventilation Modes


Mode Name Dampers Cool Curtains Min. Vent. Fans
Minimum Opened Closed On
Cross Opened Closed On
Tunnel cold with Opened Closed Off
dampers only
Tunnel cold with Opened Opened Off
dampers and cool
curtains
Tunnel Closed Opened Off

www.agrologic.com Page 29 of 61 [email protected]


Program version KIS179901E

Temperature Stages

Temperature On
Set as an offset above the required house temperature.
When reached, the fan groups set will start to run.

Temperature Off
Set as an offset above the required house temperature.
When reached, the fan group’s set will stop running.
This offset must be set lower (closer to the required temperature) than the Temperature On
offset.

Fans 1-5
Enter here which fan group or fan groups (1-5) will run when the corresponding offset
temperature is reached.
To groups 1-5, enter 12345.

Fans 6-9
Enter here which fan group or fan groups (6-9) will run when the corresponding offset
temperature is reached.
To run groups 6,7,8 and 9, enter 6789

Fan 10
Enter 1 to operate fan 10.

Fans 11-13
Enter here 1, 2 or 3 to operate fans 11, 12 or 13.
To operate all three fan groups, enter 123

Example:
Required house temperature is 23°
Temperature On is set at 2°
Temperature Off is set at 1.5°
The fan set to run will

www.agrologic.com Page 30 of 61 [email protected]


Program version KIS179901E

Humidity Control

If there is high humidity in the house, the controller will increase the ventilation to remove
the humidity.

Humidity Level To Add Fan Stage


Enter here the maximum humidity leverl desired in the house. If the humidity level is higher
then this setting, the next fan stage will come into operation.

Humidity control to cutoff temp


This offset temperature setting is used to define when the humidity control is disabled due to
low temperature in the house. This minimum temperature level is related to the required
temperature. It will be calculated from this simple formula:
Temperature cutoff = required house temperature - Humidity control cutoff temperature.

CO2 Control

CO2 Control Setup 1 Screen

CO2 level to add fan stage


Enter here a value, which will represent the CO2 reading ( in PPM) in the house. In case the
CO2 reading in the houses reaches this level (or higher), then the next fan stage will
automatically commence action.

CO2 Margin Level


Enter here the CO2 PPM level below the set-level in which the CO2 extra fan group is turned
off.

www.agrologic.com Page 31 of 61 [email protected]


Program version KIS179901E

Example; if this set level is at 3000 PPM and the value entered here is 500 PPM, then an
extra fan group to reduce the CO2 level is turned on when the CO2 level is above 3500 PPM
and is turned off when the CO2 level drops below 2500 PPM (since 3500-500=3000).

CO2 Control Cutoff Temperature


Use this parameter to set if the CO2 control will be active when the average temperature is
less than the Required house temperature.
Example; required house temperature= 22º
CO2 Control Cutoff Temperature= 2º
The CO2 control mode will be active from 20º upwards.

CO2 Control Setup 2 Screen

CO2 Average Time


The time length in seconds that you enter here is the time length used to calculate the average
CO2 level in the house.
Example; enter here 15. The unit will record the CO2 level over 15 seconds and then
calculate the average level. The CO2 level display will be updated every 15 seconds.

Average Timer
The time remaining until the end of the CO2 average cycle.

CO2 Startup Delay


When the controller is powered on, this time setting is used before CO2 measurement starts.
This is set in minutes and seconds.

CO2 Control Enable\Disabled


Enter here "1" to enable CO2 control, "0" to disable it.

www.agrologic.com Page 32 of 61 [email protected]


Program version KIS179901E

Minimum Vention

Minimum ventilation is calculated as follows:


Current weight x Number of birds x Minimum air kg = total cubic air per hour for the house.
This is the minimum amount of hour needed for the house.
There are 3 index tables set in the controller. An index contains; fan groups and the fan
groups maximum cubic air per hour output.

Cycle Time
Cycle Time is the total time frame (minutes & seconds) for the minimum ventilation.
The on / off cycle time runs within this time frame.

Minimum On Time
Enter a minimum on time out of Cycle Time (%). This is a percentage out of the Cycle time.
The run time of the fan/fans will increase according to the calculated duty cycle. The
Minimum Fan Duty Time will be used if it's larger than the Calculated Duty Cycle

Number of Birds
Enter here the total amount of birds in the house.

Current Weight
Weight of one bird, as calculated in the Weight Gain Table. This weight is updated every day
at Reset Time. This weight can be modified if needed. If the current weight is modified, the
next day's updated weight will be recalculated using this weight.

Duty Cycle
This shows the calculated Duty cycle after calculations. The Duty cycle will be displayed in
percentage. If the calculated Duty cycle is lower than the percentage set in Min Duty, then the
value of Min Duty percentage will be used as the Duty cycle.

Index Fan Groups Fan Group air capacity


1 1 36
2 12 72
3 123 110

The controller is using these settings to calculate which Index and how long the fans should
run out of the Cycle Time to supply the minimum ventilation for the house.

www.agrologic.com Page 33 of 61 [email protected]


Program version KIS179901E

Minimum cube air kilogram screen

Use this screen to set up the minimum air per kilo required for minimum ventilation.

Outside Temperature Above and Below


These are the outside temperature used to calculate minimum ventilation.

Volume Air/Hour Per Kg


The is the amount of air per hour per kilogram used to calculate the minimum ventilation.

When the outside temperature is between the two settings the cubic air per kg will be
calculated in a linear graph.
Example:
Out temperature. Min. Air Kg
Under: 10.0° 0.8
Above: 25.0° 3.0
3.5
3
2.5
Cubic air

2 cubic air
1.5
1
0.5
0
10 25
Temp

www.agrologic.com Page 34 of 61 [email protected]


Program version KIS179901E

Current Weight Gain Table;


The weight gain table is used to program the unit with a weight increase curve which will be
used in the minimum ventilation calculation. For information about your minimum
ventilation program see the User' guide supplied with your control unit.

Use the Weight Gain Graph icon to go to the


reduction graph
Enter the weight of one chick a grow day 1
Current grow day
Current weight as calculated in the weight
gain table.
This weight can be manually changed.

It is possible to setup 10 weight increase points. Each point can be set with up to a 9.999 kilo / 22
Lbs.’ increases.
Grow Day Column
Enter here the age of the birds for the each weight increase. This is the age that the birds will
be at the end of the weight increase period.
Enter all rows not in use with the value zero.
Do not enter 0 or 1 in the first Grow day edit box

If zero is entered in any of the day column edit boxes, the weight increase will not continue.

Weight Gain Column


Enter the expected weight increase to take place by the time the chicks have reached the age
set in the corresponding Grow Day edit box.
Enter all rows not in use with the value zero.

First Day Weight


Enter here a chick's weight at day 1. This is the weight that will be set as the current weight
when Grow day 1 is entered in the Grow day field.

www.agrologic.com Page 35 of 61 [email protected]


Program version KIS179901E

Example for weight increase table.


Weights are in metric measurements.

Grow day = 1
1st day weight = 0.050

Day Weight difference Calculated weight


7 0.130 0.180
14 0.250 0.430
21 0.350 0.780

0.800
0.700
0.600
0.500
0.400
Weight
0.300
0.200
0.100
0.000
1 7 14 21

In this example the day 1 weight is set at 0.050.


Over the first 7 days there will be a gradual increase in the current weight. By the end of the
7th day the current weight will have increased to 180 grams
By the grow day 14 the current weight will have increased to 430 grams
By the grow day 21 the current weight will have increased to 780 grams

Weight increase graph

You can add, move and change the weight increase graph in the same way as the temperature
reduction table.

www.agrologic.com Page 36 of 61 [email protected]


Program version KIS179901E

Ventilation Setup

Ventilation Setup 1

Ventilation State Delay


This is set in seconds. This is the minimum length of time the controller will stay in any one
ventilation mode.

Fan Stage To Stop Minimum Ventilation


Enter here the fan stage, that when reached, the fans will stop running in minimum
ventilation mode and run-in tunnel/tunnel cold mode.

First tunnel stage fan


Enter here the fan stage, that when reached, the fans will start working in tunnel ventilation
mode.

Fan State in transition mode


Enter here 0 or 1. Enter here 1, the fans continue working in the transition state going from
one ventilation mode to the other. Enter 0 here if you would like them to be off when going
from one ventilation mode to the other.

Minimum and Initial Positions


Here you set the minimum and initial positions of the dampers and curtains. Minimum
position is set in percentage and represents the minimum opening position of the damper/cool
curtain while making their steps.
Initial position is set in percentage and represents the initial opening position of the
damper/curtain in minimum ventilation state, when the fans are off.

www.agrologic.com Page 37 of 61 [email protected]


Program version KIS179901E

Ventilation Setup 2

Tunnel Cold Ventilation


Tunnel Ventilation is the ventilation mode where the Tunnel fans are running, but do to a
cold outside temperature, the inlets remain open. The cool curtain is closed

Maximum outside temperature


Set here an absolute temperature. Tunnel cold ventilation will work only if the outside
temperature is equal or less to the figure entered here.

Stage To Open Tunnel Curtain


During Cold Tunnel Ventilation, if may be necessary to open the Tunnel curtains to lower the
static pressure in the house.
This is the ventilation stage that will open the tunnel curtain to its initial opening.
The dampers will open to the percent set in Minimum Damper Postion

Maximum Ventilation Stage


This is the last ventilation stage used while in Tunnel Cold ventilation.
When the next stage starts, the dampers will close and only the tunnel curtain will be used to
regulate the static pressure.

Minimum Damper Position


In cold tunnel ventilation, when the Stage To Open Tunnel Curtain is reached, the dampers
will automatically open to the percent set here.
If the current damper is already open to larger percent than set here, the damper will not
close, it will remain at its current position.

www.agrologic.com Page 38 of 61 [email protected]


Program version KIS179901E

Stir Fan

The stir fan will run in a cycle On Off or nonstop according to the settings.

Stir Fan On When Heater Is On


Enter 1 to allow the operation while the heating system in on.
Enter 0 to disable.

Stir Fan On In Cross Ventilation


Enter 1 to allow the operation while the controller is in cross ventilation mode.
Enter 0 to disable.

Stir Fan Operation Mode


There are two options for the stir operation temperature:

0 = stir fan will start to run when the temperature set in Operation Temperature is reached.
This temperature is taken from the temperature sensor set in Sensor Select.
This option is normally used when you have placed a temperature sensor near the ceiling and
want the stir fans to run when the temperature is high. The stir fan will help circulate the hot
air and save on heating costs.

1= This is used when you want the stir fans to run at an offset temperature above the house
required temperature.

Operation Temperature
Set here the required temperature setting, or acutal temperature or offset temperature setting.

Constant Operation Temperature Difference


Set here the number of degrees above the Operation Temperature that will cause the stir fan to run
nonstop.

Sensors Select
Enter here the sensor or sensors you would like to use for the stir fan operation.

On Time
This is the ON time for the stir fan used in the run cycle.

www.agrologic.com Page 39 of 61 [email protected]


Program version KIS179901E

Off Time
This is the OFF time for the stir fan used in the run cycle.

Setup Screens

Setup Screen 1

Set Date
Set the current date here. Press on the STAR key to bring up a calendar. Chose the correct day
and month, to store press on the ENTER key. For more information about the Date function,
refer to the Image III basic guide.

Time
Enter here the current time in a 24-hour format.

Grow Day
This is the current grow day. It is incremented every day at reset-time. When a value of 1 is
entered, the user is asked if the history and daily data should be cleared. The required
temperature and current weight receive the value entered in the first-day-temperature/weight
parameters. Note: the grow-day is not incremented at reset-time if the time hasn't pass
midnight
When the grow day is set to the day 1, the Required Temp will receive the value of 1st Day
Temp (see Temperature Reduction Table) and the Current Weight will receive the value
entered in First Day Weight

Net Name
It is possible to connect the controller to a central computer. Each controller will need a "Net
name" used to recognize it in the WebChick computer program (optional).
Example; enter 1 for the net name of the first control unit. Enter 2 for the second control and
so.

Reset Time
The controller collects all its information on a 24 hours basis. Set the time in 24-Hours format
in which the daily data is registered in history and the grow day is incremented

Screen Time
This is the length of time, set in minutes that the controller will remain in the current screen
with the backlight on. At the end of this time period the controller will return to the main

www.agrologic.com Page 40 of 61 [email protected]


Program version KIS179901E

screen and the backlight will turn off. The minimum time is 2 minutes, maximum 99
minutes.
The Screen Time is used also for the Screen saver. If the control unit is at the Main screen for
the same length of time as set for the Screen time, the screen saver mode will start. The
screen saver mode will display the current time and average house temperature.

Required Temperature
Current required house temperature.

Water Multiplier
If a water meter is connected to the controller you must set here the number of liters the meter
puts out for each pulse.
For 1 liter per pulse, enter here 1.0
For 10 liters per pulse, enter here 10.0
For 100 liters per pulse, enter here 100.0

State Delay;
Minimum time setting set in seconds that the ImageIIII will remain in the current ventilation
mode. This value prevents the controller from switching between ventilation states too
frequently.

PC Communication Setup
Use this setting to help setup speed settings between the controller and the central computer.
Please contact your dealer before making changes here.
0 = 2400 text
1= 9600 text
2= 2400 binary
3= 9600 binary
Factory default setting is 0

Versions
The information supplied here is for Agrologic technicians.

www.agrologic.com Page 41 of 61 [email protected]


Program version KIS179901E

Setup Screen 2

Average Temperature Setup


Define here which temperature sensor or sensors will be used to make up the average
temperature.
The temperature sensors used to define the average temperature are the sensors that will be
used for the ventilation and cooling systems.
Example:
Enter 1234 for the average. All four inside temperature sensors will be used to make up the
inside average temperature.

Temperature Sensors Measure Delay


Enter here 0 for very fast temperature measurement.
Use 1,2 or 3 for slower measurement.
Enter 4 for slowest measurement.

UPS Mode Setup


In certain areas the power supply may be unstable and you may want to connect the controller
to a UPS to avoid electric spikes which may damage the unit.
If a UPS is connected, the controller will not know that there is a power outage and will
continue to give out control commands. In this case it may try and move the damper or cool
curtain. Since there is no power it cannot move them, the controller will go into a Flap alarm.
If you connect a UPS you must supply the controller a dry contact that will indicate that there
is a power failure. This contact should be a closed contact that will open when there is a
power failure. Connect the dry connect to digital input 19.
When the input is open (no power, UPS working) it will not try and move the dampers or
curtain, thus avoiding the flap alarm.

UPS Mode
If a UPS backup battery is connected to the controller, enter here 9999.
Enter 0 if no UPS is connected.

Fan Groups ON In Power Outage


Enter here the fan groups that will come on when the power returns. These fans will come on
only momentarily. The controller will then turn on the fans that should be running according
to the program.

www.agrologic.com Page 42 of 61 [email protected]


Program version KIS179901E

Input Delay
Your program is using 7 digital inputs for fan groups.
This is the delay time in ¼ of seconds delays.
1= ¼ of a second. 2= ½ of a second. 3= ¾ of a second. 4= one second.
You can continue to increase the delay by ¼ of a second.

Temperature Reduction Table


The temperature reduction curve table is used to automatically reduce the house requested
temperature.

Use the Room Temperature Reduction Graph


icon to go to the reduction graph

Enter here the required 1st grow day house temperature


Enter here grow day 1 at the beginning of the flock
This is the current required house temperature as
calculated in the temperature reduction curve

It is possible to set up 10 reduction points. Each Group can be reduced up to 9.9F.

Grow Day Column


Enter here the age of the birds for a temperature reduction. This is the age that the birds will
be at the end of the first reduction period.
Enter all rows not in use with the value zero.
Do not enter the value 0 or 1 in the first Grow Day edit box.

If zero is entered in any of the day column edit boxes, the temperature reduction will not
continue.

Temperature Difference Column


Enter here the temperature reduction. This reduction will take place over the number of days
set in the Grow Day column.
Enter all rows not in use with the value zero.

Calculated temperature Column


This will display the calculated temperature reduction for each row.

Grow Day
Grow day is updated at reset time providing that midnight has passed first. If Grow day is set
to the day 1, then Required Temp will receive the value of Day 1 Temp.

First day temperature


First day temperature is the required temperature for the first day of the growing period. It is
the temperature that will appear as required temperature when Grow Day is set to 1.

When Grow Day is set to 1, it is not possible to change required temperature.

www.agrologic.com Page 43 of 61 [email protected]


Program version KIS179901E

Example for required temperature reduction table;


Temperatures are in Celsius.
Grow day = 1
1st day temperature = 32.0°

Day Temperature difference Calculated temperature


7 2.0° 30.0°
14 2.0° 28.0°
21 2.0° 26.0°

35
30
25
20
Temperature
15
10
5
0
1 7 14 21

In this example the day 1 temperature is set at 32°.


Over the first 7 days there will be a gradual decrease in the house temperature. By day 7 the
requested house temperature will have decreased to 30°
By the end of day 14 the house temperature will have decreased to 28°
By the end of day 21 the house temperature will have decreased to 26°

Room Temperature Reduction Graph

Calculated required temperature

Current cursor placement

The room temperature reduction graph displays in graphic form the temperature reduction
curve as setup in the temperature reduction table.

www.agrologic.com Page 44 of 61 [email protected]


Program version KIS179901E

Setup Screen 3 Setup Screen 4

Using these two screens, you can calibrate the different sensors.
To enter the calibration mode of the Humidity, static pressure and CO2, enter in the calibrate
mode edit box 8888.
To enter the calibration mode of the temperature sensors, enter in the calibrate mode edit box
7777.

In case there are any doubts regarding the readings of any of the sensors, it is possible to
calibrate these sensors as per the deviation from the reading in doubt, thus receiving adjusted
readings. Here you set the deviations (which can be positive or negative numbers) for the
humidity, Static pressure and CO2 sensors.

Example: The humidity reading from the humidity sensor is 45%. For some reason, you feel
that the actual humidity in the house is 5% higher than the reading of the humidity sensor.
You enter 4 in the humidity cal. Correction window and then the value 50% will appear in the
measure column ( 45% humidity reading +5% deviation).
The same goes for all other sensors.

Timer Screen

Your program has one 24-hour timer.


Enter the start and stop times for the timer.
At the start time, the timer relay will be activated. At the stop time the relay will be
deactivated.

www.agrologic.com Page 45 of 61 [email protected]


Program version KIS179901E

Daily Data Screen

The controller collects and stores certain values on a day by day basis (above photo). A ‘day’
in this regard is the 24 hours' period that starts and ends at the time entered in the parameter
Reset Time.
The data that is stored is the one that was collected over the last 490 days. All collected and
stored data can be seen in a graph and table forms.
For some values, the accumulated (also named total) values since the start of the growing
period are also calculated.

Here are the daily data screen values:


 Minimum and maximum inside and outside temperatures.
 Minimum and maximum house humidity levels.
 Minimum and maximum CO2 levels.

Alarm Screens

In this screen, you can see the current alarm type.


Use the Alarm Type 1,2 and 3 icons to go to the alarm screens.

www.agrologic.com Page 46 of 61 [email protected]


Program version KIS179901E

Alarm Screen 1

Panel Alarm (#9)


There are 4 types of panel alarms: memory alarm, battery alarm, data alarm and clock alarm.
When one or more of these panel alarms occur, the Alarms displays the number 9 and the
Panel alarm type displays which of the 4 types occurred according to this table:

Table: Panel Alarm Types

Panel Alarm Type Alarm Type Number


Memory 1
Battery 2
Data 3
Clock 5

For example, if panel alarm type Battery occurs, the Panel alarm type displays ‘2’ and if
both Battery and Clock alarms occur the Panel alarm type displays ‘25’.

Here is a description of each panel alarm type:


Memory (#1): this alarm type occurs when important parameters that are saved in the
permanent memory of the panel have been corrupted. This alarm can also occur once
after the panel screens have been replaced.

Battery (#2): this alarm occurs when the panel’s rechargeable battery is faulty and needs
replacing.

Data (#3): this alarm occurs when important parameters that are saved in the volatile
memory of the panel have been corrupted.

Clock (#5): this alarm occurs when important parameters that are saved in the volatile
memory of the panel have been corrupted.

When Memory or Data alarms occur, it means that these parameters might have been
changed:
1. Required Temperature Reduction Table parameters.
2. Weight Gain Table parameters.
3. Required temperature.
4. Current weight
5. Grow day.

www.agrologic.com Page 47 of 61 [email protected]


Program version KIS179901E

Clearing the Panel Alarms


Clearing the panel alarm can be done by entering the number of alarm type that occurred in
the Panel alarms disable. For example, to clear the Memory alarm, enter the number 1 and
to clear the Data alarm, enter the number 3. The panel alarm can also be cleared by entering
the number 9 in the parameter Alarm type 1 disable.

Disabling Panel Alarms


Out of the 4 panel alarm types, only the Battery and Clock alarms can be disabled. To
disable the Battery alarm, the number 2 must be entered in the Panel alarms disable. To
disable the Clock alarm, the number 5 must be entered in the Panel alarms disable. A
summary of the panel alarm disable options is shown in the table below.

Table: Panel Alarms Disable Options

Panel Alarm Type Can be disabled?


Memory No
Battery Yes
Data No
Clock Yes

Static Pressure Alarm Screen

There are 2 static pressure alarms: Low Pressure (#8) and High Pressure (#7). The static
pressure alarms are part of Alarm Type 1 alarms.

High Pressure Alarm


The High-Pressure alarm occurs when the measured static pressure in the house is above the
value entered in the High-pressure alarm level for duration of 30 seconds. When the alarm
occurs, all the air inlets opens to a position of 30%. To release the pressure alarm click on the
High-Pressure Alarm Exit icon.

Low Pressure Alarm


The Low-Pressure alarm occurs when the measured static pressure in the house is below the
values entered in the Low pressure alarm levels. There are 2 levels, one for tunnel
ventilation and the other for cross and minimum ventilation. The third parameter, Low-
pressure alarm delay is to set the duration in which the measured pressure has to be lower

www.agrologic.com Page 48 of 61 [email protected]


Program version KIS179901E

than the levels for the alarm to occur. The Low-pressure alarm delay timer display shows
the time that is left until the alarm occurs. The alarm is cleared automatically when the static
pressure goes above the level set in this screen. For example: with the numbers shown in the
photo above, if the ventilation state is tunnel and the measured pressure is below 0.001 inch
water for more than 01:00 mm:ss, then the alarm occurs.

Temperature Alarm Screens

Hot Alarm temp offset-day time


The parameter defines a temperature level above the required temperature. For example: if
the required temperature is 23.6 and the Hot alarm temp. is set to 12.0, the temperature level
for the alarm is 35.6. This level is shown in the Hot setpoint display. When the average
temperature is above 35.6, the alarm occurs. The alarm is automatically cleared when the
average temperature in the house goes below 35.6.

The hot alarm occurs when the temperature in the house is above the temperature level set by
the parameter Hot alarm temp offset-day time. For example: if the required temperature is
23.5° and the Hot Alarm is set to 5.0°, the temperature level for the alarm is 28.5°. This level
is shown in the Hot Setpoint display. When the average temperature is above 28.5°, the
alarm occurs. The alarm is automatically cleared when the average temperature in the house
drops below 28.5°. The settings here are valid only for day time, as we set different
settings for night time.

Night start time and end time


It is possible to define certain period as night time and for that period have a different hot
alarm temp offset. Enter here start and end times (hours), which will be considered as night
time.

Hot Alarm temp offset-night time


Enter here a temperature differential above the required temperature of the house for the time
fame you have set as night time. The alarm will go on when the temperature in the house is
above the temperature level set in this parameter.

Time period for temp change


The mechanism used in the cold alarm is also used for the hot alarms, to trigger the alarm in
case there is a sharp increase in the house temperature in a certain time. Set here time in
minutes to decide the period. If in this period, the temperature will increase in more than what
is set in the max. temp change in period, then the alarm will go on.

www.agrologic.com Page 49 of 61 [email protected]


Program version KIS179901E

Max. temp change in period


Set here the temperature increase, that if will take place in the time period we have defined,
will trigger the alarm.

Example:
Required temperature: 23.5 degrees
Time period for temp change: 3 minutes
Max temp change in period: 3 degrees

The above means that if in any period of 3 minutes the house temperature will increase by 3
degrees (or more), the alarm will be triggered and go on. In this case, if in a period of 3
minutes the house temperature will decrease to the level of 26.5 degrees, then it will trigger
the alarm.

NOTE: Hot alarm can happen in 2 of the above-mentioned scenarios. The first, is when the
house temperature reaches the offset point. The second is when there is a sharp decrease in
the house temperature in a certain period. It is possible to disable the cold alarm only if the
second scenario takes place.

Cold Alarm

Cold Alarm Temp Offset


The parameter defines a temperature level below the required temperature. For example: if
the required temperature is 23.6 and the Cold alarm temp. is set to 5.0, the temperature level
for the alarm is 18.6. This level is shown in the Cold setpoint display. When the average
temperature is below 18.6, the alarm occurs. The alarm is automatically cleared when the
average temperature in the house goes above 18.6.

Time period for temp. change


Set here time in minutes to decide the period. If in this period, the temperature will decrease
in more than what is set in the max. temp change in period, then the alarm will go on.

Max. temp change in period


Set here the temperature decrease, that if will take place in the time period we have defined,
will trigger the alarm.

Example:
Required temperature: 23.5 degrees
Time period for temp change: 2 minutes

www.agrologic.com Page 50 of 61 [email protected]


Program version KIS179901E

Max temp change in period: 3 degrees

The above means that if in any period of 2 minutes the house temperature will decrease by 3
degrees (or more), the alarm will be triggered and go on. In this case, if in a period of 2
minutes the house temperature will decrease to the level of 20.5 , then it will trigger the
alarm.

NOTE: Cold alarm can happen in 2 of the above-mentioned scenarios. The first, is when the
house temperature reaches the offset point. The second is when there is a sharp decrease in
the house temperature in a certain period. It is possible to disable the cold alarm only if the
second scenario takes place.

www.agrologic.com Page 51 of 61 [email protected]


Program version KIS179901E

Water Alarms

There are 2 water alarms: Water Overflow Alarm (#1) and Water Stoppage Alarm (#2). The
water alarms are part of the Alarm Type 2 alarms.

Water Overflow (#1)


The controller counts and stores in its memory the water consumption for 20 minute time
periods. It is constantly comparing these 20 minute time periods of today to yesterdays. If
today’s consumption is more than yesterdays plus the amount entered in at Water daily
consumption increase in 20 minutes, the alarm relay will be activated. Also, if the water
consumption over the measured 20 minutes is more than the amount set in the Water
maximum in 20 minutes, the alarm relay will be activated.
For example: with the values shown in the photo above, if the measured water consumption
yesterday between 13:00 and 13:00 was 50 Liters and today at the same time the
consumption is 80 Liters, the alarm will be activated since the increase in the water
consumption from yesterday is 30 Liters which is greater than 20 Liters (the value entered in
Water addition). If the value measured today is 130 Liters, the alarm also will be activated
because 130 is greater than 120 (the value entered in Water maximum cons. in 20 minutes).

For the first 24 hours of the growing period set the Water Addition to 0 to allow the
controller to record water consumption.

Water Stoppage (#2)


If the total water consumption over any 20 minutes is less than the value entered in Water
minimum in 20 minutes, the alarm will be activated (minimum water consumption is not
compared to yesterday's consumption and is only active when the light relay is on).

www.agrologic.com Page 52 of 61 [email protected]


Program version KIS179901E

Water Consumption Table

The water consumption table screen displays the water consumption measured in 20 minute
intervals within the last hour. The displayed information is to help learn what is the normal
consumption (in order to set the correct levels for the water alarms), and also to view what
was the unusual consumption that caused an alarm. This screen is reached from the Water
Alarms Screen by tapping on the Water Con. Table icon. The water consumption of the day
before at the same times is also displayed

CO2 Alarm

High CO2 Alarm Level


Enter the maximum CO2 level for the house. Any reading above this level will set off the
High CO2 level alarm and activate the alarm relay.

High CO2 Alarm Delay


This is a time setting in minutes and seconds used as a delay before activating the High level
CO2 alarm.

Low CO2 Alarm Level


Enter the minimum CO2 level for the house. Any reading below this level will set off the
Low CO2 level alarm and activate the alarm relay.

Low CO2 Alarm Delay


This is a time setting in minutes and seconds used as a delay before activating the Low level
CO2 alarm.

www.agrologic.com Page 53 of 61 [email protected]


Program version KIS179901E

Alarm Log Screen

This screen displays alarms and the time they occurred.


All alarms are display individually. If under the Alarm Type column you see the number 12,
that represents alarm type 2 Water Stoppage (and not Cold and Hot together).

Basic installation

Main Unit
Carefully unscrew the four screws on the front panel.

To remove the front panel completely, the flat cable connecting the front panel to the
mother board must first be disconnected. Disconnect the plug from the mother board.

Connect the box to the wall in a dry place at least 1 meter away from the main
electrical enclosure.

230V power connection


Connect the 230 VAC main unit power supply to the AC POWER connector IN
connectors.

Connect the 230VAC output AC POWER OUT to the relay box MAIN connector
connectors.

Power supply

230VAC output to relay box input

230VAC main unit power input

www.agrologic.com Page 54 of 61 [email protected]


Program version KIS179901E

Main Unit – Relay Box


Connect the shielded four wire cable (supplied) between the mother board RELAY
output connectors and the relay box relay IN input. See Mother board to Relay box
diagram below.
Always connect the shielded wire between the two GDN connectors.

Mother board relay output Relay box Relay IN


1(red wire) 1(red wire)
2(green wire) 2(green wire)
3(white wire) 3(white wire)
GND(black + shielded wire) GND(black + shielded wire)

Mother Board to Relay Box

Mother Board Relay Box

1 1 If a second Relay Box is used, connect the


second box using the Relay Out connector.
2 2 Relay Out to second box Relay IN
3 3

GND GND
Including shielded wire

Power supply to relay box


Connect a 220V cable between the mother board AC Power OUT to the relay box 230V
MAIN input. See Mother board to Relay box below.

Mother board Relay box

www.agrologic.com Page 55 of 61 [email protected]


Program version KIS179901E

Temperature sensors

Use the Temperature Sensor connectors to connect Agrologic supplied temperature sensors
only.

• Connect inside temperature sensor 1 to input 1 and AGND.


• Connect inside temperature sensor 2 to input 2 and AGND.
• Connect inside temperature sensor 3 to input 3 and AGND.
• Connect inside temperature sensor 4 to input 4 and AGND.
• Connect the outside temperature sensor to input 7 and AGND.

The sensors can be placed up to150 meters from the main unit using ordinary electrical wire.

The sensor wire has no polarity.

Temperature Sensors

Outside temperature Sensor; input 7

Inside temperature Sensor; input1

www.agrologic.com Page 56 of 61 [email protected]


Program version KIS179901E

Fast analog inputs

FS1 Current Sensor


Use the FS1 current sensor to supply digital feedback when using motors that are one phase
or cannot supply the feedback.

www.agrologic.com Page 57 of 61 [email protected]


Program version KIS179901E

8/16/24/32 modular relay box

16

8 15
14
7
13
6
55 12
11

4 10

3 9

1 2
1

2 3 4 5 6 7
7 7
1. Relay dip switches
2. Removable connectors
3. Next Box
4. Main
5. Relays In
6. Relays Out
7. Emergency

2. Removable connector's
swswticheswtiches
2. Relay dip switches
swswticheswtiches

Alarm relay
swswticheswtiches
www.agrologic.com Page 58 of 61 [email protected]
Program version KIS179901E

1. Relay dip switches


All module relay cards have dip switches which when set to an ON position, will cause the
relay to operate in an emergency situation. This may happen if there is a power failure at the
IMAGE III main unit or communications failure between the IMAGE III main control unit
and the relay box.
The bottom relay is always considered number 1 and the top relay is always number 8.

• Alarm relay
The first relay (relay number 1) is always used as an Alarm relay. When there is no alarm the
NO is closed and the NC is open. When the alarm relay is activated the NO opens and the NC
closes.

2. Removable connectors
All relay connectors are removable to help make the wiring easier.

3 4 5 6 7

3. Next Box
If there is an additional relay box to be connected, use this output to supply the box with a
240V power supply.

4. Main
Main 240V power input. Connect here the main power supply for the relay box.

5. Relays In
Connect here the 4 wire cable coming from the IMAGE III motherboard relay output
connectors.

6. Relays Out
If there is an additional relay box to be connected, use this output to connect between the two
boxes.

7. Emergency
Use this output to connect to an external control unit that can be used in the case of a failure
at the main control unit. This unit is optional

www.agrologic.com Page 59 of 61 [email protected]


Program version KIS179901E

Connection Table

www.agrologic.com Page 60 of 61 [email protected]


Program version KIS179901E

Relay Setup

www.agrologic.com Page 61 of 61 [email protected]

You might also like