Multispectrum IR Flame Detector X3301 INSTRUCTIONS
Multispectrum IR Flame Detector X3301 INSTRUCTIONS
Important
Be sure to read and understand the entire
instruction manual before installing or
operating the flame detection system. Any
deviation from the recommendations in this
manual may impair system performance
and compromise safety.
ATTENTION
The X3301 includes the Automatic o i ®
(Optical Integrity) feature — a calibrated
performance test that is automatically
performed once per minute to verify A tri-color LED on the detector faceplate indicates
complete detector operation capabilities. normal condition and notifies personnel of fire
Testing with an external test lamp is not alarm or fault conditions.
approved or required.
Microprocessor controlled heated optics increase
resistance to moisture and ice.
DESCRIPTION
The X3301 housing is available in copper-free
aluminum or stainless steel, with NEMA/Type 4X
The X3301 is a multispectrum infrared (IR) flame
and IP66/IP67 rating.
detector. It provides unsurpassed detection
of fires from light to heavy hydrocarbon fuels
Outputs
combined with the highest degree of false alarm
rejection. The detector has Division and Zone Relays
explosion-proof ratings and is suitable for use in
The standard detector is furnished with fire, fault,
indoor and outdoor applications.
and auxiliary relays. All three relays are rated 5
The X3301 contains three IR sensors with their amperes at 30 Vdc.
associated signal processing circuitry. The
The Fire Alarm relay has redundant terminals
standard output configuration includes fire, fault
and normally open / normally closed contacts,
and auxiliary relays. Output options include:
normally de-energized operation, and latching or
–– 0–20 mA output (in addition to the three non-latching operation.
relays) The Fault relay has redundant terminals and
–– Pulse output for compatibility with existing normally open contacts, normally energized
Detector Electronics Corporation (Det-Tronics) operation, and latching or non-latching operation.
controller based systems (with fire and fault
The Auxiliary relay has normally open /
relays)
normally closed contacts, and is configurable
–– Eagle Quantum Premier® (EQP) compatible for energized or de-energized operation, and
model (no analog or relay outputs) latching or non-latching operation to perform as
–– HART communication a secondary relay for fire alarm or fault. All relay
functions can be configured by using the latest
version of Inspector Monitor.
2.7 3 95-8704
General APPLICATION Background IR Sources
Information IR energy is emitted from fire as well as non-
fire sources. Because non-fire sources may in
Response Characteristics some cases emit IR energy in wavelengths that
Response is dependent on the detector's are monitored by the detector, special detector
sensitivity setting, distance, type of fuel, installation and configuration considerations
temperature of the fuel, and time required for need to be given in these situations.
the fire to come to equilibrium. As with all fire
tests, results must be interpreted according to The detector differentiates fire from non-fire sources
an individual application. by using optical filters and algorithms that analyze
the characteristics of the IR energy that is within its
See Appendix A for third-party approved fire test
field of view (FOV). Typically, non-fire IR sources do
results. Additional fire test results are available
not qualify these algorithms. However, if an object or
from Det-Tronics.
person moves between the non-fire IR source and
the detector the randomly modulated IR energy that
Important Application Considerations
is produced could mimic a fire signal.
In applying any type of sensing device as
a fire detector, it is important to know of any In order to optimize the detector’s false alarm rejection
conditions that can prevent the device from performance, it is preferred that the detectors FOV
responding to fire, and also to know what other be controlled to the area that requires flame detection
sources besides fire can cause the device to monitoring. Whenever possible, sources of intense IR
respond. emissions should be eliminated from the detector’s
FOV. Although elimination of all background IR
Welding sources may not be possible, controlling the
It is recommended that the system be detectors FOV through careful installation and aiming
bypassed during welding operations in will help to optimize the detector’s performance.
situations where the possibility of a false
alarm cannot be tolerated. Gas welding It is recommended that a flame detector that has
mandates system bypass, since the gas torch
an intense IR source within its FOV (e.g., turbine
is an actual fire. Arc welding rods can contain
enclosure, fin-fan cooler) be inhibited prior to
organic binder materials in the flux that burn
during the welding operation and are detectable personnel working on or in close proximity to the
by the X3301. Welding rods with clay binders detector. Consult the factory for software and
do not burn and will not be detected by the hardware configurations that can help mitigate
X3301. However, system bypass is always the effects of background IR sources.
recommended, since the material being welded
may be contaminated with organic substances Non-Carbon Fires
(paint, oil, etc.) that will burn and possibly cause
The X3301 is a multiple spectrum IR device
the X3301 to alarm.
with detection limited to carbonaceous fuels.
Due to the possibility of an alarm condition, It should not be used to detect fires from fuels
arc welding should not be performed within that do not contain carbon, such as hydrogen,
40 feet (12.2 m) of the detector configured sulfur, and burning metals.
to very high sensitivity, within 10 feet (3.0 m)
at medium sensitivity, within 5 feet (1.5 m) at
T-Low sensitivity, or at Low sensitivity.
Important safety notes
Artificial Lighting
The X3301 should not be located within 3 feet Warning
(0.9 m) of artificial lights. Excess heating of the Do not open the detector assembly in a
detector could occur due to heat radiating from hazardous area when power is applied.
the lights. The detector contains limited serviceable
components and should never be opened.
EMI/RFI Interference Doing so could disturb critical optical
The X3301 is resistant to interference by EMI alignment and calibration parameters,
and RFI, and is EMC Directive compliant. It will possibly causing serious damage.
not respond to a 5 watt walkie-talkie at distances
greater than 1 foot (0.3 m). Do not operate a
walkie-talkie within 1 foot (0.3 m) of the X3301.
2.7 4 95-8704
INSTALLATION
Caution
The wiring procedures in this manual are note
intended to ensure proper functioning of the The recommended lubricant for threads
device under normal conditions. However, and O-rings is a silicone-free grease (p/n
because of the many variations in wiring 005003-001) available from Det-Tronics.
codes and regulations, total compliance to Under no circumstances should a lubricant
these ordinances cannot be guaranteed. Be containing silicone be used.
certain that all wiring complies with the NEC
as well as all local ordinances. If in doubt, Detector Positioning
consult the authority having jurisdiction
before wiring the system. Installation must Detectors should be positioned to provide
be done by a properly trained person. the best unobstructed view of the area to be
protected. The following factors should also be
taken into consideration:
Caution
To prevent unwanted actuation or alarm, • Identify all high risk fire ignition sources.
extinguishing devices must be disabled prior • Be sure that enough detectors are used to
to performing system tests or maintenance. adequately cover the hazardous area.
• Be sure that the unit is easily accessible for
Caution cleaning and other periodic servicing.
The multispectrum IR flame detectors are • Verify that all detectors in the system are properly
to be installed in places where the risk of located and positioned so that any fire hazards
mechanical damage is low. are within both the Field of View (FOV) and
detection range of the detector. The Q1201C
Attention Laser Aimer is recommended for establishing the
Remove the protective cap from the front of detector's FOV. Refer to the "High Resolution Field
the detector before activating the system. of View Diagrams" section for specific information
regarding detector range and FOV.
• The detector should be aimed downward at
Attention
least 10–20 degrees to allow lens openings to
O b s e rv e p re ca u t i o n s fo r h a n d l i n g
drain. See Figure 1. The detector should be
electrostatic sensitive devices. positioned so that its FOV does not cover
areas outside the area that requires flame
detection monitoring. This will minimize the
possibility of false alarms caused by activities
outside the area requiring protection.
• The detector must be mounted on a rigid
surface in a low vibration area.
• Dense fog, rain, or ice can absorb IR radiation
and reduce the sensitivity of the detector. To
ensure optimum performance, be certain that the
internal optical heater is enabled on detectors
CENTER AXIS
OF DETECTOR
that are used in applications where snow, ice,
FIELD OF VIEW
and condensation are likely to occur.
INCORRECT
oi PLATE
PLACE MAGNET
HERE TO INITIATE
MAGNETIC oi
CENTER AXIS
OF DETECTOR
FIELD OF VIEW
VIEWING WINDOW (3)
CORRECT D1974
DETECTOR
STATUS INDICATOR
Figure 1—Detector Orientation Relative to Horizon Figure 2—Front View of the X3301
2.7 5 95-8704
• Although IR detectors are less affected by smoke according to local codes, at upper locations to
than other detectors, the X3301 should not be provide ventilation and allow water vapor to escape.
placed where rising combustion products can
Conduit raceways should be inclined so that
obscure its vision. If smoke is expected before
water will flow to low points for drainage and
fire, smoke or other alternative detectors should
will not collect inside enclosures or on conduit
be used in conjunction with the X3301. For
seals. If this is not possible, install conduit drains
indoor applications, if dense smoke is expected
above the seals to prevent the collection of water
to accumulate at the onset of a fire, install
or install a drain loop below the detector with a
the detector on a side wall at least a few feet
conduit drain at the lowest point of the loop.
(approximately 1 meter) down from the ceiling.
• If possible, fire tests can be conducted to verify Conduit seals are not required for compliance
correct detector positioning and coverage. with explosion-proof installation requirements, but
are highly recommended to prevent water ingress
• For ATEX/IECEx installations, the X3301 Flame
in outdoor applications. Units with M25 threads
Detector housing must be electrically connected
must use an IP66 washer to prevent water ingress.
to earth ground.
Wiring Procedure
Detector Orientation
Wire Size and Type
Refer to Figure 2 and ensure that the oi plate The system should be wired according to local
will be oriented as shown when the X3301 is codes. The wire size selected should be based
installed and sighted. This will ensure proper on the number of detectors connected, the supply
operation of the oi system and will also minimize voltage and the cable length. Typically 16 AWG, 2.5
the accumulation of moisture and contaminants mm2 shielded cable is recommended. Wires should
between the oi plate and the viewing windows. be stripped 3/8 inch (9 mm). A minimum input
voltage of 18 Vdc must be present at the X3301.
IMPORTANT
If removed, the oi plate must be securely note
tightened to ensure proper operation of Refer to “Power Consumption” in the
the oi system (40 oz./inches [28.2 N . cm] “Specifications” section of this manual.
recommended).
The use of shielded cable is required to protect
Protection Against Moisture Damage against interference caused by EMI and RFI.
It is important to take proper precautions during When using cables with shields, terminate
installation to ensure that moisture will not come the shields as shown in Figures 7 through 12
in contact with the electrical connections or and Figure 15. Consult the factory if not using
components of the system. The integrity of the shielded cable.
system regarding moisture protection must
be maintained for proper operation and is the In applications where the wiring cable is installed
responsibility of the installer. in conduit, the conduit must not be used for wiring
If conduit is used, we recommend installing drains, to other electrical equipment.
according to local codes, at water collection points
to automatically drain accumulated moisture. It is If disconnection of power is required, separate
also recommended to install at least one breather, disconnect capability must be provided.
4.0
(10.2)
4X ø0.42 3.0 13.1
(1.1) (7.6) (33.3)
4.0
(10.2)
10.6
(27.0)
F2069
Figure 3—Q9033 Mounting Arm without Collar Attachment Dimensions in Inches (cm)
(See Figure 1 for Correct Detector Orientation.)
2.7 6 95-8704
–– Figures 7 and 8 provide examples of
WARNING typical installations with a X3301 wired to
All entries must contain appropriately rated a fire alarm panel.
plugs or fittings. It is required that each
–– If the detector is equipped with a 0–20 mA
plug or fitting be wrench-tightened to an
output, refer to Figures 9 through 12.
appropriate installation torque and meet the
minimum thread engagement requirements
2. Check all field wiring to be sure that the
per the applicable local standards, codes,
proper connections have been made.
and practices in order to retain the defined
ratings. PTFE sealant or equivalent should
be used on NPT threads. Important
Do not test any wiring connected to the
detector with a meg-ohmmeter. Disconnect
Important wiring at the detector before checking
Devices certified for hazardous locations system wiring for continuity.
shall be installed in accordance with EN/
IEC 60079-14 and NEC 505.
3. Make the final sighting adjustments and
use a 14 mm hex wrench to ensure that the
CAUTION mounting arm assembly is tight.
Installation of the detector and wiring should
be performed only by qualified personnel.
EOL Resistors (Not Used with EQP Model)
Detector Installation To ensure that the insulating material of the
Install the mounting arm assembly on a rigid wiring terminal block will not be affected by
surface. The ideal installation surface should the heat generated by EOL resistors, observe
be free of vibration and suitable to receive 3/8 the following guidelines when installing the
inch or M10 bolts with a length of at least 1 inch resistors.
(25 mm). The surface must also have sufficient
capacity to hold the detector and mounting arm 1. Required EOL resistor power rating must be
weights (see "Specifications" section). Refer to 5 watts minimum.
the Q9033 Mounting Arm and Collar Attachment note
manual, number 95-8686, for additional installation EOL resistors must be ceramic, wirewound
information. See Figure 3 for dimensions. type, rated 5 watts minimum, with actual
power dissipation not to exceed 2.5 watts.
Relay and 0-20 mA Output Models This applies to ATEX/IECEx installations
only.
Follow the instructions below to install the
X3301.
2. Resistor leads should be cut to a length of
approximately 1 1/2 inches (40 mm).
1. Make field connections following local
ordinances and guidelines in this manual. 3. Bend the leads and install the EOL resistor
as shown in Figure 6.
–– Figure 4 shows the wiring terminal strip 4. Maintain a 3/8 inch (10 mm) minimum gap
located inside the detector’s integral between the resistor body and the terminal
junction box.
block or any other neighboring parts.
–– Figure 5 shows the wiring terminal
identification for the X3301 Flame
Detector. NOTE
The EOL resistor can only be used within the
–– Figure 6 shows an EOL resistor installed flameproof terminal compartment. Unused
within the integral wiring compartment of conduit entries shall be closed with suitable
the detector (refer to “EOL Resistors” for blanking elements.
details).
2.7 7 95-8704
Figure 4—X3301 Terminal Block
9 mA + 19 mA – 29 SPARE
E2061
19 18 17 16 15 14 13 12 11
B2126
BULKHEAD
2.7 8 95-8704
X3301 DETECTOR
FIRE ALARM PANEL
9 mA + 19 mA – SPARE 29
oi TEST 3
1 IN NORMAL OPERATION WITH NO FAULTS OCCURRING, THE FAULT RELAY COIL IS ENERGIZED AND
THE NORMALLY OPEN (NO) AND COMMON (COM) CONTACTS ARE CLOSED.
3 INDIVIDUAL MANUAL oi TEST SWITCHES CAN BE INSTALLED REMOTELY OR A DETECTOR SELECTOR AND
ACTIVATION SWITCH CAN BE INSTALLED AT THE FIRE PANEL. TEST SWITCHES ARE NOT SUPPLIED.
4 REFER TO SPECIFICATIONS SECTION FOR EOL RESISTOR VALUES. REFER TO EOL RESISTORS SECTION
FOR INSTALLATION DETAILS.
5 PROPERLY CERTIFIED HAZARDOUS LOCATION METALLIC CABLE GLANDS OR STOP PLUGS ARE
REQUIRED TO FILL ALL CONDUIT ENTRIES.
6 SHIELD MUST BE CONNECTED TO THE METALLIC CABLE GLAND. MAKE CERTAIN THAT THE INSULATION
IS REMOVED TO ENSURE ELECTRICAL CONNECTION BETWEEN THE SHIELD AND THE HOUSING.
SHIELD
X3301 DETECTOR
FIRE ALARM PANEL
9 mA + 19 mA – SPARE 29
oi TEST 3
1 IN NORMAL OPERATION WITH NO FAULTS OCCURRING, THE FAULT RELAY COIL IS ENERGIZED AND
THE NORMALLY OPEN (NO) AND COMMON (COM) CONTACTS ARE CLOSED.
3 INDIVIDUAL MANUAL oi TEST SWITCHES CAN BE INSTALLED REMOTELY OR A DETECTOR SELECTOR AND
ACTIVATION SWITCH CAN BE INSTALLED AT THE FIRE PANEL. TEST SWITCHES ARE NOT SUPPLIED.
5 PROPERLY CERTIFIED HAZARDOUS LOCATION METALLIC CABLE GLANDS OR STOP PLUGS ARE
REQUIRED TO FILL ALL CONDUIT ENTRIES.
6 SHIELD MUST BE CONNECTED TO THE METALLIC CABLE GLAND. MAKE CERTAIN THAT THE INSULATION
IS REMOVED TO ENSURE ELECTRICAL CONNECTION BETWEEN THE SHIELD AND THE HOUSING.
2.7 9 95-8704
X3301 IR DETECTOR
24 VDC
PLC – + X3301 IR DETECTOR
mA 6 NO FIRE 16 NO AUX 26
5 NC FIRE NC FIRE 15 NC AUX 25 NO FIRE
+
24 VDC 5 NC FIRE 15 25
4 14 24 NC FIRE NC AUX
–
COM FAULT COM FAULT RS485 A +
24 VDC
3 NO FAULT NO FAULT 13 RS485 B 23 4 COM FAULT COM FAULT 14 RS485 A 24
–
Oi TEST1
Oi TEST1
2.7 10 95-8704
EQP Model 5. Check all field wiring to be sure that the
proper connections have been made.
1. Connect external wires to the appropriate
terminals inside the device junction box, 6. Replace the device cover and apply input
shown in Figure 13. See Figure 14 for power.
terminal identification.
7. Make the final sighting adjustments and
2. Connect the shield of the power cable to use a 14 mm hex wrench to ensure that the
“earth ground” at the power source. mounting arm assembly is tight.
3. Connect shields for the LON cable as
NOTE
indicated. See Figure 15.
Refer to the Eagle Quantum Premier system
manual, number 95-8533, for information
NOTE
regarding power requirements, network
DO NOT ground any shields at the detector
communication cable requirements, and
housing.
configuration.
4. With input power disconnected, set the
device network address (see the “Setting
Device Network Addresses” section of this
manual for switch setting procedure).
6 SHIELD 16 SHIELD
5 COM 1 A 15 COM 2 A
4 COM 1 B 14 COM 2 B
2 +Vin 12 +Vin
1 –Vin 11 –Vin
C2089
2.7 11 95-8704
2.7
+ +
– –
– POWER –
+ DISTRIBUTION +
+
–
+ – + –
CONTROLLER EQP3700DCIO EQP2100PSM EQPX3301 EQPX3301 EQPX3301 EQPX3301
P1 P1
6 SHIELD 3 4 SHIELD 9 13 SHIELD 3 13 SHIELD 3 13 SHIELD 3 13 SHIELD 3
52 B 49 5 B 2 11 B 3 14 B 4 14 B 4 14 B 4 14 B 4
53 A 50 4 A 1 10 A 2 15 A 5 15 A 5 15 A 5 15 A 5
P6
BUS BAR P3
C 45 A2207
C 1 N
FAULT NO 46 P4 P3
B 2
NC 47 A + SUPPLY A AC LINE
P9 P8 3
B IN–/OUT+ B + –
CH 1
CH 5
GND 5 57 GND GND 54 24 VDC 4 H
C COMMON C SUPPLY
RXD 2 58 RxD B 55
TXD 3 59 TxD A 56 A + SUPPLY A
12
DB-9 H N
P2 P3
CONNECTION B IN–/OUT+ B AC LINE
CH 6
CH 2
TO COM PORT 5 1+ 5+ 13
OF PC
6 1– 5– 14 C COMMON C
+ –
7 2+ 6+ 15
A + SUPPLY A 24 VDC
8 2– 6– 16 BATTERY
B IN–/OUT+ B
CH 3
CH 7
9 3+ 7+ 17
10 3– 7– 18 C COMMON C
11 4+
DIGITAL INPUTS
8+ 19
A + SUPPLY A
12 4– 8– 20
B IN–/OUT+ B
CH 4
CH 8
P4 P5
21 C C 33 C COMMON C
22 NO NO 34
RELAY 5
RELAY 1
23 NC NC 35
24 C C 36
25 NO NO 37
RELAY 6
RELAY 2
26 NC NC 38
27 C C 39
28 NO NO 40
RELAY 7
RELAY 3
29 NC NC 41
30 C C 42
31 NO NO 43
RELAY 4
RELAY 8
32 NC NC 44
95-8704
ADDRESS SWITCHES SENSOR MODULE
REMOVED FROM HOUSING
A2191
Setting Device Network Addresses The address number is binary encoded with
(EQP Model Only) each switch having a specific binary value with
Overview of Network Addresses switch 1 being the LSB (Least Significant Bit),
see Figure 17. The device’s LON address is
Each device on the LON must be assigned a equal to the added value of all closed rocker
unique address. Addresses 1 to 4 are reserved switches. All “Open” switches are ignored.
for the controller. Valid addresses for field
devices are from 5 to 250. Example: for node No. 5, close rocker switches
1 and 3 (binary values 1 + 4); for node No. 25,
IMPORTANT close rocker switches 1, 4 and 5 (binary values
If the address is set to 0 or an address 1 + 8 + 16).
above 250, the switch setting will be
ignored. Note
The field device sets the LON address
Duplicated addresses are not automatically only when power is applied to the device.
detected. Modules given the same address Therefore, it is important to set the switches
will use the number given and report to the before applying power. If an address is
controller using that address. The status word ever changed, system power must be
will show the latest update, which could be cycled before the new address will take
from any of the reporting modules using that effect.
address.
Setting Field Device Addresses After setting address switches, record the
address number and device type.
Selection of the node address is done by
setting rocker switches on an 8 switch “DIP
Switch Assembly” within the detector’s housing.
Refer to Figure 16 for switch location.
ON
WARNING
The network address switches are located 1 2 3 4 5 6 7 8
switches. For hazardous areas, the area Figure 17—Address Switches for X3301
2.7 13 95-8704
STARTUP PROCEDURE 3. Check input power to the unit.
When installation of the equipment is complete, 4. If the fire system has a logging function,
perform the “Fire Alarm Test” below. check the fire panel log for output status
information. See Table 3 for information
Fire Alarm Test regarding 0–20 mA output.
1. Disable any extinguishing equipment that is 5. The use of the Enhanced Flame Inspector
connected to the system. cable and software from Det-Tronics can be
2. Apply input power to the system. considered to determine the nature of the
fault condition. Refer to instruction manual
3. Initiate an oi test (see “Magnetic oi / 95-8751 for more information.
Manual oi ” under "Optical Integrity" in the
"Description" section of this manual). 6. Turn off the input power to the detector and
check all wiring for continuity. Important:
4. Repeat this test for all detectors in the Disconnect wiring at the detector before
system. If a unit fails the test, refer to the checking system wiring for continuity.
“Troubleshooting” section of this manual.
7. If all wiring checks out and cleaning of
5. Verify that all detectors in the system are the oi plate/window did not correct the
properly aimed at the area to be protected. fault condition, check for high levels of
(The Q1201C Laser Aimer is recommended background IR radiation by covering the
for this purpose.) detector with the factory supplied cover
6. Enable extinguishing equipment when the or aluminum foil. If the fault condition
test is complete. clears within six minutes or less, extreme
background IR is present. Re-adjust the
view of the detector away from the IR source
or relocate the detector.
TROUBLESHOOTING
If none of these actions corrects the problem,
please contact your local Det-Tronics
Warning Representative or alternatively you may contact
The sensor module (“front” half of the Det-Tronics Technical Support by calling 1-800-
detector) contains no user serviceable 765-3473 ext 2 (M-F, 8am to 5pm CST) to obtain
components and should never be tampered assistance.
with.
NOTE
1. Disable any extinguishing equipment that is It is highly recommended that a complete
connected to the unit. spare be kept on hand for field replacement
2. Inspect the viewing windows for to ensure continuous protection.
contamination and clean as necessary. The
detector is relatively insensitive to airborne
contaminants, however, thick deposits of
ice, dirt, or oil will reduce sensitivity. (Refer
to the “Maintenance” section of this manual
for complete information regarding cleaning
of the detector viewing windows.)
Current Level
Status Action
(±0.3 mA)
0 mA Power Fault Check system wiring
1
1 mA General Fault Cycle power
2
2 mA oi Fault Clean windows
3 mA High Background IR Fault Remove IR source or aim detector away from IR source
4 mA Normal Operation
20 mA Fire Alarm
1 If fault continues, return device to factory for repair.
2 See “Maintenance” section for cleaning procedure.
NOTE: For additional troubleshooting guides, refer to the Enhanced Flame Inspector instruction manual (95-8751).
2.7 14 95-8704
MAINTENANCE LOOSEN TWO CAPTIVE SCREWS
IMPORTANT
Periodic flamepath inspections are not
recommended, since the product is not
intended to be serviced and provides
proper ingress protection to eliminate
potential deterioration of the flamepaths.
GRASP VISOR AND
Warning REMOVE oi PLATE
To avoid a potential electrostatic discharge
(ESD), the painted surface of the detector
should only be cleaned with a damp cloth.
Warning B2106
The sensor module (“front” half of the Figure 18—oi Plate Removal
detector) contains no user serviceable
components and should never be tampered Important
with. When used in extreme environments, the
Note reflective surface of the detector oi plate
Refer to the X3301 Safety manual, number may eventually deteriorate, resulting in
9 5 - 8 7 2 0 , fo r s p e c i fi c re q u i re m e n t s reoccurring oi faults and the need for oi
and recommendations applicable to plate replacement.
the proper installation, operation, and
maintenance of all SIL-Certified X3301 oi Plate Removal and Replacement
Flame Detectors.
1. Disable any extinguishing equipment that
To maintain maximum sensitivity and false alarm is connected to the unit.
resistance, the viewing windows of the X3301
must be kept relatively clean. Refer to the 2. Loosen the two captive screws, then grasp
following procedure for cleaning instructions. the oi plate by the visor and remove it from
the detector. See Figure 18.
Cleaning Procedure 3. Install the new (or cleaned) oi plate.
Important
CAUTION If oi reflector plates are interchanged, the
Disable any extinguishing equipment that is oi system must be recalibrated.
connected to the unit to prevent unwanted
actuation. Note
When installing the stainless steel plate,
To clean the windows and oi plate, use the window ensure that the gasket is present and
cleaner (p/n 001680-001) and a soft cloth, cotton correctly seated to prevent moisture or
swab, or tissue and refer to the following procedure: contaminants from penetrating behind the
plate. To ensure even seating, tighten both
1. Disable any extinguishing equipment that is screws equally.
connected to the unit.
2. Since the X3301 is less affected by 4. Recalibrate the detector's oi system. Refer
contamination than other detectors, removal to the Enhanced Flame Inspector manual,
of the oi plate is needed only under extreme number 95-8751, for instructions regarding
conditions. In addition, it is not necessary oi plate replacement and oi system
to achieve perfect cleanliness, because IR recalibration.
is not significantly absorbed by slight films
of oil and/or salt. If a fault condition is still
Caution
indicated after cleaning, remove and clean
Do not replace the o i reflector plate
the oi plate using the oi Plate Removal and
Replacement procedure. without also recalibrating the oi system.
3. Clean all three viewing windows and Recalibration of the oi system requires the use
reflector surfaces thoroughly. Use a of the Inspector Connector Cable and Inspector
cotton swab and the Det-Tronics window Monitor Software. These two items are included in
cleaning solution. Use Isopropyl alcohol for
contaminations that the Det-Tronics window the oi replacement kit, or they can be purchased
cleaning solution cannot remove. separately. See the "Ordering Information" section
for details.
2.7 15 95-8704
FEATURES
X3301 Reflector Plates
• Long detection range to carbonaceous fires
X3301 models are supplied with either a black or
a stainless steel reflector plate. These plates are • Unequaled false alarm rejection
not interchangeable. Order the replacement that • Responds to a fire in the presence of
matches the reflector plate on your X3301 Flame modulated blackbody radiation (i.e., heaters,
Detector. ovens, turbines) without false alarm
• Microprocessor controlled heated optics for
Periodic Checkout Procedure increased resistance to moisture and ice
In compliance with SIL 2, a checkout of the • Automatic, manual, or magnetic oi testing
system using the Mag oi or Man oi feature • Easily replaceable oi plate
should be performed regularly to ensure that
the system is operating properly. Refer to Table • Fire, fault, and auxiliary relays standard
1 in the X3301 Safety manual, number 95-8720, • 0–20 mA isolated output (optional)
for frequency of proof tests. To test the system, • Eagle Quantum Premier LON/SLC output
perform the “Fire Alarm Test” as described in the (optional)
“Startup Procedure” section of this manual. • HART communication (optional)
Clock Battery • FDT/DTM capable
The real time clock has a backup battery that • Multiple sensitivity levels
will operate the clock with no external power. • A tri-color LED on the detector faceplate
Return the device to the factory for battery indicates normal condition and notifies
replacement if needed. personnel of fire alarm or fault conditions
• Operates under adverse weather conditions
NOTE and in dirty environments
If the backup battery is depleted, there is no • Mounting arm allows easy sighting
effect on the operation of the flame detector,
• Integral wiring compartment for ease of
but the time stamping of the data log may
installation
be affected.
• Explosion-proof/flame-proof detector housing.
Meets FM, CSA, ATEX Directive, and IECEx
certification requirements
• Class A wiring per NFPA-72
• Meets NFPA-33 response requirement for under
0.5 second (available when model selected)
• 5 year warranty
• RFI and EMC Directive compliant
Associated Manuals
List of X3301 related manuals:
TITLE FORM NUMBER
Pulse 95-8736
EQP 95-8533
SIL 2 (Safety) 95-8720
HART Addendum 95-8577
Hangar 95-8735
Q9033 Mounting Arm
95-8686
and Collar Attachment
Enhanced Flame Inspector
software for X-Series Flame 95-8751
Detectors
Q1130 Flange Mount 95-8662
Q1201 Laser Aimer 95-8404
Q1130 Flange Mount 95-8662
Q1116 Universal Air Shield 95-8597
2.7 16 95-8704
SPECIFICATIONS CURRENT OUTPUT (Optional)—
0–20 milliampere (±0.3 mA) dc current, with a
OPERATING VOLTAGE— maximum loop resistance of 500 ohms from 18–
24 Vdc nominal (18 Vdc minimum, 30 19.9 Vdc and 600 ohms from 20–30 Vdc.
Vdc maximum). Maximum ripple is 2 volts
peak-to-peak. LON Output—
Digital communication, transformer isolated (78.5
POWER CONSUMPTION— kbps).
Without heater: 4 watts at 24 Vdc nominal;
5.2 watts at 24 Vdc in alarm. TEMPERATURE RANGE—
4.5 watts at 30 Vdc nominal; Operating: –40°F to +167°F (–40°C to +75°C).
6.5 watts at 30 Vdc in alarm. Storage: –67°F to +185°F (–55°C to +85°C).
Heater only: 8 watts maximum. Hazardous location ratings from –55°C to +125°C.
Total power: 17 watts at 30 Vdc with EOL resistor
installed and heater on maximum. HUMIDITY RANGE—
EOL resistor must be ceramic, wirewound 0–95% relative humidity, can withstand 100%
type, rated 5 watts minimum, with actual power condensing humidity for short periods of time.
dissipation not to exceed 2.5 watts.
For HART model, refer to Addendum number CONE OF VISION—
95-8577. The detector has a 90° cone of vision (horizontal)
with the highest sensitivity lying along the central
POWER UP TIME— axis. Unlike conventional detectors, the X3301
Fault indication clears after 0.5 second; device provides full coverage at a minimum of 70% of
is ready to indicate an alarm condition after 30 the maximum detection distance.
seconds.
Perfect cone of vision for methane fire detection
OUTPUT RELAYS— — 100 feet (30.5 m) on and off axis on “very high”
Fire Alarm relay, Form C, 5 amperes at 30 Vdc: setting.
The Fire Alarm relay has redundant terminals
and normally open / normally closed contacts, Refer to Appendix A for FM Approved cone of
normally de-energized operation, and latching or vision data.
non-latching operation.
Fault relay, Form A, 5 amperes at 30 Vdc: RESPONSE TIME—
The Fault relay has redundant terminals and Typical response times are under 10 seconds.
normally open contacts, normally energized Models are available that can respond to
operation, and latching or non-latching automotive paint gun fires in under 0.5 seconds.
operation. See Appendix A and the Automotive Addendum,
Auxiliary relay, Form C, 5 amperes at 30 Vdc: number 95-8534, for actual response times.
The auxiliary relay has normally open / normally
closed contacts. It is configurable for energized DIMENSIONS—
or de-energized operation and latching or non- See Figure 19.
latching operation to perform as a secondary relay
for fire alarm or fault.
4.7
(11.9)
10.0 4.8
B2067
(25.4) (12.2)
2.7 17 95-8704
ENCLOSURE MATERIAL— CERTIFICATION—
Copper-free aluminum (painted) or Stainless
Steel (316/CF8M Cast). ®
Vibration—
Conformance per FM 3260: 2000, MIL-STD VdS
810C (Curve AW), DNV Note 2.4 (Class B).
WIRING—
Field wiring screw terminals are UL/CSA rated
for up to 14 AWG wire, and are DIN/VDE rated
for 2.5 mm2 wire. Screw terminal required torque For complete approval details, refer to the
range is 3.5–4.4 in.-lbs. (0.4-0.5 N·m). appropriate appendix:
Important: 18 Vdc minimum must be available
Appendix A - FM
at the detector. For ambient temperatures below
Appendix B - CSA
–10°C (14°F) and above +60°C (140°F) use field
Appendix C - ATEX
wiring suitable for both minimum and maximum
Appendix D - IECEx
ambient temperature.
Appendix E - EN54
Thread SIZE— Appendix F - Offshore
Conduit connection: Four entries, 3/4 inch NPT or Appendix G - Additional Approvals
M25. Conduit seal not required. Appendix H - Declaration of Conformity
WARRANTY PERIOD—
5 years.
2.7 18 95-8704
Replacement parts ORDERING INFORMATION
The detector is not designed to be repaired in When ordering, please specify:
the field. If a problem should develop, refer to
X3301 Multispectrum IR Flame Detector
the "Troubleshooting" section of this manual. If it
is determined that the problem is caused by an Refer to the X3301 Model Matrix for details
electronic defect, the device must be returned to
the factory for repair. Q9033 Mounting Arm is required:
–– Q9033A for aluminum detectors only
–– Q9033B for aluminum and stainless steel
Replacement Parts LIST
detectors
Part Number Description
oi Replacement kit for X3301 (5 Black Reflector Plates)
009208-001
with Inspector Connector and Monitor Accessories
oi Replacement kit for X3301 (5 Stainless Steel Reflector
010831-001 Part Number Description
Plates) with Inspector Connector and Monitor
Replacement oi Reflector Plates for X3301 with Black plate
007307-001 103881-001 Converter RS485 to USB
(requires Inspector Connector to calibrate)
Replacement oi Reflector Plates for X3301 with Stainless W6300B1003 USB Inspector Connector
010830-001 007819-002
Steel plate (requires Inspector Connector to calibrate) (Enhanced Flame Inspector software included)
NOTE: Refer to instruction manual 95-8530 to determine the correct oi 009207-001 Enhanced Flame Inspector CD
Replacement Plate. 103922-001 Model 475 HART Communicator
102740-002 Magnet
008082-001 Magnet and Adapter for Extension Pole
007739-001 Magnet and Extension Pole
007240-001 Q1116A1001, Air Shield (AL)
007818-001 Q1118A1001 Aluminum Air Shield/Flange Mount (AL)
DEVICE REPAIR AND RETURN 007818-002
Q1118S1001 Stainless Steel Air Shield/Flange
Mount (SS)
Prior to returning devices, contact the nearest 009177-001 Q1120A1001 Paint Shield mounting ring (AL)
010857-001 Q1130A1001 Flange Mount Assembly
local Detector Electronics office so that a Return
006097-002 Q1201 Green Laser
Material Identification (RMA) number can be 102871-001 Laser Battery, 3V Lithium (laser)
assigned. A written statement describing the 007255-001 Q1201C1001 X-Series Laser Holder (AL/Plastic)
malfunction must accompany the returned 007338-001 Q2000A1001 X-Series Weather Shield (AL)
device or component to assist and expedite 007338-010 Q2033A10R X3301/X3302 FOV Limiter 10° (AL)
007338-020 Q2033A20R X3301/X3302 FOV Limiter 20° (AL)
finding the root cause of the failure.
007338-030 Q2033A30R X3301/X3302 FOV Limiter 30° (AL)
007912-010 Spare Restrictor Plate 10° (AL)
Pack the unit properly. Always use sufficient 007912-020 Spare Restrictor Plate 20° (AL)
007912-030 Spare Restrictor Plate 30° (AL)
packing material. Where applicable, use an
Q9033B Stainless Steel Mounting Arm Assembly
antistatic bag as protection from electrostatic 007290-001
is for aluminum and stainless steel detectors
discharge.
Q9033A Aluminum Mounting Arm Assembly is for
007290-002
aluminum detectors only
note 011385-001 Q9033 Collar Attachment
101197-001 Stop Plug, 3/4” NPT, AL
Det-Tronics reserves the right to apply a
101197-004 Stop Plug, 3/4” NPT, SS
service charge for repairing returned 101197-005 Stop Plug, M25, AL, IP66
product damaged as a result of improper 101197-003 Stop Plug, M25, SS, IP66
packaging. 010816-001 Stop Plug, 20 Pack, 3/4”NPT, AL
010817-001 Stop Plug, 20 Pack, 3/4”NPT, SS
010818-001 Stop Plug, 20 Pack, M25, AL, IP66
Return all equipment transportation prepaid to the 010819-001 Stop Plug, 20 Pack, M25, SS, IP66
103363-001 14 mm Hex Wrench (Steel)
factory in Minneapolis.
103406-001 Screwdriver
001680-001 Window cleaner (6 pack)
NOTE 107427-040 O-ring - Rear Cover (Viton) - black or brown
It is highly recommended that a complete 005003-001 1 oz grease for detectors (silicone-free)
spare be kept on hand for field replacement 104346-154 O-ring - Rear Cover (Fluorosilicone) - blue
to ensure continuous protection. 012549-001 1 oz PTFE silicone-free lubricant
000003-067 Stainless Steel Sun Shade
000609-026 4" Pipe Mount Bracket and U-Bolt Kit
000609-035 2" Pipe Mount U-Bolt Kit
2.7 19 95-8704
X3301 Model Matrix
MODEL DESCRIPTION
X3301 Multispectrum IR Flame Detector
TYPE MATERIAL
A Aluminum
S Stainless Steel (316)
TYPE THREAD TYPE
4M 4 Port, Metric M25
4N 4 Port, 3/4" NPT
TYPE OUTPUTS
11 Relay
13 Relay and 0-20 mA
14 Eagle Quantum Premier (EQP)
15 Relay and Pulse
16 Addressable Module Only (Third Party Type)*
21 Relay-Automotive
22 EQP Automotive
23 HART, Relay and 0-20 mA
TYPE APPROVALS**
B INMETRO (Brazil)
R VNIIPO/VNIIFTRI (Russia)
T SIL/FM/CSA/QPS***/ATEX/IECEx
W FM/CSA/QPS***/ATEX/IECEx
TYPE CLASSIFICATION
1 Division/Zone Ex d e
2 Division/Zone Ex d
*The Addressable Module Only (Type 16) is not FM approved.
**Type Approvals can use one or more letters to designate
the approvals of the product.
***QPS approval applies to output types 11, 13, 15, 21, and 23.
2.7 20 95-8704
HIGH RESOLUTION FIELD OF VIEW Diagrams
0° 0°
15° 265 (80.7) 15° 15° 70 (21.3) 15°
30° 30° 30° 30°
240 (73.1) 60 (18.3)
45° 200 (60.9) 45° 45° 50 (15.2) 45°
40 (12.1) 10 (3.0)
Field of View at Indicated Distance in Feet (m) for Field of View at Indicated Distance in Feet (m) for
n-Heptane at Very High Sensitivity (1 x 1 foot) Isopropanol at Very High Sensitivity (6 in. x 6 in.)
0° 0°
15° 100 (30.5) 15° 15° 175 (53.3) 15°
30° 90 (27.4) 30° 30° 160 (48.7) 30°
80 (24.4) 140 (42.6)
45° 45° 45° 45°
70 (21.3) 120 (36.5)
60 (18.3) 100 (30.4)
50 (15.2)
80 (24.3)
40 (12.2)
30 (9.1)
60 (18.2)
20 (6.1) 40 (12.1)
10 (3.0) 20 (6.1)
10 (3.0)
20 (6.1)
20 (6.1)
30 (9.1)
30° 40 (12.1) 30°
40 (12.2) 60 (18.2)
50 (15.2) 80 (24.3)
15° 15°
60 (18.3) 100 (30.4)
70 (21.3) 120 (36.5)
80 (24.4) 0° 0°
140 (42.6)
90 (27.4) DETECTOR VERTICAL 160 (48.7)
100 (30.5)
15° FIELD OF VIEW 15° DETECTOR VERTICAL
Field of View at Indicated Distance in Feet (m) for Field of View at Indicated Distance in Feet (m) for
n-Heptane at Very High Sensitivity (6 in. x 6 in.) Diesel at Very High Sensitivity (1 x 1 foot)
2.7 21 95-8704
High Resolution Field of View Diagrams – Continued
0°
0° 15° 40 (12.2) 15°
15° 125 (38.1) 15°
30° 120 (36.6) 30° 30° 30°
35 (10.7)
105 (32) 45° 45° 30 (9.1) 45°
45°
90 (27.4)
25 (7.6)
75 (22.9)
60 (18.3) 20 (6.1)
45 (13.7) 15 (4.6)
30 (9.1) 10 (3)
15 (4.6) 5 (1.5)
15 (4.6) 5 (1.5)
30 (9.1) 30°
10 (3) 30°
45 (13.7)
15 (4.6)
60 (18.3) 15°
75 (22.9) 20 (6.1) 15°
90 (27.4) 25 (7.6)
0°
105 (32) 30 (9.1) 0°
120 (36.6) 15° DETECTOR VERTICAL
35 (10.7)
FIELD OF VIEW DETECTOR VERTICAL
125 (38.1) 30° WITH DETECTOR AT
15° FIELD OF VIEW
45° 40 (12.2) WITH DETECTOR AT
45° FROM HORIZONTAL. 30°
45° 45° FROM HORIZONTAL.
Field of View at Indicated Distance in Feet (m) for Field of View at Indicated Distance in Feet (m) for
Propane at Very High Sensitivity (32 inch plume) Methanol at Very High Sensitivity (6 in. x 6 in.)
0° 0°
15° 210 (64) 15° 15° 150 (45.7) 15°
30° 30° 30° 135 (41.2 30°
180 (54.9)
120 (36.5)
45° 150 (45.7) 45° 45° 45°
105 (32)
120 (36.5) 90 (27.4)
75 (22.9)
90 (27.4)
60 (18.3)
60 (18.3) 45 (13.7)
30 (9.1)
30 (9.1)
15 (4.6)
30 (9.1)
15 (4.6)
60 (18.3) 30° 30 (9.1) 30°
90 (27.4) 45 (13.7)
60 (18.3)
120 (36.5) 15°
75 (22.9) 15°
150 (45.7) 90 (27.4)
0° 105 (32)
180 (54.9) 0°
DETECTOR VERTICAL 120 (36.5)
15° FIELD OF VIEW
210 (64) 135 (41.2 15° DETECTOR VERTICAL
30° WITH DETECTOR AT FIELD OF VIEW
45° 45° FROM HORIZONTAL. 150 (45.7)
30° WITH DETECTOR AT
45° 45° FROM HORIZONTAL.
Field of View at Indicated Distance in Feet (m) for Field of View at Indicated Distance in Feet (m) for
Ethanol at Very High Sensitivity (1 x 1 foot) Methanol at Very High Sensitivity (1 x 1 foot)
2.7 22 95-8704
High Resolution Field of View Diagrams – Continued
0° 0°
15° 15° 15°
125 (38.1) 15° 235 (71.6)
30° 100 (30.5) 30°
30° 210 (64) 30°
45° 90 (27.4) 45°
80 (24.4) 45° 180 (54.9)
45°
70 (21.3) 150 (45.7)
60 (18.3)
120 (36.5)
50 (15.2)
40 (12.2) 90 (27.4)
30 (9.1)
60 (18.3)
20 (6.1)
10 (3) 30 (9.1)
10 (3)
30 (9.1)
20 (6.1)
30 (9.1) 30° 60 (18.3) 30°
40 (12.2) 90 (27.4)
50 (15.2)
60 (18.3) 15° 120 (36.5) 15°
70 (21.3) 150 (45.7)
80 (24.4) 0° 180 (54.9) 0°
90 (27.4) DETECTOR VERTICAL
100 (30.5) 15° FIELD OF VIEW 210 (64.0) 15° DETECTOR VERTICAL
WITH DETECTOR AT FIELD OF VIEW
125 (38.1) 235 (71.6)
30° 45° FROM HORIZONTAL. 30° WITH DETECTOR AT
45° 45° 45° FROM HORIZONTAL.
Field of View at Indicated Distance in Feet (m) for Field of View at Indicated Distance in Feet (m) for
Methane at Very High Sensitivity (32 inch plume) JP-5 at Very High Sensitivity (2 x 2 feet)
2.7 23 95-8704
High Resolution Field of View Diagrams – Continued
0° 0°
15° 100 (30.5) 15° 15° 70 (21.3) 15°
30° 30° 30° 30°
90 (27.4) 60 (18.3)
80 (24.4)
45° 45° 45° 50 (15.2) 45°
70 (21.3)
60 (18.3) 40 (12.2)
50 (15.2)
30 (9.1)
40 (12.2)
30 (9.1) 20 (6.1)
20 (6.1)
10 (3)
10 (3)
Field of View at Indicated Distance in Feet (m) for Field of View at Indicated Distance in Feet (m) for
n-Heptane at Medium Sensitivity (1 x 1 foot) Methanol at Medium Sensitivity (1 x 1 foot)
0° 0°
15° 70 (21.3) 15° 15° 15°
70 (21.3)
30° 30° 30° 30°
60 (18.3) 60 (18.3)
45° 50 (15.2) 45° 45° 50 (15.2) 45°
40 (12.2) 40 (12.2)
30 (9.1) 30 (9.1)
20 (6.1) 20 (6.1)
10 (3) 10 (3)
Field of View at Indicated Distance in Feet (m) for Field of View at Indicated Distance in Feet (m) for
Diesel at Medium Sensitivity (1 x 1 foot) Methane at Medium Sensitivity (32 inch plume)
0° 0°
15° 85 (25.9) 15° 15° 150 (45.7) 15°
30° 80 (24.4) 30° 30° 135 (41.2 30°
75 (22.9) 120 (36.5)
45° 45° 45° 45°
65 (19.8) 105 (32)
55 (16.8) 90 (27.4)
45 (13.7) 75 (22.9)
35 (10.7) 60 (18.3)
25 (7.6) 45 (13.7)
15 (4.6) 30 (9.1)
5 (1.5) 15 (4.6)
Field of View at Indicated Distance in Feet (m) for Field of View at Indicated Distance in Feet (m) for
Ethanol at Medium Sensitivity (1 x 1 foot) JP-5 at Medium Sensitivity (2 x 2 feet)
0°
15° 75 (22.8) 15°
30° 70 (21.3) 30°
60 (18.3)
45° 45°
50 (15.2)
40 (12.2)
30 (9.1)
20 (6.1)
10 (3)
• Explosion-proof for Class I, Div. 1, Groups B, C, and D (T4A) Hazardous (Classified) Locations per FM 3615.
• Dust-ignition proof for Class II/III, Div. 1, Groups E, F, and G (T4A) Hazardous (Classified) Locations per FM 3615.
• Nonincendive for Class I, Div. 2, Groups A, B, C, and D (T3C) Hazardous (Classified) Locations per FM
3611.
• Nonincendive for Class II, Div. 2, Groups F and G (T3C) Hazardous (Classified) Locations per FM 3611.
• Enclosure rating NEMA/Type 4X per NEMA 250.
• Ambient Temperature Limits: –40°F to +167°F (–40°C to +75°C).
• Automatic Fire Alarm Signaling Performance verified per FM 3260 (2000).
Flameproof per ANSI/ISA 60079-0, -1, -7, -31
Class I, Zone 1, AEx db eb IIC T6...T5
T6 (Tamb –40°C to +60°C)
T5 (Tamb –40°C to +75°C)
Zone 21, AEx tb IIIC T130°C
Tamb –40°C to +75°C
IP66
The following accessories are FM approved for use with the X3301 Flame Detector:
2.7 25 95-8704
FM Approval and Performance Report – Continued
RESPONSE CHARACTERISTICS
Medium Sensitivity
2.7 26 95-8704
FM Approval and Performance Report – Continued
T-Low Sensitivity
Low Sensitivity
2.7 27 95-8704
FM Approval and Performance Report – Continued
Medium Sensitivity
2.7 28 95-8704
FM Approval and Performance Report – Continued
T-Low Sensitivity
Low Sensitivity
2.7 29 95-8704
FM Approval and Performance Report – Continued
Distance
False Alarm Source Modulated Response Unmodulated Response
feet (m)
Sunlight, direct, reflected — No alarm No alarm
Vibration N/A No alarm N/A
Radio frequency interference 1 (0.3) No alarm (keyed) No alarm (steady)
Arc welding 40 (12.2) No alarm No alarm
LED Lamp 5 (1.5) No alarm No alarm
70 w sodium vapor lamp 3 (0.9) No alarm No alarm
250 w vapor lamp 3 (0.9) No alarm No alarm
300 w incandescent lamp 3 (0.9) No alarm No alarm
500 w unshielded quartz halogen lamp 8 (2.4) No alarm No alarm
500 w shielded quartz halogen lamp 8 (2.4) No alarm No alarm
1500 w electric radiant heater 3 (0.9) No alarm No alarm
Two 34 w fluorescent lamps 5 (1.5) No alarm No alarm
Medium Sensitivity
Distance
False Alarm Source Modulated Response Unmodulated Response
feet (m)
Sunlight, direct, reflected — No alarm No alarm
Vibration N/A No alarm N/A
Radio frequency interference 1 (0.3) No alarm (keyed) No alarm (steady)
Arc welding 10 (3) No alarm No alarm
LED Lamp 3 (0.9) No alarm No alarm
70 w sodium vapor lamp 3 (0.9) No alarm No alarm
250 w vapor lamp 3 (0.9) No alarm No alarm
300 w incandescent lamp 3 (0.9) No alarm No alarm
500 w unshielded quartz halogen lamp 3 (0.9) No alarm No alarm
500 w shielded quartz halogen lamp 3 (0.9) No alarm No alarm
1500 w electric radiant heater 3 (0.9) No alarm No alarm
Two 34 w fluorescent lamps 3 (0.9) No alarm No alarm
T-Low Sensitivity
Distance
False Alarm Source Modulated Response Unmodulated Response
feet (m)
Sunlight, direct, reflected — No alarm No alarm
Vibration N/A No alarm No alarm
Arc welding 5 (1.5) No alarm No alarm
LED Lamp 3 (0.9) No alarm No alarm
70 w sodium vapor 3 (0.9) No alarm No alarm
250 w vapor lamp 3 (0.9) No alarm No alarm
300 w incandescent lamp 3 (0.9) No alarm No alarm
500 w shielded quartz halogen lamp 3 (0.9) No alarm No alarm
500 w unshielded quartz halogen lamp 3 (0.9) No alarm No alarm
1500 w electric radiant heater 3 (0.9) No alarm No alarm
Two 34 w fluorescent lamps 3 (0.9) No alarm No alarm
2.7 30 95-8704
FM Approval and Performance Report – Continued
Low Sensitivity
Distance Modulated
False Alarm Source Unmodulated Response
feet (m) Response
Sunlight, direct, reflected — No alarm No alarm
Vibration N/A No alarm No alarm
Radio frequency interference — No alarm N/A
Arc welding 5 (1.5) No alarm No alarm
LED Lamp 3 (0.9) No alarm No alarm
70 w sodium vapor lamp 3 (0.9) No alarm No alarm
250 w vapor lamp 3 (0.9) No alarm No alarm
300 w incandescent lamp 3 (0.9) No alarm No alarm
500 w shielded quartz halogen lamp 3 (0.9) No alarm No alarm
500 w unshielded quartz halogen lamp 3 (0.9) No alarm No alarm
1500 w electric radiant heater 3 (0.9) No alarm No alarm
Two 34 w fluorescent lamps 3 (0.9) No alarm No alarm
FIELD of view
Distance Horizontal Avg. Resp Vertical Avg. Resp Vertical Avg. Resp
Fuel Size
feet (m) L, R (°) Time (s)*** Down (°) Time (s)*** Up (°) Time (s)***
1 x 1 foot 190 (57.9) +/– 45 11 +45 11 –30 8
1 x 1 foot 180 (54.9) +/– 45 8 +45 11 –30 3
n-Heptane 1 x 1 foot 180 (54.9) +/– 45 6** +45 6** –30 3**
1 x 1 foot 100 (30.5) +/– 45 4 +45 3 –30 2
6 x 6 inches 100 (30.5) +/– 45 11 +45 11 –30 7
Gasoline 1 x 1 foot 190 (57.9) +/– 45 7 +45 9 –30 5
Kerosene 1 x 1 foot 110 (33.5) +/– 45 5 +45 5 –30 4
Isopropanol 6 x 6 inches 70 (21.3) +/– 45 8 +45 6 –30 5
Diesel 1 x 1 foot 150 (45.7) +/– 45 10** +45 7** –30 7**
Ethanol 1 x 1 foot 150 (45.7) +/– 45 15 +45 13 –30 10
6 x 6 inches 40 (12.2) +/– 45 3 +45 3 –30 2
Methanol 1 x 1 foot 110 (33.5) +/– 45 8 +45 13 –30 3
1 x 1 foot 110 (33.5) +/– 45 8** +45 4** –30 3**
Xylene 1 x 1 foot 150 (45.7) +/– 45 7** +45 6** –30 3**
Toluene 1 x 1 foot 150 (45.7) +/– 45 8** +45 8** –30 4**
Methane 32 inch plume 100 (30.5) +/– 45 7 +45 8 –30 4
Propane 32 inch plume 90 (27.4) +/– 45 7 +45 9 –30 5
Ethane 32 inch plume 90 (27.4) +/– 45 5 +45 6 –30 3
Ethylene 32 inch plume 90 (27.4) +/– 45 7 +45 9 –30 5
Butane 32 inch plume 90 (27.4) +/– 45 5 +45 4 –30 2
Jet A 1 x 1 foot 100 (30.5) +/– 45 4** +45 3** –30 2**
JP-5 2 x 2 feet 180 (54.9) +/– 45 6** +45 4** –30 2**
JP-8 1 x 1 foot 100 (30.5) +/– 45 5** +45 5** –30 3**
Class A Ø12 in. x 7 in. 80 (24.4) +/– 45 4** +45 2** –30 2**
* Outdoor test condition
** Pre-burn from ignition
*** Add 2 seconds for EQP model
Ø Diameter
2.7 31 95-8704
FM Approval and Performance Report – Continued
Medium Sensitivity
Distance Horizontal Avg. Resp Vertical Avg. Resp Vertical Avg. Resp
Fuel Size
feet (m) L, R (°) Time (s)*** Down (°) Time (s)*** Up (°) Time (s)***
1 x 1 foot 75 (22.9) +/– 45 5 +45 4 –30 5
n-Heptane
1 x 1 foot 50 (15.2) +/– 45 3 +45 2 –30 3
Isopropanol 6 x 6 inches 45 (13.7) +/– 45 11 +45 8 –30 6
Diesel 1 x 1 foot 60 (18.2) +/– 45 4** +45 6** –30 4**
Ethanol 1 x 1 foot 60 (18.2) +/– 45 7 +45 8 –30 5
Methanol 1 x 1 foot 50 (15.2) +/– 45 5 +45 2 –30 6
Methane 32 inch plume 50 (15.2) +/– 45 5 +45 6 –30 3
Propane 32 inch plume 55 (16.7) +/– 45 5 +45 4 –30 5
Ethane 32 inch plume 55 (16.7) +/– 45 6 +45 5 –30 5
Ethylene 32 inch plume 55 (16.7) +/– 45 7 +45 5 –30 5
Butane 32 inch plume 55 (16.7) +/– 45 6 +45 4 –30 3
JP-5 2 x 2 feet 110 (33.5) +/– 45 7** +45 4** –30 5**
Class A Ø12 in. x 7 in. 40 (12.2) +/– 45 3** +45 3** –30 3**
** Pre-burn from ignition
*** Add 2 seconds for EQP model
Ø Diameter
T-Low Sensitivity
Distance Horizontal Avg. Resp Vertical Avg. Resp Vertical Avg. Resp
Fuel Size
feet (m) L, R (°) Time (s)*** Down (°) Time (s)*** Up (°) Time (s)***
n-Heptane 1 x 1 foot 35 (10.7) +/– 45 4 +45 4 –30 3
Methanol 1 x 1 foot 20 (6.1) +/– 45 4 +45 4 –30 2
Methane 32 inch plume 20 (6.1) +/– 45 4 +45 4 –30 4
Propane 32 inch plume 20 (6.1) +/– 45 4 +45 4 –30 5
*** Add 2 seconds for EQP model.
Low Sensitivity
Distance Horizontal Avg. Resp Vertical Avg. Resp Vertical Avg. Resp
Fuel Size
feet (m) L, R (°) Time (s)*** Down (°) Time (s)*** Up (°) Time (s)***
n-Heptane 1 x 1 foot 35 (10.7) +/– 45 8 +45 9 –30 10
Methanol 1 x 1 foot 20 (6.1) +/– 45 9 +45 9 –30 9
Methane 32 inch plume 20 (6.1) +/– 45 9 +45 9 –30 8
Propane 32 inch plume 20 (6.1) +/– 45 9 +45 9 –30 11
*** Add 2 seconds for EQP model.
2.7 32 95-8704
APPENDIX B
CSA Approval
DIVISION CLASSIFICATION:
Multispectrum IR Flame Detector/Controller X3301 Series, rated 18–30 Vdc, 4.6–17 Watts.
Relay contacts rated 30 Vdc, 5 Amps.
APPLICABLE REQUIREMENTS
CAN/CSA-C22.2 No. 0-M91 – General Requirements — Canadian Electrical Code, Part II
CAN/CSA-C22.2 No. 25-1966 – Enclosures for use in Class II Groups E, F, and G Hazardous Locations
CAN/CSA-C22.2 No. 30-M1986 – Explosion-Proof Enclosures for use in Class I Hazardous Locations
CAN/CSA-C22.2 No. 94-M91 – Special Purpose Enclosures
CAN/CSA-C22.2 No. 142-M1987 – Process Control Equipment
CAN/CSA-C22.2 No. 213-M1987 – Nonincendive Electrical Equipment for use in Class I, Division 2 Hazardous Locations
ZONE CLASSIFICATION:
CLASS 4818 04 - SIGNAL APPLIANCES - Systems - For Hazardous Locations
Ex db eb IIC T6...T5
T6 (Tamb = -50oC to +60oC)
T5 (Tamb = -50oC to +75oC)
Ex tb IIIC T130oC
(Tamb = -50oC to +75oC)
Seal required adjacent to enclosure
IP66
Ex db IIC T6...T5
T6 (Ta -55oC to +60oC)
T5 (Ta -55oC to +75oC)
Seal required adjacent to enclosure
IP66/IP67
APPLICABLE REQUIREMENTS
CAN/CSA-C22.2 No. 60079-0:2015 – Electrical apparatus for explosive gas atmospheres. Part 0: General requirements
CAN/CSA-C22.2 No. 60079-1:2016 – Explosive atmospheres. Part 1: Equipment protection by flameproof enclosures "d"
CAN/CSA-C22.2 No. 60079-7:2012 – Explosive atmospheres. Part 7: Equipment protection by increased safety "e"
CAN/CSA-C22.2 No. 60079-31:2015 – Explosive atmospheres. Part 31: Equipment dust ignition protection by enclosure "t"
The following accessories are CSA approved for use with the X3301 Flame Detector:
2.7 33 95-8704
APPENDIX C
ATEX Approval
Compliance with:
EN 60079-0: 2012+A11:2013
EN 60079-1: 2014
EN 60079-7: 2015
EN 60079-31: 2014
EN 60529: 1991+A1:2000+A2:2013
Installation instructions
The field wiring connections in the terminal compartment are ATEX certified and accepts wiring
specifications from 14-24 AWG, 2.5-0.2 mm2.
The Multispectrum infrared (IR) flame detector type X3301 shall be installed according to the instructions given
by the manufacturer.
The cable entry devices shall be certified in type of explosion protection flameproof enclosure "d" for use with
the terminal compartment in type of explosion protection flameproof enclosure "d," or in type of explosion
protection increased safety "e" for use with the terminal compartment in type of explosion protection increased
safety "e." They shall be IP66 rated, suitable for the conditions of use and correctly installed.
The metal housing for the Multispectrum infrared (IR) flame detector type X3301 must be electrically connected
to earth ground.
For ambient temperatures below –10°C and above +60°C use field wiring suitable for both minimum and
maximum ambient temperature.
2.7 34 95-8704
NOTE
Operational performance verified from –40°C to +75°C.
Note
An optional third party addressable module can only be used within the Ex d flameproof
model unless the addressable module is component certified as Ex e for use within the Ex d e
increased safety model.
NOTE
Refer to the “EOL Resistors” section of this manual for installation details. All cable entry
devices and blanking elements shall be certified to “E-generation” or “ATEX” standards, in
type of explosion protection increased safety “e” or flameproof enclosure “d” (as applicable),
suitable for the conditions of use and correctly installed. They shall maintain the degree of
ingress protection IP66 for the apparatus. Unused conduit entries shall be closed with suitable
blanking elements.
Note
For ATEX installations, the X3301 Flame Detector housing must be electrically connected to earth
ground.
The following accessories are ATEX approved for use with the X3301 Flame Detector:
2.7 35 95-8704
APPENDIX D
IECEx Approval
Certificate of Conformity
Compliance with:
IEC 60079-0: 2011, ed. 6
IEC 60079-1: 2014, ed. 7
IEC 60079-7: 2015, ed. 5
IEC 60079-31: 2013, ed. 2
IEC 60529: 2013, Ed. 2.2
Installation instructions
The field wiring connections in the terminal compartment are suitable certified and accepts wiring
specifications from 14-24 AWG, 2.5-0.2 mm2.
The Multispectrum infrared (IR) flame detector type X3301 shall be installed according to the instructions given
by the manufacturer.
The cable entry devices shall be certified in type of explosion protection flameproof enclosure "d" for use
with the terminal compartment in type of explosion protection flameproof enclosure "d" or in type of explosion
protection increased safety "e" for use with the terminal compartment in type of explosion protection increased
safety "e." They shall be IP66 rated, suitable for the conditions of use and correctly installed.
Unused entries shall be closed with suitable certified blanking elements.
The metal housing for the Multispectrum infrared (IR) flame detector type X3301 must be electrically connected
to earth ground.
For ambient temperatures below –10°C and above +60°C use field wiring suitable for both minimum and
maximum ambient temperature.
The following accessories are IECEx approved for use with the X3301 Flame Detector:
2.7 36 95-8704
APPENDIX E
EN54 Approvals
The following accessories are EN54-10, EN54-13, and EN54-17 approved for use with the X3301 Flame Detector:
Part Number Description
102740-002 Magnet
007739-001 Magnet and Extension Pole
007290-001 Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors
007290-002 Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only
011385-001 Q9033 Collar Attachment
2.7 37 95-8704
APPENDIX F
Offshore Approvals
USCG APPROVAL
Coast Guard Approval No. 161.002/49/0
The scope of this approval is for a fire detection system meeting 46 CFR 161.002, as part of the Eagle Quantum Premier System.
MARINE EQUIPMENT DIRECTIVE
DNV Certificate No. MED-B-9427
Is found to comply with the requirements in the following Regulations / Standards:
Annex A.1, item No. A.1/3.51 and Annex B, Module B in the Directive. SOLAS 74 as amended, Regulation II-2/7 & X/3,
2000 HSC Code 7, FSS Code 9 and IMO MSC.1/Circ. 1242.
The equipment are found to comply with following location / application dependent requirements
(for definition of each of the location classes, see below the table):
MODEL TEMPERATURE VIBRATION EMC ENCLOSURE
X3301 TEM-D VIB-B EMC-B ENC-C
The following accessories are offshore approved to the listed approvals, for use with the X3301 Flame Detector:
2.7 38 95-8704
APPENDIX G
Additional Approvals
SIL 2 CANADA
QPS
IEC 61508
Certified SIL 2 Capable.
Applies to specific models – refer to the SIL 2 Certified ULC/ORD-C386:2015 - Flame Detector
X3301 Safety manual (95-8720) for details. Flame detectors meeting these requirements must be
employed in accordance with appropriate parts of the
following:
–– CAN/ULC-S524, the Standard for Installation of Fire
RUSSIA & KAZAKHSTAN
Alarm Systems
–– CSA-C22.1, Canadian Electrical Code, Part 1, Safety
Standard for Electrical
VNIIFTRI ULC S529-09, edition: 3rd. Smoke detector for Fire Alarm
Certificate of Conformity to "TP TC System
012/2011" This Standard covers relevant requirements in accordance
No TC RU C-US. ГБ06.B.00418 with the following:
–– In the United States: NFPA 72 (National Fire Alarm
2ExdeIICT6/T5 IP66 Code)
T6 (Tamb = –50°C to +60°C) –– In Canada: CAN/ULC-S524 (Installation of Fire Alarm
T5 (Tamb = –50°C to +75°C) Systems); National Building Code of Canada; and
Ex tb IIIC T130°C Db. National Fire Code of Canada.
– OR –
1ExdIICT6/T5/T4 IP66
T6 (Tamb = –55°C to +60°C)
T5 (Tamb = –55°C to +75°C)
T4 (Tamb = –55°C to +125°C)
Ex tb IIIC T130°C Db.
RUSSIA
VNIIPO
CERTIFICATE OF CONFORMITY TO TECHNICAL
REGULATIONS, GOST R 53325-2012
C-US.ПБ01.B.02910
BRAZIL
UL-BR 12.0093X
Ex db eb IIC T6...T5
Ex tb IIIC T130°C
T6 (Tamb = –50°C to +60°C)
T5 (Tamb = –50°C to +75°C)
IP66
– OR –
Ex db IIC T6...T4
T6 (Tamb = –55°C to +60°C)
T5 (Tamb = –55°C to +75°C)
T4 (Tamb = –55°C to +125°C)
IP66/IP67
2.7 39 95-8704
APPENDIX H
DECLARATION OF CONFORMITY
(XURSHDQ8QLRQ
>@
'HFODUDWLRQRI&RQIRUPLW\
7KLVGHFODUDWLRQRIFRQIRUPLW\LVLVVXHGXQGHUWKHVROHUHVSRQVLELOLW\RIWKHPDQXIDFWXUHU
>@ ,WLVGHFODUHGWKDWWKHIROORZLQJHTXLSPHQW
0RGHO;6HULHV 0XOWLVSHFWUXP,QIUDUHG)ODPH'HWHFWRU
'RFXPHQWUHIHUHQFHQXPEHU'(&
>@ 0DQXIDFWXUHGE\
'HWHFWRU(OHFWURQLFV&RUSRUDWLRQ 'HW7URQLFV
WK
:HVW 6WUHHW
0LQQHDSROLV0186$
>@ ,VLQFRQIRUPLW\ZLWKWKH(VVHQWLDO+HDOWKDQG6DIHW\5HTXLUHPHQWDQGWKHUHOHYDQW8QLRQKDUPRQLVDWLRQOHJLVODWLRQ
E\FRPSO\LQJZLWK
WK
$7(;'LUHFWLYH(& XQWLO$SULO (1$
WK
(8 IURP$SULO (1
&HUWLILFDWH1R'(0.2$7(;; (1
(1
(1$$
WK
(0&'LUHFWLYH(& XQWLO$SULO (1
WK
(8 IURP$SULO (1
(1$
(1
WK
/RZ9ROWDJH'LUHFWLYH(& XQWLO$SULO (1
WK
(8 IURP$SULO
:((('LUHFWLYH(&
0DULQH(TXLSPHQW'LUHFWLYH(& $QQH[$LWHP1R$DQG$QQH[
&HUWLILFDWH1R 0('% %0RGXOH%LQWKHGLUHFWLYH62/$6
&HUWLILFDWH1R 0('' 5HJXODWLRQ,, ;+6&&RGH
)66&RGH ,0206&&LUF
&RQVWUXFWLRQ3URGXFWV5HJXODWLRQ (8 (1$
&HUWLILFDWH1R &35 9G6 (1$&
&HUWLILFDWH1R &35) %5( $SSOLFDEOHWR(430RGHO V 2QO\
>@ 3URGXFWLRQ4$1,VVXHGE\
8/,QWHUQDWLRQDO'(0.2$61%1R
%RUXSYDQJ$%DOOHUXS'HQPDUN
>@ 7KH0DUNLQJRIWKHHTXLSPHQWRUSURWHFWLYHV\VWHPVKDOOLQFOXGHWKHIROORZLQJ
,,*([GEHE,,&7«7,3
,,*([GE,,&7«7,3,3
,,'([WE,,,&7&,3
>@ :HWKHXQGHUVLJQHGKHUHE\GHFODUHWKDWWKHHTXLSPHQWVSHFLILHGDERYHFRQIRUPVWRWKHDIRUHPHQWLRQHG8QLRQ
KDUPRQLVDWLRQOHJLVODWLRQDQGKDUPRQLVHG6WDQGDUG V IRU&(&RQIRUPLW\0DUNLQJ
$SSURYDOV(QJLQHHULQJ0DQDJHU 2SHUDWLRQV0DQDJHU
-RQ0LOOHU 6DOO\'D\
6LJQDWXUH 6LJQDWXUH
'DWHRI,VVXH 'DWHRI,VVXH
'HWHFWRU(OHFWURQLFV&RUSRUDWLRQ 'HWHFWRU(OHFWURQLFV8./WG_0DWKLVHQ:D\3R\OH5RDG
:HVWWK6WUHHW_0LQQHDSROLV0186$ &ROQEURRN6ORXJK_%HUNVKLUH6/2+%8QLWHG.LQJGRP
3KRQH 3KRQH
:HVWWK6WUHHW0LQQHDSROLV0186$ 3DJHRI
7ROO)UHH_)D[_ZZZGHWWURQLFVFRP '(&
2.7 40 95-8704
95-8704
FlexSonic ® Acoustic X3301 Multispectrum PointWatch Eclipse ® IR FlexVu ® Universal Display Eagle Quantum Premier ®
Leak Detector IR Flame Detector Combustible Gas Detector with GT3000 Toxic Gas Detector Safety System