0% found this document useful (0 votes)
24 views2 pages

Cooling Calculator, 100mm, 50T, 5 Days, 20% Per Day, Inlet - 3

This document summarizes the specifications of a modular cold room for storing frozen fish at -45°C. Key details include inner dimensions of 9m x 6m x 2m, a storage capacity of 49896 kg of frozen fish stored as spheres with 0.25kg weight. The cold room uses injected polyurethane insulation on walls, roof and floor that is 100mm thick. It requires a cooling capacity of 19,141W to maintain -45°C temperature over 24 hours while accounting for heat transfer through insulation, air renewal and product thermal loads.

Uploaded by

ABDULLAH
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
24 views2 pages

Cooling Calculator, 100mm, 50T, 5 Days, 20% Per Day, Inlet - 3

This document summarizes the specifications of a modular cold room for storing frozen fish at -45°C. Key details include inner dimensions of 9m x 6m x 2m, a storage capacity of 49896 kg of frozen fish stored as spheres with 0.25kg weight. The cold room uses injected polyurethane insulation on walls, roof and floor that is 100mm thick. It requires a cooling capacity of 19,141W to maintain -45°C temperature over 24 hours while accounting for heat transfer through insulation, air renewal and product thermal loads.

Uploaded by

ABDULLAH
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Coldroom

Cold room type modular cold room


Insulation thickness: 100 mm

Floor insulation: yes


Length (inner): 9.00 m

Width (inner): 6.00 m

Height (inner): 2.00 m

Inner volume: 108.00 m³

Application negative temperature refrigeration Room temperature: -45.0 ºC

Product type FROZEN FISH Storage temperature: -45.0 ºC

Storage humidity: 70 % Freezing point: -2.2 ºC

Water content: 73 % Specific heat capacity: 3.3 kJ/kg·K

Respiration heat: 0.0 kJ/kg Specific heat below freezing point: 1.8 kJ/kg·K

Product loading Load rate: 462 kg/m³ Total load: 49896 kg

Daily turnover rate: 20 %/24h Daily turnover: 9979 kg/24h

Inlet temperature: -3.0 ºC

Product cooling Product shape: sphere Weight per piece: 0.25 kg

Product thickness: 81 mm Mass density: 892 kg/m³

Thermal conductivity: 1.4 W/m·K Air speed: 0.1 m/s

Final inner temperature: -45.0 ºC Cooling time: 24.00 h

Air temperature: -45.0 ºC

Location within a building Altitude: 0 m

Ambient temperature: 37.9 ºC Ambient relative humidity: 23 %

Thermal insulation Walls: Injected polyurethane area: 63.8 m² thickness: 100 mm

Roof: Injected polyurethane area: 55.5 m² thickness: 100 mm

Floor: Injected polyurethane area: 55.5 m² thickness: 100 mm

Door: Injected polyurethane area: 8.0 m² thickness: 75 mm

Ventilation through Door openings per day: 5.0 /24h Air volume renewal rate: 4.8 /24h
doors

Door heater Unitary heat rate: 10 W/m Perimeter: 9.0 m

Defrost Defrost type: electrical

Fans Airflow rate: 2160 m³/h Input power: 0.297 kW

Cooling needs Calculation time period: 24.0 h


Products
Refrigeration of goods: 737662 kJ
H. Transfer
Heat transfer: 293840 kJ
Air renewal
Air renewal: 88826 kJ
Loads
Thermal loads: 120021 kJ

TOTAL: 1240349 kJ

Working hours: 18.0 h


Necessary cooling Necessary capacity for preservation of 7758 W Total cooling capacity: 19141 W
capacity goods:

 Too high heat loss through panels: Heat flow through the insulation is higher than the maximum recommended values. We recommend to
increase insulation thickness.

 Floor heating: Floor heating or ventilation might be needed to prevent the ground from freezing.