0% found this document useful (0 votes)
56 views11 pages

450 kW Diesel Generator Data Sheet

This document provides specifications for the FDK-CD450/H1 360kW diesel generator. It is powered by a Cummins QSZ13-G7 engine and coupled with a Stamford alternator to produce 320kW prime power and 360kW standby power at 50Hz. Key features include a soundproof enclosure, DSE6020 control system, base fuel tank, and optional low temperature accessories. Dimension and weight are provided for both open and soundproof versions.

Uploaded by

Kevin Guo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
56 views11 pages

450 kW Diesel Generator Data Sheet

This document provides specifications for the FDK-CD450/H1 360kW diesel generator. It is powered by a Cummins QSZ13-G7 engine and coupled with a Stamford alternator to produce 320kW prime power and 360kW standby power at 50Hz. Key features include a soundproof enclosure, DSE6020 control system, base fuel tank, and optional low temperature accessories. Dimension and weight are provided for both open and soundproof versions.

Uploaded by

Kevin Guo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

GUANGDONG FUDIANKANG DIESEL GENSET CO.

, LTD
SHENZHEN FUDIANKANG DIESEL GENESET CO., LTD
Tel: 86-13710087995
Web: www.fdkenergy.com Email: info@fdkenergy.com

DATA SHEET
DIESEL GENERATOR 360KW
MODEL#FDK-CD450/H1
50HZ/1500RPM
CUMMINS MODEL: QSZ13-G7

General Features:
 All qualified generator sets are subjected to a comprehensive performance test which includes 50% load, 70% load, 100%
load, 110% load and to check, verify that all control systems, alarm and shut-down protection.
 Equipped with battery charger and 24V high performance maintenance-free lead-acid starting batteries and connecting
cables.
 Stainless galvanized zinc plates with strong corrosion-proof.
 Vibration isolators between the engine/alternator and base frame.
 Equipped with industrial silencer and flexible exhaust hose.
 Designed to comply with ISO8528/GB2820.
 Powered by Cummins engine and coupled with Stamford alternator.
 Water jacket preheater, oil heater and double air cleaner, etc. are available.

FDK Diesel Generator Set Data


Genset Model FDK-CD450/H1 Engine Make Cummins
Prime Power 320KW/400KVA Engine Model QSZ13-G7
Standby Power 360KW/450KVA Alternator model Stamford HCI444F
Output Frequency / Rated speed 50Hz/1500rpm Control System DSE6020
Rated Voltage 230V/400V Phase Three

(1) Prime power: The rating is available for an unlimited of annual operating hours in variable load applications, in accordance with

ISO8528-1.A 10% overload is available for a period of 1 hour within 12-hour period of operation, in accordance with ISO 3046-1.

(2) Standby power: The rating is applicable for supplying emergency power in variable load applications for up to 200 hours per year in

accordance with ISO8528-1. Overload is not allowed.

(3) Rated voltage: available with customer requirement.

Engine Specifications (DETAILED in APPENDIX)


Engine Model QSZ13-G7 Aspiration Turbo-charged
Engine Manufacturer Cummins (China Bore x Stroke (mm x mm) 130×163
Dongfeng) Displacement 13L
Cylinder quantity 6 Compression Ratio 17:1
Cylinder Arrangement Not available Prime power / Speed (KW/RPM) 367/1500
Cycle Not available Standby power/ Speed (KW/RPM) 4191500

ISO9001:2008 FDK reserves the right to change the specifications and designs without noice.
GUANGDONG FUDIANKANG DIESEL GENSET CO., LTD
SHENZHEN FUDIANKANG DIESEL GENESET CO., LTD
Tel: 86-13710087995
Web: www.fdkenergy.com Email: info@fdkenergy.com
Speed governor MCRS Fuel Consumption at 100% load 209 at 1500rpm
Piston Speed 8.15m/s (g/KWh)

Friction Energy Output 31kw Starter motor DC24V

Total Lubrication System Capacity (L) 75.33 Alternator DC24V

Coolant Capacity (L) 23.1 Low idle 700rpm

Alternator Specifications
Alternator model HCI444F Number of phase 3
Alternator manufacturer STAMFORD Rated voltage 400V (Available with
Exciter type Single bearing, Brushless, custom requirements)
Self-excited Power factor 0.8
Rated output prime power 400KVA Voltage regulation NL-FL ≤±1%
Rated speed 1500 rpm Insulation grade H

Rated frequency 50Hz Protection grade IP23

Alternator option: Leroy Somer, MECC, Marathon, Engga, Faraday

Control System DSE6020 (DETAILED in INSTRUCTION)


DSE6020 is an advanced control module based on micro-processor, containing all necessary functions for protection of the
genset and the breaker control. It can monitor the mains supply, breaker control and automatically start the engine when the
mains are abnormal. Accurately measure various operational parameters and display all values and alarms information on the
LCD. In addition, the control module can automatically shut down the engine and indicate the engine failure.
FEATURES
 Microprocessor control, with high stability and credibility.
 Monitoring and measuring operational parameters of the mains supply and genset.
 Indicating operation status, fault conditions, all parameters and alarms.
 Multiple protections; multiple parameters display, like pressure, temp. etc.
 Manual, automatic and remote work mode selectable.
 Real time clock for time and date display, overall runtime display, 250 log entries.
 Overall power output display.
 Integral speed/frequency detecting, telling status of start, rated operation, overspeed etc.
 Communication with PC via RS485 OR RS232 interface, using MODBUS protocol.

Soundproof Enclosure Specification


FDK silent generator is designed by professional acoustic engineers based on years of experience. Now we can make the noise
of the generator less than 80-85dB(A) at 1m, or 70-75dB(A) at 7m, 60-65dB(A) at 15m.
FEATURES
 Multi-way air intake and exhaust guarantee the power performance of the generator.
 Large-scale impedance combined type silencer effectively reduce noise of the generator.
 Internal high performance rubber damper and flexible materials reduce vibration.
 Base mounted fuel tank supports the generator running for 8 hours.

ISO9001:2008 FDK reserves the right to change the specifications and designs without noice.
GUANGDONG FUDIANKANG DIESEL GENSET CO., LTD
SHENZHEN FUDIANKANG DIESEL GENESET CO., LTD
Tel: 86-13710087995
Web: www.fdkenergy.com Email: info@fdkenergy.com
Optional
Generator set Alternator Low environment Temp ATS
 Open generator set  Stamford  Water heater  CHINT
 Silent generator set  Marathon  Oil heater  SCHNEIDER
 Trailer generator set  Mecc Alte  Battery heater  ABB
 ABB MCCB circuit breaker  Leroy Somer
 Farady
 Engga
Fuel system Control system Voltage Synchronized system

 12hrs base tank  AMF function  415/240V  CHINT Cabinet


 24hrs base tank  ATS control cabinet  400/230V  SCHNEIDER Cabinet
 Dual wall base fuel tank  DSE7320  380/220V  DSE8610 Module
 Outside fuel tank  DSE7510  220/127V  COMAQ Module
 GU620A  200/115V  DEIF Module

Dimension & Weight


Open Soundproof Version

Overall Size: 3400×1400×1800 Overall Size: 5000×1900×2250


L×W×H (mm) L×W×H (mm)

Weight (kg) 3050 Weight (kg) 5400

Sales Promises
 FDK provides a full line of brand new and high quality products. Each and every unit is strictly factory tested before
shipment.
 Quality warranty is according to our standard conditions: 12 months from BL date or 1000 running hours, whichever comes
first.
 Service and parts are available from FDK or distributors in your location.

 FDK guarantee use BRAND NEW & GENUINE MACHINE.

ISO9001:2008 FDK reserves the right to change the specifications and designs without noice.
Dongfeng Cummins
Technical Operations
Engine Model:QSZ13-G7

Curve and Datasheet:FR20454

Rev03 2016.4
Generator Engine Performance Data Engine Model Curve Number CPL Code
Dongfeng Cummins Engine Co.,Ltd QSZ13-G7 FR20454 3836
Xiangyang, Hubei Province, China
Compression Ratio: 17:1 Engine Configuration: D0C3004GX03
Cylinders: 6 Fuel System: HPCR
Bore: 130 mm Aspiration: Turbocharged & Charge Air Cooled
Stroke: 163 mm Governor Regulation: ≤1%
Displacement: 13.0 L Emission Certification: Euro StageIIIA / MEP StageIII
Engine Ratings*:
Engine Speed Standby Power Prime Power Continuous Power
r/min bhp kWm bhp kWm bhp kWm
1500 561 419 491 367 442 330
1800 625 467 548 409 491 367
* All ratings refer to AEB26.02.

Engine Fuel Consumption @1500 r/min 1500 r/min


OUTPUT POWER FUEL CONSUMPTION l/h

140
% bhp kWm Ib/bhp.h g/kWm.h gal/h l/h 120
Standby Power 100
100 561 419 0.340 207 26.6 100.9 80
Prime Power 60
100 491 367 0.344 209 23.5 89.2 40
75 369 275 0.370 225 19.0 72.0 20
50 246 184 0.408 248 14.0 52.9 0
25 123 92 0.441 268 7.5 28.6 0 100 200 300 400 500
continuous Power kWm
100 442 330 0.352 214 21.7 82.1

Engine Fuel Consumption @1800 r/min 1800 r/min


OUTPUT POWER FUEL CONSUMPTION l/h

140
% bhp kWm Ib/bhp.h g/kWm.h gal/h l/h 120
Standby Power 100
100 625 467 0.337 205 29.4 111.3 80
Prime Power 60
100 548 409 0.350 213 26.7 101.3 40
75 411 307 0.380 231 21.7 82.4 20
50 274 205 0.411 250 15.7 59.4 0
25 137 102 0.497 302 9.5 35.9 0 100 200 300 400 500
continuous Power kWm
100 491 367 0.363 221 24.9 94.3
Curves shown above represent gross engine performance capabilities obtained and corrected in accordance with GB/T18297
conditions of 29.61 in Hg (100 kPa) barometric pressure [263 ft (80 m) altitude], 77 deg F (25 deg C) inlet air temperature, and
0.30 in Hg (1 kPa) water vapor pressure with No. 2 diesel fuel.
All data obtained is based on the engine operating, under the test conditions of 14.9 in H2O (3.7kPa) inlet air restriction and
2.95 in Hg (10 kPa) exhaust restriction,not included are alternator, fan, optional equipment and driven components.
The engine may be operated up to 5200 m (17,060 ft.) altitude. 1
Generator Engine Performance Data Engine Model Curve Number CPL Code
Dongfeng Cummins Engine Co.,Ltd QSZ13-G7 FR20454 3836
Xiangyang, Hubei Province, China
Power Derate Curves @1500 r/min Power Derate Curves @1800 r/min
Standby Power Standby Power
50% 50%

40% 40%
)% )%
( 30% ( 30%
率 率
降20% 降20%
下 下
10% 10%

0% 0%
0 1000 2000 3000 4000 5000 0 1000 2000 3000 4000 5000
Altitude(m) Altitude(m)

Prime Power Prime Power


50% 50%

40% 40%
)% )%
( 30% ( 30%
率 率
降20% 降20%
下 下
10% 10%

0% 0%
0 1000 2000 3000 4000 5000 0 1000 2000 3000 4000 5000
Altitude(m) Altitude(m)

Continuous Power Continuous Power


50% 50%

40% 40%
)% )%
( 30% ( 30%
率 率
降20% 降20%
下 下
10% 10%

0% 0%
0 1000 2000 3000 4000 5000 0 1000 2000 3000 4000 5000
Altitude(m) Altitude(m)

Engine tested under the ISA conditions of 50 deg C charge temperature, 3.7kPa inlet air
restriction and 10 kPa exhaust restriction. 2
Generator Engine Performance Data Engine Model Curve Number CPL Code
Dongfeng Cummins Engine Co.,Ltd QSZ13-G7 FR20454 3836
Xiangyang, Hubei Province, China
GENERAL ENGINE DATA
Type: ………………………………………………………………………………Four cycle; Inline; 6 Cylinder
Aspiration: ……………………………………………………………………………… Turbocharged Charge Air Cooled
Compression Ratio: …………………………………………………………………………………………………… 17:1
Fire Order: ………………………………………………………………………………………… 1-5-3-6-2-4
Bore x Stroke: ………………………………………………………………………………- mm 130 x 163
Displacement: ………………………………………………………………………………- L 13.0
Low Idle Speed: ……………………………………………………………………………… - r/min 700
Maximum altitude for continuous operation: ………………………………………………………………………………
-m 5200
Approximate Engine Weight - Dry: …………………………………….……… - kg 1245
Approximate Engine Weight - Wet: …………………………………………………………………………………...………..…..……
- kg 1353
Center of Gravity from front face of block: ………………………………………………………………………………………………
- mm 519
Center of Gravity above crankshaft centerline: …………………………………………………………………………………………
- mm 201
- kg.m 2 1.48
Rotation inertia of Complete Engine (without flywheel): ………………………………………………………………………………

ENGINE MOUNTING
Maximum static mounting surface bending moment
Rear face of block: ……………………………………………………………………………………………………………………
- N.m 1356
Maximum static bending moment of FAN: ………………………………………………………………………………………………
- N.m 21
Maximum allowable weight on Engine Support: ………………………………………………………………………………………
- kg 1500

AIR INDUCTION SYSTEM


Whole air intake pipe size (recommendatory): ………………………………………………………………………………………… - mm 200
Charge air cooler pipe size (recommendatory): ………………………………………………………………………………………… - mm 110
-℃
Maximum temperature rise between ambient air and engine air inlet: ………………………………………………………………
11.1
-℃
Maximum Temp. Rise Between Engine Air Intake and Intake Manifold: ……………………………………………………………
30
Maximum Intake Manifold Temperature (unable to result in power loss at sea level):
……………………………………………………………………………………………… - ℃ 60*
-℃
Maximum Intake Manifold Temperature for Engine Protection: ……………………………………………………………………… 85
Maximum intake air restriction (heavy duty air cleaner):
clean filter: ……………………………………………………………………………………………………………………………… - kPa 3.2
dirty filter: …………………………………………………………………………………………………… - kPa 6.2
Maximum allowable pressure drop across charge air cooler and OEM CAC
piping (CACDP): …………………………………………………………………………………………………… - kPa 13

EXHAUST SYSTEM
Max. back pressure imposed by complete exhaust system: ……………………………………………………………
- kPa 13
Maximum allowable static bending moment at exhaust outlet flange: ………………………………………………………………
- N.m 19
Exhaust pipe size (recommendatory):……………………………………………………………………………………………………
- mm 130

*When excess the temperature.the durablity/reliability/performance of the engine maybe impaired.


3
Generator Engine Performance Data Engine Model Curve Number CPL Code
Dongfeng Cummins Engine Co.,Ltd QSZ13-G7 FR20454 3836
Xiangyang, Hubei Province, China
LUBRICATION SYSTEM
Oil pressure @ idle - minimum: …………………………………………………………………………………………………
- kPa 82.7
Typical oil pressure range - warm engine: ………………………………………………………………………………………………
- kPa 207 - 300
Total system capacity (standard pan): ………………………………………………………………………………………………
-L 75.33
Maximum lube oil flow to all accessories: ………………………………………………………………………………………………
- L/min 7.57

COOLING SYSTEM
Coolant Capacity (Engine Only): …………………………………………………………………………………………………… -L 23.1
-℃
Engine coolant circuit thermostat opening temperature: ………………………………………………………………………………
82
-℃
Engine coolant circuit thermostat fully open temperature: ……………………………………………………………………………
94
-℃
Maximum coolant temperature - engine out: ………………………………………………………………………………………… 102
-℃
Minimum operating block coolant temperature: ………………………………………………………………………………………… 71
-℃
Maximum coolant temperature for engine protection controls: ………………………………………………………………………
107
Maximum coolant pressure(exclusive of pressure cap; closed thermostat
at maximum no load speed): …………………………………………………………………… - kPa 407
Minimum pressure cap rating at sea level: ……………………………………………………………………………………………
- kPa 103
Maximum Coolant Friction Head External to Engine: …………………………………………………………………………………
- kPa 75
Maximum deaeration time: ……………………………………………………………………………………………………………… - min 25
Minimum fill rate (low level alarm required for most engines): ………………………………………………………………………
- L/min 19
Maximum coolant expansion space (% total system capacity): ……………………………………………………………………
-% 10
Minimum coolant expansion space (% total system capacity): ……………………………………………………………………
-% 6

FUEL SYSTEM
Maximum allowable restriction @ OEM point with maximum fuel flow: ………………………………………………………………
- kPa 13.5
Maximum fuel drain restriction (total head) before (or without) check valve:…………………………………………………………
- kPa 27
Minimum fuel tank venting requirement: ………………………………………………………………………………………………… - L/s 0.2
Maximum fuel inlet temperature: …………………………………………………………………………………… -℃ 71
Maximum heat rejection to return fuel…………………………………………………………………………………………………… - kW 5.36
Maximum design fuel flow: ……………………………………………………………………………………………………… - kg/h 204

ELECTRICAL SYSTEM
System voltage: ………………………………………………………………………………………………… -V 24
Minimum battery capacity-cold soak at -18 C (0 F) or above
Engine only cold cranking amperes: …………………………………………………………………
- CCA 900
Engine only reserve capacity: ………………………………………………………………… - min 270

COLD START CAPABILITY


-℃
Minimum ambient temperature for unaided cold start: ……………………………………………………………………………
-15
-℃
Minimum ambient temperature with Intake Air Heater(engine no load): ……………………………………………………………
-30

Exhaust Emissions Data



Gaseous Emissions per GB 20891-2014 1500 r/min
- Weight-Specific NOx+HC: …………………………………………………………………………………
- g/kW.h 3.430
- Weight-Specific CO: ……………………………………………………………………………………- g/kW.h 0.630
- Weight-Specific Particulates: ……………………………………………………………………………………
- g/kW.h 0.063

4
Generator Engine Performance Data Engine Model Curve Number CPL Code
Dongfeng Cummins Engine Co.,Ltd QSZ13-G7 FR20454 3836
Xiangyang, Hubei Province, China
Performance Data
All data is based on: Engine operating with fuel system, water pump, lubricating oil pump and air
cleaner; not included are alternator, fan, and optional equipment and driven
components.
• GB18297 Engine test code - Performance
Test Condition: • Barometric Pressure : 100 kPa (29.53 in Hg)
• Air Temperature: 25 °C (77 °F)
• Altitude: 80 m (263 ft)
• Relative Humidity: 50%
Steady State Stability Band at any constant load (+/-): 5%

Standby Power Prime Power


Engine Speed r/min 1500 1800 1500 1800
Gross Engine PowerOutput kWm 419 467 367 409
Torque: N.m 2668 2478 2337 2170
Brake Mean EffectivePressure kPa 2578 2395 2258 2097
Piston Speed m/s 8.15 9.78 8.15 9.78
Friction Horsepower kW 31 45 31 45
Coolant Flow L/min 406 475 406 475
Fuel Consumption kg/h 86.7 95.7 76.7 87.1

Engine Data
Intake Air Flow m3/min. 30.0 35.2 28.6 34.8
Exhaust Gas Temp - DryStack ℃ 513 474 491 462
Exhaust Gas Flow kg/min. 36.9 43.1 35.1 42.6
Air to Fuel ratio 24.5 26.0 26.4 28.3
Heat Rejection to Ambient kW 68 76 60 66
Heat Rejection to JacketCoolant kW 162 174 143 165
Heat Rejection to Exhaust kW 362 404 317 354
Heat Rejection to Fuel* kW 5 5 5 5

ATA CAC
Heat Rejection to Aftercooler kW 102 120 88 116
TurbochargerCompressor Outlet kPa 284 287 261 279
Charge Air Flow kg/min 35.5 41.5 33.8 41.1
TurbochargerCompressor Outlet ℃ 222 220 207 216

*This is the maxiumum heat rejection, not specified to the load listed.

5
Generator Engine Performance Data Engine Model Curve Number CPL Code
Dongfeng Cummins Engine Co.,Ltd QSZ13-G7 FR20454 3836
Xiangyang, Hubei Province, China

6
Generator Engine Performance Data Engine Model Curve Number CPL Code
Dongfeng Cummins Engine Co.,Ltd QSZ13-G7 FR20454 3836
Xiangyang, Hubei Province, China

Dongfeng Cummins Engine Co.,Ltd


Automobile Industry Development Zone, Xiangyang, Hubei Province
China 441004
Tel: 86-710-3399100
Fax: 86-710-3392893

End 7