Powell - 05PV26250 W1001546
Powell - 05PV26250 W1001546
INSTRUCTIONS IB-69000
INSTALLATION
III
mm
r SI
OPERATION
MAINTENANCE
POWELL
)
INDUSTRIES,INC .
POWELL ELECTRICAL MANUFACTURING COMPANY
•
8550 MOSLEY DRIVE HOUSTON, TEXAS 77075 USA
•
PHONE (713) 944-6900 FAX (713) 947-4453
bcsswitchgear.com | 888.599.0486 Need Help? 888.599.0486
Courtesy of NationalSwitchgear.com
BCS Switchgear Inc. Switchgear | Circuit Breakers | Parts | Tech Support
P-69000 PV-26 Vacuum Circuit Breakers IB-69000
CONTENTS
I. INTRODUCTION
II. SAFETY 1
A. X-RAYS 1
B. SAFETY LABELS 1
III. DESCRIPTION 2
A. GENERAL 2
B. THE STORED ENERGY MECHANISM . . 2
C. INTERLOCKING 7
D. VACUUM INTERRUPTER CONNECTIONS
E. OPERATING SOLENOIDS 8
F. THE ANTI-PUMP RELAY 9
G. MOTOR CUTOFF SWITCH 9
H. VACUUM INTERRUPTERS 9
J. SECONDARY DISCONNECT PLUG 9
IV. INSTALLATION 9
A. RECEIVING c
n
B. HANDLING O
'
C. STORAGE 9
D. PUTTING INTO SERVICE 10
(1) High Voltage Insulation Integrity 10
(2) Vacuum Integrity 11
(3) Control Voltage Insulation Integrity 11
(4) Mechanical Operation Check 11
(5) Electrical Operation 12
E. INSERTING BREAKER INTO SWITCHGEAR EQUIPMENT 12
F. POWER RACKING DEVICE 13
V. MAINTENANCE 13
A. GENERAL 13
Introduction
(1) 13
Inspection and Cleaning
(2) 13
B. MECHANISM AREA 14
(1) Mechanical Operation 14
(2) Lubrication 14
(3) Closing Spring Removal and Slow Closing of Mechanism
(4) Mechanism Adjustments
(a) Adjustment of Ratchet Wheel Holding Pawl
Courtesy of NationalSwitchgear.com
BCS Switchgear Inc. Switchgear | Circuit Breakers | Parts | Tech Support
Courtesy of NationalSwitchgear.com
P- 69000 PV-26 Vacuum Circuit Breakers IB-69000
ILLUSTRATIONS
Figure 1. Side view of PV-26 Circuit Breaker 2
Figure 2. Front View of PV-26 Circuit Breaker with Cover In Place . 3
Figure 3. Front View of PV-26 Circuit Breaker with Cover Removed 3
Figure 4. Charging Motor and Motor Cutoff Switch 4
Figure 5. Main Operating Mechanism - Right Oblique View 4
Figure 6. Main Operating Mechanism - Left Oblique View 4
Figure 7. Close Latch Arm Engaging Close Latch Shaft 5
Figure 8. Cam and Fundamental Linkage Positions 6
Figure 9. Interrupter and Operating Rod Mechanism 7
Figure 10. Mechanism and Trip Linkages 7
Figure 11. Shunt Trip Coil, right 8
Figure 12. Circuit Breaker in Shipping Carton 9
Figure 13. Circuit Breaker with Secondary Test Connector in Place . 10
Figure 14. Circuit Breaker Being Lifted on Crane 10
Figure 15. Main Closing Spring Assembly Installed 15
Figure 16. Main Closing Spring Assembly Compressed For Removal 15
Figure 17. Primary Trip Latch Adjusting Screw 16
Figure 18. Contact Erosion Measurements 17
Figure 19. Trip Lever Gap Adjustment 20
Figure 20. Undervoltage Device Mounted on Circuit Breaker 20
Figure 21. Undervoitage Device 21
Figure 22. Anti-Pump Relay 21
Figure 23. Ground Shoe 22
Figure 24. Auxiliary Switch 23
Figure 25. Pin Retaining Rings 23
TABLES
Table I. Circuit Breaker Lubrication 15
Table II. Interrupter and Sliding Contact Finger Assemblies 18
Table III. Control Devices 18
Table IV. Miscellaneous Parts 18
Courtesy of NationalSwitchgear.com
P-69000 PV-26 Vacuum Circuit Breakers IB-69000
)
CAUTION
Before any adjustment, sen/ icing, parts replacement, or any other act is
performed requiring physical contact with the electrical working components
or wiring of this equipment, the POWER SUPPLY MUST BE DISCONNECTED.
Courtesy of NationalSwitchgear.com
P-69000 PV-26 Vacuum Circuit Breakers IB-69000
iq
CAUTION /
REMOVAL OF SECONDARY DIS-
CONNECT PLUG WILL TRIP A
CLOSED BREAKER AND DISCHA- Attached to front cover
0 0
RGE THE MAIN CLOSING to left of secondary h
disconnect aperture.
SPRING
(b>
DANGER
BE SURE CIRCUIT BREAKER
CONTACTS ARE OPEN AND Attached to front cover
SPRINGS DISCHARGED BEFORE; at top right hand cor-
Courtesy of NationalSwitchgear.com
P-69000 PV- 26 Vacuum Circuit Breakers IB-69000
cl
Figure 2. Front View of PV-26 Circuit
Breaker with Cover In Place
Courtesy of NationalSwitchgear.com
P-69000 PV-26 Vacuum Circuit Breakers IB-69000
To insure correct synchronization of the drive and hold As the ratchet wheel is rotated, projections from its side
pawls, the hold pawl links are located by an adjustable faces will engage drive plates attached to the cam shaft and
eccentric stop located at the left front of the mechanism. the cam shaft will rotate. Attached to the ends of the cam
When the mechanism is operated manually, the top pawl shaft are crank arms and pointing outward from these are
becomes the driving pawl and the bottom pawl becomes crank pins. These engage with the bottom ends of the
the holding pawl. connecting rods (Figure 6) , the top ends of which engage
pins projecting from the spring compression plate which
straddles the main closing spring. As the cam shaft rotates,
the connecting rods pull the spring compression plate
downward,compressing the closing spring.
A
Figure 6. Main Operating Mechanism - Left
Oblique View
©
a. Drive Pawl
<3) b.
C.
Ratchet Wheel
Holding Pawl
d. Holding Pawl Adjusting Eccentric
e. Drive Plate
Figure 5. Main Operating Mechanism - f. Crank Arm
Right Oblique View g- Crank Pin
h. Secondary Trip Latch Adjusting Screw
j - Latch Check Switch
k. Connecting Rod
a. Mechanism Reset Spring
b. Close Bar Adjusting Screw
c. Motor Cutoff Cam
d. Motor Cutoff Switch Operating Arm
Courtesy of NationalSwitchgear.com
P-69000 PV-26 Vacuum Circuit Breakers IB-69000
The ratchet wheel will drive the cam shaft so that the
connecting rods go down to their lowest position and then
start to move upward. At a certain point, the spring force
will overcome friction and resistance and start to rotate the
cam shaft. At the same time, the pawls are uncoupled from
the ratchet wheel and the motor cutoff switch is operated.
The motor cutoff switch located on the right of the mecha-
nism is operated by the spring charge flag falling into the
spring charge cam (Figure 5) . The spring charge flag will
now show that the mechanism is charged. The cam shaft
would continue to rotate, except that it is restrained by the
close latch arm engaging against the close latch shaft
(Figure 7) . The main operating cam located between the
mechanism side sheets is now in a position where the main
drive linkage can move to the reset position (Figure 8a) .
Courtesy of NationalSwitchgear.com
P-69000 PV-26 Vacuum Circuit Breakers IB-69000
The linkage is restrained from movement by the With the standard electrical control scheme, as soon as
secondary trip prop acting on the primary trip prop roller. the closing spring is discharged on a closing operation, the
The component of force tends to make the primary trip prop motor is switched on to recharge the spring. This leaves
move upward, but it is restrained by the secondary trip prop the main closing cam in a position where the tripped
face acting on the primary trip prop roller. The clearance linkage can reset under the action of the reset spring
between the primary trip prop roller and the secondary trip (Figure 8d), and the primary and secondary trip props can
prop is controlled by the primary trip prop adjusting screw. fall into the reset position. The reset spring stretches
When the trip shaft is rotated by the action of the manual between an extension of the main cam roller pin and a
trip plate or the electric trip solenoid, the secondary trip spring support pin located on the left mechanism side
prop moves down and permits the primary trip prop to sheet. The trip latch check switch operated by a lever on
move upward, thus permitting the main linkage to move the trip shaft will now close (Figure 6) .
upward and the jack shaft to rotate, opening the breaker.
The jack shaft extends from the left to the right side of the
breaker frame and is supported at the main breaker frame
side sheets and by the mechanism side sheets. An exten-
sion of the jack shaft projects through the left breaker side
sheet and operates the MOC switch drive.
Courtesy of NationalSwitchgear.com
P-69000 PV-26 Vacuum Circuit Breakers IB-69000
)
The second purpose is to insure that the control circuits
cannot be broken when the breaker is in the connected
a position and the breaker cannot be moved from the con-
nected position unless its main contacts are first opened.
o
f
> 9
h
*-
'
Lower Primary Disconnect Secondary Trip Latch
e. Anti Bellows Spring d. Secondary Linkage Roller
f. Contact Pressure Spring e. Reset Spring
g Bell Crank f. Cam Shaft
h. Operating Rod g- Main Drive Cam
h. Center Phase Operating Lever
j - Main Cam Roller
k. Primary Trip Prop Adjusting Screw
C. INTERLOCKING Primary Trip Prop
m Primary Trip Prop Roller
The first purpose of the interlocks is to insure that a
breaker cannot be moved from the disconnected to the The circuit breaker can not be moved into the test
connected position unless the main breaker contacts are position ( from outside the ceil ) unless the the access door
open and the secondary control circuitry from the compart- to the levering-in shaft is closed. If the circuit breaker is in
ment to the circuit breaker is completed. the connected position, the "PUSH TO CLEAR" button will
J
Courtesy of NationalSwitchgear.com
P- 69000 PV-26 Vacuum Circuit Breakers IB-69000
trip the unit, hold it trip-free, and discharge the closing D. VACUUM INTERRUPTER CONNECTIONS
spring. When the "PUSH TO CLEAR" button is depressed,
the access door will open, exposing the levering-in shaft. Connection to the vacuum interrupter stems is made by
One- half turn of the shaft in either direction (racking the unit means of cast copper. The top stem of the interrupter is
in or out) will lock the door open and hold the push to clear threaded, and a copper casting is screwed onto this stem.
function in an engaged condition. The upper primary disconnect is threaded onto the copper
casting. A similar casting and primary disconnect assembly
With the levering- in device in the fully racked out is mounted to the bottom of the vacuum interrupter. The
position, the access door must be closed to insert the moving stem of the vacuum interrupter passes through the
breaker into the "TEST" position from the outside. The casting where multiple parallel sliding contacts make
breaker may be removed from the "TEST" position without contact with the casting and the moving stem of the
closing the access door, however, it cannot be reinserted vacuum interrupter. The multiple parallel paths of the
until the door is closed. There is an anti-rollout latch sliding contacts keep the current density low.
located at the bottom of the circuit breaker that will lock the
unit in the "TEST" position, preventing accidental removal.
E. OPERATING SOLENOIDS
The secondary disconnect plug may be inserted before
or after reaching the "TEST" position, however, it must be The closing solenoid located under the middle of the
inserted and locked in place, using the locking bar, prior to mechanism is attached to the breaker mechanism shelf by
any attempt to move the circuit breaker into the "CONNECT- two screws accessible from beneath the mechanism.(Figure
ED" position. Insertion of the secondary disconnect plug 3) .
will cause the charging motor to operate and charge the
closing spring. Note that operation of the "PUSH TO
CLEAR " button will discharge the spring, as described
above, prior to allowing access to the levering-in shaft.
Removal of the secondary disconnect plug in the "TEST"
position will cause all springs in the operating mechanism
to discharge.
Courtesy of NationalSwitchgear.com
P-69000 PV-26 Vacuum Circuit Breakers IB-69000
Courtesy of NationalSwitchgear.com
P-69000 PV-26 Vacuum Circuit Breakers IB- 69008
CAUTION
High voltage across the open gaps of the
interrupter can produce radiation. Personnel should
stand at least 1 meter (39 inches) away from the break-
er, in front of the front cover, when conducting high
voltage tests. Test voltage should not exceed 36kV, 50
or 60 Hz, or 50kV dc.
Courtesy of NationalSwitchgear.com
P- 69000 PV-26 Vacuum Circuit Breakers IB-69000
This test will have checked all of the support insulation, breakdown occurs the interrupter should be replaced.
and also the primary phase-to-phase insulation.
. .y
Caution: Remove all grounding conductors applied for this v
CAUTION
test before placing the breaker back into service. WHEN TESTING WITH DC, USE A DC HIGH POTEN-
TIAL TEST SET WITH FULL WAVE RECTIFICATION
^
MANY : DC' filG POTENTIALITEST : SETS USE HALF
'
^ ^
performance of these devices is primarily dependent upon
the integrity of the vacuum in the chamber and internal
APPLYING PEAK OLTAGEG :V S MUCH AS : TPME::
dielectric strength. Both these parameters can be readily
TIMES THE; MEASURED ; VOLfKGEL : ;; P
: THESE| |- : : I
checked by a high potential test.
MALLY HIGH VOLTAGES MAY GIVE A FALSE INDICA-
TION OF A DEFECTIVE INTERRUPTER , AND MAY
PRODUCE ABNORMAL X-RADIATION.
CAUTION
APPLYING ABNORMALLY HIGH VOLTAGE ACROSS A
No attempt should be made to try to compare the
PAIR OF CONTACTS IN VACUUM MAY PRODUCE X -
condition of one vacuum interrupter with another nor to
RADIATION. THE RADIATION MAY INCREASE WITH
correlate the condition of any interrupter with low values of
THE INCREASE IN VOLTAGE AND/ OR DECREASE IN
dc leakage current. There is no significant correlation.
CONTACT SPACING.
After the test potential is removed, discharge any
X-RADIATION PRODUCED DURING THIS TEST WITH
electrical charge that may be retained.
RECOMMENDED VOLTAGE AND NORMAL CONTACT
SPACING IS EXTREMELY LOW AND WELL BELOW
MAXIMUM PERMITTED BY STANDARDS. HOWEVER,
AS A PRECAUTIONARY MEASURE AGAINST POSSI - (3) Control Voltage Insulation Integrity
BILITY OF APPLICATION OF HIGHER THAN RECOM-
MENDED VOLTAGE AND/OR BELOW NORMAL . CON- If the user wishes to check the insulation integrity of the
TACT SPACING, IT IS RECOMMENDED THAT ALL control circuit, it may be done with a 500 volt or 1000 volt
OPERATING PERSONNEL STAND AT LEAST ONE insulation tester or with an ac high potential tester. The ac
METER AWAY : IN FRONT OF THE BREAKER. high potential test should be made at 1125 volts, 60 Hz, for
one minute. The charging motor must be disconnected at
DO NOT APPLY VOLTAGE THAT IS HIGHER THAN its connection plug prior to testing the control circuit. The
THE RECOMMENDED VALUE . DO NOT USE CON- motor itself may be similarly tested at a voltage not to
TACT SEPARATION THAT IS LESS THAN THE NOR - exceed 675 volts, 60 Hz. Be sure to remove any test
MAL OPEN POSITION SEPARATION OF THE BREAK
-
Courtesy of NationalSwitchgear.com
P-69000 PV-26 Vacuum Circuit Breakers IB-69000
test connector in place. The manual charge lever should and the access door must be closed prior to any attempt to
now be inserted into the manual charge crank and pushed engage the breaker. Refer to the section on interlocking for
down until a metallic click is heard. This indicates that the details. The rollout latch will engage at this point.
holding pawl has dropped into place on the ratchet wheel.
Lift the lever until it is horizontal and then depress. The To insert a breaker into an upper compartment, a lift
procedure is repeated until the spring charge flag indicates truck is required. Refer to the detailed procedure in the
.
that the close spring is now charged This requires about instruction book for metal- clad switchgear equipment, IB-
60 operations of the handle. Remove the handle. Push the 68000. The levering-in device and interlocking works as
round blue "PUSH TO CLOSE" plate and the breaker will described for insertion into a lower compartment.
close. The flag located above the "PUSH TO CLOSE" plate
will now read "CLOSED". Push the round red trip plate To move the circuit breaker into the "CONNECTED"
located at the top of the escutcheon and the breaker will position, in an upper or lower compartment, the secondary
open as indicated by the breaker condition flag. disconnect must be inserted and locked in place by the
locking bar. To engage the levering-in device, press the
(5) Electrical Operation "PUSH TO CLEAR " button and the access door will open
simultaneously. Note that insertion of the secondary
disconnect will charge the closing springs and depressing
To check the electrical operation of the breaker, a
the "PUSH TO CLEAR " button will discharge the closing
jumper cable must be used. First, remove the control fuses
spring. Refer to the section on interlocking for details.
in the compartment. Connect the jumper cable to the
umbilical cord in the compartment and to the breaker.
The levering-in crank may now be inserted into the
Insert the fuses. The motor mechanism will automatically
access window to engage the hex shaft. Rotate the crank
charge the stored energy closing springs. Operation of the
clockwise to move the breaker into the "CONNECTED"
closing switch on the front door of the compartment will
position. The force required to rotate the crank will be low
cause the breaker to close. The circuitry is arranged to
at the beginning of the motion when the movement of the
cause the motor to operate again and charge the closing
crank serves only to open the shutters; however, as the
spring. Operating the electrical trip switch on the front door
breaker moves toward the "CONNECTED" position the force
will cause the breaker to open. Alternately, the breaker may
required will increase due to engagement of the ground
be connected to a test cabinet to perform these functions.
contact and the primary disconnects, Once the initial
engagement is made the force will decrease, Continued
rotation will move the breaker further into the cell to ensure
E. INSERTING BREAKER INTO that contact wipe or overlap of the primary contacts is
SWITCHGEAR EQUIPMENT correct.
Refer to the metal- clad switchgear instruction book for Once the breaker has reached the fully "CONNECTED"
general information and cautions before attempting to insert position, the levering-in mechanism will stop rotating and a
a circuit breaker into the switchgear equipment. flag indicating that the breaker is fully "CONNECTED" will
appear. DO NOT attempt to force the levering-in device
Each circuit breaker and each cell is provided with a further or damage will occur. The levering-in crank may
coding plate designed to insure that no breaker with less now be removed and the access door can be closed. The
than the required voltage, continuous current or interrupting circuit breaker is now ready for service.
current rating is placed in any cell. If you attempt to insert
an improperly rated breaker into a cell, these coding plates The maximum force required on the levering-in crank
will interfere with each other and deter the insertion. The for normal insertion of a circuit breaker will not exceed 35
interference will occur before the breaker can engage the Ibs-ft. Excessive force may damage the levering-in device,
levering- in mechanism. DO NOT attempt to force a breaker circuit breaker or switchgear equipment.
past this interference or remove the coding plate from either
the cell or the breaker. To move a circuit breaker from the "CONNECTED"
position to the "DISCONNECTED" position (or "TEST'
To insert a breaker into a lower compartment, first align position), first the circuit breaker must be tripped, This
the wheels with the housing floor pan channels. Then roll may be accomplished manually or electrically. To engage
the breaker into the housing until it stops. Note that the the levering-in crank the "PUSH TO CLEAR " button must be
levering- in device must be in the fully racked out position depressed and the access door opened. (Remember that
Courtesy of NationalSwitchgear.com
P-69000 PV-26 Vacuum Circuit Breakers IB-69000
the "PUSH TO CLEAR " button will discharge all springs in inspected and necessary maintenance be performed as
the circuit breaker) . Engage the levering-in crank and rotate soon as is practical. Some atmospheric conditions such as
counter - clockwise until the indicator flag reads extremes of dust and moisture or corrosive gases might
"TEST / DISCONNECTED " and the levering - in device stops . indicate inspection and maintenance at more frequent
DO NOT attempt to rotate the crank further in the counter- intervals than 2000 operations. Very clean and dry condi-
clockwise direction or damage to the device may occur. tions combined with low switching duty will justify longer
times between inspection and maintenance operations.
The circuit breaker is now disconnected from the With experience, each user can set an inspection and
primary contacts and may be tested electrically or mechani- maintenance schedule which is best suited for the particular
cally. use.
To remove the circuit breaker from the compartment, A permanent record of all maintenance work should be
release the secondary disconnect plug by rotating the kept, the degree of detail depending on the operating
locking bar left and down. The secondary disconnect plug conditions. In any event, it will be a valuable reference for
may now be pulled out of the circuit breaker . If the circuit subsequent maintenance work and for station operation. It
breaker is in a lower compartment it may be removed by is recommended that the record include reports of tests
releasing the rollout latch on the breaker and rolling the made, the condition of breakers and repairs and adjust-
breaker out. If the circuit breaker is in an upper compart- ments that were made. This record should begin with any
ment a lift truck is required. Refer to the Metal-Clad checks done at the time of installation and energization.
Switchgear instruction book IB-68000 for a detailed proce-
dure on removal. Because of extensive quality control checks made at
the factory, the operations counter on a new circuit breaker
F. POWER RACKING DEVICE will normally register over a hundred operations. The actual
reading of the operations counter should be recorded when
the circuit breaker is put into service and whenever any
A motor- driven racking device is available as an maintenance is performed.
optional accessory refer to IB68030 for details on operation.
Before attempting any maintenance work, take note of
V. MAINTENANCE safety practices outlined in Section II of this book.
-
MAKE CERTAIN THAT THE CONTROL CIRCUITS ARE
Contact Powell ApparatusService Division for assis DE-ENERGIZED AND THE BREAKER IS RESTING SECURE-
tance in performing maintenance or setting up a main- LY OUTSIDE THE SWITCHGEAR HOUSING. DO NOT
tenance program. WORK ON A CLOSED BREAKER OR A BREAKER WITH
THE CLOSING SPRINGS CHARGED.
Courtesy of NationalSwitchgear.com
P-69000 PV-26 Vacuum Circuit Breakers IB-69000
industrial type wiper. If dirt adheres and will not come off open, remove the screw at the top of the spring rod
by wiping, remove it with distilled water or a mild solvent together with the lock washer. Remove the top cover by
such as denatured alcohol. Be sure that the breaker is dry unfastening the nine attachment screws, Remove the
before returning it to service. Do not use any type of spacer from below the top cover. Utilizing a .5-13 x 1.25
detergent to wash the surface of the insulators, as detergent inch screw in place of the original, insert screw and screw
may leave an electrical conducting residue on the surface down until tension is taken off the connecting rods (Figure
as it dries. 15) . The connecting rods can now be unhooked from the
spring yoke pins and the spring assembly removed. Care
should be taken on reassembly to insure correct location of
B. MECHANISM AREA
the spacer. See Figure 16.
(1) Mechanical Operation With the main spring assembly removed, rotate the cam
shaft so that the crank arms are pointing downward. The
Remove the circuit breaker front cover, exposing the main linkage will now move into the reset position. Push
mechanism. Make a careful visual inspection of the mech- the "PUSH TO CLOSE" plate and hold in while operating the
anism for loose, damaged or excessively worn parts. Oper- hand charge lever to rotate the cam shaft. Once the close
ate the breaker several times manually. release latch arm is past the close shaft latch plate, the
"PUSH TO CLOSE" plate may be released. As the main
See the sections headed "Mechanical Operation cam engages the main linkage roller, the jackshaft will com -
Checks " under the heading PUTTING INTO SERVICE for mence to rotate. Continue to operate the hand charge lever
further information. until the crank arms point upward. The breaker will now be
closed and there will be a gap between the contact overtra -
(2) Lubrication vel nuts and the contact spring yokes. See Figure 9.
Lubricate the mechanism and other specified parts in (4) Mechanism Adjustments
accordance with the lubrication chart, Table I, Page 16.
Several factory adjustments in the mechanism are
The chart shows the location of all surfaces which described below. No adjustment of these settings is
should be lubricated together with the type of lubricant and required for routine maintenance, but they may need to be
method of application. The guiding rule in lubrication adjusted after major overhaul or removal of the mechanism.
should be to lubricate regularly, use lubricant sparingly and DO NOT ADJUST THESE SETTINGS UNNECESSARILY.
remove all excess lubricant.
(a) Adjustment of Ratchet Wheel Holding Pawl
Anderol 757 Grease should be lightly applied to those The ratchet wheel holding pawl (c, Figure 6, Page
bearing surfaces which are accessible and a light synthetic 4) is adjusted by an eccentric cam (d, Figure 6, Page
machine oil such as Anderol A456 should be used to 4) . If the pawl is not properly adjusted, there will be a
penetrate through to surfaces which are inaccessible. The "knocking" noise when the ratcheting mechanism is
mechanism should be in the open, spring discharged operating, or the mechanism will not ratchet at all. To
position for lubrication. There is no necessity to disassem- adjust the pawl, remove the escutcheon to gain access
ble the mechanism for lubrication. Tilting the breaker will to the head of the bolt holding the eccentric cam.
facilitate the entry of the lubricant to the bearing surfaces. Loosen the bolt slightly. While charging the spring
using the charging motor to drive the mechanism, grip
(3) Closing Spring Removal and the eccentric cam with a pair of slip- joint pliers or a
similar tool and rotate the cam slightly until the ratchet-
Slow Closing of Mechanism ing operation is smooth. This may require several
charging cycles, as each charging cycle lasts only a
Disassembly of the mechanism is not required for
few seconds. When the eccentric cam is properly set,
routine lubrication; however, for major overhaul, removal of
re-tighten the mounting bolt and replace the escutch-
the closing spring is necessary. Removal of the spring
eon. Be sure that the escutcheon is reinstalled on the
permits slow closing of the vacuum interrupter contacts .
proper circuit breaker, since the escutcheon contains
The procedure for spring removal is as follows:
the nameplate with all the breaker 's rating and serial
number information.
With closing spring discharged and breaker contacts
Courtesy of NationalSwitchgear.com
P-69000 PV-26 Vacuum Circuit Breakers IB-69000
Figure 15. Main Closing Spring Assembly Figure 16. Main Closing Spring Assembly
Installed Compressed for Removal
\
Courtesy of NationalSwitchgear.com
P- 69000 PV-26 Vacuum Circuit Breakers IB-69000
The close shaft passes through the side sheets of Figure 17. Primary Trip Latch Adjusting
the mechanism frame at the front of and below the cam Screw
shaft. The left end of the shaft is shaped to make a
latch face interference with the latch arm which is fixed
to the cam shaft (Figure 7, Page 5). The other end of
the close shaft is on the right side of the mechanism
and a small lever attached to it is positioned by an
adjusting screw (b, Figure 5, Page 4) . With the main closing the breaker and measuring the gap between the
closing spring charged, turn the latch adjusting screw nut and yoke for the contact pressure spring assembly
inward toward the rear of the breaker until the latch is .
(refer to Figure 18 for location) The gap is preset at the
released and the breaker closes. Unscrew the adjust- factory to approximately .469 inches. When the vacuum
ment screw 21/2 full turns and lock in position with the .
interrupter contacts have eroded 125 inches the unit should
locking nut. .
be replaced The overtravel gap (or nut gap) will measure
.344 inches at this point (there is a 1:1 ratio between
contact wear and the overtravel gap) .
(5) Electrical Operation
After any necessary mechanical maintenance and
lubrication are done, operate the circuit breaker electrically (2) Sliding Contact Wear
several times to ensure that the electrical control system
works properly. See section headed "Electrical Operation" To examine the movable contact rod of the vacuum
under the "Putting into Service" heading in this instruction interrupter the breaker must be in the open position. Wipe
book. away the lubrication on the lower stem of the vacuum inter-
rupter ( this is located under the anti-bellows spring, refer to
.
Figure 9) Check for indications of abnormal wear identified
by exposed copper on the silver plated surface, erosion or
C. INTERRUPTER AND CONTACT AREA pitting in the surface, or excessive discoloration due to heat.
If any of these conditions are present in more that one
(1) Vacuum Interrupter Contact Erosion location on the lower stem, the assembly should be re-
placed .
At each inspection, the vacuum interrupters should be
checked for contact erosion. This is accomplished by
Courtesy of NationalSwitchgear.com
P-69000 PV-26 Vacuum Circuit Breakers IB-69000
--
4 04
(2) Primary Resistance Check
f
This check is not required for routine maintenance, but
it is suggested after any major maintenance that requires
.
disassembly of any part of the primary circuit This check
o should be done after interrupter replacement.
To return an undamaged unit back to service, the stem VI. RECOMMENDED RENEWAL
must be relubricated with a light coat of Mobilegrease 28 PARTS AND REPAIR
contact lubricant.
) PROCEDURES
(3) Mechanical Adjustment of Interrupters
A. ORDERING INSTRUCTIONS
There are no adjustments required for routine mainte-
nance. (1) Order Renewal Parts from Powell Apparatus Service
Refer to the section on vacuum interrupter replacement Division (PASD) .
for details on how to install and adjust the interrupter (2) Always specify complete nameplate information,
assembly. Settings should not be adjusted unnecessarily. including:
a. Type
(4) Vacuum Integrity b. Serial Number
c. Rated Voltage
Refer to Page 11 for information on vacuum integrity d. Rated Amps
and testing of interrupters. e. Impulse Withstand
f. Control Voltage (for control devices and coils)
D. OPTIONAL MAINTENANCE
PROCEDURES (3) Specify the quantity and description of the part, and IB-
69000. If the part is in the tables of recommended
renewal parts, give its catalog number. If the part is not
(1) High Potential Tests in the tables, the description should be accompanied
by a marked illustration from this bulletin, a photo or a
These tests are not ordinarily required for routine sketch showing the part needed.
maintenance, but should be performed after a heavy fault
interruption or after the breaker has been in storage for an (4) Standard hardware, such as screws, bolts, nuts, wash-
extended time, especially in a damp location or other ers, etc., should be purchased locally. Hardware used
adverse environment. Both the High Voltage Insulation in bolted joints of conductors must be SAE Grade 5 or
Integrity and Control Voltage Insulation Integrity tests should better in order to insure proper clamping torque and
Courtesy of NationalSwitchgear.com
P-69000 PV-26 Vacuum Circuit Breakers
prevent overheating of the joints. Hardware should be Table IV. Control Devices (1)
plated to deter corrosion.
Control Closing Shunt Charging -
Anti Pump
Voltage Coil Trip Motor Relay
B. RECOMMENDED RENEWAL PARTS Left(2)
.
worn, broken or damaged part A stock of such parts
250 VDC 50026G04 50027G03 69335G02 -
PVKUP11D55 110(5)
120 VAC 50026G01 50027G01 69335G01 PVKUP11A55-120
minimizes service interruptions caused by breakdowns and 240 VAC 50026G02 50027G06 69335G02 PVKUP11A55-240
PVBA-2RV2-A2
1
1
Latch Check Switch
Motor Cutoff Switch Assembly 50756G03
C. REPLACEMENT PROCEDURES
Ground Shope Finger Assembly
05PV26250-0 1200A & 2000A
1 Contact 69058P 01
This section includes instructions for replacing all the
2 Spring 50703P24 parts recommended as renewal parts. Before attempting
any repair work, take note of safety practices outlined in
Auxiliary Switch Assembly 50933G05
Section II of this book.
1
Courtesy of NationalSwitchgear.com
P-69000 PV-26 Vacuum Circuit Breakers IB-69000
6. Close the breaker and measure the nut gap. (Refer to a. Remove front cover of breaker.
the previous section on vacuum interrupter contact b. Unplug the trip coil from the wiring harness.
Courtesy of NationalSwitchgear.com
P- 69000 PV-26 Vacuum Circuit Breakers IB-69000
c. Remove the two bolts holding the trip coil assem- f. Trip the breaker electrically several times to insure
bly to the breaker frame and remove the assembly. that the coil is functioning properly,
d. Bolt new assembly in place and plug it into the g. Replace front cover.
wiring harness .
e. With the breaker mechanism in the reset position, (5) Undervoltage Device Assembly
check the gap between the trip coil armature and
the trip lever extending from the trip shaft. This This assembly is located in the center part of the
gap should be between 1/4 inch and 5/16 inch. If mechanism area, just to the right of the main closing spring.
necessary, bend the trip lever slightly to achieve See Figure 20. To replace it:
.
this setting See Figure 19.
f . Trip the breaker electrically several times to insure a. Remove front cover of breaker.
that coil is functioning properly. b. Remove right hand main operating spring connect-
9- Replace front cover. ing rod. See section headed "Closing Spring
Removal and Slow Closing of Mechanism" under
Maintenance in this instruction book for procedures
for removing this rod.
c. Unplug the undervoltage device from the wiring
harness.
d. Remove the two bolts holding the undervoltage
device assembly to the breaker frame and remove
the assembly.
Courtesy of NationalSwitchgear.com
P-69000 PV-26 Vacuum Circuit Breakers
undervoltage device coil. b. Unplug the motor from the wiring harness.
Apply a DC voltage of 80% of the undervoltage c. Remove the two bolts holding the motor mounting
coil rating. The undervoltage device should pick bracket to the mechanism shelf and slide the motor
up and allow the breaker to close. Close and trip to the right, disconnecting the motor shaft from the
the breaker several times, using manual or shunt mechanism, and lift the motor out.
trip, to be sure that the vibration of breaker opera- d. Lubricate the end of the shaft of the new motor
tion does not cause the undervoitage device to liberally with Anderol 757 grease.
drop out improperly. If the device does drop out e. Position the new motor assembly in the circuit
during this test, rotate the knob at the bottom of breaker, being sure that the pin on the end of the
the device to the right in 1/8 turn steps until the drive shaft engages the slot in the mechanism
proper operation is obtained. This adjustment may shaft.
be fine turned by bending the tab at the base of f. Bolt the motor to the mechanism shelf and plug it
the beam spring up in 1/16 inch steps. See Figure into the wire harness.
21. g- Operate the circuit breaker several times to insure
that the motor operates smoothly.
h. Replace front cover.
Courtesy of NationalSwitchgear.com
P- 69000 PV- 26 Vacuum Circuit Breakers
9- Relays in 250VDC closing circuits are provided with (10) Ground Shoe Finger Assembly
dropping resistors to apply the proper voltage to
the relay coil. The resistor is mounted adjacent to The ground shoe assembly is located at the rear edge
the relay. It may be replaced by unplugging it from of the breaker floor pan under the center pole of the
the relay and unscrewing the mounting feet from breaker. See Figure 23. To replace it:
the breaker frame, replacing the resistor and
reassembling. a. Remove bolts holding the ground shoe to the bot-
h. Operate the breaker several times to insure that the tom pan.
relay functions properly. b. Insert new assembly from below the breaker floor
i. Replace front cover. pan.
c. Reinstall the two mounting bolts.
Courtesy of NationalSwitchgear.com
P-69000 PV-26 Vacuum Circuit Breakers IB-69000
moved. 062'
h. Operate breaker electrically several times to insure
that it is working.
.
I Replace front cover. Figure 25. Pin Retaining Ring
NOTES:
Courtesy of NationalSwitchgear.com
POWELL ELECTRICAL MANUFACTURING COMPANY
•
8550 MOSLEY DRIVE HOUSTON, TEXAS 77075 USA
PHONE (713) 944-6900 • FAX (713) 947-4453
Courtesy of NationalSwitchgear.com