Bee Papers Solution
Bee Papers Solution
Nov- Que: State and explain Kirchhoff’s Laws in context with DC circuits 3
2020 Solution:
June- Kirchhoff’s Current Law – Kirchhoffs Current Law or KCL, states that the “total
2019 current or charge entering a junction or node is exactly equal to the charge leaving the
node as it has no other place to go except to leave, as no charge is lost within the node“.
In other words the algebraic sum of ALL the currents entering and leaving a node must
be equal to zero, I(exiting) + I(entering) = 0. This idea by Kirchhoff is commonly known as
the Conservation of Charge.
Kirchhoff’s Voltage Law – Kirchhoffs Voltage Law or KVL, states that “in any closed
loop network, the total voltage around the loop is equal to the sum of all the voltage drops
within the same loop” which is also equal to zero. In other words the algebraic sum of all
voltages within the loop must be equal to zero. This idea by Kirchhoff is known as
the Conservation of Energy.
June- Que: Compare the resistive series and parallel circuit. 3
2019 Solution:
Series Circuit Parallel Circuit
So the Current of the circuit IL1 = 20/ (20+10) = 20/30 = 2/3 = 0.66A which is the same
current passing through 10 ohm.
Case -2 Only Current Source.
Norton’s Theorem
“Any linear circuit containing several energy sources and resistances can be replaced by
a single Constant Current generator in parallel with a Single Resistor”.
As far as the load resistance, RL is concerned this single resistance, RS is the value of the
resistance looking back into the network with all the current sources open circuited and
IS is the short circuit current at the output terminals.
Jan- Que: Derive an expression for equivalent resistances of a star connected network to 7
2020 transform into a Delta connected network.
Solution:
Jan- Que: Derive an expression for the voltage across the capacitor during charging through 7
2020 the resistor at any instant Vc= V(1-e-t/RC). Assume that RC series circuit is connected across
Jan- a DC supply of voltage V.
2019 OR
Derive the equations of capacitor voltage and circuit current in a series R-C circuit
connected to a DC supply through a switch. Assume that switch is initially open and it is
closed at time t=0 second.
Solution:
Consider a circuit consisting of resistance of R ohms and a capacitor of capacitance C
farads connected in series with switch S and a battery of V volts.
At the instant of closing the switch, No charge on the capacitor and Potential difference
across the capacitor is zero.
As a result, the entire voltage V acts momentarily across the resistors R and charging
current is maximum say Im.
Initial charging current, Im = V/R
Let at any instant during charging,
Vc = p.d. across the capacitor
i = charging current
qc = charge on the capacitor = CVc
According to KVL, Applied voltage = Voltage across capacitor+ voltage across resistor
V= Vc + iR
dq
V Vc R c
dt
d CVc d Vc
V Vc R V Vc RC
dt , dt
d Vc
V Vc RC
dt
dVc dt dVc dt
V Vc RC , V Vc RC
Integrating both the side
dVc dt
V V RC
c
t
loge
V Vc
K
RC
Where, K is a constant of integration. Its value can be determined from the initial
conditions. At the instant of closing the switch S,
t = 0, Vc = 0
log eV K
Putting the value of K= logeV
t t
loge
V Vc
loge
V Vc
log eV log eV
RC RC
V Vc t V Vc t
log e e RC
V RC V
t
t
Vc V 1 e
RC
Vc V 1 e
Where λ = CR is known as time constant.
Variation of charging current with time
V Vc
i
V – Vc = iR R
t
V V 1 e t
i V
i e
t
R R i Im e
Nov - A resistance of 10Ω is connected in series with two resistances each of the 15Ω arranged in 3
2020 parallel. What resistance must be shunted across this parallel combination so that total
current taken shall be 1.5 A with 20 V applied.
Solution:
Nov – Calculate the resistance of a 100 m length of wire having a uniform cross sectional area of 3
2020 0.02 mm2 and having resistivity of 40 µΩcm
Solution
Jan - A 100V,60 Watt bulb is to be operated from a 220V supply. What is the resistance to be 4
2020 connected in series with the bulb to glow normally?
Solution
June Consider the circuit shown in Figure. Reduce the portion of the circuit to the left of 7
- terminals a–b to (a) Thévenin equivalent and (b) a Norton equivalent. Find the current
2019 through R = 16 Ohm.
Solution
Nov - For the Wheatstone bridge diagram shown in Figure 1, obtain the current flowing through 7
2020 the 20Ω resistance using Thevenin's equivalent network.
Solution
UNIT-2: AC Circuits
GTU End Sem Exam Solution
Exam Question Marks
Nov Define the following terms for AC (alternating current) signal: 04
2020 (i) Crest Factor (ii) Form Fator (iii) Average Value (iv) RMS Value.
(i) Crest Factor/Peak Factor:
Crest factor is defined as the ratio of peak value to rms value of an alternating quantity
(current or voltage).
NOV A current of 5 A flows through a non-inductive resistance in series with a choking coil when 07
2020 supplied at 250V,50Hz. If the voltage across the resistance is 125 V and across the coil 200V,
calculate (i) impedance, reactance and resistance of the coil (ii) the power absorbed by the coil
(iii) and total power.
NOV Prove that the current in purely inductive circuit lags its voltage by 90° and average power 07
2020 consumption in pure inductor is zero.
NOV Write the comparison between series resonance and parallel resonance condition in AC circuit. 03
2020/
JAN
2020
NOV Derive the relation between line-voltage and phase-voltage for three-phase four wire star 07
2020/ connection network. Also, prove that the total three-phase power consumption in star
JAN connection is PT = √3 VL IL cos φ.
2020
JAN A single phase R-L-C circuit having resistance of 8Ω, inductance of 80mH and capacitance of 07
2020 100μF is connected across single phase ac 150 V , 50Hz supply. Calculate the current, power
factor and voltage drop across inductance and capacitance.
JAN Define the following terms in connection with AC waveforms: 03
2020 1. Q-Factor 2. Power Factor 3. Form factor.
1. Q-Factor:
2. Power Factor:
It is the ratio of active (true) power to apparent power. It is also defined as the cosine of the
angle between voltage and current signals.
3. Form Factor:
The ratio of the rms value to the average value of an alternating quantity (current or voltage) is
called Form Factor.
JAN Draw impedance triangle, Voltage triangle, Power triangle for single phase R-L series circuit. 04
2020 Impedance Triangle:
JAN With neat circuit diagram and a phasor diagram prove that two watt meters are sufficient to 07
2020/ measure total power in 3-phase system.
JUNE
2019
JUNE For series resonant circuit with brief description draw the phasor diagrams for following 03
2019 conditions (i) At resonant (ii) Below resonant (iii) Above resonant.
(i) At Resonance:
At the resonance condition XL=XC. The net impedance of the circuit is only resistance. Therefore,
R-L-C circuit behaves like a purely resistive circuit. The power factor of the circuit is Unity.
(ii) Below resonance:
At the frequencies below resonant frequency, XL<XC. The net impedance is capacitive in nature.
Therefore, the circuit acts like an R-C Series circuit. The power factor of the circuit is leading.
JUNE A series RLC circuit with L= 160 mH, C= 100 μF and R = 40 Ω is connected to a sinusoidal voltage 07
2019 V(t) = 40 Sinωt, with ω= 200 rad/sec. Find (i) What is the Impedance of the circuit. (ii) Let the
current at any instant in the circuit be I(t) = I0 Sin(ωt-Φ). Find I0 (iii) What is the Phase Φ ?
Solution:
Given Data: L=160 mH, C=100 μF, R=40 Ohm, Vm=40 V, ω= 200 rad/sec
XL= ωL = 200*160*10-3 =32 Ohm
Xc=1/ ωC = 1/(200*100*10-6) = 50 Ohm
I0 = Vm/Z = 0.911 Amp
Phase angle Φ = Cos-1(R/Z) = Cos-1(40/43.86) = 24.21° (leading)
JUNE A balanced star connected load of (4+j3) Ω per phase is connected to a balance 3 phase 400 V 07
2019 supply. Find the line current, power factor, active power and reactive power.
Solution:
Impedance per phase Zph = (R22+XL2)1/2= (16+9) ½ = 5 Ohm.
In star connection Line voltage = 1.732*Phase Phase Voltage VL = 1.732*Vph
Therefore, Vph = VL/1.732 = 400/1.732 = 230.94 V
In star connection Line current = Phase Current = Vph/Zph = 230.94/5 = 46.18 Amp
Power factor Cos Φ = R/Z = 4/5 = 0.8 (lagging)
Active power = 1.732*VL*IL*Cos Φ = 1.732*400*46.18*0.8 = 25594.80 Watt
Reactive Power = 1.732*VL*IL*Sin Φ = 1.732*400*46.18*0.6 = 19196.10 VAR
JUNE For A.C. sinusoidal current prove that Irms = 0.707 Im. 03
2019
JAN Define Amplitude, Frequency and Time period for alternating quantities. 03
2019
Amplitude:
Frequency:
Time period:
JAN The maximum values of voltage and current in a circuit are 400 V and 20 A respectively. Both 07
2019 the quantities are sinusoidal with 50 Hz frequency. The instantaneous values of voltage and
current at time t=0 second are 283 V and 10 A respectively (both increasing and positive).
Obtain the equations of voltage and current in this circuit at time ‘t’ second. Also find out the
active power consumption in the circuit.
JAN In a series R-L circuit, a voltage of 10 V at 50 Hz frequency produces a current of 750 mA. In 07
2019 the same circuit with same magnitude of applied voltage with a frequency of 75 Hz produces
a current of 500 mA. Find out the values of R and L in the circuit.
UNIT-3: Transformers
GTU End Sem Exam Solution
Exam Question Marks
Jan/2021 Que: Derive the EMF equation of single-phase transformer. 04
Nov/2020 Solution:
June/2019 The magnitude of induced emf is equal to the product of number of turns and
the rate of change of flux.
d
e N
dt
magnitudes of E2 and E1 depend upon the number of turns on the secondary and
primary respectively. If N2 > N1, then E2 > E1 (or V2 > V1) and we get a step-up
transformer. On the other hand, if N2 < N1, then E2 < E1 (or V2< V1) and we get a
step-down transformer. If load is connected across the secondary winding, the
secondary e.m.f. E2 will cause a current I2 to flow through the load. Thus, a
transformer enables us to transfer a.c. power from one circuit to another with a
change in voltage level.
Nov/2020 Explain various connections of three phase transformer with diagram. 07
June/2019 Solution:
(ii) delta-delta
The primary winding is star star (Y) connected with grounded neutral and the
secondary winding is delta connected.
This connection is mainly used in step down transformer at the substation end
of the transmission line.
The ratio of secondary to primary line voltage is 1/√3 times the transformation
ratio.
There is 30° shift between the primary and secondary line voltages.
(iv) delta-star
Nov/2020 State the difference in core type and shell type transformer with neat and clean 07
June/2019 construction diagram.
Solution:
Depending upon the manner in which the primary and secondary are wound
on the core, transformers are of two types viz., (i) core-type transformer and
(ii) shell-type transformer.
In a core-type transformer, half of the primary winding and half of the secondary
winding are placed round each limb as shown in Fig.
This reduces the leakage flux. It is a usual practice to place the low-voltage
winding below the high-voltage winding for mechanical considerations.
The choice of type (whether core or shell) will not greatly affect the efficiency
of the transformer. The core type is generally more suitable for high voltage and
small output while the shell-type is generally more suitable for low voltage and
high output.
June/2019 Explain voltage step-up and step-down operation in autotransformer with diagram. 04
Solution:
An autotransformer is a transformer where a part of the winding belongs to both
the primary winding and secondary winding of the transformer. Its operating
principle is the same as the conventional transformer, then the relation between
input and output voltages, input and output currents and the ratio of number of
turns between the primary and the secondary winding is the same.
Step-down autotransformer
If an alternating voltage is applied to points A and B, and the output voltage is
measured at points B and C, a lower voltage is obtained. This transformer is a
step-down auto transformer. In this case, the turn ratio = Ns/Np < 1.
Step-up autotransformer
If an alternating voltage is applied to points A and B, and the output voltage is
measured at points B and C, a higher voltage is obtained. This transformer is a
step-up autotransformer. In this case, the turns ratio is: Ns/Np > 1.
UNIT-4: Electrical Machines
GTU End Semester Exam Solution
Exam Question Marks
Nov Que: Why single-phase induction motor is not self starting while three-phase induction 4
2020 motor is self starting. Explain in brief.
Solution: A single-phase induction motor consists of a squirrel cage rotor and a stator
carrying a single-phase winding. When a single phase supply provide to stator winding, it
produces a flux (or field) which only alternating i.e. one which alternates along one space axis
only. It is not a synchronously revolving (or rotating) flux, as in the case of a two or three
phase stator winding, fed from a 2 or 3 phase supply. Now, alternating or pulsating flux acting
on a stationary squirrel cage rotor cannot produce rotation. That is why a single phase motor
is not self-starting.
Three-phase induction motor is self-starting, because winding displacement is 120 degrees for
each phase and supply also has 120 phase shift for 3-phase. It results in a unidirectional
rotating magnetic field is developed in air gap which causes 3-phase induction motor to self-
start.
Nov Que: Explain construction of Alternator with neat diagram. 7
2020
Jan Solution:
2020
June
2019
Construction:
1. Stator: It is the stationary part of the machine and is built up of sheet-steel laminations
having slots on its inner periphery. A 3-phase winding is placed in these slots and serves
as the armature winding of the alternator. The armature winding is always connected in
star and the neutral is connected to ground.
2. Rotor: The rotor carries a field winding which is supplied with direct current through two
slip rings by a separate d.c. source. This d.c. source (called exciter) is generally a small
d.c. shunt or compound generator mounted on the shaft of the alternator. Rotor
construction is of two types, namely;
(i) Salient (or projecting) pole type
(ii) Non-salient (or cylindrical) pole type
When the armature of a d.c. motor rotates under the influence of the driving torque, the
armature conductors move through the magnetic field and hence e.m.f. is induced in them as
in a generator The induced e.m.f. acts in opposite direction to the applied voltage V(Lenz’s
law) and in known as back or counter e.m.f. Eb.
The back e.m.f. Eb (= PΦZN/60 A) is always less than the applied voltage V, although this
difference is small when the motor is running under normal conditions. Consider a shunt
wound motor shown in Fig. When d.c. voltage V is applied across the motor terminals, the
field magnets are excited and armature conductors are supplied with current. Therefore,
driving torque acts on the armature which begins to rotate. As the armature rotates, back
e.m.f. Eb is induced which opposes the applied voltage V. The applied voltage V has to force
current through the armature against the back e.m.f. Eb. The electric work done in
overcoming and causing the current to flow against Eb is converted into mechanical energy
developed in the armature. It follows, therefore, that energy conversion in a d.c. motor is only
possible due to the production of back e.m.f. Eb.
Net voltage across armature circuit = V – Eb
If Ra is the armature circuit resistance, then, Ia = (V – Eb)/Ra
Nov Que: State the comparison of generator and motor action with respect to design and 4
2020 working principle. Draw the necessary diagram.
Solution:
Sr. Differentiating
Motor Generator
No. Property
An electric generator is a
An electric motor is a machine that
machine that converts
1 Definition converts electrical energy to
mechanical energy to electrical
mechanical energy.
energy.
Electric motor follows Fleming’s Electric generator follows
2 Rule
left-hand rule. Fleming’s right-hand rule.
The working principle of a motor is
based on the current-carrying The working principle of
3 Principle conductor that experiences a force generator is based on
when it is kept in the magnetic electromagnetic induction.
field.
The shaft of an electric motor is The shaft of an electric
Driving force for driven by a magnetic force which is generator is connected to the
4
shaft developed between the armature rotor which is driven by a
and field. mechanical force.
In a generator, current is
In a motor, current is supplied to the
5 Current Usage produced in the armature
armature winding.
winding.
Ceiling fans, cars, etc. are all In power stations, generator is
6 Example
examples of motor. used to generate electricity.
Nov Que: Write working principle of DC motor with neat diagram. 7
2020
Jan Solution:
2020
Basic principle: A machine that converts d.c. power into mechanical power is known as a d.c.
motor. Its operation is based on the principle that when a current carrying conductor is placed
in a magnetic field, the conductor experiences a mechanical force. The direction of this force
is given by Fleming’s left hand rule and magnitude is given by;
F = BIl newtons
Basically, there is no constructional difference between a d.c. motor and a d.c. generator. The
same d.c. machine can be run as a generator or motor.
Consider a part of a multipolar d.c. motor as shown in Fig. When the terminals of the motor
are connected to an external source of d.c. supply:
(i) the field magnets are excited developing alternate N and S poles;
(ii) the armature conductors carry currents. All conductors under N-pole carry currents in one
direction while all the conductors under S-pole carry currents in the opposite direction.
Suppose the conductors under N-pole carry currents into the plane of the paper and those
under S-pole carry currents out of the plane of the paper as shown in Fig. Since each armature
conductor is carrying current and is placed in the magnetic field, mechanical force acts on it.
Referring to Fig. and applying Fleming’s left hand rule, it is clear that force on each
conductor is tending to rotate the armature in anticlockwise direction. All these forces add
together to produce a driving torque which sets the armature rotating. When the conductor
moves from one side of a brush to the other, the current in that conductor is reversed and at
the same time it comes under the influence of next pole which is of opposite polarity.
Consequently, the direction of force on the conductor remains the same.
Nov Que: A d-c generator has an e.m.f of 200 volts and provides a current of 10 amps. How 3
2020 much energy does it provide each minute?
Solution:
Energy = Power x Time
Power = V x I
= 200 x 10
= 2000 watts
Energy = 2000 x 60
= 120,000 Joules or 120 kJ
Demerits:
1) The power factor of the motor is very low during the light load condition.
2) The three-phase induction motor is constant speed motor. The change in speed of the motor
is very low during different loading conditions. So, the speed control of IM is difficult.
3) Single-phase induction motor is not self-starting. It requires some auxiliary for stating.
4) The motor cannot use in such applications where high starting torque is necessary like
traction and lifting weight.
To see how rotating field is produced, consider a 2-pole, 3-phase winding as shown in Fig. (i).
The three phases X, Y and Z are energized from a 3-phase source and currents in these phases
are indicated as Ix, Iy and Iz [See Fig. (ii)]. Referring to Fig. (ii), the fluxes produced by these
currents are given by:
Here Φm is the maximum flux due to any phase. Fig. (1) shows the phasor diagram of the
three fluxes. We shall now prove that this 3-phase supply produces a rotating field of constant
magnitude equal to 1.5 Φm.
(i) At instant 1 [See Fig. (ii) and Fig. (iii)], the current in phase X is zero and currents in
phases Y and Z are equal and opposite. The currents are flowing outward in the top
conductors and inward in the bottom conductors. This establishes a resultant flux towards
right. The magnitude of the resultant flux is constant and is equal to 1.5 Φm as proved under:
The phasor sum of - Φy and Φz is the resultant flux Φr [from above phasor diagram]. It is
clear that:
(ii) At instant 2, the current is maximum (negative) in Φy phase Y and 0.5 maximum
(positive) in phases X and Z. The magnitude of resultant flux is 1.5 Φm as proved under:
At instant 2, ωt = 30°. Therefore, the three fluxes are given by;
(iii) At instant 3, current in phase Z is zero and the currents in phases X and Y are equal and
opposite (currents in phases X and Y are 0.866 × max. value).
(iv) At instant 4, the current in phase X is maximum (positive) and the currents in phases Y
and Z are equal and negative (currents in phases Y and Z are 0.5 × max. value).
This establishes a resultant flux downward as shown under:
Note that the resultant flux is downward i.e., it is displaced 90° clockwise from position 1.
June Que: Classify and compare various DC motor. 4
2019
Solution:
There are three types of d.c. motors characterized by the connections of field winding in
relation to the armature viz.:
(i) Shunt-wound motor in which the field winding is connected in parallel with the
armature [See Fig. 1]. The current through the shunt field winding is not the same
as the armature current. Shunt field windings are designed to produce the
necessary m.m.f. by means of a relatively large number of turns of wire having
high resistance. Therefore, shunt field current is relatively small compared with
the armature current.
Fig.1
(ii) Series-wound motor in which the field winding is connected in series with the
armature [See Fig. 2]. Therefore, series field winding carries the armature current.
Since the current passing through a series field winding is the same as the
armature current, series field windings must be designed with much fewer turns
than shunt field windings for the same m.m.f. Therefore, a series field winding has
a relatively small number of turns of thick wire and, therefore, will possess a low
resistance.
Fig. 2.
(iii) Compound-wound motor which has two field windings; one connected in
parallel with the armature and the other in series with it. There are two types of
compound motor connections (like generators). When the shunt field winding is
directly connected across the armature terminals [See Fig. 3], it is called short-
shunt connection. When the shunt winding is so connected that it shunts the series
combination of armature and series field [See Fig. 4], it is called long-shunt
connection.
Fig. 3 Fig. 4
June Que: Give the classification of Induction motor. 3
2019
Solution:
There are mainly two types of induction motor on the basis of power supply, Single Phase
Induction Motor and Three Phase Induction Motor.
i. Single phase induction motor may be classified on the basis of their construction and
starting methods. On this basis, they can be further categorized into following types:
1. Split Phase Induction Motor
2. Capacitor Start Induction Motor
3. Capacitor Start Capacitor Run Induction Motor
4. Shaded Pole Induction Motor
ii. A three phase induction motor classified on the basis of its rotor construction. On this
basis, they can be further categorized into following types:
1. Squirrel Cage Induction Motor
2. Wound Rotor or Slip Ring Induction Motor
June Que: Explain the working of single phase induction motor with diagram. 7
2019
Solution:
When the stator winding (distributed one as stated earlier) carries a sinusoidal current (Being
fed from a single-phase supply), a sinusoidal space distributed mmf, whose peak or maximum
value pulsates (alternates) with time, is produced in the air gap. This sinusoidal varying flux
(φ ) is the sum of two rotating fluxes or fields, the magnitude of which is equal to half the
value of the alternating flux (φ / 2), and both the fluxes rotating synchronously at the speed, in
opposite directions.
The first set of figures show the resultant sum of the two rotating fluxes or fields, as the time
axis (angle) is changing from θ = 0° to π°(180).
The above figure shows the alternating or pulsating flux (resultant) varying with time or
angle.
The flux or field rotating at synchronous speed, say, in the anticlockwise direction, i.e. the
same direction, as that of the motor (rotor) taken as positive induces EMF (voltage) in the
rotor conductors. The rotor is a squirrel cage one, with bars short circuited via end rings. The
current flows in the rotor conductors, and the electromagnetic torque is produced in the same
direction as given above, which is termed as positive (+ve). The other part of flux or field
rotates at the same speed in the opposite (clockwise) direction, taken as negative. So, the
torque produced by this field is negative (-ve), as it is in the clockwise direction, same as that
of the direction of rotation of this field. Two torques are in the opposite direction, and the
resultant (total) torque is the difference of the two torques produced.
Let the flux φ1 rotate in anti clockwise direction and flux φ2 in clockwise direction. The flux
φ1 will result in the production of torque T1 in the anti clockwise direction and flux φ2 will
result in the production of torque T2 In the clockwise direction.
At standstill, these two torques are equal and opposite and the net torque developed is zero.
Therefore, single-phase induction motor is not self-starting. Note that each rotating field tends
to drive the rotor in the direction in which the field rotates.
Now assume that the rotor is started by spinning the rotor or by using auxiliary circuit, in say
clockwise direction. The flux rotating in the clockwise direction is the forward rotating flux
(φf) and that in the other direction is the backward rotating flux (φb). The slip w.r.t. the
forward flux will be
The rotor rotates opposite to the rotation of the backward flux. Therefore, the slip w.r.t. the
backward flux will be
Thus for forward rotating flux, slip is s (less than unity) and for backward rotating flux, the
slip is 2 − s (greater than unity). Since for usual rotor resistance/reactance ratios, the torques
at slips of less than unity are greater than those at slips of more than unity, the resultant torque
will be in the direction of the rotation of the forward flux. Thus if the motor is once started, it
will develop net torque in the direction in which it has been started and will function as a
motor.
June Que: State significance of the back emf in DC motor. 3
2019
Solution: The presence of back e.m.f. makes the d.c. motor a self-regulating machine i.e., it
makes the motor to draw as much armature current as is just sufficient to develop the torque
required by the load.
Armature current, Ia = (V – Eb)/Ra
(i) When the motor is running on no load, small torque is required to overcome the
friction and windage losses. Therefore, the armature current Ia is small and the
back e.m.f. is nearly equal to the applied voltage.
(ii) If the motor is suddenly loaded, the first effect is to cause the armature to slow
down. Therefore, the speed at which the armature conductors move through the
field is reduced and hence the back e.m.f. Eb falls. The decreased back e.m.f.
allows a larger current to flow through the armature and larger current means
increased driving torque. Thus, the driving torque increases as the motor slows
down. The motor will stop slowing down when the armature current is just
sufficient to produce the increased torque required by the load.
(iii) If the load on the motor is decreased, the driving torque is momentarily in excess
of the requirement so that armature is accelerated. As the armature speed
increases, the back e.m.f. Eb also increases and causes the armature current Ia to
decrease. The motor will stop accelerating when the armature current is just
sufficient to produce the reduced torque required by the load.
It follows, therefore, that back e.m.f. in a d.c. motor regulates the flow of armature current
i.e., it automatically changes the armature current to meet the load requirement.
UNIT-5: Electrical Installations
GTU End Sem Exam Solution
Exam Question Marks
June Que: State function of various parts of HT cable 03
2019 Answer:
Cores/Conductors –
It consists of one central core or a number of cores of tinned stranded copper or
aluminum conductors.
Conductors are used in stranded form to provide flexibility
Conductor numbers are 3, 7, 19, 37 and so on.
Insulation
The satisfactory operation of cable depends to a great extent upon the characteristics of
insulation.
The insulation is provided according to voltage to be withstood by cable.
Bedding (jute)- It is used to protect metallic sheet against corrosion and mechanical injury
from armouring.
A pit is dug about 4 meters deep, and the earth electrode is placed in such a way that its
face is vertical. The space around the plate is filled with layers of charcoal and salt for a
minimum thickness of 15 cm. The electrode or plate is connected to GI pipe of 12.7 mm
diameter for carrying GI each wire for connection to earth electrode. The earth wire is
securely bolted to the earth plate with the help of bolt, nut, washer and GI thimble, the
details of which is shown in the diagram.
It should be remembered that the nut and bolts thimble and washers must be of copper
for copper plate and GI for galvanized earth plate or electrode. The pit filled with charcoal
and salt is also connected with a pipe for carrying water from concrete work so that area
for the purpose of increasing dampness and moisture which ultimately reduces earth
resistance. The cement work is covered with iron plate for periodic opening. It is better to
have an independent earth plate in domestic installation.
Figure: Diagram of Plate Earthing
June Que: What is power factor and why improvement is required in that? 03
2019 Answer:
Power factor is the ratio of active power consumed by the load to the apparent power
demanded by the load.
The poor power factor leads to increased current in the conductor.
The increased current causes more losses in the current carrying conductor resulting into
poor efficiency.
Due to this, the utility imposes additional charges on certain consumer as a penalty of poor
power factor.
Hence, it is necessary to improve the power factor for certain consumers.
The improvement of power factor is very important for both consumers and generating
stations as discussed below :
(i) For consumers. A consumer* has to pay electricity charges for his maximum demand in
kVA plus the units consumed. If the consumer imporves the power factor, then there is a
reduction† in his maximum kVA demand and consequently there will be annual saving due
to maximum demand charges. Although power factor improvement involves extra annual
expenditure on account of p.f. correction equipment, yet improvement of p.f. to a proper
value result in the net annual saving for the consumer.
(ii) For generating stations. A generating station is as much concerned with power factor
improvement as the consumer. The generators in a power station are rated in kVA but the
useful output depends upon kW output. As station output is kW = kVA × cos φ, therefore,
number of units supplied by it depends upon the power factor. The greater the power
factor of the generating station, the higher is the kWh it delivers to the system. This leads
to the conclusion that improved power factor increases the earning capacity of the power
station
June Que: State and explain in brief important electrical characteristics of battery. 04
2019 Answer:
There are three important characteristics of an accumulator (or storage battery) are: 1.
Voltage 2. Capacity 3. Efficiency
1. Voltage:
The value of emf of a cell does not remain constant but varies with the change in specific
gravity of electrolyte, temperature, and the length of time since it was last charged.
2. Capacity:
There are two types of capacities of a battery.
(i) Ampere – hour capacity: It is the amount of energy which can be supplied by it. It applies
only to a certain range of load current. Thus, it is the product of the rated current during
discharge and the number of hours.
Mathematically,
𝐴 − ℎ 𝑐𝑎𝑝𝑎𝑐𝑖𝑡𝑦 = 𝐼𝑑 𝑇𝑑
(ii) Watt-hour capacity: The product of the average battery voltage during the discharge
and ampere -hour capacity is called the watt-hour capacity of the battery.
Mathematically,
𝑊 − ℎ 𝑐𝑎𝑝𝑎𝑐𝑖𝑡𝑦 = 𝑉𝑑 𝐼𝑑 𝑇𝑑
Where Vd is the average voltage of the battery during discharge
3. Efficiency:
The efficiency of the battery is the ration of output of the battery during discharging to the
input to the battery during discharging. There are two ways of defining the efficiency of the
battery.
(i) Ampere-hour efficiency: The ratio of output ampere-hour during discharging to the input
ampere-hour during charging of the battery is called ampere-hour efficiency of the battery.
𝐼𝑑 𝑇𝑑
𝜂𝐴−ℎ = × 100
𝐼𝑐 𝑇𝑐
(ii) Watt-hour efficiency: The ratio of output watt-hour during discharging to the input
watt-hours during charging of the battery is called watt-hour efficiency of the battery. It is
also known as the energy efficiency of the battery.
Mathematically,
𝐼𝑑 𝑉𝑑 𝑇𝑑
𝜂𝑊−ℎ = × 100
𝐼𝑐 𝑉𝑐 𝑇𝑐
June Que: Calculate the electricity bill amount for a month of April, if 4 bulbs of 40 W for 5 h, 07
2019 4 tube lights of 60 W for 5 h, a TV of 100 W for 6 h, a washing machine of 400 W for 3 h,
a water pump of 0.5 HP for 15 minutes are used per day. The cost per unit is Rs 3.50.
Consider 1 HP = 746 watts
Answer:
Let us calculate the energy utilization per day.
Energy utilized by bulbs = no. of bulb x wattage of bulb x duration of operation
Energy utilized by bulbs = 4 x 40 x 5 = 800 Wh
Energy utilized by tube lights = 4 x 60 x 5 = 1200 Wh
Energy utilized by TV = 100 x 6 = 600 Wh
Energy utilized by washing machine = 400 x 3 = 1200 Wh
Energy utilized by Water pump = 0.5 * 746 * 15/60 = 93.25 Wh
Total Energy utilized on per day basis = 3,893.25 Wh = 3.893 kWh or units per day
Total Energy utilized for the month of April = 3.893 * 30 = 116.8 kWh
The electricity bill amount for the month of April is Rs. 408.8.
Nov Que: Discuss types of cables used for residential and commercial wiring. 04
2020 Answer:
In residential and commercial wiring, low tension cables are employed. These cables have
voltage withstanding capacity upto 1000V. Depending on the type of insulation employed,
different types of cables are enlisted as follows:
1. Vulcanized Indian Rubber (VIR) insulated cables.
2. Tough rubber sheathed (TRS) or cabtyre sheathed (CTS) cables.
3. Lead sheathed cables.
4. Polyvinyl chloride (PVC) cables.
5. Weatherproof cables.
6. Flexible cords and cables.
7. XLPE cables.
8. Multi-strand cables.
TRS cables
Nov Que: Explain the construction of the lead-acid battery with neat diagram 04
2020 Answer:
The various parts of the lead acid battery are as follows:
1. Positive Plate or Anode: It is lead peroxide (PbO2) plate of chocolate, dark brown color.
2. Negative Plate or Cathode: It is made up of pure lead (Pb) which is grey in color.
3. Electrolyte: For necessary chemical action, aqueous solution of sulphuric acid (H2SO4) is
used as an electrolyte.
4. Separators: The positive and negative plates are arranged in groups and are placed
alternately. The separators are used to prevent them from coming in contact with each
other short circuiting the cell.
5. Container: The entire assembly of plates along with the solution is placed in the plastic
or ceramic container.
6. Bottom blocks: To prevent short circuiting of cell due to active material fallen from the
plates, the space known as bottom blocks is provided at the bottom of the container.
7. Plate Connector: The number of negative and positive plates are assembled alternately.
To connect positive plates together (or negative plates together) separate connectors are
used which are called plate connectors. The upward connection of plates are nothing but
the terminals of the cell.
8. Vent Plug: These are made of rubber and screwed to the cover of the cell. Its function is
to allow the escape of gases and prevent escape of the electrolyte.
Jan 2019 Que: Give a list of safety devices used for home appliances. 03
Answer:
Following is the list of safety devices used for home appliances:
1. Fuse
2. Miniature Circuit Breaker (MCB)
3. Earth Leakage Circuit Breaker (ELCB)
4. Residual current devices (RCDs)
In addition to above, following devices can also be used for protection:
5. Ground fault circuit interrupters (GFCIs)
6. Arc fault circuit breakers (AFCBs)
7. Surge protection devices (SPDs)
Jan 2019 Que: Why the consumers should improve their power factor? 04
Answer:
The consumer should Improve their power factor in installation as it presents several
technical and economic advantages, notably in the reduction of electricity bills.
The poor power factor leads to increased current in the conductor.
The increased current causes more losses in the current carrying conductor resulting into
poor efficiency.
Improving the PF can maximize current-carrying capacity, improve voltage to equipment,
reduce power losses, and lower electric bills.
Jan 2019 Que: What is MCCB? Where is it used? 03
Answer:
The Moulded Case Circuit Breaker (MCCB) provides overload and short circuit protection
to normal service apart from serving as a circuit breaker. The overload and instantaneous
tripping element are adjustable over wide range. This makes it ideal for distribution
applications.
Jan 2019 Que: Compute the monthly energy charges for an air conditioner having consumption of 04
2 kW. Daily usage of the air conditioner is 10 hours. Energy charges are Rs 8 per unit.
Answer:
Let us calculate the energy utilization of an air conditioner (AC) per day.
Energy utilized by AC per day = Consumption of AC x duration of operation of AC
Energy utilized by AC per day = 2kW x 10 hours = 20 kWh (units)
Considering an average month of 30 days,
Energy utilized by AC per month = 20 kWh x 30 days = 600 kWh (units)
Since the energy charges per units are Rs. 8 per unit. The total electricity bill of AC for the
month = 600 kWh x Rs. 8/- per unit = Rs. 4800
Jan 2019 Que: Write a short note on Miniature Circuit Breaker (MCB) 04
Answer:
MCB is a device which operate on the two principles for the protection against overload
and short circuit:
1. Thermal for normal overload protection
2. Magnetic for short circuit protection
The thermal operation is achieved by bimetallic strip, which deflected when heated by any
overcurrent flowing through it. In doing so, it releases latch mechanism and causes the
contact to open.
It possesses inverse time-current characteristics i.e. greater the current short the time
required to operate the MCB.
When the short circuit occurs, the rising current energizes the solenoid operating plunger
to strike the trip lever causing immediate release of the latch mechanism. Rapidity of the
magnetic solenoid operation causes instantaneous opening of contacts.
Application of MCB:
MCBS are required in homes, offices, shops, distribution boards for protection of individual
circuit and complete wiring system.
MCBs are slightly expensive than fuses but this is offset by the fact that no cost is involved
in resetting them.
Jan 2019 Que: Write a short note on Earth Leakage Circuit Breaker (ELCB) 04
An Earth Leakage Circuit Breaker (ELCB) is current operated device designed to operate
when leakage current exceeds a predetermined value. It essentially consists of an operating
coil and a trip mechanism which operates contacts controlling the supply to the circuit
concerned.
Consider a single-phase circuit. The two supply wires i.e. phase and neutral are fed through
separate winding of current transformer as shown in the figure. Another winding controls
the tripping mechanism. The current through the phase wire is equal to the current in the
neutral wire i.e. 𝐼𝑝 = 𝐼𝑛 .
A test button is included in the ELCB testing the trip mechanism. ELCB should be tested by
pressing the “Test Switch”, at least once in a month. If the ELCB does not trip even after
pressing the “Test Switch”, it means that the ELCB has become faulty and will not trip even
if the human body comes in contact with live conductor.
Jan 2020 Que: Classify different types of cables with reference to voltage and insulation materials. 03
Answer:
The underground cable is classified mainly as follows:
1. According to the voltage level
2. According to the insulation material used.
Usually, classification according to voltage level is preferred.
Jan 2020 Que: Explain the process of charging and discharging of Lead acid cell. 07
Answer:
When a lead acid cell is ready for use, its positive plate is of lead peroxide (PbO2)- chocolate
brown in color and negative plate is of spongy lead (Pb)- grey in color. Both the plates are
immersed in a dilute sulphuric acid of specific gravity 1.28. When the load is connected
across the terminals of the cell, it starts delivering current to the load and this process is
called as discharging of cell. In this process chemical energy is converted into electrical
energy.
Operation of Lead Acid Battery
During recharging :
Plates regain their original composition
Specific gravity of acid become 1.28
Terminal voltage increases from 1.8 V to 2.0 V
Electrical energy converted to chemical energy which is stored in cell.
Jan 2020 Que: Compare MCB and ELCB. 03
MCB ELCB
The MCB is only installed for one cable The ELCB is installed for both cables i.e. phase
i.e. phase cable and neutral.
MCB only functions as security when ELCB functions when there is electrocution or
there is overcurrent or short circuit. electric shock or when there is current surge.
The MCB cannot work for human The ELCB works primarily for human safety.
safety.
The MCB cannot detect leakage The ELCB can detect leakage current and
current. provide protection against it.
It is relatively cheap than ELCB It is relative expensive that MCB.
Jan 2020 Que: Write safety precautions for electrical Applications. 04
Answer:
Following precautions should be taken while working with the electricity:
1. Never work with bare feet. It is better to wear rubber shoes while working.
2. Use safety belt before starting the work on the electric pole or tower.
3. Phase or positive wire should always be connected through the switch.
4. Before replacing the blown fuse, always switch off the main switch.
5. Do not disconnect the flexible wire of an electrical apparatus from the socket by pulling
it out.
6. Do not touch electrical installation without any purpose.
7. Always keep earth connection in good condition.
8. Do not charge the battery in a dark room. The wrong connection may lead to hazard.
9. In case of fire, do not throw water on a live wire and equipment, it is dangerous. The
best remedy is to disconnect the main supply immediately.
1. Static capacitor.
The power factor can be improved by connecting capacitors in parallel with the equipment
operating at lagging power factor. The capacitor (generally known as static condenser)
draws a leading current and partly or completely neutralizes the lagging reactive
component of load current. This raises the power factor of the load. For three-phase loads,
the capacitors can be connected in delta or star as shown in Fig. Static capacitors are
invariably used for power factor improvement in factories.
2. Synchronous condenser
A synchronous motor takes a leading current when over-excited and, therefore, behaves
as a capacitor. An over-excited synchronous motor running on no load is known as
synchronous condenser. When such a machine is connected in parallel with the supply, it
takes a leading current which partly neutralizes the lagging reactive component of the load.
Thus, the power factor is improved.
3. Phase advancers.
Phase advancers are used to improve the power factor of induction motors. The low power
factor of an induction motor is due to the fact that its stator winding draws exciting current
which lags behind the supply voltage by 90o. If the exciting ampere turns can be provided
from some other a.c. source, then the stator winding will be relieved of exciting current,
and the power factor of the motor can be improved. This job is accomplished by the phase
advancer which is simply an a.c. exciter. The phase advancer is mounted on the same shaft
as the main motor and is connected in the rotor circuit of the motor. It provides exciting
ampere turns to the rotor circuit at slip frequency. By providing more ampere turns than
required, the induction motor can be made to operate on leading power factor like an over-
excited synchronous motor.