Sheet 1
Sheet 1
3. A 40 kVA, 3300/240V, 50 Hz, single-phase transformer has 660 turns on the primary.
Determine:
a) The number of turns on the secondary.
b) The maximum value of flux in the core.
c) The approximate value of primary and secondary full load currents.
5. The no-load voltage ratio of a single-phase transformer is 1200/440. Find the number
of turns in each winding if the maximum flux is set to 0.075 weber.
7. 100 kVA single-phase transformer with secondary voltage of 200 V, the primary and
secondary windings have 200 and 40 turns respectively. Calculate:
a) The primary applied voltage.
b) The primary and secondary rated currents.
c) The secondary current when a load of 25 kW with 0.8 power factor is connected.
Page 1 of 2
8. A 50 kVA, 400/2000V, single-phase transformer delivers a load of 40 kVA at 2000 V
and 0.8 PF lagging. Assume the transformer is ideal. Find:
a) The load impedance.
b) The load impedance referred to primary.
9. A single-phase 10:1 ideal transformer has a primary voltage of 39.8 kV and a primary
power of 1000 kVA at 0.8 PF lagging Find the load impedance connected to the
secondary winding.
10. Calculate the turns ratio, voltage, and volt-ampere rating of an ideal transformer so
that maximum power is transferred to a resistive load of 1ꭥ from a source with internal
voltage of 250 V and series resistance of 36 Ω.
12. Single phase power system consists of a 480 V, 60 Hz generator supplying a load
Zload = 4 + j3 Ω through a transmission line of impedance Zline = 0.18 + j0.24 Ω.
a) If the power system is exactly as described above; determine the transmission loss
and the voltage at the load terminals.
b) If a 1:10 ideal transformer is placed between the generator and transmission line
and another 10:1 transformer is placed between transmission and load. Determine
the transmission loss and the voltage at the load terminals.
Page 2 of 2