This document provides guidelines for building masonry (block) walls in Wildomar, California. It states that a building permit is required for any block wall over 3 feet high and includes a site plan submittal requirement. This standard does not apply to retaining walls, which require a site plan and structural calculations by a licensed engineer. The document also lists inspection requirements and notes for the wall design, including limitations on grade differentials, grout placement, rebar specifications, and other construction details.

Uploaded by

INEEMATE
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
30 views1 page

Block Wall Structure PDF

This document provides guidelines for building masonry (block) walls in Wildomar, California. It states that a building permit is required for any block wall over 3 feet high and includes a site plan submittal requirement. This standard does not apply to retaining walls, which require a site plan and structural calculations by a licensed engineer. The document also lists inspection requirements and notes for the wall design, including limitations on grade differentials, grout placement, rebar specifications, and other construction details.

Uploaded by

INEEMATE
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

CITY OF WILDOMAR

COMMUNITY DEVELOPMENT
DEPARTMENT OF BUILDING AND SAFETY

MASONRY (BLOCK) WALL


03-2018
A building permit is required for any masonry (block) wall that is over 3 feet high.
Please provide a site-plan of your property on the back of this handout.
This standard is not for Retaining Walls.
For Retaining Walls please provide a Site Plan with Structural Calculations by a Licensed Engineer.

NOTES:
1. This design does not allow grade differentials of more than 6” on opposing sides of the wall. This is not a
retaining wall.
2. Grout ONLY the cells containing rebar. This wall is NOT designed for all cells to be grouted.
3. All rebar to be ASTM spec. A615, Grade 40 minimum.
4. All rebar lap splices to be 24” minimum.
5. All masonry units to be ASTM C-90 Grade N.
6. Rebar to be centered in masonry cells.
7. No water course or natural drainage shall be obstructed.
8. Fence heights are regulated —Consult Planning.
The following inspections are required:
1. FOOTING: Excavation trench clean with steel in place and supported 3” above and away from the surrounding earth/dirt.
2. REBAR/PRE-GROUT: Bond beam rebar and vertical rebar in place – inspection prior to placing grout.
3. FINAL: after grout is placed — prior to any decorative cap placement.
DISCLAMIER: Alternate designs may be possible when provide with an engineered analysis. Use of this standard design is at the user’s risk and carries no implied or inferred
guarantee against failure or defects.