Report CT Test 560-GT-03

The document reports the test results of a current transformer with the following key details: 1. The current transformer was manufactured by KWK INSTRUMENTS and has a rated current of 500A. 2. Test results are provided for the secondary winding resistance, excitation characteristics, turn ratio accuracy, and phase angle accuracy across various load currents. 3. All test results were within specified tolerances for proper current transformer performance according to standard IEC 61869-2.

Uploaded by

PrfstBayu 21
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
15 views6 pages

Report CT Test 560-GT-03

The document reports the test results of a current transformer with the following key details: 1. The current transformer was manufactured by KWK INSTRUMENTS and has a rated current of 500A. 2. Test results are provided for the secondary winding resistance, excitation characteristics, turn ratio accuracy, and phase angle accuracy across various load currents. 3. All test results were within specified tolerances for proper current transformer performance according to standard IEC 61869-2.

Uploaded by

PrfstBayu 21
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

PT.

INDOTURBINE REPORT (560 -GT-3)

4.7 CT - ANALYZER

Manufacturer KWK INSTRUMENT Class 1


Type K6 P5 Frequence 50 Hz
Ipn 500.0 A Ext Ipn 120 %
Isn 5.0 A Tap R
Rated Burden 150.0.VA / 0.80 Phase R
Operating Burden 150.0 VA / 0.80
Application Metering

4.7.1 SECONDARY WINDING RESISTANCE


Test Point R-m eas ( 30 °C) R-ref ( 75°C ) R-meas ( 30 °C)+ Rlead R-ref ( 75°C )+Rlead
CT Phase R 0.222 Ω 0.260 Ω 0.222 Ω 0.260 Ω
CT Phase S 0.224 Ω 0.262 Ω 0.224 Ω 0.262 Ω
CT Phase T 0.270 Ω 0.316 Ω 0.270 Ω 0.316 Ω

4.7.2 EXCITATION
Results at rated Results at operating
Test Point Ls Kr Lm burden (150.00 VA) burden (150.00 VA)
FS Fsi FS Fsi
Phase R 0.010197 H 25.94% 0.563461 H 1.57 1.34 1.57 1.34
Phase S 0.010201 H 26.12% 0.563321 H 1.57 1.34 1.57 1.34
Phase T 0.010172 H 25.87% 0.562296 H 1.56 1.32 1.56 1.32
Stndard IEC 61869-2
Test Point V-Kn I-Kn εci (@ FS=2)Ts εci (@ FS=2)Ts
Phase R 36.596 V 0.3809 A 27.83% 0.111 s 27.83% 0.111 s
Phase S 36.596 V 0.3807 A 27.85% 0.111 s 27.85% 0.111 s
Phase T 36.596 V 0.3805 A 28.34% 0.110 s 28.34% o.110 s

4.7.3 RATIO
Result at rated burden (150.00 VA) Result at Operating burden (150.00 VA)
Test Point Turn Ratio εt Polarity
Ratio ε Δφ εc Ratio ε Δφ εc
Phase R 98.0046 -19954% OK 500.0 : 4.9125 -17496% 95.32 min 3.2580 % 500.0 : 4.9125 -17496% 95.32 min 3.2580 %
Phase S 98.0053 -1.9947% OK 500.0 : 4.9123 -17531 95.23 min 3.2576% 500.0 : 4.9123 -17531 95.23 min 3.2576%
Phase T 97.9967 -2.0034% OK 500.0 : 4.9118 -1.764% 97.22 min 3.3117% 500.0 : 4.9118 -1.764% 97.22 min 3.3117%
Date: Checked by:

25 Sept 2023 Syahril, Amin

36
PT. INDOTURBINE REPORT (560 -GT-3)
Residual magnetisme
Residual Flux
Residual Magnetisme

4.7.4 EXCITATION
Phase R

Phase S

Phase T

37
PT. INDOTURBINE REPORT (560 -GT-3)

4.7.5 CURRENT RATIO ERROR IN % AT % OF RATED CUCCRENT


Phase R

Phasa S

Phase T

Date: Checked by:

25 Sept 2023 Syahril, Amin

38
PT. INDOTURBINE REPORT (560 -GT-3)
4.7.6 PHASE IN MIN AT % OF RATED CURRENT
Phase R

Phase S

Phase T

Date: Checked by:

25 Sept 2023 Syahril, Amin

39
PT. INDOTURBINE REPORT (560 -GT-3)
4.7.7 CURRENT RATIO IN % AT % RATED CURRENT
Phase R

Phase S

Phase T

Date: Checked by:

25 Sept 2023 Syahril, Amin

40
PT. INDOTURBINE REPORT (560 -GT-3)
4.7.8 PHASE IN MIN AT % RATED CURRENT
Phase R

Phase S

Phase T

Date: Checked by:

25 Sept 2023 Syahril, Amin