Bu2500 en 4319 Desk
Bu2500 en 4319 Desk
2 BU 2500 en-4319
Table of Contents
Table of Contents
1 Introduction ................................................................................................................................................. 6
1.1 General .............................................................................................................................................. 6
1.1.1 Documentation ..................................................................................................................... 6
1.1.2 Document History ................................................................................................................. 6
1.1.3 Copyright notice.................................................................................................................... 6
1.1.4 Publisher .............................................................................................................................. 6
1.1.5 About this manual ................................................................................................................. 7
1.2 Other applicable documents .............................................................................................................. 7
1.3 Presentation conventions ................................................................................................................... 7
1.3.1 Warning information ............................................................................................................. 7
1.3.2 Other information .................................................................................................................. 7
1.3.3 Text markings ....................................................................................................................... 8
1.3.4 List of abbreviations.............................................................................................................. 9
2 Safety ......................................................................................................................................................... 10
2.1 Intended use .................................................................................................................................... 10
2.2 Selection and qualification of personnel ........................................................................................... 10
2.2.1 Qualified personnel............................................................................................................. 10
2.2.2 Qualified electrician ............................................................................................................ 10
2.3 Safety information ............................................................................................................................ 11
3 CANopen basics ........................................................................................................................................ 12
3.1 Characteristics ................................................................................................................................. 12
3.2 Topology .......................................................................................................................................... 14
3.3 Bus protocol ..................................................................................................................................... 15
3.3.1 CANopen protocols ............................................................................................................ 16
3.3.2 Communication objects ...................................................................................................... 17
4 NORD system bus ..................................................................................................................................... 18
4.1 NORD system bus participants ........................................................................................................ 19
4.2 Access to parameters and control options ....................................................................................... 20
4.2.1 Access via the NORD SimpleBox ....................................................................................... 20
4.2.2 Access via the NORD ParameterBox ................................................................................. 20
4.2.3 Access via NORDCON software ........................................................................................ 21
5 Initial setup ................................................................................................................................................ 22
5.1 Connecting the bus interface ........................................................................................................... 22
5.2 Cable material .................................................................................................................................. 23
5.3 Integration into the bus master......................................................................................................... 23
5.3.1 Installing the device description file .................................................................................... 23
5.3.2 Automatic device detection ................................................................................................. 24
5.3.3 Data format of process data ............................................................................................... 24
5.3.4 CANopen field bus address ................................................................................................ 24
5.4 Example: Commissioning the CANopen bus module ....................................................................... 25
BU 2500 en-4319 3
CANopen bus interface – Supplementary manual options for NORD - Frequency Inverters
4 BU 2500 en-4319
List of illustrations
List of illustrations
Figure 1: OSI layer model ...................................................................................................................................... 12
Figure 2: CANopen linear topology (example for up to 64 bus participants).......................................................... 14
Figure 3: CANopen standard frame – 11-bit identifier ........................................................................................... 15
Figure 4: CANopen extended frame – 29-bit identifier........................................................................................... 15
Figure 5: Example of the structure of a NORD system bus ................................................................................... 18
Figure 6: Frequency inverter status machine......................................................................................................... 35
Figure 7: Telegram traffic – SDO data exchange .................................................................................................. 47
Figure 8: Examples of monitoring parameter settings – SK TU4 bus interface ..................................................... 74
BU 2500 en-4319 5
CANopen bus interface – Supplementary manual options for NORD - Frequency Inverters
1 Introduction
1.1 General
1.1.1 Documentation
Name: BU 2500
Material number 6082502
Series: Field bus system CANopen®
1.1.4 Publisher
6 BU 2500 en-4319
1 Introduction
DANGER
This warning information warns against personal risks, which may cause severe injury or death.
WARNING
This warning information warns against personal risks, which may cause severe injury or death.
CAUTION
This warning information warns against personal risks, which may cause slight or moderate injuries.
NOTICE
This warning warns against damage to material.
Information
This information shows hints and important information.
BU 2500 en-4319 7
CANopen bus interface – Supplementary manual options for NORD - Frequency Inverters
Text
Type of information Example Marking
Instructions 1st Instructions for actions whose sequence must be
2nd complied with are numbered sequentially.
Bullet points • Bullet points are marked with a dot.
Parameters P162 Parameters are indicated by the prefix "P", a three-
digit number and bold type.
Arrays [-01]) Arrays are indicated by square brackets.
Factory settings { 0,0 } Factory settings are indicated by curly brackets.
Software descriptions "Cancel" Menus, fields, buttons and tabs are indicated by
quotation marks and bold type.
Numbers
Type of information Example Marking
Binary numbers 100001b Binary numbers are indicated by the suffix "b"
Hexadecimal numbers 0000h Hexadecimal numbers are indicated by the suffix "h"
Symbols used
Type of information Example Marking
Cross-reference Section 4 "NORD Internal cross-reference A mouse click on the text
system bus" calls up the stated point in the document.
Supplementary External cross-reference
manual
Hyperlink http://www.nord.com/ References to external websites are indicated in
blue and underlined. A mouse click calls up the
website.
Type designations
Designation Description
SK 1x0E Series SK 180E frequency inverters
SK 2xxE Series SK 200E frequency inverters
SK 2x0E-FDS Series SK 250E-FDS frequency inverters
SK 5xxE Series SK 500E frequency inverters
SK 54xE SK 540E and SK 545E frequency inverters
8 BU 2500 en-4319
1 Introduction
Abbreviation Meaning
AG Absolute encoder
AK Order label/response label
Bus module Bus module
CAN Controller Area Network
COB Communication Object
COB ID Communication Object Identifier
DIN Digital input
DIP Dual In-Line Package (= double row housing), compact switch block
DO Digital output
EDS Electronic Data Sheet
EMCY Emergency, abbreviation for CANopen error message
EMC Electromagnetic compatibility
I/O Input/Output
FI Frequency inverter
IND Index
IP Internet protocol
I/O Input, Output
IW Actual value
LSB Least Significant Byte, (smallest address)
OSI Open Systems Interconnection, communication with open systems
OV Object directory
NMT Network Management
PDO Process Data Object
PDO Rx Reception PDO
PDO Tx Transmission PDO
PPO Parameter/Process Data Object
PZD Process data
RO Read Only
Rx Receive
SDO Service Data Object
PLC Programmable Logical Controller
STR String value
STW Control word
SW Setpoint
SYNC Synchronisation Object
Tx Transmit
U8 (U16, U32) 8 Bit (16 bit, 32 bit) unsigned, without prefix
USS Universal serial interface
ZSW Status word
BU 2500 en-4319 9
CANopen bus interface – Supplementary manual options for NORD - Frequency Inverters
2 Safety
CANopen bus interfaces from Getriebebau NORD GmbH & Co. KG are used for communication by
the frequency inverter with a PLC in a CANopen field bus system provided by the operator.
Any other use of the bus interfaces is deemed to be incorrect use.
10 BU 2500 en-4319
2 Safety
BU 2500 en-4319 11
CANopen bus interface – Supplementary manual options for NORD - Frequency Inverters
3 CANopen basics
3.1 Characteristics
CANopen is an open communications profile for industrial automation systems. It is based on the CAN
bus system (CAN = Controller Area Network), which describes Layers 1 (physical layer) and 2 (data
communication) of the OSI model (Open Systems Interconnection Model = reference model for
network protocols as system architecture (ISO 11898). The CANopen profiles (application layer, plug
assignment and transfer rates) are defined in Layer 7 of the OSI model, which is based on CAN.
Item Description
OSI layer 1 Layer 1, physical layer, defines the hardware, coding, speed etc. of data transfer
OSI layer 2 Layer 2, link layer, defines the communication physics (access method in the field bus and
data backup).
Layer 7, application layer, defines the interface to the application program with the
OSI layer 7
application-orientated commands.
DS-301 Communication profile DS-301
DS-401 Device profile DS-401, I/O module
DS-402 Device profile DS-402, drive units
12 BU 2500 en-4319
3 CANopen basics
CANopen is managed by the association of users and manufacturers "CAN in Automation" (CiA) and
is published in the European standard EN 50325-4
CANopen is not a conventional Master-Slave system. In addition to client-server services, the
producer-consumer concept is also used. Field bus access rights are not assigned by a higher level
control unit, but rather, each bus participant is equally entitled to transfer data as soon as the bus is
free (Multi-Master capability). In case of simultaneous access by several participants, access is
granted to the subscriber with the highest priority. The priority is assigned by a label (ID) of the
message which is to be transferred.
CANopen® is a registered trademark of CAN in Automation (CiA).
CANopen devices can be integrated into a CANopen field bus system without configuration, however
a unique bus address and a baud rate must be specified. The node address (node identifier) of a
CANopen device, by which the field bus participant is identified, results from the bus address and the
baud rate.
Performance description
BU 2500 en-4319 13
CANopen bus interface – Supplementary manual options for NORD - Frequency Inverters
3.2 Topology
CANopen bus interfaces from Getriebebau NORD GmbH & Co. KG are connected in a linear
structure. All bus participants must communicate with the same baud rate.
Branches from a linear bus are possible using router nodes. The number of bus participants can be
increased to a maximum of 127 by using repeaters.
14 BU 2500 en-4319
3 CANopen basics
BU 2500 en-4319 15
CANopen bus interface – Supplementary manual options for NORD - Frequency Inverters
16 BU 2500 en-4319
3 CANopen basics
Object Directory (OV) The objects which are specified in the object directory contain data,
parameters or functions. Access is via Service Data Objects (SDO). An
object is addressed via the index (16-bit) and the sub-index (8-bit). The
object directory is divided into the following ranges:
Index range Use
0001h…009Fh Data types (special case)
00A0h…0FFFh Reserved
1000h…1FFFh Communication profile
2000h…5FFFh Manufacturer-specific objects
6000h…9FFFh Up to 8 standardised device profiles
A000h…AFFFh Process images from CANopen gateways (CiA 302-7)
C000h…FFFFh Reserved
Service Data Objects SDO Service Data Objects are used for confirmed transfer of data of any length
between two network participants. The SDO client is the initiating
participant and has direct access to the object directory entries of the SDO
server (read and write). SDO communication is used for parameterisation
and diagnosis.
Process Data Objects PDO Transfer of process data is made without confirmation. Process data can
contain a maximum of 8 bytes. The meaning of the process data is
specified by the identifier and the PDO mapping which is set. A Process
Data Object is always produced by a producer (transmitter), but can be
transferred to several consumers (recipients).
PDO mapping The objects "1600h"…"1603h" or "1A00h"…"1A03h" of the object directory
specify which objects (setpoints/actual values) are to be transferred in the
PDO telegrams.
Identifier Each CANopen message has an identifier (standard 11-bit, extended 29-
bit), which is used for addressing and assignment of priority.
CANopen defines a pre-set identifier assignment which enables
communication between a higher level device and up to 127 other devices.
Structure of the 11-bit identifier:
Bit Bit 9 Bit 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
10
Function code Node identifier (1…127)
BU 2500 en-4319 17
CANopen bus interface – Supplementary manual options for NORD - Frequency Inverters
Communication between the bus interface and frequency inverters from Getriebebau NORD GmbH &
Co. KG is carried out via a separate NORD system bus. The NORD system bus is a CAN field bus;
communication is via the CANopen protocol.
One or more frequency inverters in the field bus system can be accessed via a bus interface.
Item Description
1 NORD system bus (CAN field bus)
2 SK TU4 bus interface
3 Frequency inverter
4 Absolute encoder
5 Input/output extension SK TU4-IOE
6 NORD CON computer (on Windows® based PC, on which the NORD CON parameterisation and
control software is installed)
7 Field bus
18 BU 2500 en-4319
4 NORD system bus
All participants on the NORD system bus must be assigned a unique address (CAN ID). The address
of the bus interface is pre-set at the factory and cannot be changed. Connected IO extensions must be
assigned to the frequency inverters ( Technical Information/Data Sheet of the relevant IO
extension). Depending on the device, the addresses of the frequency inverter and the connected
absolute encoder can be set via the parameter P515 CAN address or via the DIP switches.
If absolute encoders are used, these must be assigned directly to a frequency inverter. This is carried
out using the following equation:
Absolute encoder address = CAN ID of the frequency inverter + 1
This results in the following matrix:
CAN-ID 32 33 34 35 …
The termination resistor must be activated on the first and last participant in the system bus
( Frequency inverter manual) The bus speed of the frequency inverter must be set to "250 kBaud"
(P514 CAN baud rate) This also applies to any absolute encoders which are connected.
BU 2500 en-4319 19
CANopen bus interface – Supplementary manual options for NORD - Frequency Inverters
20 BU 2500 en-4319
4 NORD system bus
• Connection of the NORDCON computer to a bus interface or frequency inverter for system bus
communication (CANopen) with a maximum of 32 participants (31 devices plus NORDCON).
This requires an installed system bus:
– Wired,
– Termination resistors set,
– System bus participants addressed, USS addresses set to the factory setting ("0"). If the
NORDCON software detects an active system bus, a USS address is automatically assigned to
all of the participants which are detected.
Communication is via the USS protocol. The CANopen interface of the bus interface or the device
with which the NORDCON software is connected acts as a gateway.
BU 2500 en-4319 21
CANopen bus interface – Supplementary manual options for NORD - Frequency Inverters
5 Initial setup
The bus interface must be set up in order to commission the field bus system. This consists of the
following work:
An example of the procedure for setting up the field bus system can be found at the end of this section
( Section 5.4 "Example: Commissioning the CANopen bus module").
Detailed information about EMC compliant installation can be found in the Technical Information
TI 80_0011 under www.nord.com
Connection of the bus interface to the frequency inverter and the CANopen field bus is described in
the corresponding technical information:
22 BU 2500 en-4319
5 Initial setup
The interface complies with ISO 11898. The maximum permissible voltage on the CAN_L and CAN_H
cables is -8V … +8V.
BU 2500 en-4319 23
CANopen bus interface – Supplementary manual options for NORD - Frequency Inverters
5.3.2 Automatic device detection
In order that the bus interface and the connected frequency inverters can be automatically detected by
the bus master in bus scan, the following settings must be made in the configuration software after
installation of the device description file:
• Enter the bus interface in the CANopen field bus system
• Set the bus address of the bus interface
24 BU 2500 en-4319
5 Initial setup
BU 2500 en-4319 25
CANopen bus interface – Supplementary manual options for NORD - Frequency Inverters
26 BU 2500 en-4319
6 Data transmission
6 Data transmission
6.1 Introduction
With the data communication between the frequency inverter (via the bus interface) and the bus
master (PLC) process data and parameter data are exchanged.
The process data are transferred via PDOs (Process Data Objects) and the parameter data via SDOs
(Service Data Objects).
CANopen data transfer is carried out in little-endian format (literally "little-ender format"). This is an
order system for reading bytes into the register and memory, in which the LSB (Least Significant Byte)
is in the first place and is saved in the lowest memory address. For example, the control word "047Eh"
("ready for switch-on") is transferred to the frequency inverter as "7E04h" in little-endian format.
BU 2500 en-4319 27
CANopen bus interface – Supplementary manual options for NORD - Frequency Inverters
Pre- The bus participant enters this state after 00h 80h 00h
Operational initialisation. In this state the bus participant can
be configured, i.e. transfer of SDOs (parameter
data) is possible; the PDO channel is blocked.
Operational The field bus is ready for operation. PDOs and 00h 01h 00h
SDOs can be transferred
Stopped PDO and SDO transfer blocked; only NMT 00h 02h 00h
commands can be transferred.
Data field
Start field Status field Control field Backup field Confirmation End field
(Application
(SOF) (Identifier) (Control) (CRC) field (ACK) (EOF)
data)
1-bit 12-bit/32-bit 6-bit 0…64-bit 18-bit 2-bit 7-bit
The different structures of the application data field enables the exchange of two different types of
telegram:
• PDO (Process Data Objects) for communication of process data,
• SDO (Service Data Objects) for communication of parameter data.
A PDO uses the data field exclusively for process data information and is therefore able to transfer 8
bytes of process data with each telegram.
An SDO divides the data field into a 4 byte configuration area and a 1 - 4 byte data area. This enables
access to the object data directory and therefore to the function of the bus participant (e.g. frequency
inverter) as well as parameterisation of the device. However, the possible extent of the data content is
restricted:
Control
Index Sub-index Data
byte
28 BU 2500 en-4319
6 Data transmission
BU 2500 en-4319 29
CANopen bus interface – Supplementary manual options for NORD - Frequency Inverters
Bit 10 Bit 9 Bit 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Function code1 Node identifier (1…127)1
1
The function code and node identifier give the COB ID of a PDO or SDO
Identifiers can be assigned via the CANopen object directory ( Section 6.7 "Object directories"):
CANopen bus interfaces from Getriebebau NORD GmbH & Co. KG have 5 PDO channels (transmit
and receive) and 4 SDO channels. However, less channels are provided in the so-called "Predefined
Connection Set" of the CANopen communication profile DS-301, so that address conflicts result with
devices which use the "Predefined Connection Set". To avoid address conflicts, the channels which
are additionally required are divided into the address range "64...127".
30 BU 2500 en-4319
6 Data transmission
The assignment and setting of the COB ID is normally carried out via the parameters P160 COB ID
On/Off and P161 COB ID ( Section 7.1.2 "CANopen standard parameters"). The following table
shows the factory settings of the bus interfaces SK CU4-CAO and SK TU4-CAO which enable the
exchange of process data between the bus interface and up to 4 frequency inverters which are
connected via the NORD system bus (gateway function).
BU 2500 en-4319 31
CANopen bus interface – Supplementary manual options for NORD - Frequency Inverters
The process data telegram for the communication of process data objects contains 8 bytes of process
data:
1st word 2nd word 3rd word 4th word 5th word 6th word
8 Byte
To bus interface Control word Setpoint 1 Setpoint 2 Setpoint 3 Setpoint 4 Setpoint 5
From bus interface Status word Actual Actual Actual Actual Actual
value 1 value 2 value 3 value 4 value 5
The meaning of the data which is transmitted is specified by the identifier (COB ID) and the PDO
mapping which is set.
The bus master reads the length and structure of the process data from the device description file (
Section 5.3 "Integration into the bus master").
Special modifications to the PDO communication (e.g. setting of the COB ID, assignment of
Transmission Types, etc.) can be made via the standard CANopen parameters of the bus interface
Section 7.1.2 "CANopen standard parameters".
32 BU 2500 en-4319
6 Data transmission
BU 2500 en-4319 33
CANopen bus interface – Supplementary manual options for NORD - Frequency Inverters
34 BU 2500 en-4319
6 Data transmission
Fault
Error reaction
Not on standby
Active
Fault
Starting disabled
Standby
Activated
Item Meaning
A…H Frequency inverter statuses ( Table "Frequency inverter statuses")
1…15 Status transitions ( Table "Status transitions")
BU 2500 en-4319 35
CANopen bus interface – Supplementary manual options for NORD - Frequency Inverters
Status Description
A Not on standby Initial state after switching on the frequency inverter. As soon as the loading
relay engages, the frequency inverter automatically changes to the status
"Switch-on block".
B Switch-on block Second status after switching on the frequency inverter, which can only be
exited with the control command "Shut-down". The charging relay is switched
on.
C Standby In this status, initialisation of the frequency inverter is complete. The output
voltage is blocked.
Information
During the initialisation process the response to a bus master telegram does
not yet contain the response to the control command which has been issued.
On the basis of the response from the bus participant, the control system must
determine whether the control command has been executed.
D Activated Frequency inverter ready for operation.
E Operation enabled The frequency inverter receives and processes setpoints.
F Emergency stop active Emergency stop function is being executed (the drive is stopped), the frequency
inverter changes to the status "Switch-on block".
G Error reaction active If an error occurs, the frequency inverter changes to this status and all functions
are blocked.
H Fault After processing of the response to the fault, the frequency inverter changes to
this status, which can only be exited with the control command "Acknowledge
fault".
36 BU 2500 en-4319
6 Data transmission
Status transitions
BU 2500 en-4319 37
CANopen bus interface – Supplementary manual options for NORD - Frequency Inverters
6 5 4 3 2 1 0
Starting disabled 1 X X 0 0 0 0
Ready to start 0 1 1 0 0 0 1
Activated 0 1 1 0 0 1 1
Operation enabled 0 1 1 0 1 1 1
Fault 0 X X 1 0 0 0
Error active 0 X X 1 1 1 1
38 BU 2500 en-4319
6 Data transmission
Percentage transmission
The process value is transmitted as an integer with a value range of -32768 to 32767 (8000 hex to
7FFF hex). The value "16384" (4000 hex) corresponds to 100%. The value "-16384" (C000 hex)
corresponds to -100%.
For frequencies, the 100% value corresponds to parameter P105 Maximum frequency of the
frequency inverter. For current, the 100% value corresponds to parameter P112 Torque current limit
of the frequency inverter.
Frequencies and currents result from the following formulae:
Value * × P105
Value * × P112
Frequency = 16384 Current =
16384
* 16 Bit- setpoint or actual value which is transferred via the bus.
Binary transmission
Inputs and outputs as well as digital input bits and bus output bits are evaluated bit-wise.
1st word 2nd word 3rd word 4th word 5th word 6th word
To bus interface Control word 32 Bit setpoint Setpoint 3 Setpoint 4 Setpoint 5
From bus interface Status word Actual 32 Bit actual value Actual Actual
value 1 value 4 value 5
Only the "Low" word for the position can also be transferred. This results in a limited value range from
32,767 to -32,768 rotations. This value range can be extended with the ratio factor (Parameter P607
speed ratio and P608 Reduction), however this reduces the resolution accordingly.
BU 2500 en-4319 39
CANopen bus interface – Supplementary manual options for NORD - Frequency Inverters
The parameter for setting the COB ID is a 32-bit value, which contains further information in addition
to the COB ID:
If the COB ID of a PDO Tx is changed, e.g. to the value "201h", the value "40000201h" must be
entered in the relevant parameter.
The changed COB ID only becomes valid when the corresponding bus participant is set to the status
"Operational".
40 BU 2500 en-4319
6 Data transmission
The Transmission Type is set via the CANopen standard parameter P162 PDO Transmission Type
( Section 7.1.2 "CANopen standard parameters").
BU 2500 en-4319 41
CANopen bus interface – Supplementary manual options for NORD - Frequency Inverters
Example:
1 2 3 4
Control Word (16 Bit) Setpoint 1 (16 Bit)
The PDO mapping is set wit the parameter P165 PDO Mapping Para.
Information
All Getriebebau NORD GmbH & Co. KG frequency inverters support dynamic mapping and dummy mapping.
With integration of the NORD device description file ( Section 5.3 "Integration into the bus master") no
modifications are needed for the exchange of data. By mapping the PDO with 16 Bit width, dummy mapping is
not necessary.
42 BU 2500 en-4319
6 Data transmission
Standard setting
PDO Length COB ID 1st word 2nd word 3rd word 4th word
PDO1 (Tx) 4 Byte 180h + node address ZSW IW1 — —
PDO1 (Rx) 4 Byte 200h + node address STW SW1 — —
PDO2 (Tx) 8 Byte 280h + node address ZSW IW1 IW2 IW3
PDO2 (Rx) 8 Byte 300h + node address STW SW1 SW2 SW3
PDO3 (Tx) 8 Byte 380h + node address ZSW IW1 (32 Bit) IW2
PDO3 (Rx) 8 Byte 400h + node address STW SW1, (32 Bit) SW2
PDO4 (Tx) 2 Byte 480h + node address ZSW — — —
PDO4 (Rx) 2 Byte 500h + node address STW — — —
In the standard setting, all PDO Rx are activated. Transmission to the corresponding COB ID
determines whether only one setpoint or up to three setpoints are evaluated.
Only PDO1 Tx is activated, all other PDO Tx are deactivated. The corresponding PDO Tx must be
activated if several actual values have to be communicated.
PDO Length COB ID 1st word 2nd word 3rd word 4th word
PDO1 (Tx) 8 Byte 180h + node address ZSW IW1 IW2 IW3
PDO1 (Rx) 8 Byte 200h + node address STW SW1 SW2 SW3
IW1 (32 Bit) of an
PDO2 (Rx) 4 Byte 300h + node address
absolute encoder
PDO Length COB ID 1st word 2nd word 3rd word 4th word
PDO1 (Tx) 8 Byte 180h + node address ZSW IW1 IW2 IW3
PDO1 (Rx) 8 Byte 200h + node address STW SW1 SW2 SW3
PDO2 (Tx) 5 Byte 280h + node address IW4 IW5
PDO2 (Rx) 5 Byte 300h + node address WAF 4 WAF 5
IW1 (32 Bit) of an
PDO3 (Rx) 4 Byte 400h + node address
absolute encoder
BU 2500 en-4319 43
CANopen bus interface – Supplementary manual options for NORD - Frequency Inverters
Example
The control word and setpoint 3 (each with 16 Bit) are to be transferred to the frequency inverter with
the object "Transmit PDO mapping parameter" (Index 1A00h).
• The CAN identifier "432h" is used for the transmission.
• Transmission is carried out synchronously with every third SYNC object.
• CAN identifiers ( Section 6.4 "CAN identifier and COB ID") are used for the SDO.
1. Deactivating PDO mapping: In index 1A00h, sub-index 0, set the number of mapping objects to
"0".
2. Entering mapping objects: Enter the index, sub-index and object length of the application object
into the PDO mapping parameter structure (Index 1A00h). A maximum of 8 bytes of data can be
assigned for each PDO.
The mapping parameters of the first object, index 1A00h must have the following structure:
44 BU 2500 en-4319
6 Data transmission
BU 2500 en-4319 45
CANopen bus interface – Supplementary manual options for NORD - Frequency Inverters
1. Deactivating PDO1 Tx: Write the value "80 00 00 00h" in the communication object "Transmit
PDO Communication Parameter", index 1800h, sub-index 1:
2. Setting the communication parameters for PDO1 Tx: Write the communication parameters into
the structure of the communication object "Transmit PDO Communication Parameter", index
1800h, sub-index 1...3. In addition, define Transmission Type 3 (synchronous communication with
every third SYNC object Section 6.5.6 "PDO Transmission Types (operating modes)"):
Sub-index 1, specify COB ID of the PDO = 0432h and change from invalid to valid
CAN identifier Data
Transmit 0600h 23 00 18 02 32 04 00 00 h
Received 0580h 60 00 18 01 xx xx xx xx h
As soon as the bus interface is set to the status "Operational" with the command "Start Remote Node",
the PDOs become active and the PDO Tx object can be used for the transmission of data.
46 BU 2500 en-4319
6 Data transmission
Item Meaning
A Order telegram
1 Parameter order (object specification)
2 Object data
3 Processing
B Response telegram
4 Parameter response (object specification)
5 Object data
Transmission and reception addresses for SDO access (from the bus master):
Direction of Address
Transmit 600h + node address
Received 580h + node address
BU 2500 en-4319 47
CANopen bus interface – Supplementary manual options for NORD - Frequency Inverters
Control byte
The control byte specifies the data length and the order:
2Bh Transmit 16 Bit value
23h Transmit 32 Bit value
60h Response: Error-free telegram received. Parameter communication is aborted in case of any
other response.
Index
The index states the parameter number of the frequency inverter. Parameter numbers above "2000h"
are mapped:
Parameter P102 = 66h → 2000h + 66h → 6620h
Sub-index
The sub-index states the parameter index (array value). The selected parameter set and the array
element of the parameter are coded in this area.
For parameters which neither depend on parameter sets nor consist of array elements, the sub-index
is "00h"
Application data
The values of the selected parameter are transferred in the application data area.
16-bit value 67 00 00 00h
1.03 s = 0067h
32-bit value 76 BC 2A 00h
2800,758 rev = 002ABC76h
48 BU 2500 en-4319
6 Data transmission
Control byte/
Index Sub-index Reference data
Status byte
Requirement
40h 20h 66h 01h 00h 00h 00h 00h
Response
4Bh 20h 66h 01h 67h 00h 00h 00h
Control byte
The control byte states the order:
40h Read value
Response
4Bh Deliver the 16-bit value which is read out
43h Deliver the 32 -bit value which is read out
80h Response to an incorrect query
For a list of possible error codes please refer to Section 8.3.2 "Error codes – interruption of SDO
communication".
BU 2500 en-4319 49
CANopen bus interface – Supplementary manual options for NORD - Frequency Inverters
50 BU 2500 en-4319
6 Data transmission
Sub-
Index Object Description Unit Access Type
index
1000h — Device type Device type and functionality — RO U32
1001h — Error register Error index — RO U8
1002h — Status register Status of the module — RO U32
1003h ARR Pre-defined Error Error signalled by an Emergency — — U8
Object
0 Number of errors Number of errors: Writing "0" — RW U8
deletes the error list
1 Error code Error number — RO U32
1005h — COB ID SYNC Identifier for SYNC messages — RW U32
(Default "80h")
1008h — Device name Device name — RO STR
1009h — Hardware version Hardware version — RO STR
100Ah — Software Version Software version — RO STR
100Ch — Guard Time P166 Timeout Control ("0" = Off) ms RW U16
100Dh — Life time factor Life Time = Life Time Factor x — RW U16
Guard Time
1010h — Store parameters Permanently save user settings — RW U32
For this, the signature "save"
(small case ASCII – MSB LSB,
65h, 76h, 61h, 73h) must be
written in index 1010h, sub-index
1. The saving process runs in the
background and is confirmed with
an SDO response telegram.
Information
If the CANopen address is changed
with the DIP switches after the user
settings have been saved, the saved
user settings will continue to be used.
The user settings are reset to the
factory settings by object 1011h.
BU 2500 en-4319 51
CANopen bus interface – Supplementary manual options for NORD - Frequency Inverters
Sub-
Index Object Description Unit Access Type
index
3 Revision number Software version and revision — RO U32
number
4 Serial number Serial number — RO U32
1200h REC Default Server SDO SDO Server — — U8
0 Largest sub-index Number of array elements — RO U8
1 COB ID Server>Client (rx) SDO Rx identifier("600h" + node — RO U32
address) for FI1 and bus interface
(Parameter P161 [-02])
2 COB ID Server>Client (tx) SDO Tx identifier("580h" + node — RO U32
address) for FI1 and bus interface
(Parameter P161 [-02])
1201h REC Default Server SDO SDO Server — RW U8
0 Largest sub-index Number of array elements — RW U8
1 COB ID Server>Client (rx) SDO Rx identifier("340h" + node — RW U32
address) for FI2 and bus interface
(Parameter P161 [-05])
2 COB ID Server>Client (tx) SDO Tx identifier("2C0h" + node — RW U32
address) for FI2 and bus interface
(Parameter P161 [-04])
1202h REC Default Server SDO SDO Server — RW U8
0 Largest sub-index Number of array elements — RW U8
1 COB ID Server>Client (rx) SDO Rx identifier("440h" + node — RW U32
address) for FI3 and bus interface
(Parameter P161 [-07])
2 COB ID Server>Client (tx) SDO Tx identifier("3C0h" + node — RW U32
address) for FI3 and bus interface
(Parameter P161 [-06])
1203h REC Default Server SDO SDO Server — RW U8
0 Largest sub-index Number of array elements — RW U8
1 COB ID Server>Client (rx) SDO Rx identifier("540h" + node — RW U32
address) for FI4 and bus interface
(Parameter P161 [-09])
2 COB ID Server>Client (tx) SDO Tx identifier("4C0h" + node — RW U32
address) for FI4 and bus interface
(Parameter P161 [-08])
52 BU 2500 en-4319
6 Data transmission
Sub-
Index Object Description Unit Access Type
index
603Fh — Error code Error description — RO U32
6040h — Control word Control word — RO U16
6041h — Status word Status word — RO U16
6042h — VI_target_velocity Speed setpoint rpm RW I16
6043h — VI_velocity_demand Speed setpoint after ramp rpm RO I16
6044h — VI_control_effort Actual speed value rpm RO I16
6046h ARR VI_velocity_min_max_ Max./Min. speed value — RO —
amount
1 VI_velocity_min_amount Min. speed value rpm RW U32
2 VI_velocity_max_amount Max. speed value rpm RW U32
6048h REC VI_velocity_acceleration Speed acceleration — RO —
1 Delta_speed Delta speed rpm RW U32
2 Delta_time Delta time s RW U16
6049h REC VI_velocity_deceleration Speed reduction — RO —
1 Delta_speed Delta speed rpm RW U32
2 Delta_time Delta time s RW U16
60FDh — Digital inputs profile Bit Meaning — RO U32
PDO data (00 0X 00 00) 0…15 Reserved
16 Digital input 1 (SK xU4-CAO)
17 Digital input 2 (SK xU4-CAO)
18 Digital input 3 (SK xTU4-CAO)
19 Digital input 4 (SK xTU4-CAO)
20…31 Reserved
60FEh — Digital outputs profile Bit Meaning — RW U32
0…15 Reserved
16 Digital output 1 (SK xTU4-CAO)
17 Digital output 2 (SK xTU4-CAO)
18…31 Reserved
BU 2500 en-4319 53
CANopen bus interface – Supplementary manual options for NORD - Frequency Inverters
Sub-
Index Object Description Unit Access Type
index
1400h REC Receive PDO PDO Rx characteristics — RW —
… Communication Parameter
1404h 0 Largest sub-index Number of array elements — RO U8
1 COB ID used by PDO COB ID PDO Rx (Parameter — RW U32
P161)
2 Transmission type PDO operating mode — RW U8
(Parameter P162)
3 Not used Not used
4 Reserved Reserved
5 Not used Not used
1600h REC Receive PDO Mapping PDO Rx mapping — RW —
… Parameter
1603h 0 Largest sub-index Number of array elements — RW U8
1 PDO mapping Mapped objects FI1…FI4 — RW U32
2 (Parameter P165)
3
4
1604h REC Receive PDO Mapping PDO Rx mapping — RW U32
Parameter
0 Largest sub-index Number of array elements — RW U8
1 PDO mapping Bus interface (Parameter P165, — RW U32
2 Array [-34])
3
4
1800h REC Transmit PDO PDO Tx characteristics — RW —
… Communication Parameter
1804h 0 Largest sub-index Number of array elements — RO U8
1 COB ID used by PDO COB ID PDO Tx (Parameter — RW U32
P161)
2 Transmission type PDO operating mode — RW U8
(Parameter P162)
3 Inhibit Time Minimum transmission time 100 µs RW U16
(Parameter P163)
4 Reserved Reserved
5 Event Timer Cyclic transmission timer ms RW U16
(Parameter P164)
1A00h REC Transmit PDO Mapping PDO Tx mapping — RW —
… Parameter
1A03h 0 Largest sub-index Number of array elements — RO U8
1 PDO mapping Mapped objects FI1…FI4 — RW U32
2 (Parameter P165)
3
4
1A04h REC Transmit PDO Mapping PDO Tx mapping — RW U32
Parameter
0 Largest sub-index Number of array elements — RO U8
1 PDO mapping Bus interface (Parameter P165, — RW U32
2 Array [-33])
3
4
54 BU 2500 en-4319
6 Data transmission
Sub-
Index Object Description Unit Access Type
index
2000h — Manufacturer Spec. Frequency inverter — — —
… Parameters parameters( Frequency
23E7h inverter manual)
Parameter P165 PDO Mapping Para ( Section 7.1.2 "CANopen standard parameters")
3000h 0 Largest sub-index Number of elements — RO U8
1 Control word Control word for FI1 — RW U16
2 Control word Control word for FI2 — RW U16
3 Control word Control word for FI3 — RW U16
4 Control word Control word for FI4 — RW U16
3001h 0 Largest sub-index Number of elements — RO U8
1 Status word Status word FI1 — RO U16
2 Status word Status word FI2 — RO U16
3 Status word Status word FI3 — RO U16
4 Status word Status word FI4 — RO U16
3002h 0 Largest sub-index Number of elements — RW U8
1 Setpoint 1 Setpoint 1 for FI1 — RW U16
2 Setpoint 2 Setpoint 2 for FI1 — RW U16
3 Setpoint 3 Setpoint 3 for FI1 — RW U16
41 Setpoint 4 Setpoint 4 for FI1 — RW U16
51 Setpoint 5 Setpoint 5 for FI1 — RW U16
6 Setpoint 1 Setpoint 1 FI2 — RW U16
7 Setpoint 2 Setpoint 2 FI2 — RW U16
8 Setpoint 3 Setpoint 3 FI2 — RW U16
91 Setpoint 4 Setpoint 4 FI2 — RW U16
10 1 Setpoint 5 Setpoint 5 FI2 — RW U16
11 Setpoint 1 Setpoint 1 FI3 — RW U16
12 Setpoint 2 Setpoint 2 FI3 — RW U16
13 Setpoint 3 Setpoint 3 FI3 — RW U16
141 Setpoint 4 Setpoint 4 FI3 — RW U16
15 1 Setpoint 5 Setpoint 5 FI3 — RW U16
16 Setpoint 1 Setpoint 1 FI4 — RW U16
17 Setpoint 2 Setpoint 2 FI4 — RW U16
18 Setpoint 3 Setpoint 3 FI4 — RW U16
191 Setpoint 4 Setpoint 4 FI4 — RW U16
20 1 Setpoint 5 Setpoint 5 FI4 — RW U16
BU 2500 en-4319 55
CANopen bus interface – Supplementary manual options for NORD - Frequency Inverters
Sub-
Index Object Description Unit Access Type
index
3003h 0 Largest sub-index Number of elements — RO U8
1 Actual Value 1 Actual value 1 FI1 — RO U16
2 Actual Value 2 Actual value 2 FI1 — RO U16
3 Actual Value 3 Actual value 3 FI1 — RO U16
41 Actual Value 4 Actual value 4 FI1 — RO U16
51 Actual Value 5 Actual value 5 FI1 — RO U16
6 Actual Value 1 Actual value 1 FI2 — RO U16
7 Actual Value 2 Actual value 2 FI2 — RO U16
8 Actual Value 3 Actual value 3 FI2 — RO U16
91 Actual Value 4 Actual value 4 FI2 — RO U16
101 Actual Value 5 Actual value 5 FI2 — RO U16
11 Actual Value 1 Actual value 1 FI3 — RO U16
12 Actual Value 2 Actual value 2 FI3 — RO U16
13 Actual Value 3 Actual value 3 FI3 — RO U16
141 Actual Value 4 Actual value 4 FI3 — RO U16
151 Actual Value 5 Actual value 5 FI3 — RO U16
16 Actual Value 1 Actual value 1 FI4 — RO U16
17 Actual Value 2 Actual value 2 FI4 — RO U16
18 Actual Value 3 Actual value 3 FI4 — RO U16
191 Actual Value 4 Actual value 4 FI4 — RO U16
201 Actual Value 5 Actual value 5 FI4 — RO U16
3004h 0 Digital outputs Control of digital outputs — RW U16
3005h 0 Digital inputs Status of digital inputs — RO U16
1 Only SK 54xE frequency inverters
56 BU 2500 en-4319
6 Data transmission
Example
— — 0000h 0000h
— — xx40h 0000h The mains voltage is switched on at the frequency
inverter
047Eh 0000h xx31h 0000h The frequency inverter switches to "Ready for
switch-on" status
047Fh 2000h xx37h 2000h The frequency inverter is set to "Operation
enabled" status and controlled with a 50 %
setpoint.
The frequency inverter is enabled, the motor is supplied with current and rotates with a frequency of 25 Hz.
0047Eh 2000h xx31h 0000h The frequency inverter switches to "Ready for
switch-on" status The motor brakes to a standstill
according to the parameterised ramp and is
disconnected from the power supply.
The frequency inverter is blocked again and the motor is without current.
047Fh 1000h xx37h 1000h The frequency inverter is set to "Operation
enabled" status and controlled with a 25% setpoint.
The frequency inverter is enabled, the motor is supplied with current and rotates with a frequency of 12.5 Hz.
BU 2500 en-4319 57
CANopen bus interface – Supplementary manual options for NORD - Frequency Inverters
7 Parameters
The bus interface and frequency inverter parameters are communicated as words (16 Bit/Word).
Exceptions to this are position values (POSICON), which are communicated as double words (32 Bit).
For field bus operation, several parameters must be set on the bus interface and the frequency
inverter.
The parameters can be set with
• An external control or ParameterBox ( Manual BU 0040),
• NORD CON software ( Manual BU 0000) or
• The operator's PLC project.
Bus interface SK TU3-CAO does not have any of its own parameters. It is set via the parameters of
the connected frequency inverter (for details Frequency inverter manual).
The NORD standard parameters P151 to P154 must be set on the bus interfaces SK CU4-CAO and
SK TU4-CAO. In addition, depending on the use and configuration, the CANopen standard
parameters P160…P168 must be set.
A detailed description of the bus interface parameters can be found in the following sections.
58 BU 2500 en-4319
7 Parameters
Description The setting of this parameter determines the switching state of each digital output.
Description Monitoring function of the bus interface After receipt of a valid telegram, the next
telegram must arrive within the set time. Otherwise the bus interface or the connected
frequency inverter reports an error (E010/10.3 "Time Out") and switches off. See also
parameter P513 Telegram timeout time for the frequency inverter.
BU 2500 en-4319 59
CANopen bus interface – Supplementary manual options for NORD - Frequency Inverters
Description Reset the present parameter settings of the bus interface to the factory setting.
Description Set the pause time for the system bus in order to reduce the bus load.
60 BU 2500 en-4319
7 Parameters
Description Assign reading and writing rights of each connected frequency inverter to 2 inputs and 2
outputs of the bus interface. This is carried out via the following frequency inverter
parameters:
Output 1 Evaluation via P481 Funct. BusIO Out Bits, Array [-09]
Output 2 Evaluation via P481 Funct. BusIO Out Bits, Array [-10]
BU 2500 en-4319 61
CANopen bus interface – Supplementary manual options for NORD - Frequency Inverters
Description Specification of the assignment of service data objects and process data objects (SDO
and PDO) for the connected frequency inverters and bus interface.
Note Objects, index "1200h"… "1203h", "1400h"…"1404h" and "1800h"… "1804h", each with
sub-index "1", Section 6.7 "Object directories".
1
Writing access only permissible in the "Pre-Operational" state
62 BU 2500 en-4319
7 Parameters
P161 COB ID
Setting range 0…7FFh
Description Assignment of a COB ID to service data and process data objects (SDO and PDO).
Note Objects, index "1005h", "1200h"… "1203h", "1400h…"1404h" and "1800h"… "1804h",
receive objects (Rx) each with sub-index "1", transmit objects (Tx) each with sub-index
2, Section 6.7 "Object directories".
1
Writing access only permissible in the "Pre-Operational" state
Description Specification of the transfer type for process data objects ( Section 6.5.6 "PDO
Transmission Types (operating modes)".).
Note Objects, index "1400h…"1404h" and "1800h"… "1804h", each with sub-index "2",
Section 6.7 "Object directories".
BU 2500 en-4319 63
CANopen bus interface – Supplementary manual options for NORD - Frequency Inverters
Description Specification of the minimum pause between two PDO transmissions (Transmit PDO Tx)
with the same COB ID.
In networks with numerous subscribers, the bus load can be influenced with this value.
The standard value is 10 ms (value multiplied by 100 μs).
Note Objects, index "1800h"…"1804h", sub-index "3", Section 6.7 "Object directories".
Description Definition of the delay time after the elapse of which the process data are transferred.
Once this value is exceeded, the PDOs are transmitted cyclically. The standard setting is
250 ms (value multiplied by 1 ms).
Note Objects, index "1800h"…"1804h", sub-index "5", Section 6.7 "Object directories".
h
64 BU 2500 en-4319
7 Parameters
P165 PDO Mapping Para
Setting range 0…FFFFFFFFh
Factory setting { [-01] = 30000110h } { [-02] = 30020110h } { [-03] = 30020210h } { [-04] = 30020310h }
Description Specification of objects (setpoints/actual values) which are transferred via PDO
telegrams Section 6.5.7 "PDO mapping"
Note Objects, index "1600h"…"1604h", and "1A00h"…"1A04h", each with sub-index "1"…"4",
Section 6.7 "Object directories".
1
Arrays [-33] and [-34] are settings for the bus interface itself, therefore only 2 byte.
Description Array [-01]: Defines a time interval for the monitoring of the field bus devices (slaves) by
the bus master (node-guarding).
Array [-02]: Setting of the transmission interval (heartbeat) of the field bus device (slave)
Note Objects, index "100Ch" and "1017h", Section 6.7 "Object directories".
BU 2500 en-4319 65
CANopen bus interface – Supplementary manual options for NORD - Frequency Inverters
Description Entry of the factor for monitoring of the bus master by the field bus device (slave).
"Guard Time" (Parameter P166, Array [-01] multiplied by "Life Time Factor" determines
the watchdog duration for mutual monitoring of the slave and bus master.
[-02] / [-03] = Acceleration (v) / (t) [-04] / [-05] = Deceleration (v) / (t) FI 1
[-06] / [-07] = Acceleration (v) / (t) [-08] / [-09] = Deceleration (v) / (t) FI 2
[-10] / [-11] = Acceleration (v) / (t) [-12] / [-13] = Deceleration (v) / (t) FI 3
[-14] / [-15] = Acceleration (v) / (t) [-16] / [-16] = Deceleration (v) / (t) FI 4
Description Setting of the profile parameters "acceleration" and "deceleration" ("Velocity Mode",
drive profile DS-402) (change achieved in [rpm] divided by the time which has elapsed
during the change [s]).
Note Objects, index "6048h" and "6049h", each with sub-index "1" and "2", Section 6.7
"Object directories".
Activation of the drive profile (Array [-01] = "1" affects all of the frequency inverters which
are connected to the NORD system bus. The drive profile is only valid in parameter set
1. If the drive profile is activated, objects index "3004h"..."3004" are replaced with the
objects index "6040h"..."6044h".
The drive profile is not supported by SK 5xxE frequency inverters which are connected
to the NORD system bus via the internal RJ45 interface.
66 BU 2500 en-4319
7 Parameters
Note The error message is reset when the supply voltage is switched off.
Description Display of the software version and revision number of the bus interface. Array [-03]
shows possible special versions (0 = standard version).
BU 2500 en-4319 67
CANopen bus interface – Supplementary manual options for NORD - Frequency Inverters
4 CANopen "Warning"
14 FI4 status
15
Description Display of the actual switching status of the digital bus interface inputs.
Description Display of the actual switching status of the relay outputs of the bus interface.
68 BU 2500 en-4319
7 Parameters
P176 Process data Bus In
Display range -32768…32767
Description Display of the data sent from the bus interface to the CANopen-Busmaster.
BU 2500 en-4319 69
CANopen bus interface – Supplementary manual options for NORD - Frequency Inverters
Description Display of the unique bus address (Node ID) which is set with the DIP switches of the
bus interface ( Technical Information/Data Sheet).
Note If no address is set via the DIP switches (all switches in the "OFF") position, this
parameter shows the address "127".
Description Display of the baud rate which is set with the DIP switches ( Technical
Information/Data Sheet).
0 125 kBaud
1 250 kBaud
2 500 kBaud
3 1 MBaud
70 BU 2500 en-4319
7 Parameters
Additional parameters
The following table contains a list of additional parameters which are relevant for the bus interface.
BU 2500 en-4319 71
CANopen bus interface – Supplementary manual options for NORD - Frequency Inverters
Information parameters
Information parameters are used to display current and archived error messages, as well as current
operating states and settings.
The following table contains a list of information parameters which are relevant for the bus interface.
72 BU 2500 en-4319
8 Error monitoring and error messages
Bus interfaces and frequency inverters are equipped with monitoring functions and generate error
messages in case of deviations from the normal operating state.
Function Parameter
BU 2500 en-4319 73
CANopen bus interface – Supplementary manual options for NORD - Frequency Inverters
74 BU 2500 en-4319
8 Error monitoring and error messages
Information
Archiving error messages
An error message (display via parameter P170) is only displayed as long as it is active. After the error
has been remedied, the message is deleted and is archived as the last error message in parameter
P170, Array [-02]. If the mains supply is interrupted before the error is remedied, the message is lost,
i.e. it is not archived.
Information
Error display in the SimpleBox
An error message is displayed in the operating display of the SimpleBox SK CSX-3H by display of the
error group number "E1000". The bus interface parameter P170, Array [-01] must be selected to
determine the actual error.
BU 2500 en-4319 75
CANopen bus interface – Supplementary manual options for NORD - Frequency Inverters
"FI ID" identifies the frequency inverter in which the error occurred.
76 BU 2500 en-4319
8 Error monitoring and error messages
BU 2500 en-4319 77
CANopen bus interface – Supplementary manual options for NORD - Frequency Inverters
78 BU 2500 en-4319
8 Error monitoring and error messages
Error messages which occur in relation to the bus interface are depicted as follows in the error
memory of the frequency inverter (Parameter P700 and P701).
BU 2500 en-4319 79
CANopen bus interface – Supplementary manual options for NORD - Frequency Inverters
9 Appendix
80 BU 2500 en-4319
9 Appendix
Documentation Contents
TI 275271001 Technical Information/Data Sheet for bus interface SK CU4-CAO (for IP55 devices)
TI 275281501 Technical Information/Data Sheet for bus interface SK CU4-CAO-C (for IP66 devices)
TI 275281101 Technical Information/Data Sheet for bus interface SK TU4-CAO (for IP55 devices)
TI 275281151 Technical Information/Data Sheet for bus interface SK TU4-CAO-C (for IP66 devices)
TI 275271201 Technical Information/Data Sheet for bus interface SK TU4-CAO-M12 (for IP55 devices
with M12 round plug connectors)
TI 275281251 Technical Information/Data Sheet for bus interface SK TU4-CAO-M12-C (for IP66
devices with M12 round plug connectors)
TI 275900075 Technical Information/Data Sheet for bus interface SK TU3-PNT (for IP20 devices)
BU 0180 Manual for SK 1x0E frequency inverters
BU 0200 Manual for SK 2xxE frequency inverters
BU 0250 Manual for SK 2xxE-FDS frequency inverters
BU 0500 Manual for frequency inverters SK 500E to SK 535E
BU 0505 Manual for SK 54xE frequency inverters
BU 0000 Manual for use of NORD CON software
BU 0040 Manual for use of NORD parameterisation units
Software
Software Description
EDS file Device description file for CANopen configuration software
NORDCON Parametrisation and diagnostic software
BU 2500 en-4319 81
CANopen bus interface – Supplementary manual options for NORD - Frequency Inverters
Actual value E
IW ............................................................... 32 Electrician ..................................................... 10
Actual values .................................................38 Error messages ....................................... 67, 73
B Bus interface ............................................. 79
D Frequency inverters................................... 71
Parameter data ............................................. 27
Data transmission ..........................................27
Parameter data transmission .................. 43, 47
Device characteristics ....................................23
Parameter settings
Device description file....................................23
Frequency inverters................................... 71
Device detection ............................................24
ParameterBox ............................................... 20
82 BU 2500 en-4319
Key word index
PDO Mapping Para (P165)............................65 Software version
PDO Transmission Type (P162) ...................63 P171 .......................................................... 67
Percentage transfer .......................................39 Status bit ....................................................... 34
Permissible writing cycles..............................47 Status machine
Process data ............................................24, 27 Frequency inverter .................................... 35
Process data Bus In (P176)...........................69 Status of digital in. (P174) ............................. 68
Process data bus Out (P177) ........................69 Status word ............................................. 34, 38
Process Data Objects ZSW........................................................... 32
PDOs..........................................................27 T
R TB-IO access (P154) .................................... 61
Relay status (P175) .......................................68 Telegram timeout (P513) .............................. 73
Repair ............................................................ 80 Timeout ......................................................... 73
Returns ..........................................................80 Timeout Control (P166)................................. 65
S Timeout for external bus (P151) ................... 59
Setpoints ........................................................38 U
SimpleBox......................................................20 USS protocol ................................................. 20
Software.........................................................81
BU 2500 en-4319 83
6082502 / 4319