Thermostat Manual - Siemens RDF310.2
Thermostat Manual - Siemens RDF310.2
RDF310.2/MM
CB1N3066en
2019-10-25 Smart Infrastructue
Use
For controlling the room temperature in individual rooms and zones that are…
· heated or cooled with 2-pipe fan coil units
Functions
· Selection of operating mode with the operating mode button on the thermostat
· 3-speed fan control (automatic or manual)
· Output for 2-position (on/off) valve or 3-wire (on/off) valve actuator
Applications
V1
M1
T N1
2/14
Temperature control The thermostat acquires the room temperature via its built-in sensor and maintains the
setpoint by delivering 2-position valve control commands.
The switching differential is 1 K in heating mode and 1 K in cooling mode (adjustable
via parameters P08 and P09).
Display The display shows the acquired room temperature or the setpoint of the current
operating mode. This can be selected via parameter P18. Factory setting is display of
the current room temperature.
The heating symbol or the cooling symbol displays to indicate the output status of
the relays connected to the fan coil. This means that the symbol does not display when
the thermostat operates in the neutral zone. If the thermostat is under manual heating
or cooling changeover, the heating symbol or the cooling symbol displays
permanently to indicate the control sequence. i.e. heating or cooling. This means that
the symbol displays when the thermostat operates in the neutral zone.
If required, room temperature and setpoint can also be displayed in °F in place of °C by
changing parameter P17.
Operating modes
Comfort Mode In Comfort mode, the thermostat maintains the setpoint, which can be adjusted via the
+ and - buttons. The fan can be set to automatic or manual fan speed: Low, medium or
high.
Tip! The setpoint setting range can be limited to a minimum (P05) and maximum (P06). This
helps prevent the waste of energy, and saving costs.
Protection Mode When the thermostat is in Protection mode , the relevant setpoints of heating or
cooling are maintained. These setpoints can be adjusted via control parameters P03
and P04. Factory setting of both setpoints is OFF, indicating the thermostat is not
activated when in Protection mode.
Avoiding damage To avoid damage due to moisture in very warm and humid climatic zones resulting from
due to moisture lack of air circulation in Comfort mode, the fan can be kept running all the time (e.g. in
apartments or shops during unoccupied periods), when setting parameter P21 “ON in
dead zone”. In this case, the fan keeps running at minimum fan speed 1 in the neutral
zone.
3/14
Water-based fan coil Used in conjunction with a valve, either for heating/cooling with changeover, or heating
application only, cooling only.
w w
ON The valve receives the OPEN command via control output Y11 when
1. the acquired room temperature lies by half the switching differential below the
setpoint (heating mode) or above the setpoint (cooling mode), and
2. control output Y11 was not energized for more than the “Minimum output off time”
(factory setting 1 minute)
OFF The valve receives the CLOSE command via control output Y11 when
1. the acquired room temperature lies by half the switching differential above the
setpoint (heating mode) or below the setpoint (cooling mode), and
2. control output Y11 was energized for more than the “Minimum output on time”;
(factory setting 1 minute)
Note: Control output Y12 delivers a control command which is inverted to the control
command at output Y11 and which can be used for normally open valves.
Heating/cooling When you press the heating/cooling changeover button , the thermostat changes
mode from heating to cooling, or vice versa.
If the thermostat is set to ”Cooling only” or ”Heating only” via P22, the manual
changeover function on the button is not available (the factory setting of parameter P22
is ”manual changeover”). Instead, “NOP” flashes on the display, indicating continuous
cooling or heating is set respectively.
Minimum output The minimum output on/off time of Y11 and Y12 is fixed at 1 minute. It means that any
on/off time Y11 and readjustment of the setpoint or of Heating/Cooling Mode changeover lasts for
Y12 1 minute before Y11 and Y12 react.
4/14
The fan operates either in automatic mode or at the selected speed when using manual
mode. In automatic mode, the fan speed depends on the setpoint and the current room
temperature. When the room temperature reaches the setpoint, the control valve is
closed and the fan either remains in fan speed 1 or switches off (parameter P21,
factory setting: fan speed 1 in dead zone).
In “Temperature-dependent” fan control the fan switches off (please see diagram
below). The individual switching differentials of the fan speed 1 (Q1 only) can be
adjusted via control parameters P08 – P09. The individual switching differentials of the
fan speed 2 and 3 (Q2 and Q3) are fixed at 1K.
Heating mode Cooling mode
3058D03
Valve Valve
Y11 Y11
W W
Temp Temp
Fan SDH Fan SDC
Q3 Q3
Q2 Q2
Q1 Q1
Temp Temp
SDH3 SDH2 SDH SDC SDC2 SDC3
Ventilation If desired, fan control can be set to ”Temperature-independent”, which means that
always on ventilation is always on, even within the dead zone, using at least fan speed 1. This can
be selected individually for Comfort mode via parameter P21; also refer to “Avoiding
damage due to moisture” on page 3).
Dwelling time In automatic mode, a dwelling time of 2 minutes (factory setting) is active. The fan
maintains that speed for at least 2 minutes before it switches to the next speed. This
dwelling time can be adjusted from 1…5 minutes via parameter P14.
Fan start Whenever the fan starts from standstill, it starts with speed 3 for 1 second in order to
guarantee a safe fan motor starts (to overcome inertia and friction).
Error handling
Temperature out of When the room temperature is out of the measuring range, which means above 49 °C
range or below 0 °C, the display shows the limiting temperature in flashing figures, e.g. “0 °C”
or “49 °C”.
If the current setpoint is not OFF (see parameter P03) and the thermostat is in heating
mode, when the temperature is below 0 °C, output Y11 is energized. In all other cases,
output Y11 is de-energized until the temperature returns to the measuring range, and
then the thermostat resumes Comfort mode.
5/14
To optimize the control performance, you can use local HMI to adjust a number of
control parameters. Proceed as follows to change the control parameter.
Parameter reset Reload the factory setting of the control parameters as follows:
1. Set the thermostat to Protection mode .
2. Press the + and – buttons simultaneously for 3 seconds. Release them and,
Control parameters
Para- Meaning Setting range Factory
meter setting
P03 Setpoint of heating in Protection Mode (WheatStb) OFF, 5 °C…WcoolStb 8 °C
P04 Setpoint of cooling in Protection Mode (WcoolStb) OFF, WheatStb …40 °C OFF
P05 Minimum setpoint limitation in Comfort Mode (WminNorm) 5 °C…WmaxNorm 5 °C
P06 Maximum setpoint limitation in Comfort Mode (WmaxNormf) WminNorm…40 °C 35 °C
P07 Sensor calibration -3…3 K 0K
P08 Switching differential heating mode SDH 0.5…4 K 1K
P09 Switching differential cooling mode SDC 0.5…4 K 1K
P14 Dwelling time of auto fan speeds 1…5 min 2 min
P17 Selection of °C or °F °C or °F °C
OFF: Setpoint
P18 Display of temperature or setpoint ON
ON: Room (or return air) temperature
OFF in dead zone
P21 Fan control in Comfort mode ON
ON in dead zone
0: Heating only
P22 Heating/cooling mode 1: Cooling only 3: Manual
3: Manual H/C changeover
6/14
Thermal actuator
STP23... 4884
(for small valves 2.5 mm)
Ordering
When ordering, please indicate the product name, product number and SSN number:
(e.g. room thermostat, RDF310.2/MM, S55770-T187)
7/14
1
5
4
3
8/14
The thermostat can be mounted on a recessed square conduit box with fixing centres
of 60.3 mm. The mounting location on a wall should not be in niches or bookshelves,
not behind curtains, above or near heat sources and wind outlet or inlet, and not
exposed to direct solar radiation. Mounting height is about 1.5 m above the floor.
Wiring Please also refer to the Mounting Instructions M3066… enclosed with the thermostat.
· Wiring, protection and earthing must be installed in compliance with local
regulations.
Warning!
No internal line protection for supply lines to external consumers
(Q1, Q2, Q3, Y11, Y12)
Risk of fire and injury due to short-circuits!
· Adapt the line diameters as per local regulations to the rated value of the installed
overcurrent protection device.
· The AC 230 V mains supply line must have an external circuit breaker with a rated
current of no more than 10 A.
· Only valves rated for AC 230 V may be used.
· Disconnect from supply before opening the cover
Commissioning After applying power, the thermostat makes a reset during which all LCD segments
flash, indicating that the reset has been correctly made. This takes about 3 seconds.
Then, the thermostat is ready for commissioning by qualified HVAC staff.
The control parameters of the thermostat can be set to ensure optimum performance of
the entire system (please also refer to “Parameter settings”).
Heating/cooling mode · Set the heating/cooling mode via parameter P22 depending on the application.
Factory setting is “Manual heat/cool changeover”. Set P22 accordingly in ”Cooling
only” or “Heating only” mode.
Calibrating the sensor · When the room temperature displays on the thermostat does not match the room
temperature effectively measured, you can recalibrate the temperature sensor via
parameter P07.
Setpoint and range · For comfort and energy saving reasons, it is suggested to review the setpoints and
limitation setpoint ranges (parameters P03…P06), if necessary, to change them accordingly.
Disposal
The device is considered electrical and electronic equipment for disposal in terms of the
applicable European Directive and may not be disposed of as domestic garbage.
· Dispose of the device through channels provided for this purpose.
· Comply with all local and currently applicable laws and regulations.
9/14
10/14
Connection terminals
Connection diagrams
N1 RDF310.2/MM
L
30 66A 01
V1 On/off valve AC 230 V
M1 3-speed fan
max. 10 A
L
AC 230 V
N Q1 Q2 Q3 Y12 Y11
N1
V1
M1 4(2)A
4(2)A Max.
N Max.
N1 RDF310.2/MM
L
30 66A 02
L
AC 230 V
N Q1 Q2 Q3 Y12 Y11
N1
Y L
V2 N
M1 4(2)A
4(2)A Max.
N Max.
N1 RDF310.2/MM
L
30 66A 03
L
AC 230 V
N Q1 Q2 Q3 Y12 Y11
N1
V3
M1 4(2)A
4(2)A Max.
N Max.
11/14
86mm
86mm
10.5mm
63mm
26.5mm
14mm
12/14