Thermostat Manual - Siemens RDF310.2

This document provides information about the RDF310.2/MM flush-mounted room thermostat for controlling temperature in individual rooms or zones heated or cooled by 2-pipe fan coil units. The thermostat controls a 3-speed fan and an on/off valve actuator. It has modes for manual or automatic heating/cooling changeover, displays temperature, and allows setting control parameters. Functions include temperature maintenance, operating mode selection, fan speed control, and output to control heating/cooling valves or fans.

Uploaded by

sebarm86
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
4K views14 pages

Thermostat Manual - Siemens RDF310.2

This document provides information about the RDF310.2/MM flush-mounted room thermostat for controlling temperature in individual rooms or zones heated or cooled by 2-pipe fan coil units. The thermostat controls a 3-speed fan and an on/off valve actuator. It has modes for manual or automatic heating/cooling changeover, displays temperature, and allows setting control parameters. Functions include temperature maintenance, operating mode selection, fan speed control, and output to control heating/cooling valves or fans.

Uploaded by

sebarm86
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 14

3 066

RDF310.2/MM

Flush-mounted Room RDF310.2/MM


Thermostat
for 2-pipe fan coil units

· Output for on/off valve or 3-wire on/off valve actuator


· 3-speed fan control: Automatic or manual
· Manual heating/cooling changeover or continuous Cooling only / Heating only
· Operating modes: Comfort, Protection
· Adjustable commissioning and control parameters
· Optional display of room temperature or setpoint
· Minimum and maximum setpoint limitation
· Display temperature in increments of 0.5 °C
· Operating voltage AC 230 V
· Mounting on recessed square conduit box, fixing centres 60.3 mm
· User and parameter settings can be retained or restored with power loss

CB1N3066en
2019-10-25 Smart Infrastructue
Use

For controlling the room temperature in individual rooms and zones that are…
· heated or cooled with 2-pipe fan coil units

The thermostat controls…


· a 3-speed fan
· an on/off valve actuator in a 2-pipe system

Suitable for use in systems with…


· continuous heating or cooling mode
· manual heating/cooling changeover

Functions

· Manual changeover between heating and cooling mode


· Maintenance of room temperature with integrated internal temperature sensor

· Selection of operating mode with the operating mode button on the thermostat
· 3-speed fan control (automatic or manual)
· Output for 2-position (on/off) valve or 3-wire (on/off) valve actuator

Applications

Application and output signal, diagram

· 2-pipe fan coil unit ON/OFF (heating or cooling)


3076D20

V1

M1

T N1

V1 Heating/cooling valve actuator M1 3-speed fan


N1 Thermostat

2/14

Siemens Flush-mounted Room Thermostat CB1N3066en


Smart Infrastructure 2019-10-25
Operation

Temperature control The thermostat acquires the room temperature via its built-in sensor and maintains the
setpoint by delivering 2-position valve control commands.
The switching differential is 1 K in heating mode and 1 K in cooling mode (adjustable
via parameters P08 and P09).

Display The display shows the acquired room temperature or the setpoint of the current
operating mode. This can be selected via parameter P18. Factory setting is display of
the current room temperature.
The heating symbol or the cooling symbol displays to indicate the output status of
the relays connected to the fan coil. This means that the symbol does not display when
the thermostat operates in the neutral zone. If the thermostat is under manual heating
or cooling changeover, the heating symbol or the cooling symbol displays
permanently to indicate the control sequence. i.e. heating or cooling. This means that
the symbol displays when the thermostat operates in the neutral zone.
If required, room temperature and setpoint can also be displayed in °F in place of °C by
changing parameter P17.

Operating modes

The following operating modes are available:

Comfort Mode In Comfort mode, the thermostat maintains the setpoint, which can be adjusted via the
+ and - buttons. The fan can be set to automatic or manual fan speed: Low, medium or
high.

Tip! The setpoint setting range can be limited to a minimum (P05) and maximum (P06). This
helps prevent the waste of energy, and saving costs.
Protection Mode When the thermostat is in Protection mode , the relevant setpoints of heating or
cooling are maintained. These setpoints can be adjusted via control parameters P03
and P04. Factory setting of both setpoints is OFF, indicating the thermostat is not
activated when in Protection mode.

Avoiding damage To avoid damage due to moisture in very warm and humid climatic zones resulting from
due to moisture lack of air circulation in Comfort mode, the fan can be kept running all the time (e.g. in
apartments or shops during unoccupied periods), when setting parameter P21 “ON in
dead zone”. In this case, the fan keeps running at minimum fan speed 1 in the neutral
zone.

3/14

Siemens Flush-mounted Room Thermostat CB1N3066en


Smart Infrastructure 2019-10-25
Control sequences

Water-based fan coil Used in conjunction with a valve, either for heating/cooling with changeover, or heating
application only, cooling only.

Heating mode Cooling mode


Y11 Y11

w w

T[°C] Room temperature SDH Switching differential “Heating”


W Room temperature setpoint SDC Switching differential “Cooling”
Y11 Control output “Valve”

ON The valve receives the OPEN command via control output Y11 when
1. the acquired room temperature lies by half the switching differential below the
setpoint (heating mode) or above the setpoint (cooling mode), and
2. control output Y11 was not energized for more than the “Minimum output off time”
(factory setting 1 minute)
OFF The valve receives the CLOSE command via control output Y11 when
1. the acquired room temperature lies by half the switching differential above the
setpoint (heating mode) or below the setpoint (cooling mode), and
2. control output Y11 was energized for more than the “Minimum output on time”;
(factory setting 1 minute)

Note: Control output Y12 delivers a control command which is inverted to the control
command at output Y11 and which can be used for normally open valves.

Heating/cooling When you press the heating/cooling changeover button , the thermostat changes
mode from heating to cooling, or vice versa.
If the thermostat is set to ”Cooling only” or ”Heating only” via P22, the manual
changeover function on the button is not available (the factory setting of parameter P22
is ”manual changeover”). Instead, “NOP” flashes on the display, indicating continuous
cooling or heating is set respectively.

Minimum output The minimum output on/off time of Y11 and Y12 is fixed at 1 minute. It means that any
on/off time Y11 and readjustment of the setpoint or of Heating/Cooling Mode changeover lasts for
Y12 1 minute before Y11 and Y12 react.

4/14

Siemens Flush-mounted Room Thermostat CB1N3066en


Smart Infrastructure 2019-10-25
Fan operation

The fan operates either in automatic mode or at the selected speed when using manual
mode. In automatic mode, the fan speed depends on the setpoint and the current room
temperature. When the room temperature reaches the setpoint, the control valve is
closed and the fan either remains in fan speed 1 or switches off (parameter P21,
factory setting: fan speed 1 in dead zone).
In “Temperature-dependent” fan control the fan switches off (please see diagram
below). The individual switching differentials of the fan speed 1 (Q1 only) can be
adjusted via control parameters P08 – P09. The individual switching differentials of the
fan speed 2 and 3 (Q2 and Q3) are fixed at 1K.
Heating mode Cooling mode

3058D03
Valve Valve
Y11 Y11

W W
Temp Temp
Fan SDH Fan SDC
Q3 Q3

Q2 Q2

Q1 Q1

Temp Temp
SDH3 SDH2 SDH SDC SDC2 SDC3

Ventilation If desired, fan control can be set to ”Temperature-independent”, which means that
always on ventilation is always on, even within the dead zone, using at least fan speed 1. This can
be selected individually for Comfort mode via parameter P21; also refer to “Avoiding
damage due to moisture” on page 3).

Dwelling time In automatic mode, a dwelling time of 2 minutes (factory setting) is active. The fan
maintains that speed for at least 2 minutes before it switches to the next speed. This
dwelling time can be adjusted from 1…5 minutes via parameter P14.

Fan start Whenever the fan starts from standstill, it starts with speed 3 for 1 second in order to
guarantee a safe fan motor starts (to overcome inertia and friction).

Error handling

Temperature out of When the room temperature is out of the measuring range, which means above 49 °C
range or below 0 °C, the display shows the limiting temperature in flashing figures, e.g. “0 °C”
or “49 °C”.
If the current setpoint is not OFF (see parameter P03) and the thermostat is in heating
mode, when the temperature is below 0 °C, output Y11 is energized. In all other cases,
output Y11 is de-energized until the temperature returns to the measuring range, and
then the thermostat resumes Comfort mode.

5/14

Siemens Flush-mounted Room Thermostat CB1N3066en


Smart Infrastructure 2019-10-25
Control parameters

To optimize the control performance, you can use local HMI to adjust a number of
control parameters. Proceed as follows to change the control parameter.

Parameter settings 1. Set the thermostat to Protection mode .


2. Press and hold the + and – buttons simultaneously for 3 seconds. Release them
and, within 2 seconds, press and hold the + button again for 3 seconds. Then,
P03 displays.
3. Select the required parameter by pressing the + and – buttons:

4. Press the + and – buttons simultaneously. Te current value of the selected


parameter displays on the screen. Press the + or – button to change the value.
5. You can either press the + and – buttons simultaneously to confirm the change
or wait for 5 seconds to have the change saved automatically.
6. Repeat steps 3 through 5 to change more parameters.
7. 10 seconds after the last display or setting, all changes are saved and the
thermostat returns to Protection mode.

Parameter reset Reload the factory setting of the control parameters as follows:
1. Set the thermostat to Protection mode .
2. Press the + and – buttons simultaneously for 3 seconds. Release them and,

within 2 seconds, press the button twice.


Then 888 displays during the reloading process.

Control parameters
Para- Meaning Setting range Factory
meter setting
P03 Setpoint of heating in Protection Mode (WheatStb) OFF, 5 °C…WcoolStb 8 °C
P04 Setpoint of cooling in Protection Mode (WcoolStb) OFF, WheatStb …40 °C OFF
P05 Minimum setpoint limitation in Comfort Mode (WminNorm) 5 °C…WmaxNorm 5 °C
P06 Maximum setpoint limitation in Comfort Mode (WmaxNormf) WminNorm…40 °C 35 °C
P07 Sensor calibration -3…3 K 0K
P08 Switching differential heating mode SDH 0.5…4 K 1K
P09 Switching differential cooling mode SDC 0.5…4 K 1K
P14 Dwelling time of auto fan speeds 1…5 min 2 min
P17 Selection of °C or °F °C or °F °C
OFF: Setpoint
P18 Display of temperature or setpoint ON
ON: Room (or return air) temperature
OFF in dead zone
P21 Fan control in Comfort mode ON
ON in dead zone
0: Heating only
P22 Heating/cooling mode 1: Cooling only 3: Manual
3: Manual H/C changeover

6/14

Siemens Flush-mounted Room Thermostat CB1N3066en


Smart Infrastructure 2019-10-25
Equipment combinations

ON/OFF actuators Type of unit Product no. Data sheet


Electromotoric ON/OFF actuator SFA21... 4863
Electromotoric ON/OFF valve and
actuator (only available in AP, UAE, MVI…/MXI… A6V11251892
SA and IN)
Zone valve actuators (only available in
SUA… 4832
AP, UAE, SA and IN)

Thermal actuator (for radiator valve) STA23... 4884

Thermal actuator
STP23... 4884
(for small valves 2.5 mm)

Ordering

When ordering, please indicate the product name, product number and SSN number:
(e.g. room thermostat, RDF310.2/MM, S55770-T187)

Valve actuators should be ordered separately.

7/14

Siemens Flush-mounted Room Thermostat CB1N3066en


Smart Infrastructure 2019-10-25
Mechanical design

The thermostat consists of two parts:


· Front panel which accommodates the electronics, the operating elements and the
built-in room temperature sensor
· Mounting base with the power electronics
The mounting base carries on the rear side the screw terminals. It fits on a square
conduit box with fixing centres 60.3mm. The front panel engages in the mounting base
and snaps on.

Setting and operating


elements 7
8

1
5

4
3

Legend 1 Display of the room temperature, setpoints and control parameters


2 Symbol used when displaying the current room temperature
3 Protection mode / fan mode status
Protection mode
AUTO Auto fan active
Fan speed low, medium, high
4 output is energized (auto mode) / manual cooling mode (manual mode)
output is energized (auto mode) / manual heating mode (manual mode)
5 Comfort mode
6 Buttons for adjusting the setpoints and control parameters

7 Button for changing fan operation and Protection mode ( )

8 Manual heating/cooling changeover ( )

8/14

Siemens Flush-mounted Room Thermostat CB1N3066en


Smart Infrastructure 2019-10-25
Mounting and installation

The thermostat can be mounted on a recessed square conduit box with fixing centres
of 60.3 mm. The mounting location on a wall should not be in niches or bookshelves,
not behind curtains, above or near heat sources and wind outlet or inlet, and not
exposed to direct solar radiation. Mounting height is about 1.5 m above the floor.

Wiring Please also refer to the Mounting Instructions M3066… enclosed with the thermostat.
· Wiring, protection and earthing must be installed in compliance with local
regulations.
Warning!
No internal line protection for supply lines to external consumers
(Q1, Q2, Q3, Y11, Y12)
Risk of fire and injury due to short-circuits!
· Adapt the line diameters as per local regulations to the rated value of the installed
overcurrent protection device.
· The AC 230 V mains supply line must have an external circuit breaker with a rated
current of no more than 10 A.
· Only valves rated for AC 230 V may be used.
· Disconnect from supply before opening the cover

Commissioning After applying power, the thermostat makes a reset during which all LCD segments
flash, indicating that the reset has been correctly made. This takes about 3 seconds.
Then, the thermostat is ready for commissioning by qualified HVAC staff.
The control parameters of the thermostat can be set to ensure optimum performance of
the entire system (please also refer to “Parameter settings”).

Heating/cooling mode · Set the heating/cooling mode via parameter P22 depending on the application.
Factory setting is “Manual heat/cool changeover”. Set P22 accordingly in ”Cooling
only” or “Heating only” mode.
Calibrating the sensor · When the room temperature displays on the thermostat does not match the room
temperature effectively measured, you can recalibrate the temperature sensor via
parameter P07.
Setpoint and range · For comfort and energy saving reasons, it is suggested to review the setpoints and
limitation setpoint ranges (parameters P03…P06), if necessary, to change them accordingly.

Disposal

The device is considered electrical and electronic equipment for disposal in terms of the
applicable European Directive and may not be disposed of as domestic garbage.
· Dispose of the device through channels provided for this purpose.
· Comply with all local and currently applicable laws and regulations.

9/14

Siemens Flush-mounted Room Thermostat CB1N3066en


Smart Infrastructure 2019-10-25
Technical data

Power supply Operating voltage AC 230 V +10/-15%


Frequency 50/60 Hz
Power consumption Max. 4 VA
No internal fuse!
Caution
External preliminary protection with Max C 10 A circuit breaker
required in all cases.
Outputs Fan control Q1, Q2, Q3-N AC 230 V
Rating 5 mA…4(2) A
Control output Y11-N (N.O.) / Y12-N (N.C.) AC 230 V
Rating 5 mA…4(2) A
Operational data Switching differential
Heating mode 0.5...4 K (factory setting: 1 K)
Cooling mode 0.5...4 K (factory setting: 1 K)
Setpoint setting range
Comfort mode 5...40 °C
Protection mode OFF, 5...40 °C
Factory setting of setpoints
Comfort mode 20 °C
Protection (heating and cooling) mode OFF
Built-in room temperature sensor
Measuring range 0…49 °C
Accuracy at 25 °C <±0.5 K
Temperature calibration range ±3.0 K
Resolution of settings and display
Temperature setpoints 0.5 °C
Current temperature value displayed 0.5 °C
Environmental Storage to IEC 60721-3-1
conditions Climatic conditions class 1K3
Transport to IEC 60721-3-2
Climatic conditions class 2K3
Operation to IEC 60721-3-3
Climatic conditions class 3K5 1)
Norms and standards EU Conformity (CE) CB1T3066xx*)
RCM conformity AS/NZS 61000-6-3:2007
Electronic control type 2.B (micro-disconnection on
operation)
Devices of safety class II as per EN 60730-1
Pollution class II as per EN 60730-1
Degree of protection of housing IP 30 as per EN 60529
Housing flammability class according to UL94 V-0
Environmental The product environmental declaration CB1E3066en*) contains data on environmentally
conditions compatible product design and assessments (RoHS compliance, materials
composition, packaging, environmental benefit, disposal).

10/14

Siemens Flush-mounted Room Thermostat CB1N3066en


Smart Infrastructure 2019-10-25
General Connection terminals solid wires or prepared
stranded wires
1 x 0.4-1.5 mm2
Weight 0.17 kg
Color of housing front white, RAL 9003
*) The documents can be downloaded from http://siemens.com/bt/download.
1)
No condensation is allowed.

Connection terminals

L, N Operating voltage AC 230 V


Q1 Control output “Fan speed 1 AC 230 V
Q2 Control output “Fan speed 2 AC 230 V
Q3 Control output “Fan speed 3 AC 230 V
Y11 Control output “Valve” AC 230 V (N.O.)
Y12 Control output “Valve” AC 230 V (N.C.)

Connection diagrams

N1 RDF310.2/MM
L

30 66A 01
V1 On/off valve AC 230 V
M1 3-speed fan
max. 10 A

L
AC 230 V

N Q1 Q2 Q3 Y12 Y11
N1

V1
M1 4(2)A
4(2)A Max.
N Max.

N1 RDF310.2/MM
L
30 66A 02

V2 Electromotoric actuator, e.g. SUA21/1


max. 10 A
M1 3-speed fan

L
AC 230 V

N Q1 Q2 Q3 Y12 Y11
N1

Y L
V2 N
M1 4(2)A
4(2)A Max.
N Max.

N1 RDF310.2/MM
L
30 66A 03

V3 3-wire on/off (SPDT) zone valve


M1 3-speed fan
max. 10 A

L
AC 230 V

N Q1 Q2 Q3 Y12 Y11
N1

V3
M1 4(2)A
4(2)A Max.
N Max.

11/14

Siemens Flush-mounted Room Thermostat CB1N3066en


Smart Infrastructure 2019-10-25
Dimensions

86mm

86mm

10.5mm

63mm

26.5mm

14mm

12/14

Siemens Flush-mounted Room Thermostat CB1N3066en


Smart Infrastructure 2019-10-25
13/14

Siemens Flush-mounted Room Thermostat CB1N3066en


Smart Infrastructure 2019-10-25
Issued by © Siemens Switzerland Ltd, 2010 - 2019
Siemens Switzerland Ltd Technical specifications and availability subject to change without notice.
Smart Infrastructure
Global Headquarters
Theilerstrasse 1a
CH-6300 Zug
Tel. +41 58 724 2424
www.siemens.com/buildingtechnologies
14/14

Siemens Flush-mounted Room Thermostat CB1N3066en