Electrical Methodology
Electrical Methodology
Abstract
This electrical methodology explains the electrical calculations that the software does throughout
the PV plant. It also explains the different criteria of each of the electrical cabling standards that
pvDesign offers. The following topics are introduced in the methodology:
Electrical Methodology 1
Contents
Contents
Abstract 1
Electrical Methodology 2
Contents
4 Electrical Parameters 34
4.1 Resistance calculation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
4.2 Reactance calculation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
4.3 Zero sequence impedance calculation . . . . . . . . . . . . . . . . . . . . . . . . 35
4.4 Capacitive Susceptance calculation . . . . . . . . . . . . . . . . . . . . . . . . . 36
Bibliography 43
Electrical Methodology 3
List of Figures
List of Figures
1.1 Maximum number of modules per string with module temperature from -10 ºC
to -8ºC. Source: Own elaboration. . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.2 Maximum number of modules per string with module temperature from 5 ºC to
7ºC. Source: Own elaboration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.3 Maximum number of modules per string with module temperature from 10 ºC to
12ºC. Source: Own elaboration. . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
1.4 Maximum number of modules per string with module temperature from 20 ºC to
22ºC. Source: Own elaboration. . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Electrical Methodology 4
List of Tables
List of Tables
3.1 Correction factors applied according to IEC standards, [4] and [5]. . . . . . . . . 21
3.2 Correction factors applied according to NEC standard [2] . . . . . . . . . . . . . 23
3.3 Correction factors applied according to AUS standards, [6] [7]. . . . . . . . . . . 23
3.4 Correction factors applied according to GB 50217-2018 [8] . . . . . . . . . . . . 24
3.5 Constants that depend on the nature of the conductor . . . . . . . . . . . . . . . 26
3.6 Maximum conductor temperatures for different types of insulating compound
according to IEC [4] and [5]. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
3.7 Maximum conductor temperatures for different types of insulating compound
according to NEC [2]. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
3.8 Maximum conductor temperatures for different types of insulating compound
according to Australian standards [6] [7]. . . . . . . . . . . . . . . . . . . . . . . 27
3.9 Differences between the 𝑘 used in pvDesign and the one given by the Australian
Standard [6] [7]. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
3.10 Maximum conductor temperatures for different types of insulating compound
according to [8] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
3.11 Differences between the 𝑘 used in pvDesign and the one given by the Chinese
Standard [8]. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
3.12 Maximum conductor temperatures for different types of insulating in normal
condition to electrical standards . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Electrical Methodology 5
Chapter 1. Electrical equipment calculation
Chapter 1
The upper limit of the number of modules per string is constrained by both conditions, and the
second condition marks the lower limit.
The maximum voltage will be reached in low-temperature conditions when the modules operate
at high efficiency. Therefore, based on the minimum operating temperature, the expression used
to calculate the maximum number of modules in series according to the first condition mentioned
above is given by Equation 1.1.
𝑉max DC system
𝑁 𝑠 max (𝑉max DC system ) = (1.1)
𝑉oc (𝑇cell min )
Where:
• 𝑁𝑠 max (𝑉max DC system ) is the maximum number of modules per string that can be defined
without exceeding the maximum DC voltage.
• 𝑉max DC system is the minimum of the following values: maximum input voltage at the in-
verter, and maximum approved voltage of the module in [V].
• 𝑉oc (𝑇cell min ) is the open-circuit voltage of the cell at its minimum temperature in [V], cal-
culated using Equation 1.2.
The open-circuit voltage of the PV cells as a function of their temperature is calculated using
Equation 1.2.
𝜇
𝑉oc (𝑇cell min ) = 𝑉oc (25◦𝐶) + (𝑇cell min − 25) · 𝑉oc (25◦𝐶) · (1.2)
100
Electrical Methodology 6
Chapter 1. Electrical equipment calculation
Where:
• 𝑉oc (𝑇cell min ) is the open-circuit voltage of the cell at its minimum temperature in [V].
• 𝑉oc (25◦𝐶) is the open-circuit voltage of the cell at standard conditions in [V].
• 𝜇 is the module temperature coefficient of Voc in [%/ºC].
• 𝑇cell min is the minimum temperature of the solar cells in [ºC], calculated using Equation 1.3.
The cell temperature is obtained from the minimum air temperature at the location, as recom-
mended in IEC 62548 [1] and NEC 2017 [2] standards, as expressed in Equation 1.3.
Where:
To determine the maximum number of modules per string, the second condition must be also
taken into consideration. The expression used to calculate the maximum number of modules per
string that satisfies this condition is given by Equation 1.4.
Where:
• 𝑁𝑠 max (𝑉max MPPT inverter ) is the maximum number of modules per string that can be defined
to work within the voltage range that maximizes inverter’s efficiency.
• 𝑉max MPPT inverter is the maximum voltage of the MPPT voltage range of the inverter in [V].
• 𝑉mp (25◦𝐶) is the voltage at the maximum power of the cell at standard conditions in [V].
Once both conditions have been evaluated, the most restrictive value of the maximum number
of modules per string is considered as the final one.
To ensure that the voltage given by the string is within the operation window of the inverters,
the minimum number of modules per string must ensure that the voltage given is above the
minimum MPPT voltage accepted by the inverter even at maximum temperature conditions,
where the voltage of the string will be lower. The minimum number of modules per string is
calculated using Equation 1.5.
Where:
Electrical Methodology 7
Chapter 1. Electrical equipment calculation
• 𝑉mp (𝑇cell max ) is the voltage at the maximum power of the module at maximum temperature
in [V], calculated using Equation 1.6.
The voltage of the module at its MPP when the temperature is the maximum one is calculated
using Equation 1.6.
𝜇
𝑉mp (𝑇cell max ) = 𝑉mp (25◦𝐶) + (𝑇cell max − 25) · 𝑉mp (25◦𝐶) · (1.6)
100
Where:
• 𝑉mp (𝑇cell max ) is the voltage at the maximum power of the module at maximum temperature
in [V].
• 𝑉mp (25◦𝐶) is the voltage at the maximum power of the module at standard conditions in
[V].
• 𝜇 is the module temperature coefficient of Voc in [%/ºC].
• 𝑇cell max is the maximum temperature of the solar cells in [ºC], calculated using Equation 1.7.
𝑇𝑁 𝑂𝐶𝑇 ( ◦𝐶 ) −20◦𝐶
𝑇cell max = 𝑇air max + 𝐺 max · (1.7)
800𝑊 /𝑚 2
Where:
The minimum historical temperature normally occurs after the sunrise, when the atmosphere has
been longer without the sun heating it up. For this reason, differences between both temperatures
(minimum historical temperature and minimum historical temperature limited to sunlight hours)
do not normally cause differences in the maximum number of modules per string.
Considering a system where the DC maximum voltage is 1500 V, 𝑉OC of the module is 49.6 V and
the module temperature coefficient is -0.233 %/ºC and minimum historical temperatures of -10
Electrical Methodology 8
Chapter 1. Electrical equipment calculation
ºC, 5 ºC, 10 ºC and 20 ºC, Figure 1.1, Figure 1.2, Figure 1.3 and Figure 1.4 represent the tempera-
ture variation needed in the module to get an increase on the maximum value recommended of
modules per string.
Figure 1.1: Maximum number of modules per string with module temperature from -10 ºC to
-8ºC. Source: Own elaboration.
Figure 1.2: Maximum number of modules per string with module temperature from 5 ºC to 7ºC.
Source: Own elaboration.
Electrical Methodology 9
Chapter 1. Electrical equipment calculation
Figure 1.3: Maximum number of modules per string with module temperature from 10 ºC to 12ºC.
Source: Own elaboration.
Figure 1.4: Maximum number of modules per string with module temperature from 20 ºC to 22ºC.
Source: Own elaboration.
These figures show that the differences between minimum historical temperature and the mini-
mum historical temperature limited to sunlight hours must be 0.6 ºC, 1.7 ºC, 11.6 ºC and 1.6 ºC for
the cases where the minimum historical temperature is -10 ºC, 5 ºC, 10 ºC and 20 ºC, respectively,
to denote an increase on the maximum recommended number of modules per string. Moreover,
in a range of 30 ºC (between -10 ºC and 20 ºC), only 2 units on the number of modules per string
were increased (from 27 to 29).
Due to the small differences in the results obtained with both methods and to be in compliance
with NEC 2017 [2], pvDesign uses as cell temperature the minimum historical temperature to
calculate the maximum number of modules per string.
Electrical Methodology 10
Chapter 1. Electrical equipment calculation
• String Box: The strings of modules are connected to a string box. And groups of string
boxes are connected to central inverters. The number of strings per string box ranges
from 4 to 36.
• Bus System: The strings are connected to a DC Bus collector and the connections reach
the inverters. The number of strings per DC Bus collector ranges from 4 to 36.
• String Inverter (Field): The strings are connected directly to the string inverters. The string
inverters are located in the field (outside the power stations).
• String Inverter (Station): The string inverters, in this case, are located in the power stations.
1. The fuse current must be greater than or equal to 1.56 times the module’s short circuit
current.
𝐼 fuse ≥ 1.56 · 𝐼 sc (1.8)
2. The fuse current must have a value between the cable’s load current and its maximum
current capacity.
𝐼 load ≤ 𝐼 fuse ≤ 𝐼 ccc (1.9)
Where:
1.3.2 Breakers
To size the on-load circuit breaker, the following conditions must be considered:
1. The switch current rating must be greater than or equal to 1.25 times the module’s short
circuit current.
𝐼 breaker ≥ 1.25 · 𝐼 sc (1.10)
2. The switch current rating must be less than or equal to the maximum current capacity of
cables.
𝐼 breaker ≤ 𝐼 ccc (1.11)
Where:
Electrical Methodology 11
Chapter 1. Electrical equipment calculation
Electrical Methodology 12
Chapter 2. Distribution of strings into inverters and power stations
Chapter 2
This section explains how strings are distributed into inverters and power stations in pvDesign.
• The equipment defined such as PV module, inverter, structure and power station.
• The number of modules per string.
• The maximum number of structures that can be installed in the area, along with the number
of strings defined per structure. Strings from one structure will always be connected to the
same inverter.
• The power requirements like the distribution preferences and the desired DC/AC ratio.
It is important to also mention that areas cannot be connected electrically in pvDesign, so strings
from one area must be connected to inverters defined in that area.
1. Default power stations: power stations that will be prioritised in the plant, installing as
many as possible. Default power stations are defined by users.
2. Non-default power stations: power stations that will be installed in the case that the strings
remaining are not enough to fill one additional default power station. The order of priority
when installing them will be determined by the AC power of the non-default power station.
The definition of non-default power stations will depend on the type of inverter defined.
• Central inverters: all the possible combinations of inverters that do not exceed the
total amount of inverters defined in a default power station nor the maximum value
defined for one type of inverter.
• String inverters: all the possible combinations within the limits defined by the user.
Electrical Methodology 13
Chapter 2. Distribution of strings into inverters and power stations
1. Maximum capacity: install the maximum AC power in the design. There can be two modes
of simulation:
• Obtain the desired DC/AC ratio: this option ensures that the DC/AC ratio defined
by the user is matched in every area, but may result in structures uninstalled due to
incompatible electrical configuration.
• Install the maximum peak power: this option ensures that the maximum peak power
is installed for every area, always having a resulting DC/AC ratio that does not exceed
the limits of ±0.15 with respect to the desired one.
2. Specific capacity: install a specific AC power in the design by defining the number of
inverters of each type desired. It will ensure that the DC/AC ratio defined by the user is
matched in every area.
This calculation will give as result the power stations that will be installed and the total number
of strings per area. The later step will define the distribution of strings into inverters.
For every possible power station, starting with the default one and following with the non-default
ones, the number of power stations installed is calculated by Equation 2.1.
𝑃 DC,available
𝑁 PS = 𝐹𝑙𝑜𝑜𝑟 (2.1)
𝑃 AC,PS · 𝑃 DC/AC, desired + 𝑃 DC,embedded
Where:
𝑃 AC,comb · 𝑅DC/AC, desired 1
𝑁 strings,area = 𝑅𝑜𝑢𝑛𝑑 · · 𝑁 strings,structure (2.2)
𝑃 DC,string 𝑁 string,structure
Where:
Electrical Methodology 14
Chapter 2. Distribution of strings into inverters and power stations
For every possible power station, starting with the default one and following with the non-default
ones sorted by AC power, the lower and upper amount of power stations of each type that can
be installed is calculated using Equation 2.3 and Equation 2.4.
𝑃 DC,available
𝑁 PS,lower = 𝐹𝑙𝑜𝑜𝑟 (2.3)
𝑃 AC,PS · 𝑅DC/AC, desired + 𝑃 DC,embedded
𝑃 DC,available
𝑁 PS,upper = 𝐶𝑒𝑖𝑙 (2.4)
𝑃 AC,PS · 𝑅DC/AC, desired + 𝑃 DC,embedded
Where:
• 𝑁 PS,lower is the upper amount of the power station in evaluation to install. When installing
this amount of the power station in evaluation, there cannot be other power stations in-
stalled afterwards, as would give a DC/AC ratio that deviates more from the one desired.
• 𝑁 PS,upper is the lower amount of the power station in evaluation to install. When installing
this amount of the power station in evaluation, there can be other power stations installed
afterwards.
• 𝑃DC,available is the DC power available. It is recalculated considering the lower number of
previous power stations already installed.
• 𝑃AC,PS is the active AC power of the power station in evaluation.
• 𝑅DC/AC, desired is the desired DC/AC ratio.
• 𝑃DC,embedded is the DC power loss relative to one embed power station (if applicable).
For every possible combination, it will be evaluated if installing the maximum number of strings
available would give a DC/AC ratio within the limits. If so, that number of strings will be consid-
ered as the maximum that can be installed with that combination. If not, the maximum number
of strings that can be installed for the combination in evaluation is calculated as the value that
would give the maximum possible DC/AC ratio.
From all the combinations in consideration, the resulting combination for the area in evaluation
is the one with the highest DC power and the DC/AC ratio closest to the one desired.
Electrical Methodology 15
Chapter 2. Distribution of strings into inverters and power stations
It is important to note that, with this option, the areas that will be filled first with the inverters
defined will be the ones that are closest to the substation.
To calculate the resulting combination of power stations, a similar approach to the one explained
above for maximum capacity is followed, but considering also the number of inverters that are
remaining to be installed.
For every possible power station, starting with the default one and following with the non-default
ones sorted by AC power, the number of power stations installed is calculated using Equation 2.5.
𝑁 PS = 𝑀𝑖𝑛 𝑁 remaining,PS, 𝑁 max,PS (2.5)
Where:
• 𝑁 remaining,PS is the number of power stations that can be installed according to the inverters
remaining to be installed. It is calculated as the minimum relation between the inverters
remaining and the ones defined in the power station in evaluation.
• 𝑁 max,PS is the maximum number of power stations that can be installed according to the
DC power available, calculated using Equation 2.6.
𝑃 DC,available
𝑁 max, PS = 𝐹𝑙𝑜𝑜𝑟 (2.6)
𝑃 AC,PS · 𝑅DC/AC, desired + 𝑃DC,embedded
And:
For each inverter, the optimal number of strings to get the DC/AC ratio closest to the resulting
one is using Equation 2.7.
Electrical Methodology 16
Chapter 2. Distribution of strings into inverters and power stations
Where:
This number of strings defined per inverter could imply exceeding or not reaching the number
of strings desired to be installed in the area. The number of strings remaining to be installed or
removed from defined inverters is calculated as byEquation 2.8.
𝑁 inv,
∑︁area
𝑁 strings, redistribution = 𝑁 strings, area − 𝑁 strings, i (2.8)
𝑖=1
Where:
• 𝑁 strings,redistribution is the number of strings that are remaining to be installed or that have
to be removed from defined inverters. Note that this value can be negative or positive.
• 𝑁 strings,area is the number of strings to be installed in the area.
• 𝑁 inv,area is the number of inverters defined in the area.
• 𝑁 strings,i is the number of strings installed in the inverter in evaluation.
Where:
The number of inverters to be redistributed per power station will be directly related to the total
contribution of its inverters to the total number of inverters.
𝑁 inverters, PS
𝑁 inverters, adapt PS = · 𝑁 inverters, adapt (2.10)
𝑁 inverters, total
Electrical Methodology 17
Chapter 2. Distribution of strings into inverters and power stations
Where:
Lastly, the inverters that will be adapted to include the strings remaining will be the ones with
higher AC power, as those will have a lower deviation on the DC/AC ratio.
Electrical Methodology 18
Chapter 3. Electrical Sizing Criteria
Chapter 3
This section explains the different criteria followed by each of the electrical standards that pvDe-
sign offers.
3.1 Introduction
To size the cables of the PV plant based on the electrical standards, the following criteria must
be satisfied:
• Current-carrying capacity criterion: The operating current is corrected based on the dif-
ferent characteristics of the installation and the site. This corrected value must then be
lower than the maximum current-carrying capacity that the cable can withstand. These
maximum current-carrying capacity values are based on standard tables.
• Short-circuit temperature rise criterion: The short-circuit current must be lower than the
limit supported by the cabling. This criterion is taking into account only for medium volt-
age cables.
• Voltage drop criterion: The voltage drop criterion which states that the voltage drop in
each cable should be lower than the maximum values established by the user in pvDesign.
Although this criterion is considered to size the cable, to not comply with this condition
do not imply that the cable becomes damaged, but imply that the losses will be higher.
The constraints considered when calculating the low voltage (LV) and medium voltage (MV)
cables were:
• To minimize the costs using the minimum valid cable cross-section(s). We tend to limit
the number of cross-sections to a maximum of two in each sub-system of the PV plant
(standardize the cable cross-sections).
• Copper is proposed as the conducting material for the LV DC string cables. Aluminium is
proposed as the conducting material for the rest of cables (DC, AC and MV).
The assumptions made when sizing and rating the cables are the following:
Electrical Methodology 19
Chapter 3. Electrical Sizing Criteria
• The ambient temperature is the maximum historical temperature of the site (provided by
the meteo data source).
• The soil resistivity equals 1 K·m/W if no information is available.
• The depth of cables are 700 mm for buried LV cables and 900 mm for MV cables.
• There is no space between LV cables and the MV cables are spaced 0.2 m between group
centres.
• String cables are fastened to the structures. The rest of LV cables are directly buried in
trenches. MV radial networks from the power stations to the substation are directly buried
in trenches.
• Within a single MV circuit, cables are disposed in trefoil, with a separation between them
equal to two times the diameter of the cable.
The operating current is corrected based on the different characteristics of the installation and
the site. This corrected value must then be lower than the maximum current-carrying capacity
that the cable can withstand.
The equation for the corrected allowed current is given by Equation 3.1.
Where:
• 𝐼 sizing is the sizing current for the current-carrying capacity criterion in [A].
• 𝐼 ccc are the current values standardized for each cable cross-section based on the cable and
the installation characteristics in [A]
As it is presented in the following sections, the operating current of the cable is corrected with
some factors:
1. An ambient air temperature correction factor is only applied when the cables are exposed
to air or installed in trays fastened to the structures.
2. A soil temperature correction factor is only applied when the cables are directly buried in
trenches or underground cable ducts.
3. A soil resistivity correction factor is only applied when the cables are directly buried in
trenches or underground cable ducts.
4. We consider a depth of burial correction factor is only applied when the cables are directly
buried in trenches or underground cable ducts.
Electrical Methodology 20
Chapter 3. Electrical Sizing Criteria
5. Grouping cables together leads to additional heating of the cables which increases the
current passing through them.
𝐼 operating
𝐼 sizing = (3.2)
𝐶𝐹
Where:
• 𝐼 sizing is the sizing current for the current-carrying capacity criterion in [A].
• 𝐼 operating is the load current running through the cable in [A].
• 𝐶𝐹 is the product of all the applied correction factors.
The ambient and soil temperature correction factors are calculated using Equation 3.3.
12
𝜃 i − 𝜃 a 𝛽 + 𝜃 i′
𝐶𝐹 temp = ′ · (3.3)
𝜃 i − 𝜃 a′ 𝛽 + 𝜃 i
Where:
The other correction factors that are used to size a cable according to IEC standards are given in
Table 3.1.
Table 3.1: Correction factors applied according to IEC standards, [4] and [5].
According to IEC standards [4] and [5], in order to compute the correction factor for a group of
cables:
Electrical Methodology 21
Chapter 3. Electrical Sizing Criteria
• For DC cables: Two single-core cables or one multi-core cable are considered as one current-
carrying conductor.
• For AC cables: Three single-core cables or one multi-core cable are considered as one
current-carrying conductor.
𝐼 operating
𝐼 sizing = (3.4)
𝐶𝐹
Where:
• 𝐼 sizing is the sizing current for the current-carrying capacity criterion in [A].
• 𝐼 operating is the load current running through the cable in [A]. It is the inverter continuous
output current for string inverters and the operating current for the MV system.
• 𝐶𝐹 is the product of all the applied correction factors.
The sizing current for the photovoltaic source circuit (from modules to the inverters) is given by
Equation 3.5.
1.25 · 𝐼 sc
𝐼 corrected = (3.6)
𝐶𝐹
Where:
After that, we raise the result to the next standard fuse or circuit breaker size defined in section
240.6 of the NEC. The obtained current will be denoted as 𝐼 OCPD .
Where:
• 𝐼 OCPD is the protective device rated current defined in section 240.6 of the NEC in [A].
Electrical Methodology 22
Chapter 3. Electrical Sizing Criteria
• 𝐼 sc is the short-circuit current of the PV module for the string cables and the short-circuit
current of the module multiplied by the number of strings per box/DC bus in [A].
The ambient and soil temperature correction factors are calculated using Equation 3.3. The other
correction factors that are used to size a cable according to NEC standards are given in Table 3.2.
According to NEC standards, in order to compute the correction factor for a group of cables:
• For DC cables: Two single-core cables or one multi-core cable are considered as two
current-carrying conductors.
• For AC cables: Three single-core cables or one multi-core cable are considered as three
current-carrying conductors.
Table 3.3: Correction factors applied according to AUS standards, [6] [7].
The Australian standard considers one circuit to compute the correction factor for a group of
cables as any multicore cable with 2 or 3 current-carrying cores or a group of single core cables
with 2 or 3 current-carrying cables.
Electrical Methodology 23
Chapter 3. Electrical Sizing Criteria
To adapt the values given by [8] to the type of cables that are used in photovoltaic installations,
the following considerations have been made:
• Table C.0.1-1/2 has been used for low voltage PVC cables and Table C.0.1-3/4 has been used
for low voltage XLPE cables.
• Table C.0.3 has been used for MV XLPE cables.
• The values given for single core low voltage cables have been considered for both AC and
DC cables.
• The values given for multi core medium voltage cables have been considered for both single
and multi core cables.
• Soil resistivity correction factor has been considered for XLPE and PVC low voltage cables
and for XLPE medium voltage cables.
• The correction factors for groups of cables have been extended up to 12 cables, including
also the possibility of having cables touching. To do this, the guidelines presented in other
standards such as [4] and [6] have been followed.
2
𝐼
𝜃 = 𝜃 amb + (𝜃 i − 𝜃 amb ) · (3.8)
𝐼a
Where:
Electrical Methodology 24
Chapter 3. Electrical Sizing Criteria
is only applied in the case of MV cables and the equation that is applied is valid for all the electrical
standards. [10]
√ √
𝐼 AD · 𝑡 𝐼 sc · 𝑡
𝑆= = (3.9)
𝑘 𝜀 ·𝑘
Where:
√︄
𝜃f + 𝛽
𝑘 =𝐾· 𝑙𝑛 (3.10)
𝜃i + 𝛽
Where:
• 𝐾 is a constant that depends on the nature of the conductor and the temperature limit
of the insulator in [𝐴𝑠 0.5 /𝑚 2 ]. This parameter equals 226 𝐴𝑠 0.5 /𝑚𝑚 2 for copper (Cu) and
148 𝐴𝑠 0.5 /𝑚𝑚 2 for aluminium (Al).
• 𝛽 is the reciprocal of the temperature coefficient of resistivity at 0ºC. This parameter equals
234.5 ºC for copper (Cu) and 228 ºC for aluminium (Al).
• 𝜃 f is the final short circuit temperature of the conductor in [ºC]. Its value depends on the
standard.
• 𝜃 i is the maximum allowable conductor temperature in [ºC]. It equals the maximum oper-
ational insulator temperature in normal operation.
√
𝐼 sc · 𝑡
𝑆= √︄ (3.11)
𝜃f + 𝛽
𝐾 · 𝑙𝑛
𝜃i + 𝛽
Where the 𝐾 that is a constant that depends on the nature of the conductor and the temperature
limit of the insulator and 𝛽 that is the reciprocal of the temperature coefficient of resistivity at
0ºC, are shown in Table 3.5.
Electrical Methodology 25
Chapter 3. Electrical Sizing Criteria
Table 3.6: Maximum conductor temperatures for different types of insulating compound accord-
ing to IEC [4] and [5].
2 2 𝜃 f + 234.5
𝐼 sc · 𝑡 = 0.0297 · 𝑆 Cu · 𝑙𝑜𝑔10 (3.12)
𝜃 i + 234.5
2 2 𝜃 f + 228
𝐼 sc · 𝑡 = 0.0125 · 𝑆 Al · 𝑙𝑜𝑔10 (3.13)
𝜃 i + 228
Where:
𝑙𝑛(𝑥)
𝑙𝑜𝑔10 (𝑥) = (3.14)
2.3
1 𝑚𝑚 2 = 1973.5 𝑐𝑚𝑖𝑙 (3.15)
Electrical Methodology 26
Chapter 3. Electrical Sizing Criteria
The NEC equations to calculate the section based on the short-circuit rise criterion are the same
as the method followed by the IEC.
√
𝐼 sc · 𝑡 0.5 2
𝑆 Cu = √︂ √︄ ⇒ 𝐾Cu = 224.1 ≈ 226 𝐴𝑠 /𝑚𝑚 (3.16)
0.0297 𝜃 f + 234
· 1973.5 · 𝑙𝑛
2.3 𝜃 i + 234
√
𝐼 sc · 𝑡 0.5 2
𝑆 Al = √︂ √︄ ⇒ 𝐾Al = 145.4 ≈ 148 𝐴𝑠 /𝑚𝑚 (3.17)
0.0125 𝜃 f + 228
· 1973.5 · 𝑙𝑛
2.3 𝜃 i + 228
The NEC presents the maximum conductor temperatures for different types of insulating com-
pound and they can be seen in Table 3.7.
Table 3.7: Maximum conductor temperatures for different types of insulating compound accord-
ing to NEC [2].
Table 3.8: Maximum conductor temperatures for different types of insulating compound accord-
ing to Australian standards [6] [7].
Apart from these temperature limits, the Australian Standard provides the value of 𝑘 required in
its Table 52. The differences between those values and the ones calculated using the constants
presented in Table 3.5 are outlined in Table 3.9. As the differences are negligible, the constants
from Table 3.5 have been used to apply this criterion.
Table 3.9: Differences between the 𝑘 used in pvDesign and the one given by the Australian Stan-
dard [6] [7].
Conductor and insulator 𝑘 pvDesign [𝐴𝑠 0.5 /𝑚 2 ] 𝑘 Australian standard [𝐴𝑠 0.5 /𝑚 2 ]
Cu PVC 111.3 111.0
Al PVC 73.6 73.6
Cu XLPE/EPR 143.1 143.0
Al XLPE/EPR 94.5 94.5
Electrical Methodology 27
Chapter 3. Electrical Sizing Criteria
Applying the recommended values from this standard for copper and aluminium, and the max-
imum temperature allowed by insulating materials, the differences in the value of 𝑘 between
Table 3.5 and the ones given by this standard are the ones presented in Table 3.11. The values
are very similar and the constants from Table 3.5 have been used to apply this standard.
Table 3.11: Differences between the 𝑘 used in pvDesign and the one given by the Chinese Stan-
dard [8].
Conductor and insulator 𝑘 pvDesign [𝐴𝑠 0.5 /𝑚 2 ] 𝑘 Chinese standard [𝐴𝑠 0.5 /𝑚 2 ]
Cu PVC 102.8 112.82
Al PVC 68.0 67.07
Cu XLPE/EPR 143.1 143.37
Al XLPE/EPR 94.5 93.22
√︄ √︂
𝑡 𝑡
𝜀= 1+𝐹 ·𝐴· + 𝐹2 · 𝐵 · (3.18)
𝑆 𝑆
Where:
In order to analyse the error that is made by estimating a dissipation factor equals to 1, the next
process has been followed.
Electrical Methodology 28
Chapter 3. Electrical Sizing Criteria
3. If the real dissipation factor is closed to 1, the error made would be negligible.
As presented in Figure 3.1 and Figure 3.2, the real dissipation factor for short-circuit currents
higher than 10 kA (more common short-circuit currents for the MV system of a PV plant), is
almost 1. In conclusion, the dissipation factor can be taken as 1 and the error made would be
negligible.
Figure 3.1: Dissipation factor and Cu XLPE cross-section based on short-circuit temperature rise
[𝑚𝑚 2 ]. Source: Own elaboration.
Electrical Methodology 29
Chapter 3. Electrical Sizing Criteria
Figure 3.2: Dissipation factor and Al XLPE cross-section based on short-circuit temperature rise
[𝑚𝑚 2 ]. Source: Own elaboration.
In the case of AC cables, in both LV and MV sub-systems, the minimum cable cross-section per
the voltage drop criterion is given by Equation 3.19.
𝜌 · cos 𝜙
𝑆= (3.19)
Δ𝑉 · 𝑉
𝑛· √ − 𝑋 · sin 𝜙
3·𝐼 ·𝐿
Where:
Electrical Methodology 30
Chapter 3. Electrical Sizing Criteria
In the case of DC cables, the minimum cable cross-section per the voltage drop criterion ig given
by Equation 3.20.
2·𝜌 ·𝐿·𝐼
𝑆= (3.20)
Δ𝑉 · 𝑉
Where:
The resistivity of the conducting material at a specific temperature is calculated using Equa-
tion 3.21.
Where:
• 𝜌 is the conducting material resistivity at the cable’s insulator maximum operational tem-
perature in [Ω𝑚 2 /𝑚].
• 𝜌 (20◦𝐶) is the conducting material resistivity at 20ºC in [Ω𝑚 2 /𝑚]. It equals 1/56·10−6 Ω𝑚 2 /𝑚
for copper and 1/35 · 10−6 Ω𝑚 2 /𝑚 for aluminium
• 𝛼 is a parameter that depends on the type of material used. It equals 0.00392 ◦𝐶 −1 for
copper and 0.00403 ◦𝐶 −1 for aluminium.
• 𝜃 i is the maximum allowable conductor temperature in [ºC]. It equals the maximum oper-
ational insulator temperature in normal operation.
Electrical Methodology 31
Chapter 3. Electrical Sizing Criteria
Table 3.12: Maximum conductor temperatures for different types of insulating in normal condi-
tion to electrical standards
Figure 3.3: Al XLPE cable cross-section based on resistivities at different temperatures [𝑚𝑚 2 ].
Source: Own elaboration.
Where:
Electrical Methodology 32
Chapter 3. Electrical Sizing Criteria
Considering the DC cable resistance equals to the AC cable resistance can produce a maximum
of 7% error for sections from 300 to 630 𝑚𝑚 2 . For sections lower than 300 𝑚𝑚 2 , this error is
negligible. Taking both resistances as equals causes less conservative results as it is seen in
Figure 3.4 and Figure 3.5.
Figure 3.4: AC and DC resistivities for a Cu cable based on IEC. Source: Own elaboration.
Figure 3.5: AC and DC resistivities for a Cu cable based on Tables 8 and 9 of the NEC standard.
Source: Own elaboration.
Electrical Methodology 33
Chapter 4. Electrical Parameters
Chapter 4
Electrical Parameters
This section presents the calculation of the electrical parameters for the cables of the PV plant
and the BESS. The chapter introduces the calculation of the resistance, reactance, zero sequence
resistance, zero sequence reactance and susceptance of the conductors, covering only the LV AC
and MV AC cables.
Where:
• 𝑅𝐴𝐶 is the resistance of the AC cable in [Ω/𝑚]. Subsection 3.4.2 covers the reason why the
AC resistance is taken as equal to the DC resistance.
• 𝑅𝐷𝐶 is the resistance of the DC cable in [Ω/𝑚].
Ω
• 𝜌 (𝜃 ) is the resistivity of the conductor at temperature 𝜃 in .
𝑚𝑚 2 · 𝑚
• Φ is the section of the conductor in [𝑚𝑚 2 ].
• 𝑛 is the number of circuits.
2·𝑆
𝐿 = 𝐾 + 0.2 · ln · 10−6 (4.2)
𝑑
Electrical Methodology 34
Chapter 4. Electrical Parameters
Where:
𝑋𝐿 = 2𝜋 𝑓 𝐿 (4.3)
Where:
1.851
𝛿 = √︂ (4.4)
𝜇0
2𝜋 𝑓
𝜌
Where:
𝑅1 3 © 𝛿 𝜇𝑇 ª®
𝑍 0 = 𝑅0 + j𝑋 0 = + 𝜋 𝑓 𝜇0 + j𝑓 𝜇0 3 · ln √︃ + (4.5)
𝑛 4 3 2 4 · 𝑛®
𝑟 · 𝐷𝑀
« ¬
Where:
Electrical Methodology 35
Chapter 4. Electrical Parameters
Where:
By applying the geometrical features of the cylindrical surface of a conductor, the following
formula is obtained for the capacitance:
2𝜋𝜖0𝜖𝑅
𝐶= (4.8)
𝑅2
ln
𝑅1
Where:
Electrical Methodology 36
Chapter 4. Electrical Parameters
The susceptance is then calculated from the capacitance using Equation 4.9, where "B" is the
capacitive susceptance in Siemens [S].
𝐵 = 2𝜋 𝑓 𝐶 (4.9)
Electrical Methodology 37
Chapter 5. Power Flow Model
Chapter 5
This section presents the calculation of the Power Flow Model (PFM) following the guidelines of
the WECC [16]. The PFM represents the different elements of a PV plant as equivalent systems
in a simplified way.
5.1 Introduction
According to the WECC, the representation of the PFM is carried out for PV plants of over 20 MVA
and connected to 60 kV or above. However, pvDesign calculates the equivalent model regardless
of the size of the facility, therefore this calculation is applicable to any design generated with the
software.
Since pvDesign does not include the calculation of the reactive compensation devices, the equiv-
alent reactive compensation is not considered in the calculation of the PFM. An example of a
simple power flow model is shown in Figure 5.1.
Electrical Methodology 38
Chapter 5. Power Flow Model
The base capacity used to calculate the values per unit will be considered equal to 100 MVA.
However, for overhead lines with smaller capacities of less than 20 MVA, the base capacity will
be equal to the capacity of the line.
The calculation of the short circuit resistance and reactance can be done using the copper losses
and the short circuit impedance of the transformer.
Electrical Methodology 39
Chapter 5. Power Flow Model
The copper losses given as parts per unit will represent the per unit resistance of the transformer.
The per unit reactance can then be calculated as:
√︃
𝑋𝑝𝑢 = 𝑍𝑐𝑐,𝑝𝑢2 2
− 𝑅𝑝𝑢 (5.1)
The criteria to calculate the base capacity will be the same as the one for the overhead line.
· 𝑛𝑖2
Í𝑚
𝑖=1 𝑍𝑖
𝑍𝑒𝑞 = 𝑅𝑒𝑞 + 𝑗𝑋𝑒𝑞 = (5.2)
𝑁2
𝑚
∑︁
𝐵𝑒𝑞 = 𝐵𝑖 (5.3)
𝑖=1
Where:
The criteria to calculate the base capacity will be the same as the one for the overhead line.
𝑍𝑇 𝑒𝑞 = 𝑍𝑇 (5.4)
𝑆𝑇 𝑒𝑞 = 𝑁 · 𝑆𝑇 (5.5)
Where:
Electrical Methodology 40
Chapter 5. Power Flow Model
The WECC [16] covers the case where there is a different number of inverters connected to each
power transformer, which requires the application of the same method used for the MV collector
(Equation 5.2). However, pvDesign will consider the simplified case where the default power
station will be repeated across the PV plant.
The base capacity used to convert to per unit values is calculated according to Equation 5.6:
• 𝑆𝑏𝑎𝑠𝑒 is the base capacity of the equivalent pad mounted transformer in [VA].
• 𝑆𝑖𝑛𝑣 is the rated capacity of one inverter in [VA].
• 𝑛𝑖𝑛𝑣 is the number of inverters of the equivalent system.
If different inverters are installed behind the same substation transformer, each type of inverter
will have its own pad-mounted transformer equivalent. Figure 5.2 shows an example of an equiv-
alent system with secondary inverter enabled.
Figure 5.2: Power Flow Model of a PV plant with a secondary inverter enabled. Source: pvDesign
Since the power level of a solar PV plant depends on the weather conditions, the definition of
this power will depend on the objective of the equivalent model. For interconnection studies,
which is the case in pvDesign, the PV plant is modelled at full output. For other purposes, this
PV power can be modelled at partial output.
Electrical Methodology 41
Chapter 5. Power Flow Model
For the AC coupled BESS, the batteries and PV are modelled by separate equivalent generators,
equivalent pad-mounted transformers and equivalent MV collector systems. In Figure 5.3, an
example of a PFM with batteries is presented, without enabling the secondary inverter for the
PV plant.
Figure 5.3: Power Flow Model of a PV plant with an AC coupled battery energy storage system.
Source: pvDesign
Electrical Methodology 42
Bibliography
Bibliography
[1] Technical Committee 84, “Photovoltaic (pv) arrays - design requirements,” International
Electrotechnical Commision, IEC 62548:2016, 2016.
[2] National Electrical Code Committee, “Nfpa 70 national electrical code,” International Stan-
dard, 2017.
[3] Technical Committee 82, “Ground-mounted photovoltaic power plants - design guidelines
and recommendations,” International Electrotechnical Commision, IEC TS 62738:2018, 2018.
[4] Technical Committee 20, “Power cables with extruded insulation and their accessories for
rated voltages from 1 kv (um = 1,2 kv) up to 30 kv (um = 36 kv) - part 2: Cables for rated
voltages from 6 kv (um = 7,2 kv) up to 30 kv (um = 36 kv),” International Electrotechnical
Commision, IEC 60502-2:2014, 2014.
[5] Technical Committee 64, “Low-voltage electrical installations - part 5-52: Selection and
erection of electrical equipment - wiring systems,” International Electrotechnical Commi-
sion, IEC 60364-5-52:2009, 2009.
[6] S. A. Limited and S. N. Zealand, “Electrical installations: Selection of cables. cables for al-
ternating voltages up to and including 0.6/1 kv : Typical australian installation conditions,”
AS 3008.1.1:2017, 2017.
[7] “Medium voltage cables,” Prysmian Australia Pty Ltd, Technical report, 2015.
[8] “Standard for design of cables of electric power engineering,” National Standard of the
People’s Republic of China, Technical report GB 50217-2018, 2018.
[9] Prysmian Group, “Manual tecnico y practico de cables y accesorios para media tension,”
White paper, 2008.
[10] Technical Committee 20, “Calculation of thermally permissible short-circuit currents, tak-
ing into account non-adiabatic heating effects,” International Electrotechnical Commision,
IEC 60949:1988, 1988.
[11] RatedPower, “Substation methodology. a methodology to design an air-insulated substa-
tion,” RatedPower, 2020.
[12] Technical Committee 20, “Electric cables - calculation of the current rating - part 1-1: Cur-
rent rating equations and calculation of losses - general,” International Electrotechnical
Commision, IEC 60287-1-1:2006, 2006.
[13] BICC Cables Ltd, Electric Cables Handbook, 3rd Edition. 1997.
Electrical Methodology 43
Bibliography
[14] Technical Committee 73, “Short-circuit currents in three-phase ac systems - part 3: Cur-
rents during two separate simultaneous line-to-earth short circuits and partial short-circuit
currents flowing through earth,” International Electrotechnical Commision, IEC 60909-
3:2009, 2009.
[15] IEEE, “Ieee guide for measuring earthresistivity, ground impedance, and earth surface po-
tentials of agrounding system,” IEEE Industry Applications Society, IEEE Std 81:2012, 2012.
[16] WECC Modeling and Validation Work Group, “Solar photovoltaic power plant modeling
and validation guideline,” Western Electricity Coordinating Council, 2019.
[17] RatedPower, “Overhead line methodology,” RatedPower, 2022.
[18] E. Muljadi, A. Ellis, et al, “Equivalencing the collector system of a large wind power plant,”
National Renewable Energy Laboratory, 2006.
[19] IEEE, “IEEE Recommended Practice for Industrial and Commercial Power Systems Anal-
ysis,” no. IEEE Std 399-1997, 1997.
[20] Technical Committee 20, “Electric cables - calculation of the current rating - part 3-1: Op-
erating conditions - site reference conditions,” International Electrotechnical Commision,
IEC 60287-3-1:2017, 2017.
[21] Technical Committee 64, “Low-voltage electrical installations - part 5-54: Selection and
erection of electrical equipment - earthing arrangements and protective conductors,” In-
ternational Electrotechnical Commision, IEC 60364-5-54:2011, 2006.
Electrical Methodology 44
Appendix A. Determining the distribution of strings into inverters and power stations
Appendix A
For a better understanding of the process followed by pvDesign to calculate the distribution of
strings into inverters and power stations, one case scenario with the following characteristics is
considered:
The lower and upper number of default power stations that can be installed is calculated as:
𝑃 DC,available
𝑁 defPS,lower = 𝐹𝑙𝑜𝑜𝑟 (A.2)
𝑃 AC,PS · 𝑅DC/AC, desired + 𝑃 DC,embedded
Electrical Methodology 45
Appendix A. Determining the distribution of strings into inverters and power stations
© 33156.375 𝑘𝑊 𝑑𝑐 ª
𝑁 defPS,lower = 𝐹𝑙𝑜𝑜𝑟 ®=5 (A.3)
®
𝑘𝑊 𝑑𝑐 ®
5000 𝑘𝑊 𝑎𝑐 · 1.2 +0
« 𝑘𝑊 𝑎𝑐 ¬
𝑃 DC,available
𝑁 defPS,upper = 𝐶𝑒𝑖𝑙 (A.4)
𝑃AC,PS · 𝑅DC/AC, desired + 𝑃 DC,embedded
© 33156.375 𝑘𝑊 𝑑𝑐 ª
𝑁 defPS,upper = 𝐶𝑒𝑖𝑙 ®=6 (A.5)
®
𝑘𝑊 𝑑𝑐 ®
5000 𝑘𝑊 𝑎𝑐 · 1.2 +0
« 𝑘𝑊 𝑎𝑐 ¬
The updated DC power remaining for non-default power stations is calculated as:
𝑘𝑊 𝑑𝑐
𝑃 DC,available = 33156.375 𝑘𝑊 𝑑𝑐 − 5 · 5000 𝑘𝑊 𝑎𝑐 · 1.2 = 3156.375 𝑘𝑊 𝑑𝑐 (A.6)
𝑘𝑊 𝑎𝑐
The lower and upper number of non-default power stations that can be installed is calculated as:
𝑃 DC,available
𝑁 defPS,lower = 𝐹𝑙𝑜𝑜𝑟 (A.7)
𝑃 AC,PS · 𝑅DC/AC, desired + 𝑃 DC,embedded
© 3156.375 𝑘𝑊 𝑑𝑐 ª
𝑁 defPS,lower = 𝐹𝑙𝑜𝑜𝑟 ®=1 (A.8)
®
𝑘𝑊 𝑑𝑐 ®
2500 𝑘𝑊 𝑎𝑐 · 1.2 +0
« 𝑘𝑊 𝑎𝑐 ¬
𝑃 DC,available
𝑁 defPS,upper = 𝐶𝑒𝑖𝑙 (A.9)
𝑃AC,PS · 𝑅DC/AC, desired + 𝑃 DC,embedded
© 3156.375 𝑘𝑊 𝑑𝑐 ª
𝑁 defPS,upper = 𝐶𝑒𝑖𝑙 ®=2 (A.10)
®
𝑘𝑊 𝑑𝑐 ®
2500 𝑘𝑊 𝑎𝑐 · 1.2 +0
« 𝑘𝑊 𝑎𝑐 ¬
• 5 default power stations: 2229 strings can be installed and the resulting ratio would be
1.326.
• 6 default power stations: 2229 strings can be installed and the resulting ratio would be
1.105
• 5 default power stations and 1 non-default power station: 2229 strings can be installed and
the resulting ratio would be 1.205
• 5 default power stations and 2 non-default power stations: 2229 strings can be installed
and the resulting ratio would be 1.105
Electrical Methodology 46
Appendix A. Determining the distribution of strings into inverters and power stations
From the possible combinations, installing 5 default power stations and 1 non-default power
station is selected as the optimal one, as all the strings available would be installed and the ratio
is the one closest to the desired.
𝑘𝑊 𝑑𝑐
© 2500 𝑘𝑊 𝑎𝑐 · 1.2056 1 ª®
𝑁 strings,inverter = 𝑅𝑜𝑢𝑛𝑑
𝑘𝑊 𝑎𝑐 · ® · 3 = 204 (A.12)
0.595 𝑘𝑊 𝑑𝑐/𝑚𝑜𝑑 · 25 𝑚𝑜𝑑𝑠/𝑠𝑡𝑟𝑖𝑛𝑔 3 ®
« ¬
𝑁 inv,
∑︁area
𝑁 strings, redistribution = 𝑁 strings, area − 𝑁 strings, i (A.13)
𝑖=1
𝑁 inv,
∑︁area
𝑁 strings, redistribution = 2229 − 𝑁 strings, i = 2229 − 11 · 204 = −15 𝑠𝑡𝑟𝑖𝑛𝑔𝑠 (A.14)
𝑖=1
So, the number of inverters to adapt the optimal strings defined is:
15 strings need to be removed from 5 inverters, or 3 strings per inverter. As 5 default power
stations were defined, 3 strings will be removed from one inverter in each of them.
After this calculation, the resulting combination of power stations that will give a DC/AC ratio
of 1.2056 and will be composed by:
• 5 default power stations with 2 inverters, one with 201 strings and another with 204 strings.
• 1 non-default power station with 1 inverter with 204 strings.
Electrical Methodology 47
Appendix B. Determining cable cross-sections
Appendix B
The assumptions made for the following examples are the following ones:
𝑆 VA 12 · 106
𝐼 load = √ = √ = 230 𝐴 (B.1)
𝑉 · 3 30 · 103 · 3
The IEC standard followed to size a medium voltage cable is the IEC 60502-2. The reference
conditions that the IEC standard takes as basis for its tables are the following ones:
Electrical Methodology 48
Appendix B. Determining cable cross-sections
As the medium voltage cable is directly buried, the ground temperature correction factor is given
by Equation 3.3. The conductor is aluminium whose 𝛽 equals 228 ºC. The insulator material is
XLPE whose operational temperature in normal conditions is 𝜃 i = 90 ºC.
21 12
𝜃 i − 𝜃 a 𝛽 + 𝜃 i′
90 − 25 228 + 90
𝐶𝐹 temp = ′ · = · = 0.928 (B.2)
𝜃 i − 𝜃 a′ 𝛽 + 𝜃 i 90 − 20 228 + 90
The others corrections factors are given in the following table. In order to find them in the tables,
there are few parameters that need to be taken into account.
First of all, this medium voltage cable is a single core cable. There are 10 circuits that are grouped
together to link the power stations to the substations. In this case, according to IEC, a value of
10 current-carrying conductors should be considered to obtain the correction factor for a group
of cables. Second, the cable is installed at a depth of 0.9 m and they are spaced 0.2 m between
group centres. Last, the soil resistivity that is considered equals 1 Km/W.
According to table B.3 of the IEC standard, the section chosen is 300 𝑚𝑚 2 .
According to the short-circuit current criterion, the section is obtained using Equation 3.11. The
short-circuit temperature of the XLPE is 250 ºC.
√ √
𝐼 sc · 𝑡 25000 · 1 2
𝑆= √︄ = √︄ = 266 𝑚𝑚 (B.5)
𝜃f + 𝛽 250 + 228
𝐾 · 𝑙𝑛 148 · 𝑙𝑛
𝜃i + 𝛽 90 + 228
Electrical Methodology 49
Appendix B. Determining cable cross-sections
According to the voltage drop criterion, the section is obtained using Equation 3.19.
𝑆 VA 12 · 106
𝐼 load = √ = √ = 230 𝐴 (B.11)
𝑉 · 3 30 · 103 · 3
The reference conditions that the NEC standard takes as basis for its tables of MV cables are the
following ones:
As the medium voltage cable is directly buried, the ground temperature correction factor is given
by Equation 3.3. The conductor is aluminium whose 𝛽 equals 228 ºC. The insulator material is
XHHN whose operational temperature in normal conditions is 𝜃 i = 90 ºC.
21 12
𝜃 i − 𝜃 a 𝛽 + 𝜃 i′
90 − 25 228 + 90
𝐶𝐹 temp = ′ · = · = 0.928 (B.12)
𝜃 i − 𝜃 a′ 𝛽 + 𝜃 i 90 − 20 228 + 90
The others corrections factors are given in the following table. In order to find them in the tables,
there are few parameters that need to be taken into account.
Electrical Methodology 50
Appendix B. Determining cable cross-sections
First of all, this medium voltage cable is a single core cable. There are 10 circuits that are grouped
together to link the power stations to the substations. In this case, according to NEC, a value of
30 current-carrying conductors should be considered to obtain the correction factor for a group
of cables. Second, the cable is installed at a depth of 0.9 m and they are spaced 0.2 m between
group centres. Last, the soil resistivity that is considered equals 1 Km/W.
𝐼 operating 230
𝐼 sizing = = = 453 𝐴 (B.13)
𝐶𝐹 0.928 · 0.91 · 1 · 0.6
According to table 310.60(C)(86) of the NEC standard, the section chosen is 750 kcmil.
According to the short-circuit current criterion, the section is obtained using Equation 3.11. The
short-circuit temperature of the XHHN is 250 ºC.
√ √
𝐼 sc · 𝑡 25000 · 1 2
𝑆= √︄ = √︄ = 266 𝑚𝑚 (B.15)
𝜃f + 𝛽 250 + 228
𝐾 · 𝑙𝑛 148 · 𝑙𝑛
𝜃i + 𝛽 90 + 228
According to the voltage drop criterion, the section is obtained using the same methodology as
for IEC with Equation B.9.
𝑆 𝑁 𝐸𝐶 = 𝑆𝐼 𝐸𝐶 ≈ 45𝑚𝑚 2 (B.16)
Electrical Methodology 51
Appendix B. Determining cable cross-sections
𝑆 VA 10.585 · 103
𝐼 load = √ = = 9.24 𝐴 (B.18)
𝑉· 3 1145·
The IEC standard followed to size a low voltage cable is the IEC 60364-5-52. The reference con-
ditions that the IEC standard takes as basis for its tables are the following ones:
As the low voltage cable is fastened to a structure, the ambient temperature correction factor is
given by Equation 3.3. The conductor is copper whose 𝛽 equals 234.5 ºC. The insulator material
is XLPE whose operational temperature in normal conditions is 𝜃 i = 90 ºC.
12 21
𝜃 i − 𝜃 a 𝛽 + 𝜃 i′
90 − 40 234.5 + 90
𝐶𝐹 temp = ′ · = · = 0.83 (B.19)
𝜃 i − 𝜃 a′ 𝛽 + 𝜃 i 90 − 30 234.5 + 90
The others corrections factors are given in the following table. In order to find them in the tables,
there are few parameters that need to be taken into account.
First of all, this low voltage cable is a single core cable. There are 24 circuits that are grouped
together to link the structures to a string box. In this case, according to IEC, a value of 24 current-
carrying conductors should be considered to obtain the correction factor for a group of cables.
Second, the cable is fastened to a structure and they are touching among each other.
𝐼 operating 9.24
𝐼 sizing = = = 15.4 𝐴 (B.20)
𝐶𝐹 0.833 · 0.72
According to table B.52.12 of the IEC standard, the section chosen is 1.5 𝑚𝑚 2 .
Electrical Methodology 52
Appendix B. Determining cable cross-sections
According to the voltage drop criterion, the section is obtained using Equation 3.20.
The reference conditions that the NEC standard takes as basis for its tables of LV cables are the
following ones:
As the low voltage cable is fastened to a structure, the ambient temperature correction factor is
given by Equation 3.3. The conductor is copper whose 𝛽 equals 234.5 ºC. The insulator material
is XHHN whose operational temperature in normal conditions is 𝑡ℎ𝑒𝑡𝑎 i = 90 ºC.
12 21
𝜃 i − 𝜃 a 𝛽 + 𝜃 i′
90 − 40 234.5 + 90
𝐶𝐹 temp = ′ · = · = 0.83 (B.25)
𝜃 i − 𝜃 a′ 𝛽 + 𝜃 i 90 − 30 234.5 + 90
The others corrections factors are given in the following table. In order to find them in the tables,
there are few parameters that need to be taken into account.
First of all, this low voltage cable is a single core cable. There are 24 circuits that are grouped
together to link the structures to a string box. In this case, according to NEC, a value of 48
current-carrying conductors should be considered to obtain the correction factor for a group of
cables. Second, the cable is fastened to a structure and they are touching among each other.
Electrical Methodology 53
Appendix B. Determining cable cross-sections
According to table 310.15(B)(17) of the NEC standard, the section chosen is 14 AWG.
According to the voltage drop criterion, the section is obtained using Equation 3.20.
Electrical Methodology 54
Appendix C. Determining electrical characteristics of the cable
Appendix C
Determining electrical
characteristics of the cable
After selecting the cross-section based on the three criteria that have been presented in this
methodology, the electrical characteristics of the cable are computed. These are the voltage drop,
the temperature and the short-circuit current that the cables can withstand.
2
𝐼
𝜃 = 𝜃 amb + (𝜃 i − 𝜃 amb ) · (C.1)
𝐼a
2
230
𝜃 = 25 + (90 − 25) · = 84 ◦𝐶 < 𝜃 i = 90 ◦𝐶 ⇒ 𝑂𝐾 (C.2)
414 · 0.58
√
𝜌 · cos 𝜙 𝑋𝐿 · sin 𝜙
Δ𝑉 = 3 · 𝐼 · 𝐿 · + =
𝑛·Φ 𝑛
(C.3)
√
0.036631 · 0.9 0.00004511 · sin 25.842
3 · 230 · 500 · + = 25.8𝑉
1 · 300 1
Electrical Methodology 55
Appendix C. Determining electrical characteristics of the cable
Δ𝑉
Δ𝑉 (%) = ∗ 100 = 0.086% < Δ𝑉input = 0.5% ⇒ 𝑂𝐾 (C.4)
𝑉
√︄
𝜃f + 𝛽
𝑆 ·𝐾 · 𝑙𝑛
𝜃i + 𝛽
𝐼 sc = √ (C.5)
𝑡
√︄
250 + 228
300 · 148 · 𝑙𝑛
90 + 228
𝐼 sc = √ = 28.2 𝑘𝐴 > 𝐼 sc grid = 25 𝑘𝐴 ⇒ 𝑂𝐾 (C.6)
1
Electrical Methodology 56
Appendix D. Determining electrical parameters of the cable
Appendix D
Determining electrical
parameters of the cable
After the conductor section has been selected, the electrical parameters of the cable can be com-
puted following the equations of Chapter 4.
The following example is based on the cable that was calculated in Subsection B.1.1. At the end,
the cable cross-section was 300 𝑚𝑚 2 .
𝜌 (𝜃 ) 0.03594
𝑅𝐴𝐶 ≈ 𝑅𝐷𝐶 = ·= · 500 = 0.00012Ω/𝑚 (D.2)
Φ·𝑛 300 · 1
The reactance of the conductor can be calculated from Equation 4.2 and Equation 4.3. Note that
the axial separation of the conductors in trefoil "S" has been approximated to two times the
Electrical Methodology 57
Appendix D. Determining electrical parameters of the cable
diameter of the conductor, meaning that Equation 4.2 can be calculated without knowing the
real diameter of the conductor.
2·𝑆 −6 2 · 9.77
𝐿 = 𝐾 + 0.2 · ln · 10 = 0.05 + 0.2 · ln (2 · ) · 10−6 = 0.32726 · 10−6𝐻 /𝑚 (D.4)
𝑑 9.77
1.851 1.851
𝛿 = √︂ = √︂ = 1612.7𝑚 (D.7)
𝜇0 4𝜋 · 10 −7
2𝜋 𝑓 2𝜋 · 50
𝜌 300
𝑅1 3 © 𝛿 𝜇𝑇 ª®
𝑍 0 =𝑅0 + j𝑋 0 = + 𝜋 𝑓 𝜇 0 + j𝑓 𝜇0 3 · ln √︃ +
𝑛 4 3 2 4 · 𝑛®
𝑟 · 𝐷𝑀
« ¬ (D.8)
0.00012 3 −7 −7 1612.7 1
= + 𝜋 · 50 · 4𝜋 · 10 + j50 · 4𝜋 · 10 3 · ln √3 +
1 4 0.00977 · 0.039092 4 · 1
= (0.000268 + j0.00206)Ω
Due to a small distance between the conductors in the trefoil, the zero-sequence reactance value
is much higher than the positive-sequence value
Electrical Methodology 58
Appendix D. Determining electrical parameters of the cable
Electrical Methodology 59