Vision ™Plc+Hmi User Guide: General Description

This document provides installation instructions for several VisionTMPLC+HMI models, including the V130, V350, and V430 series. It describes the onboard I/O, screen size, and other features of each model. The document also provides guidelines for mounting the controllers, wiring diagrams for the I/O, and safety and regulatory information. Detailed documentation is available on the manufacturer's website.

Uploaded by

Adithya A R
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
71 views20 pages

Vision ™Plc+Hmi User Guide: General Description

This document provides installation instructions for several VisionTMPLC+HMI models, including the V130, V350, and V430 series. It describes the onboard I/O, screen size, and other features of each model. The document also provides guidelines for mounting the controllers, wiring diagrams for the I/O, and safety and regulatory information. Detailed documentation is available on the manufacturer's website.

Uploaded by

Adithya A R
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 20

Vision™PLC+HMI User Guide

V130-33-T2/V130-J-T2 ▪ 12 Digital Inputs, including 2 Analog,


V350-35-T2/V350-J-T2 3 HSC/Shaft-encoder inputs
V430-J-T2 ▪ 12 Transistor Outputs

General Description
The products listed above are micro-PLC+HMIs, rugged programmable logic controllers that comprise
built-in operating panels.
Detailed Installation Guides containing the I/O wiring diagrams for these models, technical specifications,
and additional documentation are located in the Technical Library in the Unitronics website:
https://unitronicsplc.com/support-technical-library/

V130-T2 V350-T2 V430J-T2


Item
V130J-T2 V350J-T2
On-board I/O Model Dependent

Screen 2.4" 3.5" Color Touch 4.3" Color Touch

Keypad Yes None

Function Keys None Yes

Com Port, Built-in

RS232/485 Yes Yes Yes* Yes* Yes*


USB device,
None None Yes* Yes* Yes*
mini-B
Com Ports, separate The user may install a CANbus port (V100-17-CAN), and one of the following:
order, user-installed • RS232/RS485 port (V100-17-RS4/V100-17-RS4X)
• Ethernet (V100-17-ET2)
• Profibus Slave (V100-17-PB1)
* V430J/V350/V350J comprises both RS232/485 and USB ports; note that only one channel may be used at a time.

Standard Kit Contents


V130-T2 V350-T2 V430J-T2
Item
V130J-T2 V350J-T2
Controller Yes
Terminal Blocks Yes
Battery (installed) Yes
Slides
None Yes None
(2 sets of key labels)
Mounting Brackets Yes (2 parts) Yes (4 parts)
Rubber Seal Yes

Unitronics 1
Vision™PLC+HMI Installation Guide

Alert Symbols and General Restrictions


When any of the following symbols appear, read the associated information carefully.
Symbol Meaning Description

Danger The identified danger causes physical and property damage.


Warning The identified danger could cause physical and property damage.
Caution Caution Use caution.
▪ Before using this product, the user must read and understand this document.
▪ All examples and diagrams are intended to aid understanding, and do not guarantee operation.
Unitronics accepts no responsibility for actual use of this product based on these examples.
▪ Please dispose of this product according to local and national standards and regulations.
▪ Only qualified service personnel should open this device or carry out repairs.
▪ Failure to comply with appropriate safety guidelines can cause severe injury or property
damage.
▪ Do not attempt to use this device with parameters that exceed permissible levels.
▪ To avoid damaging the system, do not connect/disconnect the device when power is on.

Environmental Considerations
▪ Do not install in areas with: excessive or conductive dust, corrosive or flammable gas,
moisture or rain, excessive heat, regular impact shocks or excessive vibration, in
accordance with the standards given in the product’s technical specification sheet.
▪ Do not place in water or let water leak onto the unit.
▪ Do not allow debris to fall inside the unit during installation.
▪ Ventilation: 10mm space required between controller’s top/bottom edges & enclosure walls.
▪ Install at maximum distance from high-voltage cables and power equipment.

Mounting
Note that figures are for illustrative purposes only.
Dimensions: V130/V350/V130J/V350J

2 Unitronics
Vision™PLC+HMI

* Note that for models V130/V350, the bezel width is up to 8.4 mm (0.33”).

Dimensions: V430J

Model Cut-out View area


V130V130J 92x92 mm (3.622”x3.622”) 58x30.5mm (2.28"x1.2")
V350/V350J 92x92 mm (3.622”x3.622”) 72x54.5mm (2.95"x2.14")
V430J 122.5x91.5 mm (4.82”x3.6”) 96.4x55.2mm (3.79"x2.17")

Panel Mounting
Before you begin, note that the mounting panel cannot be more than 5 mm thick.
1. Make a panel cut-out of the appropriate size:
2. Slide the controller into the cut-out, ensuring that the rubber seal is in place.
3. Push the mounting brackets into their slots on the sides of the panel as shown in the figure below.
4. Tighten the bracket’s screws against the panel. Hold the bracket securely against the unit while
tightening the screw.
5. When properly mounted, the controller is squarely situated in the panel cut-out as shown in the
accompanying figures.

V130/V350/V130J/V350J

Unitronics 3
Vision™PLC+HMI Installation Guide

V430J

DIN-rail Mounting (V130/V350/V130J/V350J)

1. Snap the controller onto the DIN rail as


shown in the figure to the right.

2. When properly mounted, the controller is


squarely situated on the DIN-rail as
shown in the figure to the right.

UL Compliance
The following section is relevant to Unitronics’ products that are listed with the UL.

The following models: V130-33-R34, V130-J-R34, V130-T4-ZK1, V350-35-RA22, V350-J-RA22,


V350-35-R34, V350-J-R34, V430-J-R34
are UL listed for Hazardous Locations.

The following models: V130-33-B1,V130-J-B1,V130-33-TA24,V130-J-TA24,V130-33-T38,V130-J-T38


V130-33-TR20,V130-J-TR20,V130-33-TR34,V130-J-TR34,V130-33-RA22,V130-J-RA22,
V130-33-TRA22,V130-J-TRA22,V130-33-T2,V130-J-T2,V130-33-TR6,V130-J-TR6,V130-33-R34,
V350-35-B1, V130-T4-ZK1, V350-J-B1,V350-35-TA24,V350-J-TA24,V350-35-T38,V350-J-T38,
V350-35-TR20,V350-J-TR20,V350-35-TR34,V350-J-TR34,V350-35-TRA22,V350-J-TRA22,
V350-35-T2,V350-J-T2,V350-35-TR6,V350-J-TR6,V350-S-TA24,V350-JS-TA24,V350-35-RA22,
4 Unitronics
Vision™PLC+HMI

V350-J-RA22,V350-35-R34, V430-J-B1,V430-J-TA24,V430-J-T38, V430-J-R34,V430-J-RH2,


V430-J-TR34,V430-J-RA22,V430-J-TRA22,V430-J-T2,V430-J-RH6
are UL listed for Ordinary Location.

For models from series V130, V130-J, V430, that include “T4” or “J4” in the Model name, Suitable for
mounting on the flat surface of Type 4X enclosure.
For examples: V130-T4-R34, V130-J4-R34, V430-J4-T2

UL Ordinary Location
In order to meet the UL ordinary location standard, panel-mount this device on the flat surface
of Type 1 or 4 X enclosures

UL Ratings, Programmable Controllers for Use in Hazardous Locations,


Class I, Division 2, Groups A, B, C and D
These Release Notes relate to all Unitronics products that bear the UL symbols used to mark products
that have been approved for use in hazardous locations, Class I, Division 2, Groups A, B, C and D.

Caution ▪ This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D, or Non-
hazardous locations only.
▪ Input and output wiring must be in accordance with Class I, Division 2 wiring methods and in
accordance with the authority having jurisdiction.
▪ WARNING—Explosion Hazard—substitution of components may impair suitability for Class I,
Division 2.
▪ WARNING – EXPLOSION HAZARD – Do not connect or disconnect equipment unless power
has been switched off or the area is known to be non-hazardous.
▪ WARNING – Exposure to some chemicals may degrade the sealing properties of material
used in Relays.
▪ This equipment must be installed using wiring methods as required for Class I, Division 2 as
per the NEC and/or CEC.
Panel-Mounting
For programmable controllers that can be mounted also on panel, in order to meet the UL Haz Loc
standard, panel-mount this device on the flat surface of Type 1 or Type 4X enclosures.
Relay Output Resistance Ratings
The products listed below contain relay outputs:
Programmable controllers, Models: V430-J-R34, V130-33-R34,V130-J-R34 and V350-35-R34,
V350-J-R34
▪ When these specific products are used in hazardous locations, they are rated at 3A res.
▪ Except for models V430-J-R34, V130-33-R34, V130-J-R34, V130-T4-ZK1 and V350-35-R34,
V350-J-R34,when these specific products are used in non-hazardous environmental conditions,
they are rated at 5A res, as given in the product’s specifications.

Communication and Removable Memory Storage


When products comprise either USB communication port, SD card slot, or both, neither
the SD card slot nor the USB port are intended to be permanently connected, while the USB port is
intended for programming only.
Removing / Replacing the battery
When a product has been installed with a battery, do not remove or replace the battery unless the
power has been switched off, or the area is known to be non-hazardous.

Unitronics 5
Vision™PLC+HMI Installation Guide
Please note that it is recommended to back up all data retained in RAM, in order to avoid losing data
when changing the battery while the power is switched off. Date and time information will also need to
be reset after the procedure.

UL des zones ordinaires:


Pour respecter la norme UL des zones ordinaires, monter l'appareil sur une surface plane de type de
protection 1 ou 4X

Certification UL des automates programmables, pour une utilisation en


environnement à risques, Class I, Division 2, Groups A, B, C et D.
Cette note fait référence à tous les produits Unitronics portant le symbole UL - produits qui ont été
certifiés pour une utilisation dans des endroits dangereux, Classe I, Division 2, Groupes A, B, C et D.

Attention ▪ Cet équipement est adapté pour une utilisation en Classe I, Division 2, Groupes A, B, C et
D, ou dans Non-dangereux endroits seulement.
▪ Le câblage des entrées/sorties doit être en accord avec les méthodes
de câblage selon la Classe I, Division 2 et en accord avec l’autorité compétente.
▪ AVERTISSEMENT: Risque d’Explosion – Le remplacement de certains composants rend
caduque la certification du produit selon la Classe I, Division 2.
▪ AVERTISSEMENT - DANGER D'EXPLOSION - Ne connecter pas ou ne débranche pas
l'équipement sans avoir préalablement coupé l'alimentation électrique ou la zone est
reconnue pour être non dangereuse.
▪ AVERTISSEMENT - L'exposition à certains produits chimiques peut dégrader les propriétés
des matériaux utilisés pour l'étanchéité dans les relais.
▪ Cet équipement doit être installé utilisant des méthodes de câblage suivant la norme Class I,
Division 2 NEC et /ou CEC.

Montage de l'écran:
Pour les automates programmables qui peuvent aussi être monté sur l'écran,
pour pouvoir être au standard UL, l'écran doit être monté dans un coffret avec une surface plane de
type 1 ou de type 4X.
Certification de la résistance des sorties relais
Les produits énumérés ci-dessous contiennent des sorties relais:
▪ Automates programmables, modèles : V430-J-R34, V130-33-R34,V130-J-R34 and
V350-35-R34,V350-J-R34
▪ Lorsque ces produits spécifiques sont utilisés dans des endroits dangereux, ils supportent
un courant de 3A charge résistive.
▪ Excepté les modèles: V430-J-R34, V130-33-R34,V130-J-R34, V130-T4-ZK1 et V350-35-R34,
V350-J-R34 lorsque ces produits spécifiques sont utilisés dans un environnement non dangereux, ils
sont évalués à 5A res, comme indiqué dans les specifications du produit Plages de températures
Communication et de stockage amovible de mémoire (carte mémoire)
Produits comprend un port USB de communication, soit un port carte SD ou les deux, ni le port SD, ni
le port USB ne sont censés être utilisés en permanence, tandis que l'USB est destiné à la
programmation uniquement.

Retrait / Remplacement de la batterie


Lorsqu'un produit a été installé avec une batterie, retirez et remplacez la batterie seulement si
l’alimentation est éteinte ou si l’environnement n’est pas dangereux.

6 Unitronics
Vision™PLC+HMI

Veuillez noter qu'il est recommandé de sauvegarder toutes les données conservées dans la RAM, afin
d'éviter de perdre des données lors du changement de la batterie lorsque l'alimentation est coupée. Les
informations sur la date et l'heure devront également être réinitialisées après la procédure

Wiring
▪ Do not touch live wires.

▪ Install an external circuit breaker. Guard against short-circuiting in external wiring.


▪ Use appropriate circuit protection devices.
▪ Unused pins should not be connected. Ignoring this directive may damage the device.
▪ Double-check all wiring before turning on the power supply.
▪ To avoid damaging the wire, do not exceed a maximum torque of 0.5 N·m (5 kgf·cm).
▪ Do not use tin, solder, or any substance on stripped wire that might cause the wire
Caution strand to break.
▪ Install at maximum distance from high-voltage cables and power equipment.

Wiring Procedure
Use crimp terminals for Use crimp terminals for wiring;
- Controllers offering a terminal block with pitch of 5mm: 26-12 AWG wire (0.13 mm2 –3.31 mm2).
- Controllers offering a terminal block with pitch of 3.81mm: 26-16 AWG wire (0.13 mm2 – 1.31 mm2).

1. Strip the wire to a length of 7±0.5mm (0.270–0.300“).


2. Unscrew the terminal to its widest position before inserting a wire.
3. Insert the wire completely into the terminal to ensure a proper connection.
4. Tighten enough to keep the wire from pulling free.

▪ Input or output cables should not be run through the same multi-core cable or share
the same wire.
▪ Allow for voltage drop and noise interference with I/O lines used over an extended distance.
Use wire that is properly sized for the load.
▪ The controller and I/O signals must be connected to the same 0V signal.

I/Os

V130/V350/V130J/V350J/V430J-T2 models comprise a total of 12 inputs and 12 transistor outputs.

Input functionality can be adapted as follows:


12 inputs may be used as digital inputs. They may be wired in a group via a single jumper
as either npn or pnp.
According to jumper settings and appropriate wiring:
- Inputs 10 and 11 can function as either digital or analog inputs.
- Inputs 0, 2 and 4 can function as high-speed counters, as part of a shaft-encoder,
or as normal digital inputs.
- Inputs 1, 3 and 5 can function as either counter reset, as part of a shaft-encoder,
or as normal digital inputs.
- If inputs 0, 2 and 4 are set as high-speed counters (without reset), inputs 1, 3 and 5 can function
as normal digital inputs.

Unitronics 7
Vision™PLC+HMI Installation Guide

Input Jumper Settings

The tables below show how to set a specific jumper to change input functionality. To access the I/O
jumpers, you must open the controller according to the instructions beginning on page 11.
▪ Incompatible jumper settings and wiring connections may seriously damage the controller.
▪ Do not move JP2.

Digital Inputs 0-11: Set Type


Set to JP1 (all Inputs)
npn (sink) A
pnp (source)* B
Inputs 10/11: Set as Digital or Analog
Set to JP5 (Input 10) JP6 (Input 11)
Digital* A A
Analog B B
Analog Inputs AN0/AN1: Set Type
Set to JP3 (AN0) JP4 (AN1)
Voltage* A A
Current B B

*Default settings

I/O Wiring
npn (sink) Input
Input wiring HSC input wiring

8 Unitronics
Vision™PLC+HMI

pnp (source) Input


Input wiring HSC input wiring

Shaft-encoder

Analog Input
Analog input wiring, current (2/3-wire) Analog input wiring, current (4-wire), Voltage

▪ Shields should be connected at the signal’s source.


▪ The 0V signal of the analog input must be connected to the controller’s 0V.

Unitronics 9
Vision™PLC+HMI Installation Guide

Transistors Outputs

▪ Outputs 0 to 6 can be used as PWM outputs.

Power Supply
The controller requires an external 24VDC power supply.
▪ The power supply must include double insulation. Outputs must be rated as
SELV/PELV/Class2/Limited Power.
▪ Use separate wires to connect the functional
earth line (pin 3) and the 0V line (pin 2) to the
system earth ground.
▪ Install an external circuit breaker. Guard
against short-circuiting in external wiring.
▪ Double-check all wiring before turning
on the power supply.
▪ Do not connect either the ‘Neutral’ or ‘Line’
signal of the 110/220VAC to device’s 0V pin
▪ In the event of voltage fluctuations or non-
conformity to voltage power supply
specifications, connect the device to
a regulated power supply.

Earthing the PLC+HMI


To maximize system performance, avoid electromagnetic interference by:
▪ Mounting the controller on a metal panel.
▪ Connect each common and ground connection directly to the earth ground of your system.
▪ For ground wiring uses the shortest and thickest possible wire.

10 Unitronics
Vision™PLC+HMI

Communication

▪ V130/ V130J
These models comprise a built-in RS232/RS485 serial port (Port 1)
▪ V430J/ V350/V350J
These models comprise built-in ports: 1 USB and 1 RS232/RS485 (Port 1).

Note that physically connecting a PC to the controller via USB suspends RS232/RS485
communications via Port 1. When the PC is disconnected, RS232/RS485 resumes.

RS232/RS485 Port

▪ Turn off power before making communications connections.

Caution ▪ Always use the appropriate port adapters.


▪ Signals are related to the controller’s 0V; the same 0V is used by the power supply.
Caution ▪ The serial port is not isolated. If the controller is used with a non-isolated external device,
avoid potential voltage that exceeds ± 10V.

▪ Use RS232 to download programs from a PC, and to communicate with serial devices and
applications, such as SCADA.
▪ Use RS485 to create a multi-drop network containing up to 32 devices.
Pinouts
The pinouts below show the PLC port signals.
RS232 RS485** Controller Port
Pin # Description Pin # Description
1* DTR signal 1 A signal (+)
2 0V reference 2 (RS232 signal)
3 TXD signal 3 (RS232 signal)
4 RXD signal 4 (RS232 signal) Pin #1
5 0V reference 5 (RS232 signal)
6* DSR signal 6 B signal (-)
* Standard programming cables do not provide connection points for pins 1 and 6.
** When a port is adapted to RS485, Pin 1 (DTR) is used for signal A,
and Pin 6 (DSR) signal is used for signal B.
Note that it is possible to establish a PC to PLC connection using RS232 even when the PLC is set to
RS485 (this eliminates the need to open the controller to set jumpers).
To do so, remove the RS485 connector (pins 1 & 6) from the PLC and connect a standard RS232
programming cable.
Note that this is possible only if DTR and DSR signals of RS232 are not used (which is the standard
case).

Unitronics 11
Vision™PLC+HMI Installation Guide

Setting RS232/RS485 Communication Parameters, V130/V350/V130J/V350J


This port may be set to either RS232 or RS485 via jumper.
The accompanying figure shows the jumper factory
default settings.
These jumpers may be used to:
▪ Set communications to RS485, by setting both
COMM jumpers to ‘485’.
▪ Set RS485 termination, by setting both TERM
jumpers to ‘OFF’.
To access the jumpers, you must open the controller
according to the instructions on page 11.

Setting RS232/RS485 Communication Parameters, V430J


This port may be set to either RS232 or RS485 via DIP switches:
The table shows the DIP switches factory default settings. Use the table to adapt the settings.
Switch Settings
1 2 3 4 5 6
RS232* ON OFF OFF ON OFF OFF
RS485 OFF ON ON OFF OFF OFF
RS485 with OFF ON ON OFF ON ON
termination**
* Default factory setting
** Causes the unit to function as an end unit in an RS485 network

USB Port

▪ The USB port is not isolated.


Caution
Make sure that the PC and the controller are grounded to same potential.

The USB port may be used for programming, OS download, and PC access.

12 Unitronics
Vision™PLC+HMI

Opening the Controller


▪ Before performing these actions, touch a grounded object to discharge any electrostatic charge.
▪ Avoid touching the PCB board directly. Hold the PCB board by its connectors.

1. Turn off the power supply, disconnect, and dismount the controller.
2. The back cover of the controller comprises 4 screws, located in the corners.
Remove the screws, and pull off the back cover.

Changing I/O Settings


After opening the controller and exposing the I/O board, you can change the jumper settings according
to the table shown above.

Changing Communication Settings (V130/V350/V130J/V350J Only)


1. To access the communication jumpers, hold the I/O PCB board by its top and bottom connectors
and steadily pull the board off.
2. Locate the jumpers, and then change the settings as required, according to the jumpers’ settings
shown on page 10.

Closing the Controller


1. Gently replace the board. Make certain that the pins fit correctly into their matching receptacle.
Do not force the board into place; doing so may damage the controller.
2. Replace the back cover of the controller and fasten the corner screws.

Note that you must replace the back cover securely before powering up the controller.

Unitronics 13
Vision™PLC+HMI Installation Guide
V130-33-T2/V130-J-T2
V350-35-T2/V350-J-T2
Vision™PLC+HMI V430-J-T2
Technical Specifications

Order Information
Item
V130-33-T2 PLC with Classic panel, Monochrome display 2.4"
V130-J-T2 PLC with Flat panel, Monochrome display 2.4"
V350-35-T2 PLC with Classic panel, Color touch display 3.5’’
V350-J-T2 PLC with Flat panel, Color touch display 3.5’’
V430-J-T2 PLC with Flat panel, Color touch display 4.3’’
You can find additional information, such as wiring diagrams, in the product’s installation guide
located in the Technical Library at www.unitronics.com.

Power Supply
V130-T2 V350-T2 V430J-T2
Item V130J-T2 V350J-T2
Input voltage 24VDC
Permissible range 20.4VDC to 28.8VDC with less than 10% ripple
Max. current
See Note 1
consumption
npn inputs 210mA@24VDC 230mA@24VDC 230mA@24VDC
pnp inputs 110mA@24VDC 135mA@24VDC 135mA@24VDC
Notes:
1. To calculate the actual power consumption, subtract the current for each unused element from the maximum
current consumption value according to the values below:

Backlight Ethernet card


V130/J 10mA 35mA
V350/J/V430J 20mA 35mA

Digital Inputs
Number of inputs 12. See note 2
Input type See note 2
Galvanic isolation None
Nominal input 24VDC
voltage
Input Voltage
pnp (source) 0-5VDC for Logic ‘0’
17-28.8VDC for Logic ‘1’
npn (sink) 17-28.8VDC for Logic ‘0’
0-5VDC for Logic ‘1’
Input Current 8mA@24VDC
Input impedance 3KΩ
Response Time 10ms typical, when used as normal digital
input
Input Cable length
Normal digital Up to 100 meters
Input
High Speed Input Up to 50 meters, shielded, see Frequency table below

14 Unitronics
Vision™PLC+HMI

High speed inputs Specifications below apply when wired as HSC/shaft-encoder.


See Note 2
Frequency (max) See Note 3
Cable length (max.) HSC Shaft-encoder
10m 30kHz 20kHz
25m 30kHz 13kHz
50m 25kHz 9kHz
Duty cycle 40-60%
Resolution 32-bit

Notes:
2. V130/V350/V130J/V350J/V430J-T2 models comprise a total of 12 inputs.

12 inputs may be used as digital inputs. They may be wired, in a group, and set to either
npn or pnp via a single jumper.
In addition, according to jumper settings and appropriate wiring:
- Inputs 10 and 11 can function as either digital or analog inputs.
- Inputs 0, 2, and 4 can function as high-speed counters, as part of a shaft-encoder,
or as normal digital inputs.
- Inputs 1, 3, and 5 can function as either counter reset, as part of a shaft-encoder,
or as normal digital inputs.
- If inputs 0, 2, 4 are set as high-speed counters (without reset), inputs 1, 3, 5 can function as normal digital
inputs.
3. pnp/npn maximum frequency is at 24VDC.

Analog Inputs
Number of inputs 2, according to wiring as described above in Note 2
Input type Multi-range inputs: 0-10V, 0-20mA, 4-20mA
Input range 0-20mA, 4-20mA 0-10VDC
Input impedance 243Ω >150KΩ
Maximum input rating 25mA, 6V 15V
Galvanic isolation None
Conversion method Successive approximation
Resolution (except 4-20mA) 10-bit (1024 units)
Resolution (at 4-20mA) 204 to 1023 (820 units)
Conversion time One configured input is updated per scan. See Note 4
Precision 0.9%
Status indication Yes – if an analog input deviates above the permissible range, its value will be
1024.
Notes:
4. For example, if 2 inputs are configured as analog, it takes 2 scans to update all analog values.

Unitronics 15
Vision™PLC+HMI Installation Guide

Digital Outputs
Number of outputs 12 transistor pnp (source)
Output type P-MOSFET (open drain)
Isolation None
Output current 0.5A maximum per output
(resistive load) 3A maximum total per common
Maximum frequency 50Hz (resistive load)
0.5Hz (inductive load)
PWM maximum frequency 0.5KHz (resistive load). See Note 2
Short circuit protection Yes
Short circuit indication Via software
On voltage drop 0.5VDC maximum
Power supply for outputs
Operating voltage 20.4 to 28.8VDC
Nominal voltage 24VDC

Notes:
2. Outputs 0 to 6 can be used as PWM outputs.

Graphic Display Screen


V130-T2 V350-T2 V430J-T2
Item
V130J-T2 V350J-T2
LCD Type STN, LCD display TFT, LCD display TFT, LCD display
Illumination backlight White LED White LED White LED
Display resolution 128x64 pixels 320x240 pixels 480x272 pixels
Viewing area 2.4" 3.5" 4.3"
Colors Monochrome 65,536 (16-bit) 65,536 (16-bit)
Screen Contrast Via software Fixed Fixed
(Store value to SI 7,
values range: 0 to
100%)
Touchscreen None Resistive, analog Resistive, analog
‘Touch’ indication None Via buzzer Via buzzer
Screen brightness control Via software Via software
(Store value to SI 9, (Store value to SI 9, values range: 0 to 100%)
0 = Off, 1 = On)
Virtual Keypad None Displays virtual keyboard when the application requires
data entry.

Keypad
V130-T2 V350-T2 V430J-T2
Item
V130J-T2 V350J-T2
Number of keys 20 keys,including 10 5 programmable function keys
user-labeled keys
Key type Metal dome, sealed membrane switch
Slides Slides may be Slides may be installed None
installed in the operating panel
in the operating faceplate to custom-label
panel faceplate to the keys. Refer to V350
custom-label the Keypad Slides.pdf.
keys. Refer to V130 Two sets of slides are
Keypad Slides.pdf. supplied with the
A complete set of controller: one set of
blank slides is arrow keys, and one
available by separate blank set.
order
16 Unitronics
Vision™PLC+HMI

Unitronics 17
Vision™PLC+HMI Installation Guide

Program
V130-T2 V350-T2 V430J-T2
Item
V130J-T2 V350J-T2
Memory size
Application Logic 512KB 1MB 1MB
Images 128KB 6MB 12MB
Fonts 128KB 512KB 512KB

Operand type Quantity Symbol Value


V130-T2 V350-T2
Item V130J-T2 V350J-T2
V430J-T2
Memory Bits 4096 8192 MB Bit (coil)
Memory Integers 2048 4096 MI 16-bit signed/unsigned
Long Integers 256 512 ML 32-bit signed/unsigned
Double Word 64 256 DW 32-bit unsigned
Memory Floats 24 64 MF 32-bit signed/unsigned
Fast Bits 1024 1024 XB Fast Bits (coil) – not retained
Fast Integers 512 512 XI 16 bit signed/unsigned
(fast, not retained)
Fast Long Integers 256 256 XL 32 bit signed/unsigned
(fast, not retained)
Fast Double Word 64 64 XDW 32 bit unsigned (fast, not retained)
Timers 192 384 T Res. 10 ms; max 99h, 59 min, 59.99s
Counters 24 32 C 32-bit

Data Tables 120K dynamic data (recipe parameters, datalogs, etc.)


192K fixed data (read-only data, ingredient names, etc)
Expandable via SD card. See Removable Memory below
HMI displays Up to 1024

Program scan time 20µs per 1kb 15µs per 1kb


of typical of typical
application application

Removable Memory
Micro SD card Compatible with standard SD and SDHC; up to 32GB store datalogs, Alarms, Trends,
Data Tables, backup Ladder, HMI, and OS.
See Note 6
Notes:
6.User must format via Unitronics SD tools utility.

18 Unitronics
Vision™PLC+HMI

Communication Ports
Port 1 1 channel, RS232/RS485 and USB device (V430/ V350/V350J only). See Note 7
Galvanic isolation No
Baud rate 300 to 115200 bps
RS232
Input voltage ±20VDC absolute maximum
Cable length 15m maximum (50’)
RS485
Input voltage -7 to +12VDC differential maximum
Cable type Shielded twisted pair, in compliance with EIA 485
Cable length 1200m maximum (4000’)
Nodes Up to 32
USB device
(V430/V350/V350J only)
Port type Mini-B, See Note 9
Specification USB 2.0 complaint; full speed
Cable USB 2.0 complaint; up to 3m
Port 2 (optional) See Note 8
CANbus (optional) See Note 8

Notes:
7. This model is supplied with a serial port: RS232/RS485 (Port 1). The standard is set to either RS232 or RS485
according to jumper settings. Refer to the product’s Installation Guide.
8. The user may order and install one or both of the following modules:
- An additional port (Port 2). Available port types: RS232/RS485 isolated/non-isolated, Ethernet
- A CANbus port
Port module documentation is available on the Unitronics website.
9. Note that physically connecting a PC to the controller via USB suspends RS232/RS485 communications
via Port 1. When the PC is disconnected, RS232/RS485 resumes.

I/O Expansion
Additional I/Os may be added. Configurations vary according to module.
Supports digital, high-speed, analog, weight and temperature measurement I/Os.
Local Via I/O Expansion Port. Integrate up to 8 I/O Expansion Modules comprising up
to 128 additional I/Os. Adapter required (P.N. EX-A2X).
Remote Via CANbus port. Connect up to 60 adapters to a distance of 1000 meters from
controller; and up to 8 I/O expansion modules to each adapter (up to a total of
512 I/Os). Adapter required (P.N. EX-RC1).

Miscellaneous
Clock (RTC) Real-time clock functions (date and time)
Battery back-up 7 years typical at 25°C, battery back-up for RTC and system data, including
variable data
Battery replacement Yes. Coin-type 3V, lithium battery, CR2450

Unitronics 19
Vision™PLC+HMI Installation Guide

Dimensions
V130-T2 V350-T2 V430J-T2
Item
V130J-T2 V350J-T2
Size Vxxx 109 x 114.1 x 68mm 109 x 114.1 x 68mm
(4.29 x 4.49 x 2.67”). (4.29 x 4.49 x 2.67”).
See Note 10 See Note 10
Vxxx-J 109 x 114.1 x 66mm 109 x 114.1 x 66mm 136 x 105.1 x 61.3mm
(4.92 x 4.49 x 2.59”). (4.92 x 4.49 x 2.59”). (5.35 x 4.13 x 2.41”).
See Note 10 See Note 10 See Note 10
Weight 315g (11.11 oz) 335g (11.81 oz) 365g (12.87 oz)

Notes:
10. For exact dimensions, refer to the product’s Installation Guide.

Environment
Operational temperature 0 to 50ºC (32 to 122ºF)
Storage temperature -20 to 60ºC (-4 to 140ºF)
Relative Humidity (RH) 10% to 95% (non-condensing)
Mounting method Panel mounted (IP65/66/NEMA4X)
DIN-rail mounted (IP20/NEMA1)
Operating Altitude 2000m (6562 ft)
Shock IEC 60068-2-27, 15G, 11ms duration
Vibration IEC 60068-2-6, 5Hz to 8.4Hz, 3.5mm constant amplitude,
8.4Hz to 150Hz, 1G acceleration.

The information in this document reflects products at the date of printing. Unitronics reserves the right, subject to all applicable laws, at any time, at its sole
discretion, and without notice, to discontinue or change the features, designs, materials and other specifications of its products, and to either permanently or
temporarily withdraw any of the forgoing from the market.
All information in this document is provided "as is" without warranty of any kind, either expressed or implied, including but not limited to any implied warranties of
merchantability, fitness for a particular purpose, or non-infringement. Unitronics assumes no responsibility for errors or omissions in the information presented in
this document. In no event shall Unitronics be liable for any special, incidental, indirect or consequential damages of any kind, or any damages whatsoever arising
out of or in connection with the use or performance of this information.
The tradenames, trademarks, logos and service marks presented in this document, including their design, are the property of Unitronics (1989) (R"G) Ltd. or other
third parties and you are not permitted to use them without the prior written consent of Unitronics or such third party as may own them
UG_V130_350_430-T2 12/22

20 Unitronics