Vision ™Plc+Hmi User Guide: General Description
Vision ™Plc+Hmi User Guide: General Description
General Description
The products listed above are micro-PLC+HMIs, rugged programmable logic controllers that comprise
built-in operating panels.
Detailed Installation Guides containing the I/O wiring diagrams for these models, technical specifications,
and additional documentation are located in the Technical Library in the Unitronics website:
https://unitronicsplc.com/support-technical-library/
Unitronics 1
Vision™PLC+HMI Installation Guide
Environmental Considerations
▪ Do not install in areas with: excessive or conductive dust, corrosive or flammable gas,
moisture or rain, excessive heat, regular impact shocks or excessive vibration, in
accordance with the standards given in the product’s technical specification sheet.
▪ Do not place in water or let water leak onto the unit.
▪ Do not allow debris to fall inside the unit during installation.
▪ Ventilation: 10mm space required between controller’s top/bottom edges & enclosure walls.
▪ Install at maximum distance from high-voltage cables and power equipment.
Mounting
Note that figures are for illustrative purposes only.
Dimensions: V130/V350/V130J/V350J
2 Unitronics
Vision™PLC+HMI
* Note that for models V130/V350, the bezel width is up to 8.4 mm (0.33”).
Dimensions: V430J
Panel Mounting
Before you begin, note that the mounting panel cannot be more than 5 mm thick.
1. Make a panel cut-out of the appropriate size:
2. Slide the controller into the cut-out, ensuring that the rubber seal is in place.
3. Push the mounting brackets into their slots on the sides of the panel as shown in the figure below.
4. Tighten the bracket’s screws against the panel. Hold the bracket securely against the unit while
tightening the screw.
5. When properly mounted, the controller is squarely situated in the panel cut-out as shown in the
accompanying figures.
V130/V350/V130J/V350J
Unitronics 3
Vision™PLC+HMI Installation Guide
V430J
UL Compliance
The following section is relevant to Unitronics’ products that are listed with the UL.
For models from series V130, V130-J, V430, that include “T4” or “J4” in the Model name, Suitable for
mounting on the flat surface of Type 4X enclosure.
For examples: V130-T4-R34, V130-J4-R34, V430-J4-T2
UL Ordinary Location
In order to meet the UL ordinary location standard, panel-mount this device on the flat surface
of Type 1 or 4 X enclosures
Caution ▪ This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D, or Non-
hazardous locations only.
▪ Input and output wiring must be in accordance with Class I, Division 2 wiring methods and in
accordance with the authority having jurisdiction.
▪ WARNING—Explosion Hazard—substitution of components may impair suitability for Class I,
Division 2.
▪ WARNING – EXPLOSION HAZARD – Do not connect or disconnect equipment unless power
has been switched off or the area is known to be non-hazardous.
▪ WARNING – Exposure to some chemicals may degrade the sealing properties of material
used in Relays.
▪ This equipment must be installed using wiring methods as required for Class I, Division 2 as
per the NEC and/or CEC.
Panel-Mounting
For programmable controllers that can be mounted also on panel, in order to meet the UL Haz Loc
standard, panel-mount this device on the flat surface of Type 1 or Type 4X enclosures.
Relay Output Resistance Ratings
The products listed below contain relay outputs:
Programmable controllers, Models: V430-J-R34, V130-33-R34,V130-J-R34 and V350-35-R34,
V350-J-R34
▪ When these specific products are used in hazardous locations, they are rated at 3A res.
▪ Except for models V430-J-R34, V130-33-R34, V130-J-R34, V130-T4-ZK1 and V350-35-R34,
V350-J-R34,when these specific products are used in non-hazardous environmental conditions,
they are rated at 5A res, as given in the product’s specifications.
Unitronics 5
Vision™PLC+HMI Installation Guide
Please note that it is recommended to back up all data retained in RAM, in order to avoid losing data
when changing the battery while the power is switched off. Date and time information will also need to
be reset after the procedure.
Attention ▪ Cet équipement est adapté pour une utilisation en Classe I, Division 2, Groupes A, B, C et
D, ou dans Non-dangereux endroits seulement.
▪ Le câblage des entrées/sorties doit être en accord avec les méthodes
de câblage selon la Classe I, Division 2 et en accord avec l’autorité compétente.
▪ AVERTISSEMENT: Risque d’Explosion – Le remplacement de certains composants rend
caduque la certification du produit selon la Classe I, Division 2.
▪ AVERTISSEMENT - DANGER D'EXPLOSION - Ne connecter pas ou ne débranche pas
l'équipement sans avoir préalablement coupé l'alimentation électrique ou la zone est
reconnue pour être non dangereuse.
▪ AVERTISSEMENT - L'exposition à certains produits chimiques peut dégrader les propriétés
des matériaux utilisés pour l'étanchéité dans les relais.
▪ Cet équipement doit être installé utilisant des méthodes de câblage suivant la norme Class I,
Division 2 NEC et /ou CEC.
Montage de l'écran:
Pour les automates programmables qui peuvent aussi être monté sur l'écran,
pour pouvoir être au standard UL, l'écran doit être monté dans un coffret avec une surface plane de
type 1 ou de type 4X.
Certification de la résistance des sorties relais
Les produits énumérés ci-dessous contiennent des sorties relais:
▪ Automates programmables, modèles : V430-J-R34, V130-33-R34,V130-J-R34 and
V350-35-R34,V350-J-R34
▪ Lorsque ces produits spécifiques sont utilisés dans des endroits dangereux, ils supportent
un courant de 3A charge résistive.
▪ Excepté les modèles: V430-J-R34, V130-33-R34,V130-J-R34, V130-T4-ZK1 et V350-35-R34,
V350-J-R34 lorsque ces produits spécifiques sont utilisés dans un environnement non dangereux, ils
sont évalués à 5A res, comme indiqué dans les specifications du produit Plages de températures
Communication et de stockage amovible de mémoire (carte mémoire)
Produits comprend un port USB de communication, soit un port carte SD ou les deux, ni le port SD, ni
le port USB ne sont censés être utilisés en permanence, tandis que l'USB est destiné à la
programmation uniquement.
6 Unitronics
Vision™PLC+HMI
Veuillez noter qu'il est recommandé de sauvegarder toutes les données conservées dans la RAM, afin
d'éviter de perdre des données lors du changement de la batterie lorsque l'alimentation est coupée. Les
informations sur la date et l'heure devront également être réinitialisées après la procédure
Wiring
▪ Do not touch live wires.
Wiring Procedure
Use crimp terminals for Use crimp terminals for wiring;
- Controllers offering a terminal block with pitch of 5mm: 26-12 AWG wire (0.13 mm2 –3.31 mm2).
- Controllers offering a terminal block with pitch of 3.81mm: 26-16 AWG wire (0.13 mm2 – 1.31 mm2).
▪ Input or output cables should not be run through the same multi-core cable or share
the same wire.
▪ Allow for voltage drop and noise interference with I/O lines used over an extended distance.
Use wire that is properly sized for the load.
▪ The controller and I/O signals must be connected to the same 0V signal.
I/Os
Unitronics 7
Vision™PLC+HMI Installation Guide
The tables below show how to set a specific jumper to change input functionality. To access the I/O
jumpers, you must open the controller according to the instructions beginning on page 11.
▪ Incompatible jumper settings and wiring connections may seriously damage the controller.
▪ Do not move JP2.
*Default settings
I/O Wiring
npn (sink) Input
Input wiring HSC input wiring
8 Unitronics
Vision™PLC+HMI
Shaft-encoder
Analog Input
Analog input wiring, current (2/3-wire) Analog input wiring, current (4-wire), Voltage
Unitronics 9
Vision™PLC+HMI Installation Guide
Transistors Outputs
Power Supply
The controller requires an external 24VDC power supply.
▪ The power supply must include double insulation. Outputs must be rated as
SELV/PELV/Class2/Limited Power.
▪ Use separate wires to connect the functional
earth line (pin 3) and the 0V line (pin 2) to the
system earth ground.
▪ Install an external circuit breaker. Guard
against short-circuiting in external wiring.
▪ Double-check all wiring before turning
on the power supply.
▪ Do not connect either the ‘Neutral’ or ‘Line’
signal of the 110/220VAC to device’s 0V pin
▪ In the event of voltage fluctuations or non-
conformity to voltage power supply
specifications, connect the device to
a regulated power supply.
10 Unitronics
Vision™PLC+HMI
Communication
▪ V130/ V130J
These models comprise a built-in RS232/RS485 serial port (Port 1)
▪ V430J/ V350/V350J
These models comprise built-in ports: 1 USB and 1 RS232/RS485 (Port 1).
Note that physically connecting a PC to the controller via USB suspends RS232/RS485
communications via Port 1. When the PC is disconnected, RS232/RS485 resumes.
RS232/RS485 Port
▪ Use RS232 to download programs from a PC, and to communicate with serial devices and
applications, such as SCADA.
▪ Use RS485 to create a multi-drop network containing up to 32 devices.
Pinouts
The pinouts below show the PLC port signals.
RS232 RS485** Controller Port
Pin # Description Pin # Description
1* DTR signal 1 A signal (+)
2 0V reference 2 (RS232 signal)
3 TXD signal 3 (RS232 signal)
4 RXD signal 4 (RS232 signal) Pin #1
5 0V reference 5 (RS232 signal)
6* DSR signal 6 B signal (-)
* Standard programming cables do not provide connection points for pins 1 and 6.
** When a port is adapted to RS485, Pin 1 (DTR) is used for signal A,
and Pin 6 (DSR) signal is used for signal B.
Note that it is possible to establish a PC to PLC connection using RS232 even when the PLC is set to
RS485 (this eliminates the need to open the controller to set jumpers).
To do so, remove the RS485 connector (pins 1 & 6) from the PLC and connect a standard RS232
programming cable.
Note that this is possible only if DTR and DSR signals of RS232 are not used (which is the standard
case).
Unitronics 11
Vision™PLC+HMI Installation Guide
USB Port
The USB port may be used for programming, OS download, and PC access.
12 Unitronics
Vision™PLC+HMI
1. Turn off the power supply, disconnect, and dismount the controller.
2. The back cover of the controller comprises 4 screws, located in the corners.
Remove the screws, and pull off the back cover.
Note that you must replace the back cover securely before powering up the controller.
Unitronics 13
Vision™PLC+HMI Installation Guide
V130-33-T2/V130-J-T2
V350-35-T2/V350-J-T2
Vision™PLC+HMI V430-J-T2
Technical Specifications
Order Information
Item
V130-33-T2 PLC with Classic panel, Monochrome display 2.4"
V130-J-T2 PLC with Flat panel, Monochrome display 2.4"
V350-35-T2 PLC with Classic panel, Color touch display 3.5’’
V350-J-T2 PLC with Flat panel, Color touch display 3.5’’
V430-J-T2 PLC with Flat panel, Color touch display 4.3’’
You can find additional information, such as wiring diagrams, in the product’s installation guide
located in the Technical Library at www.unitronics.com.
Power Supply
V130-T2 V350-T2 V430J-T2
Item V130J-T2 V350J-T2
Input voltage 24VDC
Permissible range 20.4VDC to 28.8VDC with less than 10% ripple
Max. current
See Note 1
consumption
npn inputs 210mA@24VDC 230mA@24VDC 230mA@24VDC
pnp inputs 110mA@24VDC 135mA@24VDC 135mA@24VDC
Notes:
1. To calculate the actual power consumption, subtract the current for each unused element from the maximum
current consumption value according to the values below:
Digital Inputs
Number of inputs 12. See note 2
Input type See note 2
Galvanic isolation None
Nominal input 24VDC
voltage
Input Voltage
pnp (source) 0-5VDC for Logic ‘0’
17-28.8VDC for Logic ‘1’
npn (sink) 17-28.8VDC for Logic ‘0’
0-5VDC for Logic ‘1’
Input Current 8mA@24VDC
Input impedance 3KΩ
Response Time 10ms typical, when used as normal digital
input
Input Cable length
Normal digital Up to 100 meters
Input
High Speed Input Up to 50 meters, shielded, see Frequency table below
14 Unitronics
Vision™PLC+HMI
Notes:
2. V130/V350/V130J/V350J/V430J-T2 models comprise a total of 12 inputs.
12 inputs may be used as digital inputs. They may be wired, in a group, and set to either
npn or pnp via a single jumper.
In addition, according to jumper settings and appropriate wiring:
- Inputs 10 and 11 can function as either digital or analog inputs.
- Inputs 0, 2, and 4 can function as high-speed counters, as part of a shaft-encoder,
or as normal digital inputs.
- Inputs 1, 3, and 5 can function as either counter reset, as part of a shaft-encoder,
or as normal digital inputs.
- If inputs 0, 2, 4 are set as high-speed counters (without reset), inputs 1, 3, 5 can function as normal digital
inputs.
3. pnp/npn maximum frequency is at 24VDC.
Analog Inputs
Number of inputs 2, according to wiring as described above in Note 2
Input type Multi-range inputs: 0-10V, 0-20mA, 4-20mA
Input range 0-20mA, 4-20mA 0-10VDC
Input impedance 243Ω >150KΩ
Maximum input rating 25mA, 6V 15V
Galvanic isolation None
Conversion method Successive approximation
Resolution (except 4-20mA) 10-bit (1024 units)
Resolution (at 4-20mA) 204 to 1023 (820 units)
Conversion time One configured input is updated per scan. See Note 4
Precision 0.9%
Status indication Yes – if an analog input deviates above the permissible range, its value will be
1024.
Notes:
4. For example, if 2 inputs are configured as analog, it takes 2 scans to update all analog values.
Unitronics 15
Vision™PLC+HMI Installation Guide
Digital Outputs
Number of outputs 12 transistor pnp (source)
Output type P-MOSFET (open drain)
Isolation None
Output current 0.5A maximum per output
(resistive load) 3A maximum total per common
Maximum frequency 50Hz (resistive load)
0.5Hz (inductive load)
PWM maximum frequency 0.5KHz (resistive load). See Note 2
Short circuit protection Yes
Short circuit indication Via software
On voltage drop 0.5VDC maximum
Power supply for outputs
Operating voltage 20.4 to 28.8VDC
Nominal voltage 24VDC
Notes:
2. Outputs 0 to 6 can be used as PWM outputs.
Keypad
V130-T2 V350-T2 V430J-T2
Item
V130J-T2 V350J-T2
Number of keys 20 keys,including 10 5 programmable function keys
user-labeled keys
Key type Metal dome, sealed membrane switch
Slides Slides may be Slides may be installed None
installed in the operating panel
in the operating faceplate to custom-label
panel faceplate to the keys. Refer to V350
custom-label the Keypad Slides.pdf.
keys. Refer to V130 Two sets of slides are
Keypad Slides.pdf. supplied with the
A complete set of controller: one set of
blank slides is arrow keys, and one
available by separate blank set.
order
16 Unitronics
Vision™PLC+HMI
Unitronics 17
Vision™PLC+HMI Installation Guide
Program
V130-T2 V350-T2 V430J-T2
Item
V130J-T2 V350J-T2
Memory size
Application Logic 512KB 1MB 1MB
Images 128KB 6MB 12MB
Fonts 128KB 512KB 512KB
Removable Memory
Micro SD card Compatible with standard SD and SDHC; up to 32GB store datalogs, Alarms, Trends,
Data Tables, backup Ladder, HMI, and OS.
See Note 6
Notes:
6.User must format via Unitronics SD tools utility.
18 Unitronics
Vision™PLC+HMI
Communication Ports
Port 1 1 channel, RS232/RS485 and USB device (V430/ V350/V350J only). See Note 7
Galvanic isolation No
Baud rate 300 to 115200 bps
RS232
Input voltage ±20VDC absolute maximum
Cable length 15m maximum (50’)
RS485
Input voltage -7 to +12VDC differential maximum
Cable type Shielded twisted pair, in compliance with EIA 485
Cable length 1200m maximum (4000’)
Nodes Up to 32
USB device
(V430/V350/V350J only)
Port type Mini-B, See Note 9
Specification USB 2.0 complaint; full speed
Cable USB 2.0 complaint; up to 3m
Port 2 (optional) See Note 8
CANbus (optional) See Note 8
Notes:
7. This model is supplied with a serial port: RS232/RS485 (Port 1). The standard is set to either RS232 or RS485
according to jumper settings. Refer to the product’s Installation Guide.
8. The user may order and install one or both of the following modules:
- An additional port (Port 2). Available port types: RS232/RS485 isolated/non-isolated, Ethernet
- A CANbus port
Port module documentation is available on the Unitronics website.
9. Note that physically connecting a PC to the controller via USB suspends RS232/RS485 communications
via Port 1. When the PC is disconnected, RS232/RS485 resumes.
I/O Expansion
Additional I/Os may be added. Configurations vary according to module.
Supports digital, high-speed, analog, weight and temperature measurement I/Os.
Local Via I/O Expansion Port. Integrate up to 8 I/O Expansion Modules comprising up
to 128 additional I/Os. Adapter required (P.N. EX-A2X).
Remote Via CANbus port. Connect up to 60 adapters to a distance of 1000 meters from
controller; and up to 8 I/O expansion modules to each adapter (up to a total of
512 I/Os). Adapter required (P.N. EX-RC1).
Miscellaneous
Clock (RTC) Real-time clock functions (date and time)
Battery back-up 7 years typical at 25°C, battery back-up for RTC and system data, including
variable data
Battery replacement Yes. Coin-type 3V, lithium battery, CR2450
Unitronics 19
Vision™PLC+HMI Installation Guide
Dimensions
V130-T2 V350-T2 V430J-T2
Item
V130J-T2 V350J-T2
Size Vxxx 109 x 114.1 x 68mm 109 x 114.1 x 68mm
(4.29 x 4.49 x 2.67”). (4.29 x 4.49 x 2.67”).
See Note 10 See Note 10
Vxxx-J 109 x 114.1 x 66mm 109 x 114.1 x 66mm 136 x 105.1 x 61.3mm
(4.92 x 4.49 x 2.59”). (4.92 x 4.49 x 2.59”). (5.35 x 4.13 x 2.41”).
See Note 10 See Note 10 See Note 10
Weight 315g (11.11 oz) 335g (11.81 oz) 365g (12.87 oz)
Notes:
10. For exact dimensions, refer to the product’s Installation Guide.
Environment
Operational temperature 0 to 50ºC (32 to 122ºF)
Storage temperature -20 to 60ºC (-4 to 140ºF)
Relative Humidity (RH) 10% to 95% (non-condensing)
Mounting method Panel mounted (IP65/66/NEMA4X)
DIN-rail mounted (IP20/NEMA1)
Operating Altitude 2000m (6562 ft)
Shock IEC 60068-2-27, 15G, 11ms duration
Vibration IEC 60068-2-6, 5Hz to 8.4Hz, 3.5mm constant amplitude,
8.4Hz to 150Hz, 1G acceleration.
The information in this document reflects products at the date of printing. Unitronics reserves the right, subject to all applicable laws, at any time, at its sole
discretion, and without notice, to discontinue or change the features, designs, materials and other specifications of its products, and to either permanently or
temporarily withdraw any of the forgoing from the market.
All information in this document is provided "as is" without warranty of any kind, either expressed or implied, including but not limited to any implied warranties of
merchantability, fitness for a particular purpose, or non-infringement. Unitronics assumes no responsibility for errors or omissions in the information presented in
this document. In no event shall Unitronics be liable for any special, incidental, indirect or consequential damages of any kind, or any damages whatsoever arising
out of or in connection with the use or performance of this information.
The tradenames, trademarks, logos and service marks presented in this document, including their design, are the property of Unitronics (1989) (R"G) Ltd. or other
third parties and you are not permitted to use them without the prior written consent of Unitronics or such third party as may own them
UG_V130_350_430-T2 12/22
20 Unitronics