0% found this document useful (0 votes)
35 views2 pages

2mva Tr. For HF-1

The document provides a test report for a high voltage breaker. It details equipment specifications, test equipment used, results of insulation resistance measurements, VCB timing tests, contact resistance tests, coil resistance tests, and high potential tests. All test results were found to be satisfactory and the breaker was deemed fit for service.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
35 views2 pages

2mva Tr. For HF-1

The document provides a test report for a high voltage breaker. It details equipment specifications, test equipment used, results of insulation resistance measurements, VCB timing tests, contact resistance tests, coil resistance tests, and high potential tests. All test results were found to be satisfactory and the breaker was deemed fit for service.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
You are on page 1/ 2

TEST REPORT FOR HT BREAKER

ELECTROTEST DOC. No :
DATE :
PVT. LTD. TESTING DATE : 20-12-2023
FEEDER :- 2MVA TR-1 FOR HF-1
CLIENT : TSL, JAMSHEDPUR PANEL:- 6.6 KV HT SWBD
Page 1 of 2
LOCATION : NEW S/S ST MILLS FEEDER NO. :- 12

01. EQUIPMENT DETAILS :-

Make L&T Rated Volts 12kV


Name 2MVA TR-1.FOR HF-1 Rated Current 1250 A
Sl. No. M-2022-42 Making Capacity 40kA
Installation INDOOR Breaking Capacity 40kA
Mfg. Year 2022 Operating Duty O-0.3s-CO-3MIN-CO
Type VK10M40H

02. TESTING EQUIPMENT DETAILS:-


CALIBRATION
INSTRUMENT MAKE SL. NO. RANGE
DUE DATE
Digital Insulation tester Motwane A02747J21 0 – 5 KV 12-01-2025
Digital Multimeter Fluke 55030407 0-1000 V 12-01-2025
CRM 100 Scope 2300.06AI0990 0-100 A/0-2000µΩ 12-01-2025
Breaker Time Interval Meter Scope 2100.02AI0832 ----- 12-01-2025

03. INSULATION RESISTANCE MEASUREMENT : ( 2.5 ) KV DC MEGGER FOR 1 MIN.


I.R. VALUE
Reference
Before Hi Pot After Hi Pot Limits
R – R’ 505 GΩ 510 GΩ
Y – Y’ 511 GΩ 515 GΩ
B – B’ 502 GΩ 510 GΩ
R–E 418 GΩ 420 GΩ
Y–E 415 GΩ 419 GΩ ≥100 MΩ
B–E 421 GΩ 422 GΩ
R–Y 247 GΩ 248 GΩ
Y–B 298 GΩ 299 GΩ
B–R 321 GΩ 324 GΩ

04. VCB TIMING TEST :-

PHASE CLOSING TIME ( in ms) TRIP TIME ( in ms) CLOSE – OPEN TIME ( in ms)
TC1 TC2 TC1 TC2
Rph 25 21 23 23 23
Yph 25 21 23 23 23
Bph 25 21 23 24 23
05. VCB CONTACT RESISTANCE TEST :-
REFERENCE MEASURED VALUE NO. OF JOINTS LIMIT REMARKS
TEST REPORT FOR HT BREAKER
ELECTROTEST DOC. No :
DATE :
PVT. LTD. TESTING DATE : 20-12-2023
FEEDER :- 2MVA TR-1 FOR HF-1
CLIENT : TSL, JAMSHEDPUR PANEL:- 6.6 KV HT SWBD
Page 2 of 2
LOCATION : NEW S/S ST MILLS FEEDER NO. :- 12

R – R’ 23 µΩ 05
Y – Y’ 23 µΩ 05 <100 µΩ OK
B – B’ 21 µΩ 05

06. COIL RESISTANCE TEST :


COIL No. MEASURED VALUE RATED VALUE DEVIATION REMARKS
Closing Coil 37.5 Ω 37.2 Ω 0.8% OK
Tripping Coil-1 37.1 Ω 37.2 Ω 0.2% OK
Tripping Coil-2 37.4 Ω 37.2 Ω 0.5% OK
Motor Coil 5.45 MΩ NA NA OK

a) Hi – Pot Test of Close Condition :-


Reference Applied voltage ( AC ) Time in Min Measured Leakage
in KV Current (mA)
R – Y+B+E 14.0 1.0 0.3
Y – R+B+E 14.0 1.0 0.2
B – R+Y+E 14.0 1.0 0.3

b) Hi – pot Test of Open Condition :-


Reference Applied voltage ( AC ) Time in Min Measured Leakage
in KV Current (mA)
R – R’+E 8.0 1.0 0.1
Y – Y’+E 8.0 1.0 0.1
B – B’+E 8.0 1.0 0.1

Remarks:- Test results found satisfactory, BREAKER is fit for service.

TEST PERFORMED BY: TEST WITNESSED BY:


Name : Vishal & Dhanai Name : Nandan kumar
Organization: Electrotest Pvt. Ltd Organization : TSL E&P

Checked by/
ELECTROTEST TSL (E&P) TSL ETD
Approved By
Name: Abhishek Singh
Designation: Manager
Signature.
Date: