v7dfts3 Instructions
v7dfts3 Instructions
Basic Features:
Luxurious look with 2x4 ‘7-Segment’ Display.
33 Default Modes.
Modes can be Customized as per user's requirement.
Wide range of Applications with multiple Operating Modes.
Wide Timing Range 0.1 s to 999 Days.
User Friendly Keys & Key Operations with Lock & Unlock.
Two Timers with Two separate Relay Output.
Preset Time Editable during Run Time.
Modes can be saved & Re-called through two Profiles P1/P2.
Wide Input Supply Range : 110-240V AC (Un) , -20% to +10% of Un
Wide Signal Sensing Range: 85-265V AC/100-265V DC & 24-60V AC/DC.
High Timing Accuracy.
IP-30 Protection for front facial & Housing.
Suitable for 48x48 Panel Mounting.
IEC 61812-1, CE, RoHS Compliance.
CAUTION:
1. Always follow instructions stated in the Product Leaflet. Before installation, ensure that specifications agree with intended application.
2. Installation must be done by skilled technician only.
3. Automation device must be properly installed so that they are protected against any risk of involuntary actuations.
4. Suitable dampers should be provided in event of excessive vibrations.
5. Use of 250mA fuse in series with product supply is recommended.
Note:
1. Product innovation being a continuous process, we reserve right to alter specifications without any prior notice.
2. Using of AC 2 Wire Proximity Sensor (Input signal range- 85-265V AC):
Please add the input bleeder resistance across signal input terminals (12 & 14) to prevent false signal Sensing due to leakage current of
proximity sensor. Generally suggested value of Bleeder resistance is 22K, 5W (Attached with the product as an accessory) Considering
2.5mA leakage current but it may vary depending upon the Leakage current of proximity sensor.
Copyright © GIC
TERMINAL DETAILS:
Copyright © GIC
LED Indications LED Indication Condition
SV (Red) Continuous ON Set Value
P1/P2 (Red) Continuous ON P1 Running
Up/Down (Red) Continuous ON Up Counting
SG (Green) Continuous ON Signal Present
OP1 (Red) Continuous ON Relay OP1 ON
OP2 (Red) Continuous ON Relay OP2 ON
Environmental Characteristics:
Copyright © GIC
Environmental Compliance:
Cold Heat IEC 60068-2-1 Ed. 6.0 (2007-03) -----
Dry Heat IEC 60068-2-2 Ed. 5.0 (2007-07) -----
Vibration IEC 60068-2-6 Ed. 7.0 (2007-12) 5g
Repetitive Shock IEC 60068-2-27 Ed. 4.0 (2008-02) 40g, 6 ms
Non-Repetitive Shock IEC 60068-2-27 Ed. 4.0 (2008-02) 30g, 15 ms
Copyright © GIC
Connections:
Connection Diagram:
Signal Input:
While using Proximity or some other sensor problem of false signal detection may observed due to
Leakage current of the Sensor in such a case bleeder resistor needs to be added between signal I/P
Terminals. Refer following connections & calculations to use sensors.
Proximity Sensor connection : Table 1
1. For Signal sensing circuit with proximity sensor :
Type Connection Diagram Remark / Note
PNP
3 Wire & 2 *Connection diagram for
wire proximity detector leakage current <
switch 0.1mA
NPN
3 Wire & 2 *Connection diagram for
wire proximity detector leakage current <
switch 0.1mA
Copyright © GIC
Nomenclature for Front Facia:
Meaning of notations of first digit of Seven segment display during run time:
'' - Time running on device is in Second scale.
'' - Time running on device is in Minutes scale.
'' - Time running on device is in Hours scale.
''- Time running on device is in Hours: Minutes scale.
'' - Time running on device is in Minutes: Seconds scale.
'' - Time running on device is in Days scale.
Key Conventions:
1. 'Enter' Key Long Presses at power on – Program mode (with version display).
2. 'Enter' key short press in Program mode – Value/parameter entered & Move to next menu.
3. 'Enter' short press during Run mode – Edit Preset Time during Timer Operation
4. 'ESC' key long press during Run mode – Edit mode.
5. 'ESC' key short press in Program mode – Return to previous menu.
6. 'ESC' key short press in online edit - Will come out of online edit
7. 'ESC + Enter' long pressed run mode - lock / unlock.
8. 'ESC + Up' key long press in run mode - Getting profile/Profile Recall & Run.
9. 'Down' key long press in Run mode - Resets timer1.
10. 'Down' Key short press in Online Program mode - Blinking preset digit gets decremented.
11. 'UP' key long press in run mode - Resets timer 2 (if both timers are selected).
12. 'UP' key short press during run mode – If both timers are configured then display will show Set value of both the timers for
2 sec. When only one timer is configured then it will have no effect on the screen
13. 'Up/down' short press in Program mode – Increment / Decrement the value or parameter.
14. 'Down + UP' key long press in run mode when both timers are selected – Reset the timer1 and timer2 both.
Timeout:
1. If user is in Program mode or in Profile selection, & there is no any single key press event for 2 minute, then device will
RUN with previous settings (Restart the Operation).
2. If user is in Edit Preset Time during Timer Operation & there is no any single key press event for 2 minute, then device will
RUN with previous settings (Resume the Operation).
Copyright © GIC
Dimensions:
Mechanical Dimensions:
Note:
1. The mounting panel thickness should be 1 to 5 mm.
2. To allow easier operation, it is recommended that Adapters be mounted so that the gap between sides with hooks is at least
15 mm (i.e. with the panel cutouts separated by at least 60 mm).
3. It is possible to horizontally mount Timers side by side. Attach the Flush Mounting Adapters so that the surfaces without
hooks are on the sides of the Timers (However, if Timers are mounted side by side, water resistance will be lost).
Copyright © GIC
Abbreviations used on seven segment Display during Programming & Operation:
Abbreviation Meaning
Customized Mode Configuration/Selection - User can built their own Mode/Profile as per their requirement.
or Do you want to keep Relay ON/OFF for specific timing or Do you want to keep Relay ON/OFF continuously
or Signal Based Mode selection or Non-signal Based Mode Selection in customized Mode
Number of cycles ON/OFF Cycles i.e. user can select the two cycles with different ON time & OFF time
Cycle Repeat. Do you want repeat cycle? Select 'YES' or 'NO'.
Do you want to take Action if the transition of signal occurs during timing before 'Action after time Completion' or relay state
changeover. Here user can define the action to be taken if Transition of the signal occurs during Run Time. Action can be
taken on the SP or SA, user can take actions like 'Break'; 'Pause'; 'Reload'; 'Return' & 'Relay OFF'.
Reload the timing. When this action is selected the relay1 is kept ON for the time same as previous one.
Stops the timing/mode operation without changing output state and wait for signal state to start the mode/timing operation
once again.
Stop the timing/mode operation with changing output state to OFF state and wait for signal state to start mode/timing
operation once again.
Action after time Completion ,on opposite transition of signal i.e. if cycles starts on signal present then action for ATT is at
signal absent.
Transition of the signal during Run Timing after 'Action after time Completion'. Here user can define the action to be taken if
Transition of the signal occurs during Run Time. Action can be taken on the SP or SA, user can take actions like 'No'; 'Reload';
'New Time' & 'Relay OFF'.
Copyright © GIC
Mode Functionality:
Copyright © GIC
7 MODE -06: When the supply is applied and input signal is
INVERTED SIGNAL ON removed, the preset 'OFF' time duration (TOFF)
DELAY TYPE 2 starts. After the time period has elapsed, the
output is switched ON. Signal change has no effect
during timing period. Output stays ON until
supply voltage has been interrupted.
Copyright © GIC
13 MODE-12: A permanent supply is required. The timer
ASYMMETERIC function is triggered by input signal. When input
RECYCLER PULSE START signal is applied the output is switched OFF while
TYPE 2 the first preset time period (TOFF) elapses. Once
this time period has elapsed output is switched
ON for the second preset time period (TON). Once
this second time period (TON) had elapsed then
output is switched OFF and the cycle will start
from the beginning again. If input signal is
removed during timing (TON or TOFF) the cycle
will stop and output is switched OFF, cycle will
start with output OFF state when the input signal
applied again.
14 MODE – 13: On application of signal the preset time (T) starts.
SIGNAL ON OFF DELAY After this preset time has elapsed, output is
switched ON. During this timing, if signal is
removed then output is switched ON immediately
and OFF delay is started. Once this time period
has elapsed the output is switched OFF.
During this OFF delay if signal is reapplied the
output switched OFF immediately and ON Delay
restarted.
Copyright © GIC
19 MODE – 18: On application of supply voltage, the preset timing
ACCUMULATIVE DELAY duration commences. When input signal is
ON SIGNAL applied, the timing pauses & resumes only when
the input signal is removed. The output is
switched ON at the end of the preset time
duration (TOFF).
25 MODE - 24: TRAILING When the input signal to the timer is removed,
EDGE IMPULSE 2 the output is immediately switched ON for the
preset time duration (TON) after which it is
switched OFF. If the input signal is applied during
the pre-set time, the output remains unaffected.
Copyright © GIC
26 MODE - 25: On application of supply and input signal, the
DELAYED IMPULSE preset 'OFF' time duration (TOFF) starts. The
output is switched ON at the end of preset 'OFF'
time duration. Then the preset 'ON' time starts
irrespective of the signal state & ON till the
completion of ' TON’. During the output OFF
period if signal is applied then timing is restarted,
but output is unaffected. The signal change has no
effect during time period TON.
27 MODE-26: A permanent supply is required. When signal is
DELAYED IMPULSE applied the output will remain OFF while the first
TYPE 2 preset time period (TOFF) elapses. Once this time
period has elapsed the output is switched ON for
the second preset time period (TON). Once this
second time period (TON) had elapsed then
output is switched OFF and cycle stops. Output
stays OFF until supply voltage has been
interrupted. During timing period (TON or TOFF) if
signal is removed then output is switched OFF and
the cycle stops, cycle will start with output OFF
state when the input signal applied again.
28 MODE-27: The timing period (TOFF) starts when the supply is
DELAYED PULSE applied to the timer. After the preset has elapsed
(CONSTANT SUPPLY) output is switched ON for the preset pulse (TON)
POWER BASED duration. To reset the timer the supply has to be
interrupted. If this interruption occurs during the
pulsed output (TON) then the output is switched
OFF and the timer will reset.
29 MODE-28: The timing period (TOFF) will start when input
DELAYED PULSE signal is applied with the supply connected. After
(REMOTE TRIG.) preset time (TOFF) has elapsed the output is
switched ON for the per-selected pulse (TON)
duration. To reset the timer either input signal
needs to be removed or supply has to interrupt. If
this action occurs during the pulsed output cycle
(TON) then output is switched OFF and the timer
will reset.
30 MODE-29: Supply to the unit must be continuous. On
DELAYED PULSE application of input signal the time period ’TOFF’
(CONST. SUPPLY TYPE starts to run. On completion of ’TOFF’, the relay
1) output is switched ON immediately and the time
period ’TON’ starts to run. On completion of ’TON’
the output is switched OFF. The input signal has
no effect until’ TOFF’ + ’ TON’ have completely
expired.
31 MODE-30: ON PULSE When the supply is connected and signal is
(CONTROL SWITCH applied, output is switched ON and the timing
RESETTABLE)/ WATCH function starts. If signal is removed and applied
DOG TYPE during the preset timing then timing is restarted
and output stays ON. After preset time(TON) has
elapsed the output is switched OFF
Copyright © GIC
32 MODE – 31: On application of supply voltage the output is
ON PULSE (SUPPLY switched ON. The first pulse of input signal starts
RESET) the preset time period. Receiving pulses during
the time period extends it and output stays ON.
Receiving no signal pulses during the time period
completes it and output is switched OFF. Output
stays OFF until supply voltage has been
interrupted.
33 MODE – 32: Leading After every signal, the output contact changes
Edge Bi-stable or Step their states, alternately switching from open to
Relay close & vice versa.
Copyright © GIC
Operating Procedure:
User can use the Default Modes (33 Modes) or can built own modes as per their requirement. Following are the Operating Procedures for Default
& Customized modes.
Copyright © GIC
MODE NO. 00: ON DELAY
On application of the supply voltage, the preset time duration (T) starts. On completion of the preset time, the output is switched ON &
remains on till the supply voltage is present.
Select the menu as given below to configure the Timer1 Select the menu as given below to configure the Timer1
for ON Delay (Default) for ON Delay (Customized)
Down Up Down Up
Device configuration selection : Select
Device configuration selection : Select
Timer1 (Timer1 will get configure)
Both (Both Timers will get configure)
Timer 1 Mode Selection – Select Default Mode Timer 1 Mode Selection – Select Customized Mode
Select the Time Scale for which O/P should remain Relay Status after Power ON – Select Relay OFF
OFF. Here selected in Sec as an example
Select the Time for which O/P should remain Do you want O/P OFF for Specific time duration or
OFF. Here selected 10 Sec as an example continuously – Select for specific time
Timer 2 Mode Selection – Select Default Mode Select the Time Scale for which O/P should remain
OFF. Here selected in Hour as an example
Select Default Mode - 00 Select the Time for which O/P should remain
OFF. Here selected 001 as an example
Select the Time Scale for which O/P should remain Do you want O/P ON for Specific time duration or
OFF. Here selected in Sec . as an example continuously – Select Continuosly
. Select the Time for which O/P should remain Time Counting Mode Up or Down
OFF. Here selected 10.0 Sec as an example Here Up Counting selected as an example
.
Copyright © GIC
MODE-01: ON DELAY CONSTANT SUPPLY TYPE 2
Timing will commence when the supply is present and input signal is not applied. After the time period has elapsed, output is switched ON. If
signal is applied then the timing period stops. Timing will restart only when signal is removed. Therefore there are two methods this timer can
be controlled, either by application or removal of signal input and with the interruption of the supply voltage to the timer with signal removal.
Select the menu as given below to configure the Timer1 Select the menu as given below to configure the Timer1
for ON DELAY CONSTANT SUPPLY TYPE 2 (Default) for ON DELAY CONSTANT SUPPLY TYPE 22 (Customized)
Down Up
Down Up Device configuration selection : Select
Timer1 (Timer1 will get configure)
Device configuration selection : Select
Both (Both Timers will get configure)
Timer 1 Mode Selection – Select Customized Mode
Timer 1 Mode Selection – Select Default Mode
Select Customized Mode – Signal Based
Select Default Mode - 01 Initial Relay Status before signal status detection –
Select OFF
Select Default Mode - 01 Select the Time for which O/P should remain
OFF. Here selected 30 sec as an example
Select the Time Scale for which O/P should remain Do you want take action if signal transition occurs
OFF. Here selected in Hour : Minute as an example during timing? - Select Yes
Select the Time for which O/P should remain On which signal condition do you want to take
. OFF. Here selected 1 Hr : 10 Min as an example Action? Select Signal Present
Time Counting Mode Up or Down What Action do you want to take if signal transition
Here Down Counting selected as an example occurs during timing – Select Return
Copyright © GIC
MODE-02: ON DELAY CONSTANT SUPPLY TYPE 3
A permanent supply is required. The timing period starts when the signal is applied and will continue irrespective of any further changes to signal
input. After the time period has elapsed output is switched ON. Signal change has no effect during timing period. To reset the timer, signal must be
removed and then applied.
Select the menu as given below to configure the Timer1 Select the menu as given below to configure the Timer1
for ON DELAY CONSTANT SUPPLY TYPE 3 (Default) for ON DELAY CONSTANT SUPPLY TYPE 3 (Customized)
Down Up
Down Up Device configuration selection : Select
Timer1 (Timer1 will get configure)
Device configuration selection : Select
Both (Both Timers will get configure)
Timer 1 Mode Selection – Select Customized Mode
Timer 1 Mode Selection – Select Default Mode
Select Customized Mode – Signal Based
Select Default Mode - 02 Initial Relay Status before signal status detection –
Select OFF
Select Default Mode - 02 Select the Time for which O/P should remain
OFF. Here selected 30 sec as an example
Select the Time Scale for which O/P should remain Do you want take action if signal transition occurs
OFF. Here selected in Second as an example during timing? - Select No
Select the Time for which O/P should remain Select the action after above time completion on
OFF. Here selected 10 Sec as an example signal present transition – Select no
Copyright © GIC
MODE-03: ON DELAY (CONTROL SWITCH RESETTABLE)
When the supply is connected and signal is applied, the timing function starts. If signal is removed and applied during the preset timing then
timing is restarted and output stays OFF. After preset time has elapsed the output is ON.
Select the menu as given below to configure the Timer1 Select the menu as given below to configure the Timer1
for ON DELAY - CONTROL SWITCH RESETTABLE (Default) for ON DELAY - CONTROL SWITCH RESETTABLE (Customized)
Down Up
Down Up Device configuration selection : Select
Timer1 (Timer1 will get configure)
Device configuration selection : Select
Both (Both Timers will get configure)
Timer 1 Mode Selection – Select Customized Mode
Timer 1 Mode Selection – Select Default Mode
Select Customized Mode – Signal Based
Select Default Mode - 03 Relay Status after Power ON before signal detection
– Select Relay OFF
Select Default Mode - 03 Select the Time for which O/P should remain
OFF. Here selected 10 sec as an example
Select the Time Scale for which O/P should remain Do you want take action if signal transition occurs
OFF. Here selected in Hour : Minute as an example during timing? - Select Yes
Select the Time for which O/P should remain On which signal condition do you want to take
OFF. Here selected 10 Second as an example Action? Select Signal Present
Time Counting Mode Up or Down What Action do you want to take if signal transition
Here Down Counting selected as an example occurs during timing – Select Reload
Copyright © GIC
MODE – 04: SIGNAL ON DELAY
Time commences as supply and signal is present. When input signal is removed, the timing stopped. The output is switched ON at the end of the
preset time duration (TOFF). When output is ON if signal is removed then output is switched OFF.
Select the menu as given below to configure the Timer1 Select the menu as given below to configure the Timer1
for SIGNAL ON DELAY (Default) for SIGNAL ON DELAY (Default)
Down Up Down Up
Device configuration selection : Select
Device configuration selection : Select
Timer1 (Timer1 will get configure)
Both (Both Timers will get configure)
Select the Time for which O/P should remain Action to be taken on signal transition or level –
select level
OFF. Here selected 10 Sec as an example
Select the Time for which O/P should remain On which signal condition do you want to take
OFF. Here selected 3 Day as an example Action? Select Signal Absent
Copyright © GIC
MODE - 05: INVERTED SIGNAL ON DELAY
On application of supply voltage, if signal is absent then the preset time duration (TOFF) starts. On preset time completion, the output is
switched ON. If signal is applied during timing period, then timing stops and timing restarts when signal is removed.
Select the menu as given below to configure the Timer1 Select the menu as given below to configure the Timer1
for INVERTED SIGNAL ON DELAY (Default) for INVERTED SIGNAL ON DELAY (Customized)
Down Up
Down Up Device configuration selection : Select
Timer1 (Timer 1 will get configure)
Device configuration selection : Select
Both (Both Timers will get configure)
Timer 1 Mode Selection – Select Customized Mode
Timer 1 Mode Selection – Select Default Mode
Select Customized Mode – Signal Based
Select Default Mode - 05 Initial Relay Status before signal status detection –
Select OFF
Select the Time Scale for which O/P should remain
Do you want take action if signal transition occurs
OFF. Here selected in Hour : Minute as an example
during timing? - Select Yes
Select the Time for which O/P should remain On which signal condition do you want to take
. OFF. Here selected 1 Hr : 10 Min as an example Action? Select Signal Present
Copyright © GIC
MODE -06: INVERTED SIGNAL DELAY TYPE 2
When the supply is applied and input signal is removed, the preset 'OFF' time duration (TOFF) starts. After the time period has elapsed, the output
is switched ON. Signal change has no effect during timing period. Output stays ON until supply voltage has been interrupted.
Select the menu as given below to configure the Timer1 Select the menu as given below to configure the Timer1
for INVERTED SIGNAL DELAY TYPE 2 (Default) for INVERTED SIGNAL DELAY TYPE 2 (Customized)
Down Up
Down Up Device configuration selection : Select
Timer1 (Timer1 will get configure)
Device configuration selection : Select
Both (Both Timers will get configure)
Timer 1 Mode Selection – Select Customized Mode
Timer 1 Mode Selection – Select Default Mode
Select Customized Mode – Signal Based
Select Default Mode - 06 Initial Relay Status before signal status detection –
Select OFF
Select Default Mode - 06 Select the Time for which O/P should remain
OFF. Here selected 30 sec as an example
Select the Time Scale for which O/P should remain Do you want take action if signal transition occurs
OFF. Here selected in Hour : Minute as an example during timing? - Select No
Select the Time for which O/P should remain Select the action after above time completion on
. OFF. Here selected 1 Hr : 10 Min as an example
signal present transition – Select no
Time Counting Mode Up or Down Do you want to repeat this cycle after every signal
Here Down Counting selected as an example transition - Select No
Copyright © GIC
MODE – 07: SIGNAL OFF DELAY
On application of supply voltage & input signal, the output is switched ON. When the signal is removed the preset time duration commences &
the output is switched OFF at the end of the time duration. If signal is applied during timing period, then timing stops and timing restarts when
signal is removed.
Select the menu as given below to configure the Timer1 Select the menu as given below to configure the Timer1
for SIGNAL OFF DELAY (Default) for SIGNAL OFF DELAY (Customized)
Down Up Down Up
Device configuration selection : Select
Device configuration selection : Select
Timer1 (Timer1 will get configure)
Both (Both Timers will get configure)
Timer 1 Mode Selection – Select Default Mode Timer 1 Mode Selection – Select Customized Mode
Select Customized Mode – Signal Based
Select Default Mode - 07
Initial Relay Status before signal status detection –
Select the Time Scale for which O/P should remain Select OFF
ON. Here selected in Second as an example
On which signal condition do you want to take
Action? Select Signal Present
Select the Time for which O/P should remain
ON. Here selected 10 Sec as an example
Action to be taken on signal transition or level –
select level
Timer 2 Mode Selection – Select Default Mode
Status of O/P after signal Present detection– select
ON
Select Default Mode - 07 Do you want O/P ON for Specific time duration or
continuously – Select for continuously
Select the Time Scale for which O/P should remain
Select the action after above time completion on
ON. Here selected in Hour : Minute as an example signal present transition – Select New Time
Select the Time for which O/P should remain Select the Time Scale for which O/P should remain
. ON. Here selected 1 Hr : 10 Min as an example ON. Here selected in Second as an example
Copyright © GIC
MODE-08: OFF DELAY CONST. SUPPLY TYPE 2
A permanent supply is required. When the input signal is applied the output is switched ON immediately. When input signal is removed the
timing period starts. After the time period has elapsed output is switched OFF. Once the timing period has started further actions of input
signal will have no effect. However once the timing cycle has been completed the process may be started again applying input signal. While the
timer is executing the only way to reset the timer is to interrupt the supply.
Select the menu as given below to configure the Timer1 Select the menu as given below to configure the Timer1
for OFF DELAY CONST. SUPPLY TYPE 2 (Default) for OFF DELAY CONST. SUPPLY TYPE 2 (Customized)
Down Up
Down Up Device configuration selection : Select
Timer1 (Timer1 will get configure)
Device configuration selection : Select
Both (Both Timers will get configure)
Timer 1 Mode Selection – Select Customized Mode
Timer 1 Mode Selection – Select Default Mode
Select Customized Mode – Signal Based
Select Default Mode - 08 Initial Relay Status before signal status detection –
Select OFF
Select Default Mode - 20 Select the action after above time completion on
signal present transition – Select New Time
Select the Time Scale for which O/P should remain Select the Time Scale for which O/P should remain
ON. Here selected in Hour : Minute as an example ON. Here selected in Second as an example
Select the Time for which O/P should remain Select the Time for which O/P should remain
ON. Here selected 10 Sec as an example ON. Here selected 30 sec as an example
Copyright © GIC
MODE - 09: CYCLIC ON/OFF
On application of supply voltage, the output is initially switched ON for the preset 'ON' time duration (TON) after which it is switched OFF for
the preset 'OFF' time duration (TOFF). This Cycle repeats and continues till supply is present.
Select the menu as given below to configure the Timer1 Select the menu as given below to configure the Timer1
for CYCLIC ON/OFF (Default) for CYCLIC ON/OFF (Customized)
Down Up Down Up
Device configuration selection : Select
Device configuration selection : Select
Timer1 (Timer1 will get configure)
Both (Both Timers will get configure)
Select the Time Scale for which O/P should remain Relay Status after Power ON – Select Relay ON
ON. Here selected in Minute as an example
Select the Time Scale for which O/P should remain Select the Time Scale for which O/P should remain
ON. Here selected in Hour as an example
OFF. Here selected in Second as an example
Select the Time for which O/P should remain Select the Time for which O/P should remain
OFF. Here selected 10 Sec as an example
ON. Here selected 001 as an example
Do you want O/P OFF for Specific time duration or
Timer 2 Mode Selection – Select Default Mode continuously – Select for specific time
Select the Time Scale for which O/P should remain
Select Default Mode - 09
OFF. Here selected in Minute as an example
Copyright © GIC
MODE - 10: CYCLIC OFF/ON
On application of supply voltage, the output is initially switched OFF for the preset 'OFF' time duration (TOFF), after which it is switched ON for
the preset 'ON' time duration (TON). This Cycle repeats and continues till supply is present.
Select the menu as given below to configure the Timer1 Select the menu as given below to configure the Timer1
for CYCLIC OFF/ON (Default) for CYCLIC OFF/ON (Customized)
Down Up Down Up
Device configuration selection : Select
Device configuration selection : Select
Timer1 (Timer1 will get configure)
Both (Both Timers will get configure)
Select the Time Scale for which O/P should remain Relay Status after Power ON – Select Relay ON
OFF. Here selected in Second as an example
Select the Time for which O/P should remain Do you want O/P OFF for Specific time duration or
OFF. Here selected 10 Sec as an example continuously – Select for specific time
Select the Time Scale for which O/P should remain Select the Time Scale for which O/P should remain
ON. Here selected in Minute as an example OFF. Here selected in Minute as an example
Select the Time for which O/P should remain Select the Time for which O/P should remain
ON. Here selected 1 Mnute as an example OFF. Here selected 10 Mnute as an example
Select the Time Scale for which O/P should remain
Select Default Mode - 10 ON. Here selected in Hour as an example
Select the Time Scale for which O/P should remain Select the Time for which O/P should remain
ON. Here selected 001 as an example
OFF. Here selected in Minute as an example
Copyright © GIC
MODE-11: ASYMMETRIC CYCLE PULSE START
A permanent supply is required. The timer function is triggered by the input signal. When input signal applied the output is switched ON while
the first preset time period (TON) elapses. Once this time period (TON) has elapsed output is switched OFF for the second preset time (TOFF)
period. Once this second time period (TOFF) had elapsed then output switched ON and the cycle will start from the beginning again. If input
signal is removed during timing (TON or TOFF) the cycle will stop and output is switched OFF, cycle will start with output ON state when the
input signal applied again.
Action to be taken on signal transition or level –
Select the menu as given below to configure the Timer1
select Level
for ASYMMETRIC CYCLE PULSE START (Default)
Down Up
Device configuration selection : Select Status of O/P after signal Present detection– select
Timer 1 (Timer1 will get configure) ON-OFF
Timer 1 Mode Selection – Select Default Mode How many cycles you want? - Select One
Select the Time Scale for which O/P should remain Select the Time Scale for which O/P should remain
ON. Here selected in Second as an example ON. Here selected in Second as an example
Select the Time for which O/P should remain Select the Time for which O/P should remain
ON. Here selected 10 Sec as an example
ON. Here selected 30 sec as an example
Select the Time Scale for which O/P should remain
Select the Time Scale for which O/P should remain
OFF. Here selected in Second as an example
OFF. Here selected in Second as an example
Select the Time for which O/P should remain Select the Time for which O/P should remain
OFF. Here selected 10 Sec as an example OFF. Here selected 30 sec as an example
Time Counting Mode Up or Down Do you want take action if signal transition occurs
Here Down Counting selected as an example during timing? - Select No
Save these settings in Profile P1 or P2 On which signal condition do you want to take
Here P1 selected as an example Action? Select Signal Present
Timer 1 Mode Selection – Select Customized Mode Do you want to repeat this cycle after every signal
transition - Select Yes
Select Customized Mode – Signal Based Time Counting Mode Up or Down
Here Up Counting selected as an example
Relay Status after Power ON before signal detection Save these settings in Profile P1 or P2
– Select Relay OFF Here P2 selected as an example
Copyright © GIC
MODE-12: ASYMETERIC RECYCLER PULSE START TYPE 2
A permanent supply is required. The timer function is triggered by input signal. When input signal is applied the output is switched OFF while
the first preset time period (TOFF) elapses. Once this time period has elapsed output is switched ON for the second preset time period (TON).
Once this second time period (TON) had elapsed then output is switched OFF and the cycle will start from the beginning again. If input signal
is removed during timing (TON or TOFF) the cycle will stop and output is switched OFF, cycle will start with output OFF state when the input
signal applied again.
Action to be taken on signal transition or level –
Select the menu as given below to configure the Timer1
select Level
for ASYMETERIC RECYCLER PULSE START TYPE 2 (Default)
Down Up
Device configuration selection : Select Status of O/P after signal Present detection– select
Timer 1 (Timer1 will get configure) OFF-ON
Timer 1 Mode Selection – Select Default Mode How many cycles you want? - Select One
Select the Time Scale for which O/P should remain Select the Time Scale for which O/P should remain
ON. Here selected in Second as an example ON. Here selected in Second as an example
Select the Time for which O/P should remain Select the Time for which O/P should remain
ON. Here selected 10 Sec as an example
ON. Here selected 30 sec as an example
Select the Time Scale for which O/P should remain
Select the Time Scale for which O/P should remain
OFF. Here selected in Second as an example
OFF. Here selected in Second as an example
Select the Time for which O/P should remain Select the Time for which O/P should remain
OFF. Here selected 10 Sec as an example OFF. Here selected 30 sec as an example
Time Counting Mode Up or Down Do you want take action if signal transition occurs
Here Down Counting selected as an example during timing? - Select No
Save these settings in Profile P1 or P2 On which signal condition do you want to take
Here P1 selected as an example Action? Select Signal Present
Timer 1 Mode Selection – Select Customized Mode Do you want to repeat this cycle after every signal
transition - Select Yes
Select Customized Mode – Signal Based Time Counting Mode Up or Down
Here Up Counting selected as an example
Relay Status after Power ON before signal detection Save these settings in Profile P1 or P2
– Select Relay OFF Here P2 selected as an example
Copyright © GIC
MODE – 13: SIGNAL ON OFF DELAY TYPE 1
1) On application of signal the preset time (T) starts. After this preset time has elapsed, output is switched ON. During this timing, if signal is
removed then output is switched ON immediately and preset timing is restarted. Signal has no effect during this timing. Once this time period has
elapsed the output is switched OFF.
2) On application of signal the preset time (T) starts. After this preset time has elapsed, output is switched ON. When output is ON and signal is
removed then preset timing is restarted (output stays ON). Signal has no effect during this timing. Once this time period has elapsed the output is
switched OFF.
Select the Time Scale for which O/P should remain
Select the Time Scale for which O/P should remain
OFF. Here selected in Second as an example OFF. Here selected in Second as an example
Timer 2 Mode Selection – Select Default Mode Do you want take action if signal transition occurs
during timing? - Select Yes
Select Default Mode - 13 On which signal condition do you want to take
Action? Select Signal Absent
Select the Time Scale for which O/P should remain
Select the action after above time completion on
OFF. Here selected in Hour : Minute as an example
signal present transition – Select Break
Relay Status after Power ON before signal detection Save these settings in Profile P1 or P2
– Select Relay OFF Here P2 selected as an example
Copyright © GIC
MODE – 14: SIGNAL ON OFF DELAY
On application of signal the preset time (T) starts. After this preset time has elapsed, output is switched ON. During this timing, if signal is removed
then output is switched ON immediately and OFF delay is started. Once this time period has elapsed the output is switched OFF.
During this OFF delay if signal is reapplied the output switched OFF immediately and ON Delay restarted.
Select the menu as given below to configure the Timer1 On which signal condition do you want to take
for SIGNAL ON OFF DELAY TYPE 2 (Default) Action? Select Signal Present
Down Up
Device configuration selection : Select
Both (Both Timers will get configure)
Action to be taken on signal transition or level –
select level
Timer 1 Mode Selection – Select Default Mode
Status of O/P after signal Present detection– select
OFF
Select Default Mode - 14
Select the Time Scale for which O/P should remain
Select the Time Scale for which O/P should remain OFF. Here selected in Second as an example
OFF. Here selected in Second as an example
Select the Time for which O/P should remain
Select the Time for which O/P should remain OFF. Here selected 10 Sec as an example
OFF. Here selected 10 Sec as an example
Select Default Mode - 14 On which signal condition do you want to take
Action? Select Signal Absent
Select the Time Scale for which O/P should remain
OFF. Here selected in Hour : Minute as an example Select the action after above time completion on
signal present transition – Select Break
Select the Time for which O/P should remain
. OFF. Here selected 1 Hr : 10 Min as an example Select the action after above time completion on
signal present transition – Select Reload
Time Counting Mode Up or Down
Here Down Counting selected as an example
Do you want take action if signal transition occurs
during timing after Relay changeover? - Select Yes
Save these settings in Profile P1 or P2
Here P1 selected as an example
On which signal condition do you want to take
Select the menu as given below to configure the Timer1 Action? Select Signal Absent
for SIGNAL ON OFF DELAY TYPE 2 (Customized)
Down Up What action do you want to take if the transition of
Device configuration selection : Select signal Absent occurs after change in O/P state –
Timer1 (Timer1 will get configure) Select Pause
Copyright © GIC
MODE – 15: SIGNAL OFF/ON (NEW)
On application of input signal, the preset delay time period (T) starts. During this timing if signal is removed then timing is stopped and timing will
be restarted when signal applied again. After this time period has elapsed output is switched ON. On removal of input signal, the preset time
period starts again & the output is switched OFF when the preset time duration is complete. Output stays OFF until supply voltage has been
interrupted.
Timer 1 Mode Selection – Select Default Mode Select the Time Scale for which O/P should remain
OFF. Here selected in Second as an example
Select Default Mode - 15 Select the Time for which O/P should remain
OFF. Here selected 10 Sec as an example
Select the Time Scale for which O/P should remain
Do you want take action if signal transition occurs
OFF. Here selected in Second as an example during timing? - Select Yes
Select the Time for which O/P should remain On which signal condition do you want to take
OFF. Here selected 10 Sec as an example Action? Select Signal Absent
Time Counting Mode Up or Down What Action do you want to take if signal transition
Here Down Counting selected as an example occurs during timing – Select Return
Save these settings in Profile P1 or P2 What Action do you want to take After above time
Here P1 selected as an example completion on signal absent transition? – Select
Reload
Select the menu as given below to configure the Timer1
for SIGNAL OFF/ON (NEW) (Customized) Do you want take action if signal transition occurs
during timing after O/P relay changeover? - Select
Down Up Yes
Device configuration selection : Select On which signal condition do you want to take
Timer1 (Timer1 will get configure) Action after O/P relay changeover ? Select Signal
Present
Timer 1 Mode Selection – Select Customized Mode What Action do you want to take if signal transition
occurs during timing after O/P relay changeover –
Select Return
Select Customized Mode – Signal Based
Do you want to repeat this cycle after every signal
transition - Select Yes
Copyright © GIC
MODE - 16: IMPULSE ONENERGIZING
On application of supply voltage, the output is instantly switched ON for the preset time duration (TON) after it is switched OFF.
Select the menu as given below to configure the Timer1 Select the menu as given below to configure the Timer1
for IMPULSE ONENERGIZING (Default) for IMPULSE ONENERGIZING (Default)
Down Up Down Up
Device configuration selection : Select Device configuration selection : Select
Both (Both Timers will get configure)
Both (Both Timers will get configure)
Timer 1 Mode Selection – Select Default Mode Timer 1 Mode Selection – Select Customized Mode
Select the Time Scale for which O/P should remain Relay Status after Power ON – Select Relay ON
ON. Here selected in Second as an example
Select the Time for which O/P should remain Do you want O/P ON for Specific time duration or
ON. Here selected 10 Sec as an example continuously – Select for specific time
Timer 2 Mode Selection – Select Default Mode Select the Time Scale for which O/P should remain
ON. Here selected in Hour as an example
Select the Time for which O/P should remain
Select Default Mode - 03
ON. Here selected 001 as an example
Select the Time Scale for which O/P should remain Do you want O/P OFF for Specific time duration or
. ON. Here selected Minute . as an example continuously – Select Continuosly
Select the Time for which O/P should remain ON. Time Counting Mode Up or Down
Here selected in 10 Minute. as an example Here Up Counting selected as an example
Time Counting Mode Up or Down Save these settings in Profile P1 or P2
Here UP Counting selected as an example Here P2 selected as an example
Copyright © GIC
MODE - 17: IMPULSE ON/OFF
On application or removal of input signal, the output is switched ON & the preset time duration (TON) starts. On completion of the time duration
the output is switched OFF. During timing period, changing the state of the input signal dose not affects output but resets time.
Select the Time Scale for which O/P should remain
ON. Here selected in Hour : Minute as an example Select the action after above time completion on
signal present transition – Select Break
Select the Time for which O/P should remain
. ON. Here selected 1 Hr : 10 Min as an example Select the action after above time completion on
signal present transition – Select Reload
Time Counting Mode Up or Down
Here Down Counting selected as an example Do you want take action if signal transition occurs
during timing after Relay changeover? - Select Yes
Copyright © GIC
MODE – 18: ACCUMULATIVE DELAY ON SIGNAL
On application of supply voltage, the preset timing duration commences. When input signal is applied, the timing pauses & resumes only when
the input signal is removed. The output is switched ON at the end of the preset time duration (TOFF).
Select the menu as given below to configure the Timer1 Select the menu as given below to configure the Timer1
for ACCUMULATIVE DELAY ON SIGNAL (Default) for ACCUMULATIVE DELAY ON SIGNAL (Customized)
Down Up Down Up
Device configuration selection : Select
Device configuration selection : Select
Timer1 (Timers1 will get configure)
Both (Both Timers will get configure)
Select the Time for which O/P should remain Action to be taken on signal transition or level –
select level
OFF. Here selected 10 Sec as an example
Select the Time for which O/P should remain On which signal condition do you want to take
. OFF. Here selected 8 Min : 5 Sec as an example Action? Select Signal Present
Time Counting Mode Up or Down What Action do you want to take if signal transition
occurs during timing – Select Pause
Here UP Counting selected as an example
Copyright © GIC
MODE - 19: ACCUMULATIVE DELAY ON INVERTED SIGNAL
Time commences as supply and signal is present. When input signal is removed, the timing pauses & resumes only when the input signal is
applied. The output is switched ON at the end of the preset time duration (TOFF).
Select the menu as given below to configure the Timer1 Select the menu as given below to configure the Timer1
for ACCUMULATIVE DELAY ON INVERTED SIGNAL (Default) for ACCUMULATIVE DELAY ON INVERTED SIGNAL (Customized)
Down Up Down Up
Device configuration selection : Select
Device configuration selection : Select
Timer1 (Timer 1 will get configure)
Both (Both Timers will get configure)
Select the Time for which O/P should remain Action to be taken on signal transition or level –
select level
OFF. Here selected 10 Sec as an example
Select the Time for which O/P should remain On which signal condition do you want to take
OFF. Here selected 8 Min : 5 Sec as an example Action? Select Signal Absent
.
Copyright © GIC
MODE - 20: ACCUMULATIVE IMPULSE ON SIGNAL
On application of supply voltage, the output is switch ON & the preset timing duration commences. When input signal is applied, the timing
pauses & resumes only when the input signal is removed. The output is switched OFF at the end of the preset duration (TON).
Select the menu as given below to configure the Timer1 Select the menu as given below to configure the Timer1
for ACCUMULATIVE IMPULSE ON SIGNAL (Default) for ACCUMULATIVE IMPULSE ON SIGNAL (Customized)
Down Up Down Up
Timer 1 Mode Selection – Select Customized Mode
Timer 1 Mode Selection – Select Default Mode
Select Customized Mode – Signal Based
Select Default Mode - 20
Initial Relay Status before signal status detection –
Select OFF
Select the Time for which O/P should remain Action to be taken on signal transition or level –
select level
ON. Here selected 10 Sec as an example
Select the Time Scale for which O/P should remain Select the Time for which O/P should remain
ON. Here selected in Minute: Second as an example ON. Here selected 30 sec as an example
Copyright © GIC
MODE - 21: LEADING EDGE IMPULSE 1
On application of supply voltage & input signal, the output is switched ON for preset time. After completion of preset time period, output is
switched OFF. If the input signal is applied or removed during preset timing period, the output and timing remains unaffected.
Select the menu as given below to configure the Timer1 Select the menu as given below to configure the Timer1
for LEADING EDGE IMPULSE 1 (Default) for LEADING EDGE IMPULSE (Customized)
Down Up Down Up
Device configuration selection : Select
Device configuration selection : Select
Timer1 (Timer1 will get configure)
Both (Both Timers will get configure)
Select the Time for which O/P should remain Action to be taken on signal transition or level –
select level
ON. Here selected 10 Sec as an example
Select the Time Scale for which O/P should remain Select the Time for which O/P should remain
OFF. Here selected in Hour : Minute as an example ON. Here selected 30 sec as an example
Select the Time for which O/P should remain Do you want take action if signal transition occurs
OFF. Here selected 1 Hr : 10 Min as an example during timing? - Select No
.
Copyright © GIC
MODE - 22: LEADING EDGE IMPULSE 2
On application of the input signal the output is immediately switched ON. The output remains ON for the preset time duration (T) after which it is
switched OFF. If the input signal is removed during the preset time, the output immediately switched OFF.
Select the menu as given below to configure the Timer1 Select the menu as given below to configure the Timer1
for LEADING EDGE IMPULSE 2 (Default) for LEADING EDGE IMPULSE 2 (Customized)
Down Up Down Up
Device configuration selection : Select
Device configuration selection : Select
Timer1 (Timer1 will get configure)
Both (Both Timers will get configure)
Select the Time for which O/P should remain Action to be taken on signal transition or level –
select level
ON. Here selected 10 Sec as an example
Select the Time Scale for which O/P should remain Do you want take action if signal transition occurs
ON. Here selected in Hour : Minute as an example during timing? - Select Yes
Select the Time for which O/P should remain On which signal condition do you want to take
. ON. Here selected 1 Hr : 10 Min as an example Action? Select Signal Absent
Copyright © GIC
MODE - 23: TRAILING EDGE IMPULSE 1
When the supply voltage is applied and input signal is removed, the output is switched ON for the preset time duration (T).After completion of
preset time period, output is switched OFF. If I/p signal is applied during the preset timing period then output is switched OFF & timing stops.
Select the menu as given below to configure the Timer1 Select the menu as given below to configure the Timer1
for TRAILING EDGE IMPULSE 1 (Default) for TRAILING EDGE IMPULSE (Customized)
Down Up
Down Up Device configuration selection : Select
Timer1 (Timer1 will get configure)
Device configuration selection : Select
Both (Both Timers will get configure)
Timer 1 Mode Selection – Select Customized Mode
Timer 1 Mode Selection – Select Default Mode
Select Customized Mode – Signal Based
Select Default Mode - 23 Initial Relay Status before signal status detection –
Select OFF
Select the Time Scale for which O/P should remain
-- Select Default Mode - 23
ON. Here selected in Second as an example
Copyright © GIC
MODE - 24: TRAILING EDGE IMPULSE 2
When the input signal to the timer is removed, the output is immediately switched ON for the preset time duration (TON) after which it is
switched OFF. If the input signal is applied during the preset time, the output remains unaffected.
Select the menu as given below to configure the Timer1 Select the menu as given below to configure the Timer1
for TRAILING EDGE IMPULSE 2 (Default) for TRAILING EDGE IMPULSE 2 (Customized)
Down Up
Down Up Device configuration selection : Select
Timer1 (Timer1 will get configure)
Device configuration selection : Select
Both (Both Timers will get configure)
Timer 1 Mode Selection – Select Customized Mode
Timer 1 Mode Selection – Select Default Mode
Select Customized Mode – Signal Based
Select Default Mode - 24 Initial Relay Status before signal status detection –
Select OFF
Select the Time Scale for which O/P should remain
Select Default Mode - 24
ON. Here selected in Second as an example
Copyright © GIC
MODE - 25: DELAYED IMPULSE
On application of supply and input signal, the preset 'OFF' time duration (TOFF) starts. The output is switched ON at the end of preset 'OFF' time
duration. Then the preset 'ON' time starts irrespective of the signal state & ON till the completion of ' TON’. During the output OFF period if signal
is applied then timing is restarted, but output is unaffected. The signal change has no effect during time period TON.
Select the menu as given below to configure the Timer1 Action to be taken on signal transition or level –
for DELAYED IMPULSE (Default)
Down Up select level
Device configuration selection : Select Status of O/P after signal Present detection– select
Timer1 (Timers1 will get configure) OFF-ON
Timer 1 Mode Selection – Select Default Mode No. of OFF-ON Cycles required – Select One
Select the Time Scale for which O/P should remain Select the Time Scale for which O/P should remain
ON. Here selected in Second as an example
ON. Here selected in Second as an example
Select the Time for which O/P should remain Select the Time for which O/P should remain
ON. Here selected 10 Sec as an example
ON. Here selected 10 Sec as an example
Select the Time Scale for which O/P should remain
Select the Time Scale for which O/P should remain
OFF. Here selected in Second as an example
OFF. Here selected in Hour : Minute as an example
Select the Time for which O/P should remain Select the Time for which O/P should remain
. OFF. Here selected 1 Hr : 10 Min as an example OFF. Here selected 10 Sec as an example
Select the menu as given below to configure the Timer1 During which O/P (Relay) status do you want to
take action if transition of signal present occurs
for DELAYED IMPULSE (Customized)
during timing? - Select OFF
Down Up
Device configuration selection : Select
Timer1 (Timer1 will get configure) What Action do you want to take if signal transition
occurs during timing – Select Reload
Timer 1 Mode Selection – Select Customized Mode Do you want to repeat this cycle after every signal
transition - Select Yes
Select Customized Mode – Signal Based Time Counting Mode Up or Down
Here Up Counting selected as an example
Copyright © GIC
MODE-26: DELAYED IMPULSE TYPE 2
A permanent supply is required. When signal is applied the output will remain OFF while the first preset time period (TOFF) elapses. Once this
time period has elapsed the output is switched ON for the second preset time period (TON). Once this second time period (TON) had elapsed then
output is switched OFF and cycle stops. Output stays OFF until supply voltage has been interrupted. During timing period (TON or TOFF) if signal is
removed then output is switched OFF and the cycle stops, cycle will start with output OFF state when the input signal applied again.
Timer 1 Mode Selection – Select Default Mode
How many cycles you want? - Select One
Select Default Mode - 26
Do you want to repeat the cycle? - Select NO
Select the Time Scale for which O/P should remain
ON. Here selected in Second as an example
Select the Time Scale for which O/P should remain
ON. Here selected in Second as an example
Select the Time for which O/P should remain
ON. Here selected 10 Sec as an example
Select the Time for which O/P should remain
ON. Here selected 10 Sec as an example
Select the Time Scale for which O/P should remain
OFF. Here selected in Second as an example Select the Time for which O/P should remain
OFF. Here selected 10 Sec as an example
Select the Time for which O/P should remain
OFF. Here selected 10 Sec as an example
Select the Time for which O/P should remain
OFF. Here selected 30 Sec as an example
Time Counting Mode Up or Down
Here Down Counting selected as an example
Copyright © GIC
MODE-27: DELAYED PULSE (CONSTANT SUPPLY) POWER BASED
The timing period (TOFF) starts when the supply is applied to the timer. After the preset has elapsed output is switched ON for the preset pulse
(TON) duration. To reset the timer the supply has to be interrupted. If this interruption occurs during the pulsed output (TON) then the output
is switched OFF and the timer will reset.
Select the menu as given below to configure the Timer1 Select the menu as given below to configure the Timer1
for DELAYED PULSE (CONSTANT SUPPLY) POWER BASED (Default) DELAYED PULSE (CONSTANT SUPPLY) POWER BASED (Customized)
Down Up Down Up
Device configuration selection : Select
Device configuration selection : Select
Timer1 (Timer1 will get configure)
Both (Both Timers will get configure)
Do you want O/P OFF for Specific time duration or
Select the Time for which O/P should remain continuously – Select for specific time
OFF. Here selected 10 Sec as an example
Select the Time Scale for which O/P should remain
Select the Time Scale for which O/P should remain
ON. Here selected in Sec as an example OFF. Here selected in Second as an example
Select the Time for which O/P should remain
Select the Time for which O/P should remain OFF. Here selected 010 Second as an example
ON. Here selected 10 Sec as an example
Do you want O/P ON for Specific time duration or
Timer 2 Mode Selection – Select Default Mode continuously – Select for Specific Time
Select the Time Scale for which O/P should remain
Select Default Mode - 27 ON. Here selected in Second as an example
Select the Time for which O/P should remain
Select the Time Scale for which O/P should remain ON. Here selected 030 Second as an example
OFF. Here selected in Sec . as an example
Select the Time Scale for which O/P should remain Do you want to repeat the cycle? - Select NO
ON. Here selected in Sec as an example
Time Counting Mode Up or Down Save these settings in Profile P1 or P2
Here Down Counting selected as an example Here P2 selected as an example
Copyright © GIC
MODE-28: DELAYED PULSE (REMOTE TRIGGER)
The timing period (TOFF) will start when input signal is applied with the supply connected. After preset time (TOFF) has elapsed the output is
switched ON for the per-selected pulse (TON) duration. To reset the timer either input signal needs to be removed or supply has to interrupt. If
this action occurs during the pulsed output cycle (TON) then output is switched OFF and the timer will reset.
Select the Time Scale for which O/P should remain
Select the Time Scale for which O/P should remain
OFF. Here selected in Second as an example
OFF. Here selected in Second as an example
Time Counting Mode Up or Down Do you want take action if signal transition occurs
during timing? - Select Yes
Here Down Counting selected as an example
Save these settings in Profile P1 or P2 On which signal condition do you want to take
Here P1 selected as an example Action? Select Signal Absent
Select the menu as given below to configure the Timer1 On which Relay condition do you want to take
for DELAYED PULSE -REMOTE TRIGGER (Customized) Action if the transition of the signal occurs during
Down Up timing? Select ON
Device configuration selection : Select
Timer1 (Timer1 will get configure) What Action do you want to take if signal transition
occurs during timing – Select Relay OFF
Timer 1 Mode Selection – Select Customized Mode
Do you want to repeat this cycle after every signal
transition - Select Yes
Select Customized Mode – Signal Based
Time Counting Mode Up or Down
Here Up Counting selected as an example
Initial Relay Status before signal status detection –
Select OFF
Save these settings in Profile P1 or P2
Here P2 selected as an example
On which signal condition do you want to take
Action? Select Signal Present
Copyright © GIC
MODE-29: DELAYED PULSE (CONST. SUPPLY TYPE 1)
Supply to the unit must be continuous. On application of input signal the time period ’TOFF’ starts to run. On completion of ’TOFF’, the relay
output is switched ON immediately and the time period ’TON’ starts to run. On completion of ’TON’ the output is switched OFF. The input
signal has no effect until ’ TOFF’ + ’ TON’ have completely expired.
Select the menu as given below to configure the Timer1 Select the menu as given below to configure the Timer1
for ODELAYED PULSE -CONST. SUPPLY TYPE 1 (Default) for DELAYED PULSE -CONST. SUPPLY TYPE 1 (Customized)
Down Up
Down Up Device configuration selection : Select
Timer1 (Timer1 will get configure)
Device configuration selection : Select
Both (Both Timers will get configure)
Timer 1 Mode Selection – Select Customized Mode
Timer 1 Mode Selection – Select Default Mode
Select Customized Mode – Signal Based
Select Default Mode - 29
Initial Relay Status before signal status detection –
Select OFF
Select the Time Scale for which O/P should remain
ON. Here selected in Second as an example On which signal condition do you want to take
Action? Select Signal Present
Select the Time for which O/P should remain
ON. Here selected 10 Sec as an example Action to be taken on signal transition or level –
select Level
Select the Time Scale for which O/P should remain
OFF. Here selected in Second as an example Status of O/P after signal Present detection– select
OFF-ON
Select the Time for which O/P should remain
OFF. Here selected 10 Sec as an example How many cycles you want? - Select One
Timer 2 Mode Selection – Select Default Mode Do you want to repeat the cycle? - Select NO
Select Default Mode - 29 Select the Time Scale for which O/P should remain
ON. Here selected in Second as an example
Select the Time Scale for which O/P should remain Select the Time for which O/P should remain
ON. Here selected in Hour : Minute as an example ON. Here selected 30 sec as an example
Select the Time for which O/P should remain Select the Time Scale for which O/P should remain
OFF. Here selected in Second as an example
ON. Here selected 10 Sec as an example
Copyright © GIC
MODE-30: ON PULSE (CONTROL SWITCH RESETTABLE)/ WATCH DOG TYPE
When the supply is connected and signal is applied, output is switched ON and the timing function starts. If signal is removed and applied
during the preset timing then timing is restarted and output stays ON. After preset time(TON) has elapsed the output is switched OFF.
Select the menu as given below to configure the Timer1 Select the menu as given below to configure the Timer1
for ON DELAY CONSTANT SUPPLY TYPE 2 (Default) for ON DELAY CONSTANT SUPPLY TYPE 2 (Customized)
Down Up
Down Up Device configuration selection : Select
Timer1 (Timer1 will get configure)
Device configuration selection : Select
Both (Both Timers will get configure)
Timer 1 Mode Selection – Select Customized Mode
Timer 1 Mode Selection – Select Default Mode
Select Customized Mode – Signal Based
Select Default Mode - 30 Relay Status after Power ON before signal detection
– Select Relay OFF
Select Default Mode - 30 Select the Time for which O/P should remain
ON. Here selected 30 sec as an example
Select the Time Scale for which O/P should remain
Do you want take action if signal transition occurs
ON. Here selected in Hour : Minute as an example
during timing? - Select Yes
Select the Time for which O/P should remain On which signal condition do you want to take
OFF. Here selected 10 Second as an example Action? Select Signal Present
Time Counting Mode Up or Down What Action do you want to take if signal transition
Here Down Counting selected as an example occurs during timing – Select Reload
Copyright © GIC
MODE – 31: ON PULSE (SUPPLY RESET)
On application of supply voltage the output is switched ON. The first pulse of input signal starts the preset time period. Receiving pulses during
the time period extends it and output stays ON. Receiving no signal pulses during the time period completes it and output is switched OFF.
Output stays OFF until supply voltage has been interrupted.
Select the menu as given below to configure the Timer1 Select the menu as given below to configure the Timer1
for ON PULSE (SUPPLY RESET) (Default) for ON PULSE (SUPPLY RESET) (Customized)
Down Up
Down Up Device configuration selection : Select
Timer1 (Timer1 will get configure)
Device configuration selection : Select
Both (Both Timers will get configure)
Timer 1 Mode Selection – Select Customized Mode
Timer 1 Mode Selection – Select Default Mode
Select Customized Mode – Signal Based
Select Default Mode - 31 Relay Status after Power ON before signal detection
– Select Relay ON
Save these settings in Profile P1 or P2 Select the action after above time completion on
Here P1 selected as an example signal present transition – Select no
Copyright © GIC
MODE – 32: Leading Edge Bi-stable or Step Mode:
After every signal, the output contact changes their states, alternately switching from open to close & vice versa.
Important Note:
As per the timing diagram this mode is not time base mode, hence ideally there is no need to enter the time. But if we havce select action on
Signal present as relay ON contineuosly, then as per flow chart of the TDT2 (Action on Transition during Run Time) will not shown. So select relay
on time maximum i.e 999 Days.
Select the menu as given below to configure the Timer1
Select the menu as given below to configure the Timer1 for Leading Edge Bi-stable or Step Mode (Customized)
for Leading Edge Bi-stable or Step Mode
(Default) Down Up
Device configuration selection : Select
Down Up Timer1 (Timer1 will get configure)
Timer 1 Mode Selection – Select Default Mode
Select Customized Mode – Signal Based
Select Default Mode - 32 Relay Status after Power ON before signal detection
– Select Relay ON
Select the Time Scale for which O/P should remain On which signal condition do you want to take
ON. Here selected in Day as we want to select Action? Select Signal Present
maximum time.
Action to be taken on signal transition or level –
select Level
Select the Time for which O/P should remain
ON. Here selected 999 Days as we want to Status of O/P after signal absent detection– select
select maximum time. ON
Do you want output to be ON for specific time
Timer 2 Mode Selection – Select Default Mode
duration or continuously – select for Specific time
duration
Select the Time Scale for which O/P should remain
ON. Here selected in Day as we want to select
Select Default Mode - 32 maximum time.
Select the Time Scale for which O/P should remain
Select the Time Scale for which O/P should remain ON. Here selected in 999 Day as we want to select
ON. Here selected in Day as we want to select maximum time.
maximum time.
Do you want take action if signal transition occurs
Select the Time Scale for which O/P should remain during timing? - Select Yes
ON. Here selected in 999 Day as we want to select
maximum time. On which signal condition do you want to take
Action? Select Signal Present
Time Counting Mode Up or Down
Here Down Counting selected as an exampl What Action do you want to take if signal transition
occurs during timing – Select Reload
Save these settings in Profile P1 or P2 Select the action after above time completion on
Here P1 selected as an example signal present transition – Select no
Timer 1 Mode Selection – Select Select the Time Scale for which O/P should remain
Customized Mode OFF. Here selected in Second as an example
Timer 1 Mode Selection – Select Select the Time for which O/P should remain
Customized Mode OFF. Here selected 20 Sec as an example
Relay Status after Power ON – Select Relay Do you want output to be ON for specific time duration or
OFF continuously – select for Specific time duration
Select the Time for which O/P should remain Time Counting Mode Up or Down
OFF. Here selected 10 Sec as an example Here Up Counting selected as an example
Do you want output to be ON for specific
Save these settings in Profile P1 or P2
time duration or continuously – select for
Specific time duration Here P2 selected as an example
Do you want to repeat the Cycle? Select
Yes
Copyright © GIC
2) Star delta Mode:
Select the menu as given below to configure the Timer1 Timer 2 Mode Selection – Select
for Star -Delta Mode(Customized) :
Customized Mode
Copyright © GIC
3. Forward-Reverse Mode:
Copyright © GIC
Select the menu as given below to configure the Timer for Forward-Reverse Mode (Customized) :
Down Up
Device configuration selection : Select Relay Status after Power ON before signal detection
Both (Both Timers will get configure) – Select Relay OFF
Timer 1 Mode Selection – Select On which signal condition do you want to take
Customized Mode Action? Select Signal Absent
Timer 1 Mode Selection – Select Action to be taken on signal transition or level –
Customized Non-Signal Based select level
Relay Status after Power ON – Select Relay Status of O/P after signal Absent detection– select
ON OFF-on
Do you want output to be ON for specific
time duration or continuously – select for How many cycles you want? - Select One
Specific time duration
Select the Time Scale for which O/P should
Do you want to repeat the Cycle? Select No
remain ON. Here selected in Minute as an
example
Select the Time Scale for which O/P should remain ON.
Select the Time for which O/P should remain
Here selected in Minute as an example
ON. Here selected 10 Minute as an example,
Do you want output to be OFF for specific Select the Time for which O/P should remain ON. Here
time duration or continuously – select for selected 10 Minute as an example,
Specific time duration
Select the Time Scale for which O/P should remain OFF.
Select the Time Scale for which O/P should Here selected in Minute as an example
remain OFF. Here selected in Minute as an
example
Select the Time for which O/P should remain OFF (Pause
Select the Time for which O/P should remain Time). Here selected 3 Minute as an example.
ON. Here selected 16 Minute as an example,
as OFF Time= T (On Time) + 2 X Pause Time
= 10+ (2 X 3) = 16 Minute Do you want take action if signal transition occurs
during timing? - Select No
How many cycles you want? - Select One
Do you want to repeat this cycle after every signal
transition - Select Yes
Do you want to repeat the Cycle? Select Yes
Time Counting Mode Up or Down
Here Up Counting selected as an example
Timer 2 Mode Selection – Select
Customized Signal Based
Save these settings in Profile P1 or P2
Here P2 selected as an example
Timer 1 Mode Selection – Select
Customized Signal Based
Copyright © GIC