Pvsyst King Group
Pvsyst King Group
Author
Project: New Project
Variant: New simulation variant
PVsyst V7.2.4
VC0, Simulation date:
29/03/24 09:34
with v7.2.4
Project summary
Geographical Site Situation Project settings
Long Hòa A Latitude 9.92 °N Albedo 0.20
Vietnam Longitude 105.74 °E
Altitude 4m
Time zone UTC+7
Meteo data
Long Hòa A
Meteonorm 8.0 (1991-2009), Sat=100% - Synthetic
System summary
Grid-Connected System Tables on a building
Simulation for year no 1
System information
PV Array Inverters
Nb. of modules 200 units Nb. of units 1 Unit
Pnom total 139 kWp Pnom total 115 kWac
Pnom ratio 1.209
Results summary
Produced Energy 192.9 MWh/year Specific production 1388 kWh/kWp/year Perf. Ratio PR 81.81 %
Table of contents
Project and results summary 2
General parameters, PV Array Characteristics, System losses 3
Near shading definition - Iso-shadings diagram 5
Main results 6
Loss diagram 7
Special graphs 8
P50 - P90 evaluation 9
Cost of the system 10
CO₂ Emission Balance 11
PVsyst V7.2.4
VC0, Simulation date:
29/03/24 09:34
with v7.2.4
General parameters
Grid-Connected System Tables on a building
PV Field Orientation
Orientation Sheds configuration Models used
Fixed planes 2 orientations Nb. of sheds 200 units Transposition Perez
Tilts/azimuths 9 / 92 ° Sizes Diffuse Perez, Meteonorm
9 / -88 ° Sheds spacing 1.31 m Circumsolar separate
Collector width 1.30 m
Ground Cov. Ratio (GCR) 99.7 %
Shading limit angle
Limit profile angle 84.5 °
PV Array Characteristics
PV module Inverter
Manufacturer Risen Energy Co., Ltd Manufacturer Huawei Technologies
Model RSM132-8-695BHDG Model SUN2000-115KTL-M2-400V
(Original PVsyst database) (Custom parameters definition)
Unit Nom. Power 695 Wp Unit Nom. Power 115 kWac
Number of PV modules 200 units Number of inverters 1 Unit
Nominal (STC) 139 kWp Total power 115 kWac
Array #1 - PV Array
Orientation #1
Tilt/Azimuth 9/92 °
Number of PV modules 100 units Number of inverters 5 * MPPT 10% 0.5 units
Nominal (STC) 69.5 kWp Total power 57.5 kWac
Modules 5 Strings x 20 In series
At operating cond. (50°C) Operating voltage 200-1000 V
Pmpp 65.5 kWp Max. power (=>30°C) 125 kWac
U mpp 770 V Pnom ratio (DC:AC) 1.21
I mpp 85 A
Array #2 - Sub-array #2
Orientation #2
Tilt/Azimuth 9/-88 °
Number of PV modules 100 units Number of inverters 5 * MPPT 10% 0.5 units
Nominal (STC) 69.5 kWp Total power 57.5 kWac
Modules 5 Strings x 20 In series
At operating cond. (50°C) Operating voltage 200-1000 V
Pmpp 65.5 kWp Max. power (=>30°C) 125 kWac
U mpp 770 V Pnom ratio (DC:AC) 1.21
I mpp 85 A
PVsyst V7.2.4
VC0, Simulation date:
29/03/24 09:34
with v7.2.4
Array losses
Array Soiling Losses Thermal Loss factor DC wiring losses
Loss Fraction 3.0 % Module temperature according to irradiance Global array res. 145 mΩ
Uc (const) 20.0 W/m²K Global wiring resistance 73 mΩ
Uv (wind) 0.0 W/m²K/m/s Loss Fraction 1.5 % at STC
LID - Light Induced Degradation Module Quality Loss Module mismatch losses
Loss Fraction 2.0 % Loss Fraction -0.3 % Loss Fraction 2.0 % at MPP
System losses
Unavailability of the system
Time fraction 2.0 %
7.3 days,
3 periods
AC wiring losses
Inv. output line up to injection point
Inverter voltage 400 Vac tri
Loss Fraction 1.50 % at STC
Inverter: SUN2000-115KTL-M2-400V
Wire section (1 Inv.) Copper 1 x 3 x 95 mm²
Wires length 89 m
PVsyst V7.2.4
VC0, Simulation date:
29/03/24 09:34
with v7.2.4
Iso-shadings diagram
PVsyst V7.2.4
VC0, Simulation date:
29/03/24 09:34
with v7.2.4
Main results
System Production
Produced Energy (P50) 192.9 MWh/year Specific production (P50) 1388 kWh/kWp/year Performance Ratio PR 81.81 %
Produced Energy (P90) 188.3 MWh/year Specific production (P90) 1355 kWh/kWp/year
Produced Energy (P95) 187.0 MWh/year Specific production (P95) 1345 kWh/kWp/year
Legends
GlobHor Global horizontal irradiation EArray Effective energy at the output of the array
DiffHor Horizontal diffuse irradiation E_Grid Energy injected into grid
T_Amb Ambient Temperature PR Performance Ratio
GlobInc Global incident in coll. plane
GlobEff Effective Global, corr. for IAM and shadings
PVsyst V7.2.4
VC0, Simulation date:
29/03/24 09:34
with v7.2.4
Loss diagram
1707 kWh/m² Global horizontal irradiation
PVsyst V7.2.4
VC0, Simulation date:
29/03/24 09:34
with v7.2.4
Special graphs
Daily Input/Output diagram
PVsyst V7.2.4
VC0, Simulation date:
29/03/24 09:34
with v7.2.4
Probability distribution
PVsyst V7.2.4
VC0, Simulation date:
29/03/24 09:34
with v7.2.4
Operating costs
Item Total
EUR/year
Total (OPEX) 0.00
System summary
Total installation cost 0.00 EUR
Operating costs 0.00 EUR/year
Produced Energy 193 MWh/year
Cost of produced energy (LCOE) 0.000 EUR/kWh
PVsyst V7.2.4
VC0, Simulation date:
29/03/24 09:34
with v7.2.4