A6V10999604 - Rotary Actuators For Ball Valves - en
A6V10999604 - Rotary Actuators For Ball Valves - en
● For 2-port and 3-port control ball valves, internally threaded connections (VAI61..
and VBI61..) or externally threaded connections (VAG61.. and VBG61..), DN15 to
DN50
● For open/close ball valves 2-port and changeover ball valves 3-port, internally
threaded connections (VAI60.. and VBI60..) or externally threaded connections
(VAG60.. and VBG60..), DN15 to DN50
● Nominal torque 10 Nm
● Operating voltage GLB141.9E and GLB161.9E AC 24 V ~ / DC 24…48 V ⎓
● Operating voltage GLB341.9E AC 100…240 V ~
● Operating voltage GLB161.9E/MO AC 24 V ~ / DC 24 V ⎓
● GLB161.9E/MO: RS-485 for Modbus RTU communication
● Pre-wired with 0.9 m long connection cables
30
Functions
AC 24 V ~ /
141.9E 161.9E ─
DC 24…48 V ⎓
GLB.. AC 24 V ~ /
─ ─ 161.9E/MO
DC 24 V ⎓
AC 100…240 V ~ 341.9E ─ ─
Control type Open-close / three-position Modulating control (0/2…10 V) Modbus RTU
Rotary direction Clockwise or counter-clockwise direction depends … ─
… on the type of control … on the setting of the rotary ─
… on the setting of the rotary direction DIL switch
direction DIL switch. cw ccw
2... 2...
cw ccw
GD..1ERW_Z08
GD..1E_Z06
0... 0 0... 0
2 / 14
Siemens A6V10636203_en--_f
Smart Infrastructure 2021-11-08
AC 24 V ~ /
141.9E 161.9E ─
DC 24…48 V ⎓
GLB.. AC 24 V ~ /
─ ─ 161.9E/MO
DC 24 V ⎓
AC 100…240 V ~ 341.9E ─ ─
Position indication: Mechanical Rotary angle position indication by a position indicator/hand lever.
Position indication: Electrical Output voltage U = DC 0/2...10 V is generated proportional to
the rotary angle.
U depends on the rotary direction of the DIL switch setting.
Self-adaptation of rotary angle span When self-adaption is active, the actuator automatically detects
mechanical end of the rotary angle range.
Manual adjustment The rotary actuator can be manually adjusted by pressing the gear train disengagement button.
Rotary angle limitation The rotary angle of the shaft adapter can be limited mechanically with a set screw.
Modbus RTU (RS-485), not Setpoint 0...100 %
galvanically isolated valve position
Actual value 0...100 % for
valve position
Override control Open / Close
/ Min / Max / Stop
Setpoint monitoring and
backup mode
Housing
The housing consists essentially of flame retardant, non brominated, non chlorinated glass
fibre reinforced plastic.
Type summary
Type Stock no. Control Operating Position indicator Self-adaption of Aux. Rotary
voltage U = DC 0…10 V ⎓ rotational angle switches direction
range switch
AC 24 V ~ /
GLB141.9E S55499-D204 Open-close or DC 24…48 V ⎓ ‒ ‒ ‒
three-position
GLB341.9E S55499-D205 AC 100…240 V ~
Modulating AC 24 V ~ / yes
GLB161.9E S55499-D277
DC 0/2...10 V ⎓ DC 24…48 V ⎓
yes yes ‒
AC 24 V ~ /
GLB161.9E/MO S55499-D681 Modbus RTU
DC 24 V ⎓
3 / 14
A6V10636203_en--_f Siemens
2021-11-08 Smart Infrastructure
Accessories / Spare parts
Spare parts
Individual spare parts are not available. Components of the accessory kit ASK77.3 1),
available as an accessory, can however be used for spare parts.
Description Components
ASK77.3 Accessory Kit BV for GxBxx1.9E Mounting bracket (base plate)
Axle with sleeve and spring
Manual lever with locking clip
1)
Can also be used as rotary actuator for ball valves together with the actuator for air dampers G..B.1E.
Accessories
Equipment combinations
GLB..9E.. and VA..61..
2-port control ball valves
4 / 14
Siemens A6V10636203_en--_f
Smart Infrastructure 2021-11-08
GLB.. 9E.. and VA..60.. open/close ball valves 2-port and
VB..60.. changeover ball valves 3-port
‒ ‒ VBG60.15-8T G1B 8 15
VBI60.15-12T Rp ½“ ‒ ‒ 12 15
‒ ‒ VBG60.20-13T G1¼B 13 20
VBI60.20-16T Rp 1” ‒ ‒ 16 20
‒ ‒ VBG60.25-13T G1½B 13 25 350 ‒
VBI60.25-16T Rp 1” ‒ ‒ 16 25
VBI60.32-25T Rp 1¼” VBG60.32-25T G2B 25 32
VBI60.40-49T Rp 1½” VBG60.40-49T G2¼B 49 40
VBI60.50-73T Rp 2” VBG60.50-73T G2¾B 73 50
3)
Data sheet N4213
4)
Data sheet N4214
Product documentation
5 / 14
A6V10636203_en--_f Siemens
2021-11-08 Smart Infrastructure
Notes
Safety
Caution
Mounting
Both ball valve and rotary actuator can easily be assembled at the mounting location. Neither
special tools nor adjustments are required.
Orientation
90° 90°
4716Z16
Installation
WARNING
6 / 14
Siemens A6V10636203_en--_f
Smart Infrastructure 2021-11-08
Engineering
If condensation occurs at the mounting site, the use of the temperature adapter ALJ100 is
recommended in order to protect the actuator. If the medium temperature is ≤ 0 °C, the
adapter shaft must be greased with silicon grease.
TM Medium temperature
TA Ambient temperature
GLB161.9E/MO
The Modbus converter is designed for analog control at 0...10 V.
Commissioning
When commissioning the system, check wiring and the functions of the rotary actuator.
Manual adjustment
The rotary actuator can be manually adjusted into any position between 0° and 90° by
pushing the gear train disengagement slider.
If a control signal from the controller is present, this will take priority in determining the
position after the slider is released.
Maintenance
Disposal
7 / 14
A6V10636203_en--_f Siemens
2021-11-08 Smart Infrastructure
Technical data
Function data
Nominal torque 10 Nm
Maximum torque (blocked) 16 Nm
Minimum holding torque 10 Nm
Nominal rotary angle (with position indication) 90°
Maximum rotary angle (mechanic limitation) 95° ± 2°
Runtime for 90° rotary angle 150 s
Actuator sound power level 28 dB(A)
Inputs
Positioning signal for GLB141.9E
Operating voltage (wires 1-6/G-Y1) clockwise
AC 24 V ~ / DC 24…48 V ⎓ (wires 1-7/G-Y2) counterclockwise
Positioning signal for GLB341.9E
Operating voltage (wires 4-6/N-Y1) clockwise
AC 100…240 V ~ (wires 4-7/N-Y2) counterclockwise
Communication GLB161.9E/MO
Communication protocol
Modbus RTU RS-485, not galvanically isolated
Number of nodes Max. 32
Address range 1...248 / 255
Factory setting 255
Transmission formats 1-8-E-1 / 1-8-O-1 / 1-8-N-1 / 1-8-N-2
Factory setting 1-8-E-1
Baud rates (kbaud) Auto / 9.6 / 19.2 / 38.4 / 57.6 / 76.8 / 115.2
Factory setting Auto
Bus termination 120 Ω electronically switchable
Factory setting Off
8 / 14
Siemens A6V10636203_en--_f
Smart Infrastructure 2021-11-08
Outputs
Position indicator (GLB161.9E..)
Output signal (wires 9-2/U-G0)
Output voltage U DC 0...10 V ⎓
Max. output current DC ±1 mA
Protected against faulty wiring max. AC 24 V ~ / DC 24…48 V ⎓
Connection cables
Cable length 0.9 m
Cross section of prewired connection cables 0.75 mm2
Permissible length for signal lines 300 m
Degree of protection
Insulation class As per EN 60730
AC 24 V ~ / DC 24…48 V ⎓ III
AC 100…240 V ~ II
Housing protection IP 54 as per EN 60529
Environmental conditions
Operation IEC 60721-3-3
Climatic conditions Class 3K5
Mounting location interior, weather-protected
Temperature extended -32…+55 °C
Humidity (non-condensing) <95 % r.F.
Transport IEC 60721-3-2
Climatic conditions Class 3K5 / Class 2K3
Temperature extended -32…+70 °C
Humidity (non-condensing) <95 % r.F.
Storage IEC 60721-3-1
Climatic conditions Class 1K3
Temperature extended -32…+50 °C
Humidity (non-condensing) <95 % r.F.
Mechanical conditions Class 2M2
Environmental compatibility
The product environmental declaration A5W00026068 2) contains data on environmentally compatible product
design and assessments (RoHS compliance, materials composition, packaging, environmental benefit, disposal).
Dimensions
Actuator W x H x D see „Dimensions“, p. 12
Weight
Without packaging 0.69 kg
External Modbus converter 0.15 kg
1)
C-UL: Permitted only to DC 30 V ⎓
2)
The documents can be downloaded from http://siemens.com/bt/download.
9 / 14
A6V10636203_en--_f Siemens
2021-11-08 Smart Infrastructure
Diagrams
Internal Diagrams
GLB141.9E (open-close, three-p.) GLB161.9E.. (modulating) GLB341.9E (open-close, three-p.)
GLB161.9E/MO
AC 24 V ~ / DC 24 V ⎓
Connection diagrams
GLB1..9E.. (AC 24 V ~ / DC 24…48 V ⎓)
Open-close, single wire control Open-close, two wire control Three-position control Modulating control
Single Pole Single Throw (SPST) Single Pole Double Throw (SPDT)
10 / 14
Siemens A6V10636203_en--_f
Smart Infrastructure 2021-11-08
GLB161.9E/MO (AC 24 V ~ / DC 24 V ⎓)
Modbus (AC 24 V ~ / DC 24 V ⎓)
Open-close, single wire control Open-close, two wire control Three-position control
Single Pole Single Throw (SPST) Single Pole Double Throw (SPDT)
Cable labeling
11 / 14
A6V10636203_en--_f Siemens
2021-11-08 Smart Infrastructure
Dimensions
Actuator
4657M01b
Dimensions in mm
= > 100 mm Minimum clearance from ceiling or wall for mounting,
= > 200 mm connection, operation, maintenance etc.
12 / 14
Siemens A6V10636203_en--_f
Smart Infrastructure 2021-11-08
Temperature adapter (optional)
42
162.8
70
64 23.5
Revision numbers
13 / 14
A6V10636203_en--_f Siemens
2021-11-08 Smart Infrastructure
Issued by © Siemens Switzerland Ltd, 2021
Siemens Switzerland Ltd Technical specifications and availability subject to change without notice.
Smart Infrastructure
Global Headquarters
Theilerstrasse 1a
6300 Zug
Switzerland
Tel. +41 58-724 24 24
www.siemens.com/buildingtechnologies
Document ID A6V10636203_en--_f
Issue 2021-11-08