Example Distance Distance
Example Distance Distance
Page 2
Preface
This paper describes how to test distance protection zones. It contains an application example that will be
used throughout the paper. The theoretical background of the distance protection function will be explained.
This paper also covers the definition of the necessary Test Object settings as well as the
Hardware Configuration for distance protection tests. Finally the Distance or Advanced Distance test
modules are used to perform the tests that are needed for the distance protection zones.
Page 3
1 Application Example
Note: Testing of associated functions (e.g., Automatic Reclosure, Switch on to Fault), are not part of this
document.
Page 4
Parameter Name Parameter Value Notes
Frequency 50 Hz
VT (primary/secondary) 110000 V / 110 V
CT (primary/secondary) 600 A /1 A
Solidly grounded Transformer starpoint
64° Line angle (short-circuit angle ϕsc)
0.218 Ω/km Secondary line reactance per length unit (Ω/km)
Power System Data
32.5 km (20.19 miles) Line length in km (miles)
0.6 Zero sequence compensation factor K0 1)
Angle for the Zero sequence compensation
0°
factor
Distance protection 1.2 s Trip time for forward-pick-up
general settings 1.6 s Trip time for non-directional pick-up
Overcurrent Pick-up program
Distance protection Pick-up value
pickup settings (secondary 1.5 A
for phase faults = 1.5 x In CT
values) 3I0 / pick-up value
0.2 A
for neutral current =0.2 x In CT
Forward Operating mode Z1
6Ω X(Z1) Reactance of zone 1
Rphph (Z1) Resistance for phase to phase faults
2.9 Ω
of zone 1
Rphe (Z1) Resistance for phase to ground faults
2.9 Ω
of zone 1
Trip time zone 1 (valid for phase to phase and
0s
phase to ground faults)
Forward Operating mode Z2
9.2 Ω X(Z2) Reactance of zone 2
Distance protection Rphph (Z2) Resistance for phase to phase faults
zone settings for quadrilateral 4.4 Ω
of zone 2
shapes (secondary values) Rphe (Z2) Resistance for phase to ground faults
4.4 Ω
of zone 2
Trip time zone 2 (valid for phase to phase and
0.4 s
phase to ground faults)
Reverse Operating mode Z3
5.6 Ω X(Z3) Reactance of zone 3
Rphph (Z3) Resistance for phase to phase faults
2.7 Ω
of zone 3
RphE (Z3) Resistance for phase to ground faults
2.7 Ω
of zone 3
Trip time zone 3 (valid for phase to phase and
0.8 s
phase to ground faults)
1) The structure of this parameter is depends on the manufacturers (see chapter 2.3 “Zero-Sequence Compensation”). In this example
this factor is valid for all zones.
Table 1: Relay parameters for this example (quadrilateral impedance diagram)
Page 5
Parameter Name Parameter Value Notes
Forward Operating mode Z1
6.66 Ω Reach for phase to phase faults of zone 1
6.66 Ω Reach for phase to ground faults of zone 1
Trip time zone 1 (valid for phase to phase and
0s
phase to ground faults)
Forward Operating mode Z2
Distance protection 10.2 Ω Reach for phase to phase faults of zone 2
zone settings for mho shapes
(secondary values) 10.2 Ω Reach for phase to ground faults of zone 2
Trip time zone 2 (valid for phase to phase and
0.4 s
phase to ground faults)
Reverse Operating mode Z3
6.22 Ω Reach for phase to phase faults of zone 3
6.22 Ω Reach for phase to ground faults of zone 3
Trip time zone 3 (valid for phase to phase and
0.8 s
phase to ground faults)
Table 2: Relay parameters for this example (Mho shape; see table 1 for all other parameters)
Page 6
2 Theoretical Introduction to Distance Characteristics
Distance relays are applied as short-circuit protection in almost all systems where overcurrent relays cannot
be used for reasons of selectivity, a requirement for fault detection or where this is a need for short
disconnection times. They are mainly applied in ring networks with multiple feeds and meshed HV networks.
110 kV 600 A
1A Z´line = 0.404 Ω∠64°, 32.5 km
110kV 110 V
BB A 3 3
There are different types of impedance characteristics. For this example only the Quadrilateral and Mho
types will be used.
Page 7
1
2
1
3
1
4
1
5
1
1. Settings of zone 1
2. Settings of zone 2
3. Settings of zone 3
4
1 2
1 4. Setting of the line angle (it depends on
the type of relay, whether this setting
exists or not)
5. Setting of the distance characteristic
angle
6. Directional characteristic (the directional
1 characteristic depends on the type of
5
1 relay)
6
1
3
1
Page 8
1 4
1
2
1 5
1
3
1 6
1
7
1
7
1
5
1
4
1 1. Setting of zone 1 for phase faults
2. Setting of zone 2 for phase faults
2
1 3. Setting of zone 3 for phase faults
4. Setting of zone 1 for ground faults
1 5. Setting of zone 2 for ground faults
6. Setting of zone 3 for ground faults
7. Setting of the line angle
3
1
6
1
Note: For the logic of the Ground Distance Elements see chapter 2.3 “Zero-Sequence Compensation”.
Page 9
2.2 Line Impedance Angle (Short-Circuit Angle)
The short-circuit angle between the fault voltage and current is a characteristic factor of a particular fault.
This angle depends on the voltage level and the protected equipment (e.g., overhead line, cable and
transformer). This can be examined more closely.
1105 1211
Page 10
2.3 Zero-Sequence Compensation
α ⋅ Zg (1-α ) Zg α ⋅ Zg (1-α ) Zg
Zloop = 2 ⋅ α ⋅ Zline (
Zloop = α ⋅ Zline + Zg )
Zloop Zloop
α= α=
2Zline Zline + Zg
For phase to phase faults the distance between the relay and the fault can be calculated from the loop
impedance by just using the line impedance. However, for phase to ground faults the ground impedance is
also needed. To take the ground impedance into account, a zero sequence compensation factor (grounding
factor) is used. The definition of this factor depends on the manufacturer of the relay:
Page 11
Some examples for the settings of these parameters are shown below
Figure 10: Zero sequence compensation factor for distance protection devices from SIEMENS
Setting this factor will influence the resulting zone for phase to ground faults as shown below.
(1 + kL ) ⋅ Z1
Z1
Figure 11: Influence of the zero sequence compensation factor on the zone
Page 12
3 Practical Introduction
The Advanced Distance test module and the Distance test module are designed for testing distance
protection functions (e.g., impedance diagram, trip times, etc.).
Note: The functionality of the Advanced Distance test module and the Distance test module is different!
Figure 12: Test View of the Advanced Distance test module and Distance test module
For all following discussions, the Advanced Distance test module is used. This test module incorporates the
functionality of the Distance test module.
You find the Advanced Distance test module on the start screen of the OMICRON Test Universe software.
Advanced Distance can also be inserted into an OCC File (a Control Center document).
Test Module on Control Center’s Insert tab
Page 13
3.1.1 Device Settings
General relay settings (e.g., relay type, relay ID, substation details, CT and VT parameters) are entered in
the RIO function Device.
Note: The parameters V max and I max limit the output of the currents and voltages to prevent
damage to the device under test. These values must be adapted to the respective
Hardware Configuration when connecting the outputs in parallel or when using an amplifier.
The user should consult the manual of the device under test to make sure that its input rating
will not be exceeded.
Page 14
3.1.2 Defining the Distance Protection Parameters
More specific data concerning the distance protection relay can be entered in the RIO function Distance.
The definition of the distance impedance diagram has to be made here as well.
Note: Once an Advanced Distance / Distance test module is inserted, this RIO function is available.
System Settings
The first tab contains the definition of the system data, the relay behavior as well as the relay tolerances.
6
4
1 7
4
3
2
3
4
4
2
1
5
4
Page 15
1. The line length and line angle are the magnitude and angle of the impedance Z of the protected line.
They are needed to calculate faults correctly with respect to the power system.
If the line reactance X is set in the relay, then the impedance Z has to be calculated out of the reactance
Ω
X X ′ ⋅ l 0.218 km ⋅ 32.5 km
X and the line angle ϕ. Line length = Z = = = = 7.88 Ω (see Table 1).
sin ϕ sin ϕ sin 64°
2. Regarding the feeder connection diagram (Figure 2) the PT is placed at line. If at busbar is chosen, the
voltage will have the nominal value after tripping.
3. The CT starpoint has to be set according to the connection of the secondary windings of the CT. For this
example the feeder connection diagram (Figure 2) shows that the CT grounding is towards the line.
4. The impedance and time tolerances are found in the relay manual.
5. The grounding factor compensates the effect of the ground impedance on the distance zones (see
chapter 2.3 “Zero-Sequence Compensation”). For further information about the settings of the grounding
factor, refer to the Help.
6. Select this checkbox to enter all impedances in primary values.
7. This checkbox must be activated, if a 5 A relay is tested that uses 1 A as reference for the impedance
calculation.
Page 16
Zone Settings
As shown above, no zone is set by default. Click New to insert a zone. Afterwards the characteristic editor
can be opened by clicking edit. Here the distance zone can be entered.
Click Add to add a new element to the Element list. The element can be either a line or an arc.
> A line has to be set with an angle and a point on the line. This point can be set either in Cartesian or in
polar coordinates. Therefore, the options Line cartesian and Line polar exist.
> A circle has to be set with a center point, a radius, a start angle, an end angle as well as a direction. As
the center can be set in Cartesian as well as in polar coordinates, the options Arc cartesian and
Arc polar can be used.
Page 17
It is also possible to use Predefined shapes.
1
1 2 3
1. Mho shape
2. Lens/Tomato shape 2
3. Quadrilateral
Note: The shape of a distance zone depends on the type of relay as well as on the settings in the
relay. The shape can be found in the relay manual. The elements for one quadrilateral as well
as for one mho shape are shown below.
Page 18
After the first zone has been defined, the Zone settings tab will look like this:
If additional zones are required, the first zone can be copied (1) and appended to the list (2). Afterwards the
settings of the other zones can be adapted. After all the zones have been entered the list could look like this:
3 4 5 6 7 3 5 6
Page 19
After all of the zones are defined, the tripping time for each zone can be set. It is also possible to define
separate tolerances for each of the zones.
Note: In this example different starting zones have been defined. The zones ZS1 are only in the
forward direction. Therefore, the forward directional end time is set as the tripping time for these
zones. The zones ZS2 cover the complete impedance plane and, therefore, have the non-
directional end time as the tripping time (see Table 1).
Page 20
3.2 Global Hardware Configuration of the CMC Test Set
The global Hardware Configuration specifies the general input/output configuration of the CMC test set. It
is valid for all subsequent test modules and, therefore, it has to be defined according to the relay’s
connections. It can be opened by double clicking the Hardware Configuration entry in the OCC file.
3.2.1 Example Output Configuration for Protection Relays with a Secondary Nominal Current of 1 A
Page 21
3.2.2 Example Output Configuration for Protection Relays with a Secondary Nominal Current of 5 A
Note: Make sure that the rating of the wires is sufficient when connecting them in parallel.
The following explanations only apply to protection relays with a secondary nominal current of
1 A.
Page 22
3.2.3 Analog Outputs
The analog outputs, binary inputs and outputs can all be activated individually in the local Hardware
Configuration of the specific test module (see chapter 3.3 “Local Hardware Configuration for Distance
Protection Testing”).
1
2
1. The start command is optional (it is needed if Starting is selected as a time reference in the test).
2. The trip command has to be connected to a binary input. BI1 … BI10 can be used.
3. For wet contacts adapt the nominal voltages of the binary inputs to the voltage of the circuit breaker trip
command or select Potential Free for dry contacts.
4. The binary outputs and the analog inputs etc. will not be used for the following tests.
Page 23
3.2.5 Wiring of the Test Set for Relays with a Secondary Nominal Current of 1A
Note: The following wiring diagrams are examples only. The wiring of the analog current inputs may
be different if additional protective functions such as sensitive ground fault protection are
provided. In this case IN may be wired separately.
Protection
Relay
VA
VB
VC
(-) (-)
IA
IB
IC
IN
Trip
(+)
optional
Start
(+)
Page 24
3.3 Local Hardware Configuration for Distance Protection Testing
The local Hardware Configuration activates the outputs/inputs of the CMC test set for the selected
test module. Therefore, define it separately for each individual test module. Click Hardware
Configuration on the Home tab.
Page 25
3.4 Defining the Test Configuration
3.4.1 General Approach
When testing the distance protection function, the following steps are recommended:
> Pick-up Test: The respective pick-up function (e.g., Overcurrent starting) is tested. This test is not
explained in this document.
> Trip time test: The trip times of the distance protection function are verified.
> Zone reach test: The zone reaches of the distance protection are verified.
The trip time test, as well as the zone reach test, is performed with the Advanced Distance test module.
Page 26
Trip Time Test
Trigger and Settings tabs:
2
6
1
4
5
Page 27
Shot Test tab:
The trip times are tested with the shot test. With this test method test shots can be placed in the impedance
plane. These test shots can either be set manually by entering R and X or |Z| and Phi values or an angle
can be entered (1) and the values can be set relative to the respective zone (2). To do so, the option
|Z| relative has to be selected. If this option is used, the test shots will be adapted whenever the zone
settings change. Select the Follow line angle change option to adapt the angle of the test shots to a
changing line angle.
For this test, test shots are placed both inside and outside of the tripping zones. Hence, it is possible to test
the trip times of all the tripping zones, as well as the directional and non-directional end time.
Page 28
Zone Reach Test
In the Trigger and the Settings tab the same adjustments as for the trip time test apply.
For the zone reach test the Search Test is used. With this tab the user can define search lines. The test
module applies test shots along these lines to search for the reach of each zone. It is also possible to use
the Check Test. With this test lines are again defined. However, this time test shots will be placed along
these lines outside the tolerance bands. This confirms if the zone reach is within the defined tolerances.
3
6
1
1
2
4 4
6
3
1. Search lines can be defined either by dragging a line in the impedance plane or by setting a start point,
an angle and the length. After defining a line, click Add to add it to the list of test lines.
2. By activating Follow line angle change and Relative test lines can be defined in a way that they adapt
to changes of the zone settings or the line angle.
3. In the forward and reverse direction, one search line is defined to test the reactance settings X of the
zones.
4. The resistance settings R of the zones are tested in the same way.
5. Using search lines in parallel to the resistance search lines, the characteristic angle is confirmed.
6. Test lines along the line angle can also be set. This confirms that the relay works correctly in the area
where faults normally occur.
Page 29
Support
When you are working with our products we want to provide you with the greatest
possible benefits. If you need any support, we are here to assist you!
At our technical support hotline, you can reach well-educated technicians for all of
your questions. Around the clock – competent and free of charge.
Additionally, you can find our Service Center or Sales Partner closest to you at
www.omicron.at or www.omicronusa.com.
Browse through the knowledge library and find application notes, conference papers,
articles about daily working experiences, user manuals and much more.
Learn more about your product in one of the training courses offered by the
OMICRON Academy.
OMICRON electronics GmbH, Oberes Ried 1, 6833 Klaus, Austria, +43 59495
Page 30