Válvula de Gas NPT V88J1006

The document provides specifications for V48A and V88A,J diaphragm gas valves. It details the features, applications, specifications, dimensions, ratings, and approvals of the valves. The valves are solenoid-operated and suitable for LP, natural, and manufactured gases to control flow in applications like boilers, water heaters, and rooftop heaters.

Uploaded by

ycrnsf
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
63 views4 pages

Válvula de Gas NPT V88J1006

The document provides specifications for V48A and V88A,J diaphragm gas valves. It details the features, applications, specifications, dimensions, ratings, and approvals of the valves. The valves are solenoid-operated and suitable for LP, natural, and manufactured gases to control flow in applications like boilers, water heaters, and rooftop heaters.

Uploaded by

ycrnsf
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

V48A & V88A,J

Diaphragm Gas Valves


SPECIFICATION DATA

FEATURES
• Line voltage, 2-wire thermostat or controller used with a
V48; V88 used with 24V thermostat.
• Valves provide slow opening and fast closing.
• Two second maximum closing time.
• V88J rated for 150°F (66°C) ambient temperature.
• V48A and V88A rated for either 1/2 or 1 psi (3.4 or 6.9
kPa), depending on model. V88J rated for 1 psi (6.9 kPa).
• One model for natural and LP gases.
• Wide range of sizes and capacities.
• Firm closing; diaphragm is both weight and spring loaded.
• Valve closes on power failure; recommended for final
shutoff service.
• Adjustable or fixed bleed orifices available for installation by
OEM.
• Valve position indicator on 1-1/4 in. V48A2227.

APPLICATION
The V48 and V88 are solenoid-operated diaphragm valves
suitable for LP (Liquefied Petroleum), natural, and
manufactured gases. They are normally used on atmospheric
boilers, commercial water heaters, and rooftop heaters.

65-0053-02
V48A & V88A,J DIAPHRAGM GAS VALVES

SPECIFICATIONS Maximum Fluid Temperature:


V48A, V88A: 125°F (52°C).
V88J: 150°F (66°C).
Models:
V48A (120 Vac) or V88A (24 Vac) solenoid operated Thermostat Heat Anticipator Setting: For 60 Hz V88, set at
diaphragm valves for 1/2 or 1 psi (3.4 or 6.9 kPa) maximum 0.6A; for 50Hz set at 0.65A.
operating pressure.
Dimensions: See Fig. 1.
V88J (24 Vac) solenoid operated diaphragm valves for 1 psi
(6.9 kPa) operating pressure and 150°F (66°C) maximum Weight: See Table 1.
ambient temperature.
Table 1. Valve Weight.
Type of Gas: Suitable for liquefied petroleum (LP), natural,
manufactured, and sulfur-bearing gases. Pipe Size (in.) lb kg
3/4 2-1/2 1.13
Valve Capacity: See table in Fig. 2.
1 3 1.36
Valve Pattern: Straight-through, non-offset. 1-1/4 3-1/2 1.59
Valve Body Material: Die-cast aluminum. 1-1/2 4 1.81
2 9 4.08
Pilot Tapping:
3/4 through 1-1/2 inch valves: 1/8-27 NPT. 2-1/2 8-1/2 3.86
2 through 3 inch valves: 1/4-18 NPT. 3 9-1/2 4.31
Bleed Tapping: 1/8-27 NPT. Approvals: (60 Hz models only):
Valve Opening Time: Underwriters Laboratories Inc. Listed: File No. MH1639;
Five seconds maximum at 2 oz/in.2 (0.86 kPa) pressure. Guide No. YIOZ.
Adjustable bleed valve assembly or fixed bleed orifices CSA 158158-2500005576 (Z21.21-CSA C I 6.5).
available for longer opening time (NPT threads only; see NOTE: All models rated at 50 Hz and all models with BSP.PI
Accessories). threads are not CSA Design Certified.

Valve Closing Time (on power failure; measured at Optional Feature: Valve position indicator is available on
2 oz/in.2 (0.86 kPa) pressure): 2 seconds maximum. 1-1/4 inch V48A2227.

Maximum Operating Pressure: See Table 2. Replacement Coil Assemblies:a


116930: 24V, 60 Hz V88A
Power Consumption (maximum): 9 watts or 15 VA. 116931: 120V, 60 Hz V48A.
116932: 220V, 50 Hz V48A
Ambient Temperature Rating: 116932: 240V, 60 Hz V48A
V48A and V88A: 32°F to 125°F (0°C to 52°C). 118888: 24V, 60 Hz V88J
V88J: 32°F to 150°F (0°C to 66°C). a These V48/V88 bonnet assemblies and solenoid operators
are not compatible with old style valve bodies.

Table 2. Models Available.


Maximum Operating
Pressure
Model Voltage and Frequency psi kPa Pipe Size (in.) Thread Typea
V48A 120V, 60 Hz 1/2 3.4 3/4, 1, 1-1/4, 1-1/2 NPT
1 6.9 1, 1-1/4, 1-1/2, 2, 2-1/2, 3
V88A 24V, 60 Hz 1/2 3.4 3/4, 1, 1-1/4, 1-1/2 NPT
1 6.9 3/4, 1, 1-1/4, 1-1/2, 2, 2-1/2, 3
V88J 24V, 60 Hz 6.9 1, 1-1/4
a
NPT—American Standard Taper Pipe Threads.

65-0053-02 2
V48A & V88A,J DIAPHRAGM GAS VALVES

C 3-11/16
(94) VALVE APPROXIMATE DIMENSIONS
1-13/16 SIZE A B C D E F
(46) (IN.)
IN. MM IN. MM IN. MM IN. MM IN. MM IN. MM
3/4 4-11/16 119.1 3/4 19.1 4-5/8 117.5 3-1/2 88.9 1-5/8 41.3 3-13/16 96.8
1 5-1/16 128.6 1 25.4 5 127.0 3-11/16 93.7 2-1/16 52.4 4-5/16 109.5
1-1/4 5-9/16 141.3 1-1/4 31.8 5-7/8 149.2 5-5/16 134.9 2-3/8 60.3 5-5/16 134.9
1-1/2 5-9/16 141.3 1-1/4 31.8 5-7/8 149.2 5-5/16 134.9 2-3/8 60.3 5-5/16 134.9
A 2 6-15/16 176.2 2-1/4 57.2 9-1/2 241.3 8-3/8 212.7 3-9/16 90.5 5-5/16 236.5
1 2-1/2 6-15/16 176.2 2-1/4 57.2 9-1/2 241.3 8-3/8 212.7 3-9/16 90.5 9-5/16 236.5
3 6-15/16 176.2 2-1/4 57.2 9-1/2 241.3 8-3/8 212.7 3-9/16 90.5 9-5/16 236.5

E 2 1 BLEED TAPPING: 1/8-27 NPT.

2 PILOT TAPING (2): 1/8-27 NPT FOR 3/4 THROUGH 1-1/2 IN. SIZES,
1/4-18 NPT FOR 2 THROUGH 3 IN. SIZES;
B D
M8487A
F

Fig. 1. Mounting dimensions of V48A and V88A,J Diaphragm Gas Valves in in. (mm).

Table 3. Extending Valve Opening Timea By Adding a Bleed Orifice.


Valve Opening Time (seconds)
Orifice No. 122160, Orifice No. 124674,
Valve Size (in.) No Orifice 0.018 in. (0.46 mm) 0.011 in. (0.28 mm)
1 1 2 3
1-1/4 1 5 6
1-1/2 1 5 6
2 4 15 32
2-1/2 4 23 37
3 5 24 37
a Time
to reach 80% gas flow at fully open position. Inlet pressure; 4.2 in. wc (1.05 kPa) for 1 to 2 in. valves; 5 in. wc (1.25 kPa)
for 2-1/2 and 3 in. valves. Pressure drop across valves at fully open position. 0.2 in. wc (0.05 kPa) for 1 to 2 in. valves; 1 in. wc
(0.25 kPa) for 2-1/2 and 3 in. valves.

3 65-0053-02
V48A & V88A,J DIAPHRAGM GAS VALVES

[2.5] 10 PRESSURE DROP VS. CAPACITY


FOR 0.64 SP GR. GAS
9
[2.0] 8
7
A.G.A.RATING FOR
[1.5] 6 0.64 SP. GR. GAS AT
1 IN. PRESSURE DROP
5 VALVE SIZE CAPACITY

3/4 IN. 668 cf/h


[1.0] 4
1 IN. 1021 cf/h
1-1/4 IN. 2100 cf/h
1-1/2 IN. 2400 cf/h
[0.75] 3 2 IN. 4178 cf/h
2-1/2 IN. 5100 cf/h
2.5 3 IN. 5562 cf/h

[0.5] 2

1.5
PRESSURE DROP—INCHES W.C. [kPa]

3
2-1/2
[0.25] 1.0
2
0.9
[0.2] 0.8 1-1/2
0.7 1-1/4

[0.15] 0.6
1

0.5 3/4

[0.1] 0.4

[0.075] 0.3

0.25

[0.05] 0.2

0.15

[0.025] 0.1
1 1.5 2 2.5 3 4 5 6 7 8 9 10 1.5 2 2.5 3 4 5 6 7 8 9 10

MULTIPLY BY 100 MULTIPLY BY 1000 M8491A

CAPACITY IN CUBIC FEET PER HOUR (cf/h)


FOR GAS WITH SPECIFIC GRAVITY OF 0.64
[1 cf/h = 0.0283 m3/hr]

Fig. 2. Pressure drop vs. capacity chart for sizing gas valves.

Automation and Control Solutions


Honeywell International Inc.
1985 Douglas Drive North
® U.S. Registered Trademark
Golden Valley, MN 55422 © 2012 Honeywell International Inc.
65-0053-02 JPG Rev. 11-12
www.honeywell.com/buildingsolutions Printed in U.S.A.