50 HZ and 60 HZ Air-Cooled Product With Evolution™ or Nexus™ Control
50 HZ and 60 HZ Air-Cooled Product With Evolution™ or Nexus™ Control
DIAGNOSTIC
REPAIR
MANUAL
S TA N D B Y G E N E R AT O R S
Q: Can I use a fuel shut off valve that is not “Full
Flow Rated”?
WARNING
A: No, it must be a Full Flow Rated valve and must also
Operating, servicing and maintaining this
match the required fuel pipe ID dimensions.
equipment can expose you to chemicals
including engine exhaust, carbon monoxide, Q: Do pipe elbows, tees, sediment traps, etc., affect
phthalates, and lead, which are known to the gas pipe size and flow?
State of California to cause cancer and birth A: Yes, they are restrictions to gas flow. You must add
defects or other reproductive harm. To 2.5ft. (.76m) per each elbow, tee, etc. to the overall
minimize exposure, avoid breathing exhaust, calculated distance from the source to the generator.
do not idle the engine except as necessary, Q: Can I leave the unit on the shipping pallet and
service your equipment in a well-ventilated install it?
area and wear gloves or wash your hands A: No, it must be installed per local jurisdiction, code
frequently when servicing your equipment. and the instructions as outlined by Generac.
For more information go to
www.P65Warnings.ca.gov. Q: Can the generator be mounted indoors or in a
(000393)
structure?
A: No, it is designed, manufactured and sold for outdoor
Frequently Asked Questions use only!
Q: Do I have to supply the generator with the 100% Q: Can I run the Main AC and Control Wires in the
loaded BTU rated fuel supply and pipe size? same conduit?
A: Yes, the generator needs the 100% loaded BTU fuel A: Yes, this wiring can be run in the same conduit if the
rating to start, run and handle loads. The fuel pipe appropriate rated wire and insulation is used and it
must be sized for 100% load, regardless of the load. meets code.
Q: What distance does the gas regulator need to be Q: Can the Transfer Switch be mounted outdoors?
from the generator? A: Only if it’s a NEMA 3R rated transfer switch.
A: Distance is best practices per the regulator
manufacturer's instruction to assure proper operation
of the regulator and also to meet code.
Unit running in AUTO GREEN Check MLCB. NONE Check MLCB. If the MLCB
but no power in house. or is in the ON position contact
Flashing the servicing dealer.
GREEN
(2017
Units and
newer
with
Firmware
version
1.17 and
up.)
Unit shuts down during RED Check the LED’s/ HIGH Check ventilation around
operation. Screen for alarms. TEMPERATURE the generator, intake,
exhaust and rear of
generator. If no obstruction
contact serving dealer.
Unit shuts down during RED Check the LED’s/ OVERLOAD Clear alarm and remove
operation. Screen for alarms. REMOVE LOAD household loads from the
generator. Put back in
AUTO and restart.
Unit was running and RED Check the LED’s/ RPM SENSE LOSS Clear alarm and remove
shuts down, attempts to Screen for alarms. household loads from the
restart. generator. Put back in
AUTO and restart. It may be
a fuel issue so contact the
servicing dealer.
Unit will not start in NONE See if screen says NOT ACTIVATED Refer to activation section in
AUTO with utility loss. unit not activated. owners manual.
Unit will not start in GREEN Check screen for None If the start up delay is
AUTO with utility loss. start delay greater than expected,
countdown. contact servicing dealer to
adjust from 2 to 1500
seconds.
Unit will not start in RED Check the LED’s/ LOW OIL Check Oil Level/Add Oil Per
AUTO with utility loss. Screen for alarms. PRESSURE Owners Manual. If oil level
is correct contact servicing
dealer.
Unit will not start in RED Check the LED’s/ RPM SENSE LOSS Clear alarm. Check the
AUTO with utility loss. Screen for alarms. battery using the control
panel under the MAIN menu
using the BATTERY MENU
option. If it states battery is
GOOD contact servicing
dealer. If it states CHECK
BATTERY replace the
battery.
Unit will not start in RED Check the LED’s/ OVERCRANK Check fuel line shutoff valve
AUTO with utility loss. Screen for alarms. is in the ON position. Clear
alarm. Attempt to start the
unit in MANUAL. If it does
not start or starts and runs
rough, contact servicing
dealer.
Unit will not start in RED Check the LED’s/ OVERLOAD Clear alarm and remove
AUTO with utility loss. Screen for alarms. REMOVE LOAD household loads from the
generator. Put back in
AUTO and restart.
Unit will not start in RED Check the LED’s/ FUSE PROBLEM Check the 7.5 Amp fuse. If it
AUTO with utility loss. Screen for alarms. is bad replace it with an ATO
7.5 Amp fuse, if not contact
servicing dealer.
Unit will not start in RED Check the LED’s/ OVERSPEED Contact servicing dealer.
AUTO with utility loss. Screen for alarms.
Unit will not start in RED Check the LED’s/ UNDERVOLTAGE Contact servicing dealer.
AUTO with utility loss. Screen for alarms.
Unit will not start in RED Check the LED’s/ UNDERSPEED Contact servicing dealer.
AUTO with utility loss. Screen for alarms.
Unit will not start in RED Check the LED’s/ STEPPER Contact servicing dealer.
AUTO with utility loss. Screen for alarms. OVERCURRENT
Unit will not start in RED Check the LED’s/ MISWIRE Contact servicing dealer.
AUTO with utility loss. Screen for alarms.
Unit will not start in RED Check the LED’s/ OVERVOLTAGE Contact servicing dealer.
AUTO with utility loss. Screen for alarms.
Yellow LED illuminated YELLOW Check the screen for LOW BATTERY Clear alarm. Check the
in any state. additional battery using the control
information. panel under the MAIN menu
using the BATTERY MENU
option. If it states battery is
GOOD contact servicing
dealer. If it states CHECK
BATTERY replace the
battery.
Yellow LED illuminated YELLOW Check the screen for BATTERY Contact servicing dealer.
in any state. additional PROBLEM
information.
Yellow LED illuminated YELLOW Check the screen for CHARGER Contact servicing dealer
in any state. additional WARNING
information.
Yellow LED illuminated YELLOW Check the screen for SERVICE A Perform SERVICE A
in any state. additional maintenance, hit ENTER to
information. clear.
Yellow LED illuminated YELLOW Check the screen for SERVICE B Perform SERVICE B
in any state. additional maintenance, hit ENTER to
information. clear.
Yellow LED illuminated YELLOW Check the screen for Inspect Battery Inspect Battery, hit ENTER
in any state. additional to clear.
information.
Section 5 – Disassembly
Section 5.1 Major Disassembly .............................191
2013 Front Engine Access ....................................191
2017 HSB Front Access .......................................197
Major Disassembly ................................................201
Torque Specifications ...........................................207
Section 6 – Electrical Data
Section 6.1 0L6822-B WD/SD Air-cooled
2017 HSB Evolution 9 kW 60 Hz............................209
Section 6.2 0L6823-B WD/SD Air-cooled
2017 HSB Evolution 60 Hz .....................................215
Section 6.3 0L6824-B WD/SD Air-cooled
2017 HSB Evolution 50 Hz .....................................221
Section 6.4 0K2945-E WD/SD Air-cooled
Pre 2017 HSB Evolution 8 kW 60 Hz .....................227
Section 6.5 0J9961-D WD/SD Air-cooled
Pre 2016 HSB Evolution 11-22 kW 60 Hz..............233
Appendix A Controller Identification.......................239
Probing and Pin Extraction ...................................239
Evolution 1.0 Controller ........................................240
Nexus Controller ...................................................242
Appendix B EcoGen Drawings ................................249
Eco Gen Oil Make-Up System (6 kW) ..................249
Electrical Formulas ..................................................253
Specifications
Table 1-1. 60 Hz – Generator with Evolution Controller
Unit 8 kW 9 kW 11 kW 13 kW 14 kW 15 kW 16 kW 17 kW 20 kW 22 kW
Rated Voltage 240
Rated Max. Continuous
Load Current (Amps) 240 33.3/29.2 37.5/33.3 41.6/37.5 54.2/54.2 58.3/54.2 62.5/62.5 66.6/66.6 70.8/66.6 83.3/75.0 91.6/86.3
Volts (LP/NG)
Main Line Circuit Breaker 35 Amp 40 Amp 50 Amp 55 Amp 60 Amp 60 Amp 65 Amp 65 Amp 90 Amp 100 Amp
Main Line Circuit Breaker
35 Amp 40 Amp 50 Amp 55 Amp 60 Amp 60 Amp 70 Amp 70 Amp 100 Amp 100 Amp
(2017)
Phase 1
Rated AC Frequency 60 Hz
Battery Requirement Group 26R, 12 Volts and 525 CCA Minimum
Battery Requirement (2017) Group 26R, 12 Volts and 525 CCA Minimum or Group 35AGM, 12 Volts and 650 CCA Minimum
Steel/
Enclosure, Evolution Steel n/a Steel Steel Steel Steel Steel Aluminum Aluminum
Aluminum
Enclosure, Evolution (2017) Aluminum Steel Aluminum
This unit is tested in accordance to UL 2200 standards with an operating temperature of 20° F (-29° C) to 122°F. (50° C). For areas
Normal Operating Range where temperatures fall below 32° F (0° C), a cold weather kit is highly recommended. When operated above 77° F (25° C) there
may be a decrease in engine power. (Please reference the engine specifications section).
These generators are rated in accordance with UL 2200, Safety Standard for Stationary Engine Generator Assemblies and CSA-C22.2 No. 100-04 Standard for Motors
and Generators.
* Natural Gas ratings will depend on specific fuel Btu/joules content. Typical derates are between 10-20% off the LP gas rating.
** Circuits to be moved must be protected by same size breaker: For example, a 15 amp circuit in the main panel must be a 15 amp circuit in the transfer switch.
These generators are rated in accordance with UL 2200, Safety Standard for Stationary Engine Generator Assemblies and CSA-C22.2 No. 100-04 Standard for Motors
and Generators.
* Natural Gas ratings will depend on specific fuel Btu/joules content. Typical derates are between 10-20% off the LP gas rating.
** Circuits to be moved must be protected by same size breaker: For example, a 15 amp circuit in the main panel must be a 15 amp circuit in the transfer switch.
* Resistance values shown are based on new windings at 20 °C. Actual readings may vary based on type of meter used and any other components or connections
included in the circuit being tested.
* Resistance values shown are based on new windings at 20 °C. Actual readings may vary based on type of meter used and any other components or connections
included in the circuit being tested.
* 426 engine has a decompression system that will not allow full compression pressure while cranking. Can range from 60 to 110 psi.
IMPORTANT NOTE: All unit specifications are subject to change.
This unit is tested in accordance to UL 2200 standards with an operating temperature of 20° F (-29° C)
Normal Operating Range to 122°F. (50° C). For areas where temperatures fall below 32° F (0° C), a cold weather kit is highly
recommended. When operated above 77° F (25° C) there may be a decrease in engine power. (Please
reference the engine specifications section).
* Resistance values shown are based on new windings at 20 °C. Actual readings may vary based on type of meter used and any other components or connections
included in the circuit being tested.
Table 1-13. EcoGen™ with Nexus Controller - Stator Winding Resistance Values / Rotor Resistance
Power Windings: Across 11 & 22 0.2124 - 0.2468
Power Windings: Across 33 & 44 0.2124 - 0.2468
Sensing Windings: Across 11 & 44 0.4248 - 0.4936
Excitation Windings: Across 2 & 6 1.59 - 1.84
Rotor Resistance 10.81
6
Insulation Resistance
2
The insulation resistances of stator and rotor windings
are a measurement of the integrity of the insulating 4
material that separates the electrical windings from the 0
generator steel core. This resistance can degrade over 003004
time or due to such contaminates as dust, dirt, oil, grease Figure 1-1. Typical Stator Output Leads
and especially moisture. In most cases, failures of stator
and rotor windings are due to a break down in the To calculate the minimum acceptable Megohmmeter
insulation. In many cases, a low insulation resistance is readings use the following formula:
caused by moisture that collects while the generator is
shut down. When problems are caused by moisture Minimum Insulation Generator Rated Volts
buildup on the windings, this can usually be corrected by = +1
Resistance (In “Megohms”) 1000
drying the windings. Cleaning and drying the windings
can usually eliminate dirt and moisture that has built up in Example: Generator is rated at 120 VAC. Divide 120 by
the generator windings. 1000 to obtain 0.12. Then add 1 to obtain 1.12 megohms.
Minimum insulation resistance for a 120 VAC stator is
The Megohmmeter 1.12 megohms.
Introduction 120
+ 1 = 1.2 megohms
A Megohmmeter (often called a megger), consists of a 1000
meter calibrated in megohms and a power supply.
If the stator insulation resistance is less than the
IMPORTANT NOTE: When testing stators and rotors, calculated minimum resistance, clean and dry the stator.
set Megohmmeter to 500 volts and apply voltage for a Then, repeat the test. If resistance is still low, replace the
maximum of one second. Follow the Megohmmeter stator.
manufacturers instructions carefully. Do not exceed 500
Use the Megohmmeter to test for shorts between isolated
volts or apply voltage longer than 1 second.
windings as outlined in “Stator Insulation Tests.”
Megohmmeter HIGH voltages could cause damage to
other components on the generator. Take the proper
precautions before testing.
Up and Down
EDIT DEALER
The UP and DOWN triangle keys perform a number of 002463
functions depending on which screen of a menu is active.
Figure 1-4. Evolution Sub Menu
• Move to the next choice (the menu to be selected
will flash on and off). History
• Left and right arrows to move between the various The History Menu displays two history logs:
editable menus.
• Alarm Log: displays the last 50 alarm conditions.
• Increase or decrease a value or change a choice in They are in date and time order, numbered from 1
an editable menu (i.e. from Yes to No). to 50, with 1 being the most recent. Use the UP
and DOWN triangle keys to move from alarm to
alarm. Each alarm lists the date, time, and
description of the alarm.
• Run Log: displays the last 50 Run events. It will
display the date and time as well as a brief
description of the event; for instance Running –
Utility Lost; Stopped – Auto.
Use the UP and DOWN triangle keys to move from the Dealer
most recent Run event (1) to the oldest (50). The Dealer Menu displays three selections:
Maint • Display
The MAINT Menu displays three selections: Maint Log, • Dealer Edit
Run Hrs, and Scheduled. • Test
Selecting the Edit Menu enables editing of the following • Output Frequency (Hz)
selections: • Engine Speed (RPM)
• Language • Utility Input Volts
• Fuel Selection • Ambient Temperature (ºF)
• Cold Smart Start (firmware 1.14 and above) • V Firmware Hardware
• Current Date/Time • Bootloader EEPROM
• Exercise Time • Command
• Exercise Frequency • Node Hz Volts
• Firmware Update Use the UP and DOWN triangle keys to move between
selections.
Table 1-15. Cold Smart Start Parameters
Dealer Edit
Node 8 - 20 kW 22 kW
The Dealer Edit Menu displays these selections:
Cold Smart Start (2015-02) • Startup Delay
and Ambient Temp display X X
• Run Hours
screen
• Util Volts Low Value
Temperature Threshold 50 ºF 20 ºF
• Util Recovery Volts
Default Setting Yes Yes • Calibrate Current 1
Transfer Time Delay 30 sec 30 sec • Calibrate Current 2
• Calibrate Volts
Run Hrs • 2-Wire Start Select
View the amount of actual run hours on the unit. • Reset Maintenance
These are editable selections within this menu selection.
Scheduled
View when the next scheduled maintenance is due. Test
Provides four test tools integral to the control panel:
Maint Log
Inputs, Outputs, Display, and QT-Test.
Review the history of maintenance recorded on the unit.
• INPUTS displays the status of the 8 input channels
monitored by the control panel. See Table 1-16.
Evolution Dealer Menu Each input represents an open or closed set of
contacts, and will display either a “0” or “1”. A “0”
DEALER: DISPLAY represents an open contact. A “1” represents a
closed contact. This screen also displays Utility
Voltage.
DEALER EDIT TEST • OUTPUTS displays the status of the output relays
002468
Figure 1-9. Evolution Dealer Menu used by the control panel to initiate commands (like
ESC
Running Manual
Running-Utility Lost
Running-Remote Start ENTER SYSTEM DATE/TIME
Running-2 Wire Start
Running - Exercise
Switched Off Battery Condition ENTER
Stopped - Auto BATTERY SUB MENUS
Stopped - Alarm “Good” “Inspect Battery” or “Check Battery” ESC
ENTER ESC
ENTER ENTER
- 1 thru 50 + - Run Log + “Run Log” ENTER
ESC ESC HISTORY
- 1 thru 50 + - Alarm Log + “Alarm Log” ESC
ENTER ENTER
Warning Message(s)
DEALER
Charger Warning
Charger Missing AC ENTER
Low Battery
Battery Problem
Exercise Set Error
USB Warning
Language ENTER Language Language Language
Download Failure + + +
ESC
FIRMWARE ERROR-9 Å English Æ + English - - + Espanol - - + Francais -
Overload Cooldown
SEEPROM ABUSE
Fuel Warning ESC
Fuel Selection ENTER Fuel Selection
ESC
Å NG or LP Æ + NG or LP -
Alarm Message(s)
High Temperature
Low Oil Pressure ESC
Cold Smart Start? ENTER Cold Smart Start?
Overcrank
ESC
Overspeed Å YES or NO Æ - YES or NO +
Overvoltage
Undervoltage
Overload ESC ESC
Underspeed
RPM Sensor Loss Time ENTER Current Date/Time ENTER Select Month (1-12) ENTER
Controller Fault ESC
Å Manual or AUTO Æ Å 2/13/16 13:00 Æ - 2 +
Wiring Error
Stepper Overcurrent
FIRMWARE ERROR-7
ESC ESC
Overload Remove Load
Low Volts Remove Load Exercise Time ENTER Select Frequency ENTER Quiet Test Mode ? ENTER
Stepper Over Current ESC
Å 14:00 Wednesday Æ - WEEKLY + - YES or NO +
Fuse Problem*
- BIWEEKLY +
- MONTHLY + Quiet Test Mode only
*“Fuse Problem” on Firmware on certain models
1.11 and older ONLY
ESC
ENTER
DOWN ARROW = -
Run Hours (H)
0.0
ESC ENTER
ENTER
Maint. Log Scheduled
- 1 thru 50 + EXAMPLE:
"Battery Maintained" Inspect Battery 200 RnHr or 12/27/13
"Schedule A Serviced"
and
+ Language + "Schedule B Serviced"
Next Maintenance 200 RnHr or 12/27/13
"Maintenance Reset"
- + Portuguese -
"Inspect Battery"
"Service Schedule A"
"Service Schedule B"
Select “Yes” then Press “Enter” to continue or Press “ESCAPE” to escape out of updating.
During update process the Blue “Manual” light flashes, then the Green “Auto” light flashes.
Sequence does this twice. When update is complete the unit returns to Install Wizard menu.
When the controller powers up the very first screen displays the version number for a few seconds.
When update is complete remove Thumb Drive, then follow the Install Wizard Menu.
Select Date (1-31) ENTER Select Year (0-99) ENTER Select Hour (0-23) ENTER Select Min (0-59)
- 13 + - 16 + - 13 + - 0 +
Possible Message(s)
Corrupted File "Current:V XXXX " ENTER "Are You Sure?"
Invalid File
File Not Found "USB: V XXXX" ESC "- Yes or No +"
Unsupported Device 005615
Power Up Unit
FIRMWARE V 1.01
Use UP and DOWN arrows to select fuel type then press “ENTER”
HARDWARE V 1.05
ENTER
Activated Unit
ESC
Cold Smart Start? ENTER Cold Smart Start?
Å YES or NO Æ - YES or NO +
To activate go to
www.activategen.com
Note: If language was previously
programmed this goes directly to
“Select Hour”
Language + Language + L
Serial 1234567890
PASSCODE xxxxx + _______ - - + English - - +
ENTER
Use up and down arrows to change selection 0 Defaults to
thru 9. Press "Enter" to acccept selection and English if not
to move to the next digit. If passcode is correct selected.
goes to "Install Wizard." If not correct goes to
the message below.
Select Hour (0-23) ENTER Select Min (0-59) ENTER
- 14 + - 0 +
Wrong Passcode
* *
Try Again * Holding the Up or Down arrow
button for 2 seconds will speed dial
through the selections
Select F
“NOT ACTIVATED!” Install Wizard ENTER Quiet Test Mode ? ENTER
- WEE
Hours of Protection
Set Exercise - YES or NO + - BIWE
0 (H)
- MON
UP ARROW = +
DOWN ARROW = -
ESC
ENTER Select Month (1-12) ENTER Select Date (1-31) ENTER Select Year (0-99)
- 2 + - 13 + - 13 +
* * *
Select Frequency
ENTER Select Hour (0-23) ENTER Select Min (0-59) ENTER Select Day
- WEEKLY +
- BIWEEKLY + - 14 + - 0 + - Wednesday +
- MONTHLY +
* * *
000429
ESC
ENTER ESC
HISTORY MAIN
EDIT DEALER
ENTER
- Language +
ESC
English
Fuel Selection
ESC
NG or LP
Possible Message(s)
"Corrupted File"
"Invalid File"
EXERCISE TIME "File Not Found"
ESC "Unsupported Device"
14:00 Wednesday
"Insert USB"
Firmware Update
System not in the OFF position
Disabled Press OFF
UP ARROW = +
DOWN ARROW = -
000430
* 50 Hz Display
HISTORY MAINT
*
ENTER ESC
Util Recovery Volts Util Recovery Volts
ESC
Å 190 - 216 Æ Å 175 - 198 Æ
* DEALER:
ENTER
Calibrate Current1 DEALER EDIT
Current 0.0
ESC
Å 1186 - 1780 Æ Å 1640 Æ
*
Calibrate Current 1, Calibrate Current 2,
Calibrate Current2 Current 0.0 Calibrate Volts. Special note: Press Enter
ESC to modify use the Up and Down arrows to
Å 1186 - 1780 Æ Å 1640 Æ make the change. Pressing Enter or ESC
* saves the changes. This is different from all
the others under Dealer Edit.
Calibrate Volts Calibrate Volts
ESC
Å 750 - 1280 Æ Å 1120 Æ
*
ENTER
(Performs Segment
2 Wire Start Select test of the display)
ESC
ESC
Å No or Yes Æ EcoGen Only
* Off Grid Mode
Yes or No
Reset Maintenance
ESC
Å No or Yes Æ UP ARROW = +
*
DOWN ARROW = -
“Battery Voltage”
ESC
0 - 13.7
“Charging Status”
ESC
“Charging” or “Not Charging”
Output Volts”
ESC
0
DISPLAY
Utility Input Volts
ESC
T TEST 0
FIRMWARE V 1.01
ESC
HARDWARE V 1.05
OUTPUTS:Gen. 0 V
ESC
0 0 0 0 0 0 0 0
Commands:
Bootloader V0.2
ESC “Running Manual”
EEPROM V1.01
To Test Displays “Running - Utility Loss”
ESC
Press Enter “Running - Remote Start”
COMMAND:
ESC “Running - 2-wire Start”
Switched Off
“Running - Exercise”
IN AUTO PRESS
ESC “Switched Off”
ENTER FOR QT-TEST
Node Hz Volts “Stopped - Auto”
ESC
15 KW 60 120/240 “Stopped - Alarm”
ENTER ESC or ENTER
PRESS ENTER TO Note: Units equipped with Quiet Test only. Unit
ESC
STOP Quiet Test must be in AUTO and have Utility available in order
to view this screen and test the Quiet Test function.
000431
003047
Figure 1-23. Alarm Log Display
There are four selections in the Main Menu: History, The Status Menu displays four choices: State, Display,
Status, Edit, and Debug. Command, and Versions. Use the up and down triangle
keys to move:
• State displays the current state of the panel along
with the current date, time and day. See Figure 1-
30 for the complete list of possible Status
messages which will be displayed.
003044 • Display provides up to five generator parameters:
Figure 1-21. Nexus Display Main Menu Run Hours, RPM, Hz, Battery, and Hours Under
Load (if enabled)
– Run Hours displays the total number of hours Generator starts and transfers. It is adjustable from
the generator has run (in 0.0 Hours format). 10 to 30 seconds.
– RPM displays the engine speed (in RPM). • Reset Maintenance will reset the Maintenance
– Hz displays the generator output frequency (in warning clock.
0.0 Hz format).
Debug
– Battery displays the battery voltage (i.e. 12.9).
Provides four test tools integral to the control panel:
– Hours Under Load displays the total number Inputs, Outputs, Display, and QT-Test.
of hours the unit has actually provided power.
• TEST Inputs displays the status of the 8 input
• Command displays the current command. See channels that the control panel monitors. See
Figure 1-30 for the list of possible commands Table 1-17. Each input represents an open or
which will be displayed. closed set of contacts, and will display either a “0”
• Versions displays the version of Software and or “1”. A “0” represents an open contact. A “1”
Hardware of the panel. represents a closed contact.
003061 003069
Figure 1-25. Nexus Status Menu Figure 1-27. Nexus Test Inputs Display
NOTE: For the unit to perform an actual weekly Quiet 1 Not Used Not Used
Test Exercise, it must be enabled in the Exercise Time
2 Low Oil Pressure Not Used
editing menu.
3 High Temperature Not Used
8 Manual Transfer
RESET
ALARM LOG RUN LOG STATE DISPLAY COMMAND VERSIONS MAINTENANCE
INPUTS OUTPUTS DISPLAYS QT TEST
EXERCISE If so equipped
ESC SOFTWARE
TIME
HARDWARE
Section 1.4 Nexus Menu System Navigation
Nexus Units A
A C
E
B
F
D G
C I
E H
F
G
K H J
I
003083
A. Evolution Controller F. Field Boost Diode
J
B. Field Excitation Ground Wire 0 G. 12 VDC
C. +VDC Gated Variable Wire 4 H. Wire 4A
L D. Rotor I. Field Boost Relay
003084 E. Wire 4 J. 12 VDC
A. Nexus Controller G. 12 VDC Wire 13 Figure 2-2. Evolution Field Boost Circuit
B. Field Excitation Ground Wire 0 H. Wire 56
C. +VDC Gated Variable Wire 4 I. To Starter
D. Rotor J. Starter Contactor Operation
E. Wire 4 K. Crank Relay
F. Field Boost Diode L. 12 VDC Engine Cranking
Figure 2-1. Nexus Field Boost Circuit See Figure 2-3. When the engine is cranking (Evolution
2200 rpm), field boost voltage causes the rotor to
Evolution Units magnetize. The rotor magnetic field induces a voltage
into the stator AC power windings, and the stator
Evolution units have a dedicated field flash relay with
excitation (DPE) windings. During cranking, field boost
logic that is separate from the start circuit. Depending on
magnetism is capable of creating approximately one-half
the firmware version, the field flash will turn on and off
the unit’s rated voltage.
depending on engine speed and system voltage.
Firmware versions up to 1.11 – Field boost turns on at
2200 rpm. Field boost shuts off after 10 seconds, or when
voltage is 88 VAC, whichever comes first.
E F
003085
100 VAC
A. To Load F. Rotor
STATOR
B. Main Line Circuit Breaker G. Field Boost Circuit
C. Stator Power Winding H. Voltage Regulator
D. Magnetic Field I. Stator Excitation Winding
E. Engine - Direct drive
Field Excitation
AC voltage from the DPE winding provides power to the
MAGNETIC FIELD
AVR. The AVR gates and converts AC voltage to DC 002476
voltage, and provides regulated variable DC voltage to Figure 2-4. Low Field Excitation Voltage =
the rotor through Wires 4 and 0. When the starter Low Magnetic Lines of Flux = Low AC Output
disengages (cranking stopped), the AVR continues to
provide excitation voltage to the rotor.
The AVR senses the AC output voltage through Sensing
Wires 11 and 44 (11S & 44S for Evolution), which are
connected to the main power leads (11 and 44) in the
stator windings. The AVR will continue to increase
excitation voltage to the rotor until the desired AC output
voltage is reached. It will continue to regulate excitation 200 VAC
voltage as necessary to provide a constant AC output
voltage to the load. STATOR
concentrated the lines of flux around the rotor, which cut 002477
Figure 2-5. Increased Field Excitation Voltage =
across the stationary stator windings, the greater the
Increased Magnetic Lines of Flux =
voltage induced into the stator.
Increased AC Output Voltage
MLCB
240 VAC
44S Sensing
Evolution
Controller
44 Neutral 11 11S Sensing
33 22
Field Boost
Diode
Rotor
4
Brushes
4 DC Field Excitation
MLCB
240 VAC
44 Sensing
Nexus
Controller
44 Neutral 11 11 Sensing
33 22
To Starter
120 VAC 120 VAC Contactor
Field Boost
Diode
Rotor
4
Brushes
4 DC Field Excitation
Overloaded
Overload Check for Overloaded
ALARM 2103 Unit has run and attempted to accept load 10 times, could not accept due to
Remove Load condition on unit
overload condition
Introduction Procedure
Use the “Flow Charts” in conjunction with the detailed 1. Set the Main Line Circuit Breaker (MLCB) to the
instructions in Section 2.3, Diagnostic Tests . Test CLOSED (ON) position.
numbers and/or verbiage used in the flow charts 2. Disconnect and isolate Wire 23 (from ground) in
correspond to the numbered tests and/or verbiage in the customer connection area of the generator or
Section 2.3. the transfer switch to ensure that the generator
The first step in using the flow charts is to identify the correct DOES NOT transfer power to the load (structure)
problem on the following pages. For best results, perform all during testing.
tests in the exact sequence shown in the flow charts. 3. Navigate to the voltage display using the dealer
menu map for the controller.
4. Set the controller to MANUAL. Allow generator to
Preliminary Output Voltage Test start and stabilize.
(Evolution Only, Non-Synergy, Firmware 5. Visually monitor the output volts displayed on the
v1.12 and Above) controller. Record the value indicated.
When an Alarm of the 1900 group (Undervoltage) is 6. Set the digital multimeter (DMM) to measure AC
displayed on the controller, certain tests need to be voltage.
performed to determine the actual fault. With firmware 7. Connect one meter test lead to Wire 11 and the
v1.12 and above, up to four minutes (in Manual Mode) is other meter test lead to Wire 44 at the load side of
now available to measure output voltage before shutting the MLCB.
down on “Under Voltage”. Measuring output voltage as 8. Measure and record the voltage indicated on the
described in this test will help determine the next step in DMM.
troubleshooting. Refer to Table 2-1.
When measuring output voltage, it is important to look at Measured Voltage Output at MLCB: __________
the output voltage displayed on the control panel as well 9. Shut the unit down by pressing the OFF button on
as measuring actual output voltage of the generator. the controller.
NOTE: If the unit enters a shutdown during this 10. Connect Wire 23.
procedure, acknowledge the alarm by pressing the OFF
button and then ENTER. Restart unit if necessary to
complete the test.
TEST FB2 -
BAD EVOLUTION TEST WIRE 4A
PROBLEM 1, TEST 4 –
PERFORM FIXED BAD
EXCITATION / ROTOR NEXUS
GOOD
AMP DRAW
PROBLEM 1, TEST 4 –
PERFORM FIXED
TEST FB4 - TEST FB3 - DIODE EXCITATION / ROTOR
GOOD DIODE TEST TEST EVOLUTION AMP DRAW
NEXUS
REPLACE CONTROLLER
003106
IMPORTANT NOTE: Clear any faults in the controller before proceeding with any running diagnostic steps!
NOTE: Perform FBCT “Field Boost Circuit Test” PRIOR to performing Test 4. After performing “Field Boost Circuit Test”
in it's entirety, compare the results with the “Test 4 Results Table” to determine letter code result A through H on this
page and the next.
B D
REPLACE CONTROLLER
Check GENservice bulletins on
C
IF NEXUS CONTROLLER-
controller replacement.
UTILIZE APPENDIX B CHECK
DMM
FUSES
TEST 8 –
TEST 6 – TEST
TEST 5 – TEST RESISTANCE GOOD
EXCITATION
SENSING CIRCUIT CHECK OF
WINDING CIRCUIT
WIRES 11 AND 44 ROTOR CIRCUIT
2 AND 6
BAD
GOOD GOOD
ROTOR CIRCUIT
FAILURE
BAD
REPAIR
OR TEST 7 – TEST
REPLACE STATOR TEST 9 –
GOOD REPAIR CHECK
OR BAD
BRUSHES &
REPLACE
SLIP RINGS
BAD PERFORM
STATOR GOOD
INSULATION BAD
RESISTANCE
TEST 10 –
BAD TEST ROTOR
ASSEMBLY
REPLACE TEST 10 –
STATOR GOOD TEST ROTOR
ASSEMBLY TEST 7 – TEST GOOD
ONLY GOOD
STATOR
003107
IMPORTANT NOTE: Clear any faults in the controller before proceeding with any running diagnostic steps!
TEST 4 – PERFORM
E FIXED EXCITATION / F TEST 7 –
TEST STATOR
BAD
ROTOR AMP DRAW
GOOD
H
PERFORM
TEST 10 –
STATOR
TEST ROTOR
INSULATION
ASSEMBLY BAD
RESISTANCE
GOOD
TEST 7 – TEST 10 –
TEST STATOR TEST ROTOR
PERFORM ROTOR ASSEMBLY
INSULATION
RESISTANCE TEST GOOD BAD
SECTION 1.2 BAD GOOD
FREQUENCY AND
VOLTAGE O.K.
VOLTAGE OUTPUT
REFER TO AT BREAKER IS
PROBLEM 1 BELOW 220 OR
ABOVE 270 VOLTS
FREQUENCY O.K.,
BUT VOLTAGE STOP
INCORRECT TESTS
VOLTAGE
TEST 3 -
OUTPUT AT
CALIBRATE
BREAKER IS
VOLTAGE
BETWEEN
003109
220-270 VAC
IMPORTANT NOTE: Clear any faults in the controller before proceeding with any running diagnostic steps!
Problem 3 – Voltage and Frequency Drop Excessively When Loads Are Applied
GOOD OVERLOADED
TEST 12 - CHECK
DISCONTINUE REDUCE LOADS TO UNIT’S
STEPPER MOTOR
TESTING RATED CAPACITY
CONTROL GOOD
BAD
REPAIR OR REPLACE
TEST 16 - CHECK
ENGINE CONDITION
GOOD
GO TO “PROBLEM 18 -
TEST 7 - CHECK ENGINE ENGINE STARTS HARD
LOOK FOR A SHORTED CONDITION
GOOD STATOR AC CONDITION AND RUNS
IN A CONNECTED LOAD OR IN ONE
POWER WINDINGS GOOD ROUGH/LACKS POWER”
OF THE LOAD CIRCUITS
SECTION 4.5
BAD
REPAIR OR REPLACE 003110
TEST 1 – CHECK
AC OUTPUT ERRATIC PROCEED TO PROBLEM 3
VOLTAGE
HIGH TEST 3 -
OR CALIBRATE
LOW VOLTAGE
003111
IMPORTANT NOTE: Clear any faults in the controller before proceeding with any running diagnostic steps!
Safety
Service personnel who work on this equipment should be
aware of the dangers of such equipment. Extremely high
and dangerous voltages are present that can kill or cause
serious injury. Gaseous fuels are highly explosive and
can ignite by the slightest spark. Engine exhaust gases
contain deadly carbon monoxide gas that can cause
unconsciousness or even death. Contact with moving
parts can cause serious injury. The list of hazards is
seemingly endless.
When working on this equipment, use common sense
and remain alert at all times. Never work on this
equipment while you are physically or mentally fatigued.
If you do not understand a component, device or system,
do not work on it.
Test 1 – Check AC Output Voltage NOTE: “Residual” voltage may be defined as the voltage
produced by rotor residual magnetism alone. The amount
General Theory of voltage induced into the stator AC power windings by
residual voltage alone will be approximately 2 to 16 VAC,
Use a DMM to check the generators output voltage. Test depending on the characteristics of the specific generator.
output voltages at the unit’s main circuit breaker (MLCB) If a unit is supplying residual voltage only, either excitation
terminals. Refer to the unit’s Data Plate for rated line-to- current is not reaching the rotor or the rotor windings are
line and line-to-neutral voltages. open and the excitation current cannot pass. On current
units with air-cooled engines, “field boost” current flow is
DANGER available to the rotor after the engine reaches 2200 rpm.
Electrocution. High voltage is present at
test terminals. Contact with live terminals Test 3 – Calibrate Voltage
will result in death or serious injury.
(000311) General Theory
IMPORTANT NOTE: The generator will be running. When voltage output is too high or too low, it is possible
Connect meter test clamps to the high voltage terminals to adjust voltage output of the generator. To access this
while the generator is shut down. Stay clear of power menu a password will be required to be entered into
terminals during the test. Make sure the meter clamps controller.
are securely attached and will not shake loose.
NOTE: Replacement controllers must be checked but
Procedure typically do not require calibration unless output is not
within the specifications. (Refer to the unit data decal and
1. Set the DMM to measure AC voltage. to the Specifications section in the front of this manual.)
2. See Figure 2-8. With the engine shut down,
connect the meter test leads across the load Procedure
terminals of the generator MLCB. This will 1. Set DMM to measure AC voltage.
measure line-to-line voltage. 2. Open the Main Line Circuit Breaker (MLCB) on the
generator.
3. Using appropriate back probes, measure output
voltage at the AVR connector (Wires 11S and 44S).
4. On the controller, press the ESC key until the main
menu is present. (Refer to the Menu Navigation
found in Section 1.10)
5. While at this screen proceed to enter the
appropriate password:
For Evolution:
UP, UP, ESC, DOWN, UP, ESC, UP, ENTER
Figure 2-8. MLCB Test Points For Nexus:
ESC, UP, UP, ESC, DOWN, UP, ESC, UP, UP, ENTER
3. Set the MLCB to the “Open” position. Verify that all 6. After the password has been entered, proceed to
electrical loads are disconnected from the the EDIT menu for Nexus controller, or to DEALER
generator. EDIT for Evolution controller.
4. Set the controller to MANUAL. 7. Press the down arrow key until the screen
indicates CALIBRATE VOLTAGE and press
NOTE: AC under and over-voltage shut downs have a ENTER.
10 second delay.
8. After pressing enter, a value will appear on the
5. Set the MLCB to the “Closed” position. Measure screen.
and record the voltage. NOTE: The default setting from the factory for calibration
6. Set the controller to OFF. is 1024. The Evolution controller is adjustable from 750-
1280.The Nexus controller is adjustable from 700-1300.
Results
Calibration factor must NOT be adjusted below 990 or
1. If the DMM indicated approximately 240-244 VAC, above 1040. Adjusting outside of this window could result
the output voltage is good. in damage to the generator.
2. If the DMM indicated any other readings the 9. Set controller to MANUAL.
voltage is bad. Refer back to the flow chart.
Table 2-9. TEST 4 Results – Fixed Excitation Test/Rotor Amp Draw Test (8-20 kW)
Results: Size A B C D E F G H
Voltage Results Above 50 Above 50 Below 50 Zero or Below 50 Below 50 Above 50 Below 50
ALL
Wire 2 & 6 VAC VAC VAC Residual Volts VAC VAC VAC VAC
Voltage Results Above 50 Below 50 Above 50 Zero or Below 50 Below 50 Above 50 Below 50
ALL
Wire 11 & 44 VAC VAC VAC Residual Volts VAC VAC VAC VAC
Static Rotor Amp 14 kW 1.46-1.70 1.46-1.70 1.46-1.70 Zero Current Above 2.3A 1.46-1.70 Zero Current 1.46-1.70
Draw 15 kW 1.33-1.54 1.33-1.54 1.33-1.54 Draw Above 2.3A 1.33-1.54 Draw 1.33-1.54
16 kW 1.33-1.54 1.33-1.54 1.33-1.54 Above 2.3A 1.33-1.54 1.33-1.54
17 kW 1.33-1.54 1.33-1.54 1.33-1.54 Above 2.3A 1.33-1.54 1.33-1.54
20 kW 1.16-1.36 1.16-1.36 1.16-1.36 Above 2.0A 1.16-1.36 1.16-1.36
22 kW 1.00-1.17 1.00-1.17 1.00-1.17 Above 2.0A 1.00-1.17 1.00-1.17
8 kW 1.76-2.05 1.76-2.05 1.76-2.05 Above 2.5A 1.76-2.05
10 kW 1.76-2.05 1.76-2.05 1.76-2.05 Above 2.5A 1.76-2.05
11 kW 1.76-2.05 1.76-2.05 1.76-2.05 Above 2.5A 1.76-2.05
12 kW 1.46-1.70 1.46-1.70 1.46-1.70 Above 2.3A 1.46-1.70
Running Rotor 14 kW 1.46-1.70 1.46-1.70 1.46-1.70 Zero Current Above 2.3A 1.46-1.70 Zero Current
Above 2.5A
Amp Draw 15 kW 1.33-1.54 1.33-1.54 1.33-1.54 Draw Above 2.3A 1.33-1.54 Draw
1.09 DC
Amps
Battery
Wire 4 In Appropriate
Wire Harness
12.9 VDC
0 1.09 A 11.83W
56/4A 003126
Figure 2-11. Rotor Amp Draw Test
NOTE: To calculate rotor amp draw take the battery voltage applied, divided by the actual resistance reading of the
rotor. Rotor resistance can be measured between Wires 4 and 0 in the appropriate harness.
Test 5 – Test Sensing Circuit Wires NOTE: Stator winding resistance values are very low
11(S) and 44(S) and some meters will not read such a low resistance, and
will simply indicate different ranges of resistance. The
General Theory manufacturer recommends a high quality digital type
meter capable of reading a very low resistance.
The voltage regulator (internal to the controller) requires a
reference voltage in order to regulate at a specific voltage 5. Connect one meter test lead to the appropriate
and to recognize if the alternator is producing voltage. The harness pin for Wire 11 on Nexus, or 11S on
alternator may be producing voltage, but if the voltage Evolution. Connect the other meter test lead to the
regulator cannot sense the voltage, it will fault out for under- NEUTRAL connection. Measure and record the
voltage. This test will verify the integrity of the sensing resistance.
circuit. 6. Connect one meter test lead to the appropriate
harness pin for Wire 44 on Nexus or 44S on
Required Tools Evolution. Connect the other meter test lead to the
• Meter test leads capable of measuring voltage NEUTRAL connection. Measure and record the
inside a connector without damaging the socket. A resistance.
set of Black and Red test leads for this application a. If the meter indicated a resistance value of less
are available from the manufacturer. Contact your than 0.2 ohms in Steps 5 and 6, stop testing
nearest servicing dealer for more information. See and refer back to the flow chart (Good).
Figure 2-9. b. If the meter indicated OPEN in Steps 5 or 6,
NOTE: It is not recommended to use any testing device proceed to Step 7.
other than the manufacturer's approved test lead adapters. 7. See Figure 2-12. Disconnect the lower bulkhead
C1 connector (if unit is equipped.)
Procedure 8. Connect one meter test lead to C1 (if unit is
1. Remove the 7.5 amp fuse from the control panel. equipped) to the appropriate harness pin with Wire
2. Remove the controller and the cover to expose the 11. Connect the other meter test lead to the
NEUTRAL connection, measure and record the
lower harness connections.
resistance.
3. Disconnect the appropriate harness connector
9. Connect one meter test lead to C1 (if unit is
from the controller.
equipped) to the appropriate harness pin for Wire 44.
4. Set the DMM to measure resistance. Connect the other meter test lead to the NEUTRAL
connection. Measure and record the resistance.
Procedure
1. Remove the 7.5 amp fuse from the control panel.
2. Expose the controller lower harness connections
by removing the controller mounting hardware.
3. Disconnect the harness connector containing
Wires 2 and 6 from the controller.
4. Set the DMM to measure resistance.
5. Connect one meter test lead to the harness pin for
Wire 2 and the other meter test lead to the harness
pin for Wire 6. Measure and record the resistance.
a. If the meter indicated a resistance value
Figure 2-12. C1 Connector (if unit is equipped) consistent with the values found in Section 1.1
Specifications, stop testing and refer back to
Results the flow chart (Good).
1. If the meter indicated a resistance value of less b. If the meter indicated an OPEN, proceed to
than 0.2 ohms in Steps 5 through 9, refer back to Step 6.
flow chart (Good).
6. See Figure 2-13 and Figure 2-14. Disconnect the
2. If the meter indicated a resistance value of OPEN lower bulkhead C1 connector (if unit is equipped).
in Step 5 and a value less than 0.2 ohms in Step 8, On Evolution units locate the STR connector and
repair or replace Wire 11 between the controller disconnect.
and the C1 connector (if unit is equipped). 7. On the harness connector (disconnected in Step 6)
3. If the meter indicated a resistance value of OPEN that leads to the stator, connect one meter test lead
in Step 6 and a value less than 0.2 ohms in Step 9, to Wire 2 and the other meter test lead to Wire 6.
repair or replace Wire 44 between the controller Measure and record the resistance.
and the C1 connector (if unit is equipped, see
Figure 2-12). Results
4. If the meter indicated OPEN in either Step 8 or Step 1. If the meter indicated a resistance value consistent
9, proceed to Test 7 – Test the Stator with a with the values found in the table in the front of the
DMM. manual, stop testing and refer back to the flow
chart (Good).
Test 6 – Test Excitation Winding 2. If the meter indicated a resistance value of OPEN
Circuit 2 and 6 in Step 5, but a resistance value consistent with the
values found in the table in the front of the manual
General Theory in Step 7, repair or replace Wire 2 and/or 6
between the controller and the connector (C1
The voltage regulator (internal to the controller) requires
Connector on Nexus, STR Connector on
unregulated voltage from the stator in order to supply
Evolution). Measure Ohms between Wire 2 and 2,
excitation power to the regulator. The regulator supplies
or Wire 6 and 6 to confirm which wire is open.
DC field excitation current to the rotor. The alternator may
be producing this voltage, but if the voltage is not being 3. If the meter indicated a resistance value of OPEN
supplied to the regulator, it will fault out for under-voltage. or a resistance value inconsistent with the values
This test will verify the integrity of the Excitation (DPE) found in the table in the front of the manual in Step
winding inside the stator and connections to the voltage 5 and Step 7, replace the stator.
regulator.
Test 7 – Test the Stator with a DMM
Required Tools
• Meter test leads capable of measuring voltage General Theory
inside a connector without damaging the socket. A This test will use a digital multimeter (DMM) to test the
set of Black and Red test leads for this application stator windings for the following faults:
are available from the manufacturer. Contact your
• An OPEN circuit condition
nearest servicing dealer for more information. See
Figure 2-9. • A “short-to-ground” condition
• A short circuit between windings
NOTE: It is not recommended to use any testing device
other than the manufacturer's approved test lead adapters. Table 2-13 has been provided to record the results of the
following procedure. These results may be required when
requesting factory support.
C1 Pin 1 Wire 44 Ground 5. Connect one meter test lead to the appropriate
harness pin for Wire 4 and connect the other meter
C1 Pin 2 Wire 11 Ground test lead to the appropriate harness pin for Wire 0.
Measure and record the resistance.
C1 Pin 4 Wire 2 Ground
6. Connect one meter test lead to the appropriate
Shorted Condition harness pin for Wire 4 and connect the other meter
test lead to a ground connection. Measure and
C1 Pin 4 Wire 2 C1 Pin 2 Wire 11
record the resistance.
C1 Pin 4 Wire 2 C1 Pin 1 Wire 44 a. If the meter indicated the correct rotor
resistance values as stated in the front of the
C1 Pin 4 Wire 2 Stator Lead Wire 11
manual, proceed to Step 9.
C1 Pin 4 Wire 2 Stator Lead Wire 44 b. If the meter indicated INFINITY, proceed to
Step 7.
Stator Lead Wire 11 C1 Pin 1 Wire 44
7. If testing C1 Configuration A (if unit is equipped),
Stator Lead Wire 11 Stator Lead Wire 44 locate and disconnect the bulkhead C1 connector.
If testing C1 Configuration B (if unit is equipped),
stop test and refer to Test 8 Results.
NOTE: Read Section 1.2, Testing, Cleaning and
Drying carefully. If the winding tests good, perform the 8. Connect one meter test lead to C1 (if unit is
insulation resistance test. If the winding fails the equipped) to the appropriate harness pin for Wire 4
and connect the other meter test lead to C1 (if unit
insulation resistance test (using a Megohmmeter), clean
is equipped) to the appropriate harness pin for
and dry the stator as outlined in Section 1.2 Testing,
Wire 0. Measure and record the resistance. If the
Cleaning and Drying. Then, repeat the insulation meter indicated INFINITY, stop testing and refer
resistance test. If the winding fails the second resistance back to flow chart (Rotor Circuit Failure).
test (after cleaning and drying), replace the stator
9. Locate the starter contactor relay (SCR) and
assembly. disconnect Wire 56 (blue wire).
NOTE: These results may be needed when requesting 10. Disconnect the harness connector from the
factory support. controller.
NOTE: Stator winding resistance values are very low. 11. Connect one meter test lead to the disconnected
Some meters will not read such a low resistance, and will Wire 56 and connect the other meter test lead to
the appropriate harness pin for Wire 4. Measure
simply indicate CONTINUITY. The manufacturer
and record the resistance.
recommends a high quality digital type meter capable of
reading a very low resistance.
46 Diagnostic Repair Manual
Section 2.3 Diagnostic Tests
• If the DMM indicated CONTINUITY, refer back to Terminals of the generator main line circuit breaker
flow chart. (MLCB).
2. Set the controller to MANUAL.
Results 3. Let engine stabilize. Measure and record the
1. Repair, replace, or reconnect wires as necessary. frequency.
2. Replace any damaged slip rings or brush holder. Results
3. Clean and polish slip rings as required.
1. If the meter indicated 59-61 Hertz, refer back to
flow chart.
Test 10 – Test Rotor Assembly 2. If the meter indicated a value outside the accepted
range, refer back to flow chart.
General Theory
A rotor having open windings will cause loss of excitation Test 12 – Check Stepper Motor Control
current flow and as a result generator AC output voltage
will drop to “residual” voltage. A “shorted” rotor winding Procedure: V-Twin and Single Cylinder
can result in a low voltage condition.
NOTE: For Nexus units follow only Steps 1-3 and 7-10.
Procedure 1. Remove air cleaner cover to access stepper motor
1. Remove the brush assembly from the slip rings to and/or visually see throttle plates.
prevent interaction. 2. Physically move the throttle and verify the stepper
2. Set a DMM to measure resistance. motor, linkage and throttle do not bind in any way. If
any binding is felt repair or replace components as
3. Connect one meter test lead to the positive slip ring
needed. The stepper motor will have resistance as
(nearest the rotor bearing) and the common test
it moves through its travel.
lead to the negative slip ring, measure and record
the resistance. 3. Physically and visually move the throttle to the
closed position by pulling the Stepper motor arm
4. Connect one meter test lead to the positive slip ring
towards the idle stop. See Figure 2-16, Figure 2-
and connect the other meter test lead to a ground
17, Figure 2-18, and Figure 2-19 for Evolution
connection. Measure and record the resistance.
units. See Figure 2-20, Figure 2-21, and Figure 2-
22 for Nexus units.
Results
4. Set the controller to MANUAL.
1. Compare the resistance measured in Step 3 with
Section 1.1 Specifications. Replace rotor as 5. Observe and record the stepper motor movement.
required. a. On Nexus units, it should open.
2. If the DMM indicated CONTINUITY in Step 4, b. On Evolution units the stepper motor will cycle
replace the rotor assembly. the mixer to a full open throttle position (which
opens both venturis), back to a closed position
and then to the starting position, which is a
Test 11 – Check AC Output Frequency slight opening of the throttle in the small venturi.
General Theory 6. Set the controller to OFF.
7. Physically move the throttle to the open position by
Generator AC frequency is proportional to the operating
pulling the stepper motor arm away from the idle stop.
speed of the rotor. The 2-pole rotor will supply a 60 Hertz
AC frequency at 3600 rpm. 8. Set the controller to MANUAL.
9. Observe and record the stepper motor movement.
NOTE: Engine Speed is in direct correlation to frequency
(Hertz). The controller monitors Wire 18 to maintain 10. Set the controller to OFF.
proper frequency. 11. If no movement was seen in Steps 5 or 9 remove
the controller and verify the six pin connector on
Tools Required the controller is seated properly. Remove the
• A meter that is capable of measuring AC connector and then connect it and test again. If
frequency. problems persist, proceed to Step 12.
Procedure
1. See Figure 2-8. Connect an accurate AC
frequency meter across the Wires 11 and 44
Figure 2-16. Evolution Stepper Motor Starting Figure 2-19. Evolution Stepper Motor Mid-point =
Position and/or Mid-point Starting Point, Smaller Venturi Partially Open
Procedure
1. Set a DMM to measure AC voltage.
2. Connect an accurate AC frequency meter and an
AC voltmeter across the stator AC power winding
leads.
3. Start the engine. Let it stabilize and warm-up.
4. Apply electrical loads to the generator equal to the
rated capacity of the unit. Measure and record the
frequency and the voltage.
underpowered engine can be the result of a dirty air generator and load bank to cool before shutting
cleaner, loss of engine compression, faulty fuel settings, down.
or incorrect ignition timing, etc. A decrease in available
horsepower will proportionally lead to a decrease in kW. Results
Procedure
1. Connect a load bank to the output circuit of the
generator. This should be done at the generator's
MLCB.
2. Place the Amp meter over the circuit being
checked. CT1 “Current Calibration1” – Wire 11 and
CT2 “Current Calibration2” – Wire 44.
3. Start the generator and allow it to warm up for 10
seconds.
4. Place a load on the generator that matches the
rated output of the generator.
5. Select the correct Current Calibration display menu
under the Dealer Edit menu.
6. Press ENTER to view generator output and the
calibration value of that CT.
7. Adjust up or down the generator display to match
the Amp meter’s calibrated reading. (Use the
controllers UP and DOWN arrows to make
adjustments)
8. Once the display panel reading matches the amp
meter, press the ENTER button to save the new
calibration. Repeat the process for CT2 Current
Calibrations.
9. When both calibration adjustments are correct,
remove the load from the generator and allow the
Enclosure 002489
The transfer switch enclosure is either a National Figure 3-2. Load Connected to Standby Power Source
Electrical Manufacturer’s Association (NEMA) Type 1 or
a Type 3R. Based on NEMA Standard 250, the following Utility Closing Coil C1
standard applies: See Figure 3-3. The utility closing coil (C1) utilizes
NEMA 1 – Enclosures constructed for indoor use to rectified Utility source power to actuate the LOAD
provide a degree of protection against incidental contact contacts to the UTILITY position. When energized, the
with the enclosed equipment and to provide a degree of coil will move the LOAD contacts to an “over center”
protection against falling dirt. position. The coil and the spring force will complete the
Type 3R Enclosures constructed for either indoor or transfer to UTILITY. A bridge rectifier, which changes the
outdoor use to provide a degree of protection to Utility source alternating current (AC) to direct current
personnel against access to hazardous parts; to provide (DC), is sealed in the coil wrappings. If either coil or
a degree of protection of the equipment inside the bridge rectifier replacement becomes necessary, replace
enclosure against ingress of solid foreign objects (falling the coil assembly.
dirt); to provide a degree of protection with respect to
harmful effects on the equipment due to the ingress of
water (rain, sleet, snow); and that will be undamaged by
the external formation of ice on the enclosure. A
B
Transfer Switch Contactor
The basic 2-pole CONTACTOR consists of a pair of C
movable LOAD contacts, a pair of stationary UTILITY
contacts, and a pair of stationary STANDBY contacts.
The LOAD contacts connect to the UTILITY contacts by a D
utility closing coil or to the STANDBY contacts using the
standby closing coil. See Figure 3-1 and Figure 3-2. The E
LOAD contacts can be moved to either the UTILITY or
STANDBY position by means of a manual transfer
F
handle. The closing coils are energized and actuated by
the voltage source from the side to which the load is
being transferred. For example, if the CONTACTOR is in 002490
the UTILITY position, the standby closing coil will A. Utility Closing Coil C1 C. Limit Switch SW3
energize utilizing Standby voltage. B. Bridge Rectifier E. Bridge Rectifier
C. Limit Switch SW2 F. Standby Closing Coil C2
STANDBY UTILITY Figure 3-3. The “V-Type” Transfer Mechanism
Figure 3-4 shows the transfer relay electrical schematic. Figure 3-4. Typical Transfer Relay Schematic
Transfer relay operation is controlled by the generator
controller. The transfer relay operates as follows: 5. When the controller senses that utility source
1. Generator battery voltage (12 VDC) is available to voltage has been restored (nominal for 15
the transfer relay coil from the Evolution controller, seconds), the Wire 23 circuit will open from ground.
via Wire 194 to the relay. a. The transfer relay will de-energize, the
a. The 12 VDC circuit is completed through the normally closed contacts will close and the
transfer relay coil and back to the controller via normally open contacts will open.
Wire 23. b. When the normally closed relay contacts close,
b. Controller logic holds the Wire 23 circuit open utility source voltage is delivered to the utility
to ground (Normally Open circuit) and the relay closing coil to energize that coil.
is de-energized. c. Transfer back to UTILITY occurs.
c. When de-energized, the relay contacts are in
their normal condition (one set open, N.O.; and Neutral Lug
one set closed, N.C.)
The generator is equipped with an ungrounded neutral.
d. The normally closed relay contacts deliver The neutral lug in the transfer switch is isolated from the
utility source power to the utility closing circuit switch enclosure.
of the transfer switch.
e. The normally open relay contacts will deliver Manual Transfer Handle
standby source power to the transfer switch
standby closing circuit only when the transfer The manual transfer handle is retained in the transfer
relay is energized by the control panel. switch enclosure on a u-shaped bracket. Use the handle
to manually move the contactor to the UTILITY or
2. During automatic system operation, when the
“STANDBY position.
generator controller senses that Utility source
voltage has dropped out, the controller will initiate a
ten second “Line Interrupt Delay” timer. At the end Customer Connections
of the factory default ten second delay the See Figure 3-6. During system installation, the control
controller will crank and start the engine. wires must be properly landed between the generator
3. When the circuit board senses that the engine has and transfer switch.
started (via Wire 18 from the magneto circuit), the
controller will initiate a ten second “Engine Warm- Utility N1 and N2
up Timer.”
N1 and N2 provide the utility voltage-sensing signal to
4. When the “engine warm-up timer” has timed out, the controller. The controller utilizes the sensing circuit as
controller logic closes the Wire 23 circuit to ground. follows:
a. The transfer relay energizes. If utility source voltage drops below the set nominal value
b. The relay’s normally closed contacts open and for ten seconds (default), controller logic will initiate
the normally open contacts close. automatic cranking and startup. The controller will
c. When the normally open contacts close, transfer the switch to the STANDBY position after a five
standby source power is delivered to the second engine warm-up timer.
standby closing coil and transfer to STANDBY
occurs.
Load T1
Wire T1, connected to the Load side of the contactor,
provides 120 VAC for the battery charging circuit (the
battery charger is an integral component of the
controller). The charger maintains battery voltage
anytime the load terminals have voltage available.
Control 194, 23
Wires 194 and 23 provide control of the transfer relay by
the controller. Wire 194 provides continuous DC voltage
to the transfer switch. Wire 23 is held open from ground
by controller logic until a utility failure is sensed.
Fuse Holder
The fuse holder holds three fuses, designated as fuses
F1, F2, and F3.
002509
Fuses F1, F2
These two fuses protects the N1 and N2 circuit against
overload.
Fuse F3
This T1 fuse protects the battery charger against
overload.
Fuse F4
This T2 fuse protects the battery charger against
overload (50 Hz only).
WH
GRN
T
CIRCUIT BREAKER
UT
2 POLE
GN
NE
D
E1
E2
PANELBOARD
N1 N2
A BONDING JUMPER IS
PROVIDED BETWEEN
THE NEUTRAL LUG
AND ENCLOSURE
AT THIS LOCATION
N1 N2 T1
(FACTORY INSTALLED)
209 210 0 194 23
LOAD SHED
DEVICE
N1
GROUND BAR DISCONNECT N2
BONDING T1
BREAKER CONNECTION
Section 3.1 Description and Major Components
STANDBY
(C2 & VR2)
GROUND LUG
(LOCATED ON THE
REAR OF UNIT)
0
E1 T1 T2 E2
23
194
UTILITY
METER
SOCKET
TO GROUNDING
ELECTRODE
002492
Figure 3-10. LSM 120 Volt Generator Running Priority One Enabled, Waiting 30 Seconds
Figure 3-11. LSM 120 Volt Generator Running Priority Two Enabled, Waiting 30 Seconds
Figure 3-12. LSM 120 Volt Generator Running Enabling Priority Three, Overload
Figure 3-13. LSM 120 Volt Generator Running Overload Detected Waiting 5 Minutes
Figure 3-14. LSM 120 Volt Generator Running Priority One Enabled, Waiting 30 Seconds
Figure 3-15. LSM 120 Volt Generator Running Holding At Priority 2, Waiting 30 Minutes
Figure 3-16. LSM 120 Volt Generator Running 30 Min Exp, Enabling Priority Three
Figure 3-17. LSM 120 Volt Generator Running All Priorities Restored
Load Shed Module Operation 1. Turn on the utility supply to the ATS.
OPCB 24/120 Volt Module 2. Press and hold the TEST button on the OPCB for
approximately 1 second.
The Overload Prevention Control Board (OPCB) can
control an air conditioner (24 VAC) directly or a separate 3. Verify that all of the connected loads to be “shed”
contactor (24 VAC or 120 VAC operating coil) which can become disabled. The method of verification will
control any load connected to it. depend on the type of load.
4. After five (5) minutes verify A/C1 (Priority 1) are
The OPCB load contacts can be powered from either a energized. Status LED AC 1 and Load 1 is ON.
24 VAC or 120 VAC power supply. The 24 VAC supply is
from a Class 2 transformer which can be purchased from 5. After another 15 seconds, verify A/C2 (Priority 2) are
the manufacturer. energized. Status LED AC 2 and Load 2 are ON.
Wire 194 from the HSB controller supplies 12 VDC to the 6. After another 15 seconds, verify A/C3 (Priority 3) is
module. Wire 0 provides the ground for the logic side of energized. Status Load 3 is ON.
the module. Wire 23 is monitored by the module to identify 7. After another 15 seconds, verify A/C4 (Priority 4) is
when transfer to standby and back to utility has energized. Status Load 4 is ON.
occurred.T1 and Neutral are used to monitor the
frequency of the generator for load control.
NOTE: When utilizing the optional 24 VAC configuration,
the power supply transformer (Class 2) must have
connections to the LOAD and NEUTRAL connection at
the OPCB. Limit each output to 1 Amp.
NOTE: 120 volt contactors cannot be used in
conjunction with 24 volt contactors. The OPCB must be
wired with one or the other.
A generator overload condition is determined by generator
frequency. Loads are shed when the frequency is <58 Hz
for 3 seconds or <50 Hz for ½ Second (For 60Hz).
Figure 3-18. OPCB TEST Button
Smart A/C Module (SACM)
Up to four air conditioner loads can be managed by the Load Shed Operation
Smart A/C Module (SACM). The SACM manages the NOTE: The following sequence of operation is the same
loads by “shedding” the connected loads in the event of a for the SACM and the OPCB 24/120 modules.
drop in generator frequency (overload). Loads to be shed
The 4 green status LEDs will indicate when a load priority
are in 4 priority levels on the module.
level is enabled or disabled.
Priorities A/C 1-4 have connections for an air conditioner. All loads are enabled when the transfer signal is off. (ATS
To control an air conditioner, no additional equipment is in Utility position).
required. Internal normally closed relays interrupt the 24
When utility power is interrupted, T1 is de-activated. The
VAC thermostat control signal to disable the air
module remains powered via Wire 194 (12 VDC) and
conditioner load.
Wire 0. Wire 23 is not grounded (high, 12 VDC) at this
Four LEDs, located on the SACM, illuminate when a load time.
is connected and powered. The SACM has a test button
As the generator starts, runs, and transfers, Wire 23 is
used to simulate an overload condition. This button
pulled to ground (low, 0 VDC). Once the transfer switch
operates even when the transfer signal is inactive.
goes to the standby position, T1 is powered by the
A generator overload condition is determined by generator generator.
frequency. Loads are shed when the frequency is <58 Hz The module senses that the system is on standby and
for 3 seconds or <50 Hz for ½ Second (For 60Hz). disables all loads. A 5 minute timer is activated.
• A/C1 (Priority 1) load(s) are enabled after 5 minutes.
Test Button
• A/C2 (Priority 2) load(s) are enabled after 15 seconds.
The OPCB/SACM load shed module has a TEST button
which forces the unit to act as if an overload has • A/C3 (Priority 3) load is enabled after another 15
occurred. This button operates even when the transfer seconds.
signal is inactive. • A/C4 (Priority 4) load is enabled after another 15
The TEST button will work when the ATS is in the Utility seconds.
or the Generator position. When an overload is detected all loads are disabled.
Generator overload condition is determined by generator frequency drops below specifications, the OPCB/SACM
frequency. Loads are shed when the frequency is <58 Hz will disable again. This will continue until the frequency
for 3 seconds or <50 Hz for ½ second (For 60Hz). does not drop when the priority is enabled, the system is
If an overload is detected within 15 seconds of a priority returned to utility, or the TEST button is pressed.
being enabled, that load is then locked out. The When utility voltage returns, Wire 23 is released from
sequence will continue until all load levels have been ground (back to 12 VDC, high) and the transfer switch
checked (temporarily bypassing the faulting level). The returns to the utility position. The OPCB/SACM will
level that caused the overload will not be enabled/tested disable all loads, time out for 5 minutes and then enable
again for 30 minutes. The OPCB/SACM will attempt to all 4 priorities at the same time.
enable the load every 30 minutes. During enabling, if the
Figures 3-19 through 3-33 follow the sequence of operation when an overload condition occurs on example Priority Circuit
3. After a 30 minute timer expires, Priority 3 is activated. If the frequency is still OK then all priorities will remain active.
Figure 3-24.
Figure 3-28.
SACM
T1 THERMOSTAT 1
0 GROUND
194 +12V
T1 T1 AIR
23 TRANSFER
CONDITIONER 1
00 NEUTRAL 00
THERMOSTAT 2
A/C 1
23 AIR
194 CONDITIONER 2
0 A/C 2
A/C 1
A/C 3 THERMOSTAT 3
A/C 2
A/C 3
0:00 AIR
CUSTOMER CONNECTION
Timer: CONDITIONER 4
DC VOLTAGE
(PCB) GROUND CONTROL
AC VOLTAGE
24VAC
NEUTRAL
GROUND
23 194 HZ
B
TR A 60.1
Figure 3-32. SACM
Power Supply Connections for 1. Mount the contactor module and connect the load
Contactors to the main contacts.
The Overload Prevention Control Board (OPCB) can be 2. Connect the contactor coil to the desired LSM
powered from either a 24 VAC or 120 VAC power supply. (Contactor 1, 2, 3 or 4) terminals on the terminal
The 24 VAC supply is from a class 2 transformer that can strip.
be purchased from the manufacturer. Mounting holes are 3. Connect additional load shedding contactors in a
provided in the enclosure subplate for mounting of the similar fashion.
transformer. The 120 VAC supply is fused at 5 amps and
is factory connected to OPCB terminals labeled “T1” and Power Management Module (PMM)
“Neutral”.
The PMM is for use with the Overload Prevention Control
24 VAC Supply Board (OPCB).
The Power Management Module (PPM) 24 VAC
Transformer connections are made as shown in Figure contactor is NOT supplied with the transfer switch. It can
3-36. be purchased separately from the manufacturer.
• Blue wire - OPCB “LOAD SUPPLY 1” terminal The OPCB is mounted in the transfer switch. The OPCB
• Black wire - OPCB “T1” terminal provides 24 VAC to the PMM contactor operating coil via
• White wire - OPCB “NEUTRAL” terminal the installed 24 VAC transformer. These PMM contactor
coil connections are made at the OPCB terminal strip.
• Yellow wire - OPCB “LOAD SUPPLY 2” terminal
B C
A. Ground Stud
B. Line Connections Terminals L1 & L2
C. Load Connections Terminals T1 & T2
D. Contactor Control Connections
Figure 3-34. Power Supply Connections Figure 3-35. PMM Starter Kit
LOAD 1 C
0 Ground SUPPLY
A 194 +12V T1 D
B
23 Transfer NEUTRAL E
LOAD 2 F
A/C 1 SUPPLY
24V 1
LOAD 1
1A MAX 2
A/C 2
24V 1
LOAD 2
1A MAX 2
A/C 1 & LOAD 1
1
LOAD 3 G
A/C 2 & LOAD 2
1A MAX 2
LOAD 3 1
LOAD 4
LOAD 4 1A MAX 2
002521
A. Factory wiring E. White
B. Transformer leads Field installed F. Yellow
C. Blue G. Existing wiring
D. Black
Figure 3-36. 24 VAC Supply Connections
LOAD 1 B
0 Ground SUPPLY
A D
194 +12V T1
23 Transfer NEUTRAL
E
LOAD 2
A/C 1 SUPPLY
24V 1
LOAD 1
1A MAX 2
A/C 2 C
24V 1
LOAD 2
1A MAX 2
A/C 1 & LOAD 1
1
LOAD 3
A/C 2 & LOAD 2
1A MAX 2
LOAD 3 1
LOAD 4
LOAD 4 1A MAX 2
003403
A. Factory wiring D. T1 (Factory)
B. Jumper Wire T1 to Load Supply 1 E. 00 (Factory)
C. Jumper Wire Neutral to Load Supply 2
Figure 3-37. 120 VAC Supply Connections
Enclosure Specifications
UL Rating Type 3R
Temperature -30 to 50 deg C (-22 to 122 deg F)
F F
Connections
G H I
A C
000106 B D
Figure 3-38. SMM Features and Controls
J
000108
Table 3-2. Lockout Switch Settings Figure 3-39. Smart Management Module Connections
Lockout
Legend – Figure 3-39
Switch Mode Function
Position A Red (240 VAC - Line)
B Black (240 VAC - Line)
If overloaded, module sheds
load until utility returns. C Red (240 VAC - Load)
Contactor is OPEN. D Black (240 VAC - Load)
ON GENERATOR
NOTE: Early version goes into E White - Neutral (as required)
lockout mode. Load is never
activated until Utility returns. F Green - Ground (as required)
G Black - Factory (PCB)
Power is available on module
ON UTILITY output (contactor output). H Red - Factory (PCB)
Contactor is CLOSED. I Blue - Factory (PCB)
Module detected an overload and shed its load. This state only
1 second flash
Shed Generator occurs in generator mode, or during a first time utility power up for
(1 On – 1 Off)
five minutes of initial operation.
Lockout 6 second flash Module output is disabled and there is no power to the appliance
Generator
Switch Active (6 On – 6 Off) while in generator mode. Lockout switch must be ON. See Table 2.
Test button triggers a typical shed condition and overrides all other
Test 1 second flash Generator or Utility
states except generator lockout switch ACTIVE state.
Module powers up
Checks frequency
Monitors frequency**
Contact opens –
If <52Hz for 1s or
Load is shed for 5
If <58Hz for 3.5s minutes (Priority 1) or
Utility
more*
Contact closes
If frequency meets
acceptable levels
Note: When monitor frequency and Pressing the TEST button will
monitor power source levels are reached, immediately override all settings and
Up to 5 minute delay
before contactor closes
* Each priority setting above Priority 1 will increase delay time in 15 second increments, starting with 15 seconds at Priority 2.
** If the frequency drops below acceptable levels for the pre-determined durations, all modules will shed.
† During lock out, the module will continuously monitor power source. If utility returns before the 30 minute lock out is satisfied, the module will allow five minutes to elapse from utility return time, and then close the contact.
Note 1: If the frequency is under 58 Hz when a module attempts to close the contactor after a shed, the module will wait another 5minutes plus Priority delay before attempting to enable.
Note 2: The "Checks power source" block monitors frequency and will change state, Generator or Utility, after it detects 1 minute of stable operation in the new state.
000105b
75
Section 3.1 Description and Major Components
Section 3.1 Description and Major Components
Transferring to Standby
12 VDC is delivered to the transfer relay through Wire 194 and back to the controller through Wire 23. When the five
second engine warm-up timer expires, the controller will take Wire 23 to ground which will energize the Transfer Relay.
The N.O. and N.C. relay contacts will change states. This will connect generator voltage from E1 through wire 205 at
relay connector 6 to E2A relay connector 4. The voltage will go through the N.C contact of XB1. Voltage from both E1
and E2 will be available at the C2 coil. This voltage will pass through the rectifier in the coil and the coil will energize.
Generator voltage is now delivered to the standby closing coil (C2), via generator voltage E1 and E2, the now closed
TR1 contacts, Wire 205, the limit switch (XB1), Wire B, and a bridge rectifier. The standby closing coil energizes and
the main current carrying contacts of the transfer switch are actuated to the “Standby” position.
• As the main contacts move toward the “Standby” position, limit switch XA1 closes (Utility Coil). When the
contacts are in the “Standby” position, a mechanical interlock actuates XB1 to its open position. When SW3
opens the C2 coil de-energizes.
• Generator voltage is now available to the LOAD terminals (T1 and T2) of the transfer switch and 120 VAC is also
supplied to the controller on Wire T1 for the battery charger. (220 VAC on T1 and T2 50 Hz only.)
NOTE: This is an example of Transfer Switch Operational Analysis. For troubleshooting use the operational analysis
with the appropriate wiring/schematic diagrams. XA1 and XB1
Transferred to Standby
When the standby coil (C2) energizes it pulls the contactor to an “over center” position towards the STANDBY position,
the transfer switch electronically/mechanically snaps to that position. Upon closure of the main contacts to the
STANDBY position limit switches XA1 and XB1 mechanically actuate to “arm” the circuit for re-transfer to the UTILITY
position. When XB1 changes, it opens the circuit providing voltage to the standby closing coil (C2). Voltage from the
generator, connected through T1 and T2, provides power to customer connected loads.
NOTE: This is an example of Transfer Switch Operational Analysis. For troubleshooting use the operational analysis
with the appropriate wiring/schematic diagrams.
Utility Restored
Utility voltage is restored and available to terminals N1 and N2. The Utility voltage is “sensed” by the controller and, if it
is above 75% of nominal for 15 consecutive seconds, a transfer back to UTILITY will occur.
NOTE: The TR1 open contacts 1 and 4 keep the switch from immediately transferring to the utility position.
NOTE: This is an example of Transfer Switch Operational Analysis. For troubleshooting use the operational analysis
with the appropriate wiring/schematic diagrams.
Overloaded
Overload Check for Overloaded
ALARM 2103 Unit has run and attempted to accept load 10 times, could not accept due to
Remove Load condition on unit
overload condition
Introduction
Use the “Flow Charts” in conjunction with the detailed instructions in Section 3.4. Test numbers used in the flow charts
correspond to the numbered tests in Section 3.4. The first step in using the flow charts is to identify the correct problem
on the following pages. For best results, perform all tests in the exact sequence shown in the flow charts.
Problem 6 — With Controller in Automatic Mode and Utility Failed, Generator Runs but
Transfer to Standby Does Not Occur
GOOD
TEST 21 – CHECK
MANUAL TRANSFER BAD REPAIR OR REPLACE MECHANISM
SWITCH OPERATION
GOOD
TEST 22 – CHECK
23 AND 194 BAD REPAIR OR REPLACE AS NEEDED
CIRCUIT
GOOD
TEST 23 – TEST
TRANSFER BAD REPLACE
RELAY
GOOD
TEST 24 – CHECK
STANDBY CONTROL BAD REPAIR AS NEEDED
CIRCUIT
Problem 7 – In Automatic Mode, Generator Starts When Loss of Utility Occurs, Generator
Shuts Down When Utility Returns But There is No Re-transfer to Utility Power
Or
Generator Transfers to Standby During Exercise or in Manual Mode
TEST 21 – CHECK
MANUAL TRANSFER BAD REPAIR OR REPLACE MECHANISM
SWITCH OPERATION
GOOD
TEST 25 – CHECK
WIRE 23 BAD REPAIR OR REPLACE AS NEEDED
GOOD
TEST 23 – TEST
TRANSFER BAD REPLACE
RELAY
GOOD
TEST 26 – CHECK
UTILITY CONTROL BAD REPAIR OR REPLACE AS NEEDED
CIRCUIT
Problem 8 – Unit Starts and May or May Not Transfer When Utility Power is On
TEST 35 –
TEST 28 –
CHECK VOLTAGE CORRECT UTILITY
CHECK FUSE GOOD BAD
AT TERMINAL SOURCE VOLTAGE
F1 & F2
LUGS N1 & N2
BAD GOOD
GOOD BAD
GOOD BAD
SMM Problem 1 – Load Management Module (SMM) LED is OFF, Load Not Powered
NO YES
ENABLE MLCB
AND/OR VERIFY LINE VOLTAGE ENABLE CIRCUIT
GENERATOR AVAILABLE? BREAKER
OPERATION
SMM Problem 2 – Load Management Module (SMM) LED is ON, Load Not Powered
SMM Problem 3 – Load Management Module (SMM) LED is Flashing, Load Not Powered
Integrated SACM Problem 1 – Generator starts and runs in AUTO with Utility Present
NOTE: Verify the integrity of all wires and connections relative to the function of the Integrated SACM Board. AC
Voltage value must equal Generator Output voltage.
NOTE: This procedure will require SD/WD 100000060381.
1. Check for AC Voltage on N1 and N2 at the connection deck on the generator.
4. Check for AC Voltage at the lower end of N1 and N2 FusesAC Voltage Present?
YES Go To Step 3
AC Voltage Present?
NO Go To Next Step
2. Check for AC Voltage on Wire 11 and Wire 44 at the MLCB (Generator Circuit Breaker).
4. Check for DC Voltage across Wire 23 and Wire 194 at the Customer Control Connection on the Integrated SACM
board.
5. Check for AC Voltage at Pin 8 and Pin 4 on the white Molex Connector.
6. Check for AC Voltage at Pin 8 of the white Molex Connector and Terminal 2 of the C2 Coil.
7. Check for AC Voltage on Pin 8 and Terminal 1 of the XB1 Limit Switch.
Integrated SACM Problem 3 – Transfer to Utility Does Not Occur after Utility Returns
NOTE: Verify the integrity of all wires and connections relative to the function of the Integrated SACM Board. AC
Voltage value must equal Generator Output voltage. DC Voltage value should be at least 9 VDC.
NOTE: This procedure will require SD/WD 100000060381.
1. Check for AC Voltage at the Utility Connection (before Utility Main Circuit Breaker).
3. Check for DC Voltage across Wire 23 and Wire 194 at the Customer Control Connection on the Integrated SACM
board.
4. Check for AC Voltage at Pin 3 (N1A) and Pin 6 (N2A) on the white Molex Connector.
5. Check for AC Voltage at Pin 3 (N1A) and Pin 5 (N2A) of the white Molex Connector.
6. Check for AC Voltage at Pin 3 (N1A) of the white Molex Connector and Terminal 2 of the C1 Coil.
7. Check for AC Voltage on Pin 3 (N1A) on the white Molex Connector and Terminal 1 of the XA1 Limit Switch.
8. Check for AC Voltage on Pin 3 (N1A) and Pin 2 (Wire 126) of the white Molex Connector.
6. Set the controller to MANUAL. 5. See Figure 3-49. Insert the un-insulated end of the
7. If transfer to the STANDBY position does not occur, handle over the transfer switch-operating lever.
check the voltage across terminal lugs E1 and E2. 6. Manually actuate the contactor lever up to the
The DMM should indicate generator line-line UTILITY position.
voltage. 7. Actuate the operating lever down to the STANDBY
position.
Results
8. Repeat Step 5 several times. When the contactor
1. If normal transfer to the STANDBY position occurs, lever is moved, slight force should be needed until
discontinue testing. the lever reaches its center position. As the lever
2. If transfer to the STANDBY position did not occur moves past its “over center” position, an over-
but the Generator continued to run for longer than center spring should snap the movable LOAD
10 seconds, and the DMM did not indicate voltage contacts against the stationary STANDBY or
across E1 and E2, proceed to Test 1—Check AC UTILITY contacts.
Output Voltage. 9. Actuate the contactor to the UTILITY position.
3. If transfer to the STANDBY position did not occur
B
and the DMM indicated proper voltage across E1
and E2 this test is GOOD. Refer to back to flow A
chart.
4. If transfer to the STANDBY position did not occur D
and the generator faulted on under-voltage, refer to
Problem 1 – Generator Shuts Down for Under
Voltage.
C
194
2. Disconnect Wire 194 from the transfer switch side COIL NOMINAL RESISTANCE = 120 Ohms
003429
of the terminal block in the generator, and then Figure 3-50. Clear Transfer Relay Test Points
check for DC voltage at this terminal block.
a. If DC voltage is now present but wasn’t before,
check for a short to ground between generator
and transfer switch. 205
9 12
Test 23 – Test Transfer Relay
N1A
13 14
General Theory
23
In automatic mode, transfer to standby will not occur until 194
COIL NOMINAL RESISTANCE = 163 Ohms 003430
the transfer relay (TR1) energizes. When TR1 relay
Figure 3-52. Yellow Transfer Relay Test Points
Diagnostic Repair Manual 99
Section 3.4 Diagnostic Tests
1 2 F
3 4
SW2
5 6
SW1
7 8
B
SW3
H
E1 E2
D E1 205 T1 T2
C2
1 2
C
E2
G
002524
4. Remove Wire B from the C2 coil. 11. Measure between the E2 terminal and the bottom
5. Set the controller to AUTO mode. Turn off utility terminal of the SW3, the DMM should indicate 240
power supply to the transfer switch, simulating a VAC.
utility failure. The generator should start and the a. If 240 VAC was NOT measured, verify the limit
transfer relay should energize. switch (SW3) is wired correctly, proceed to
6. Measure across lugs E1 and E2, the DMM should Test 27 – Test Limit Switches.
indicate 240 VAC. b. If 240 VAC was measured, proceed to Step 12.
a. If 240 VAC was NOT measured, go back to 12. Measure between the E2 terminal and terminal 2 of
Test 20. the C2 coil, the DMM should indicate 240 VAC.
b. If 240 VAC was measured, proceed to Step 7. a. If 240 VAC was NOT measured, repair or
7. Measure for the voltage on Wire B from the lug to 1 replace Wire B.
of the C2 coil (Wire B previously removed from the b. If 240 VAC was measured, replace the C2 coil.
coil) and B, the DMM should indicate 240 VAC.
a. If 240 VAC was NOT measured, repair or Test 25 – Check Wire 23
replace Wire E2.
b. If 240 VAC was measured, proceed to Step 8. General Theory
8. Measure between the E2 lug and Terminal 9 on the The controller located in the generator is responsible for
TR1, the DMM should indicate 240 VAC. grounding Wire 23 in order to initiate a transfer. When
a. If 240 VAC was NOT measured, repair or Wire 23 closes to ground the transfer relay (TR1)
replace Wire E1. energizes. To initiate a transfer back to Utility the TR1
relay must de-energize. If the TR1 relay is staying
b. If 240 VAC was measured, proceed to Step 8. energized, a faulty Wire 23 could be the cause. This test
9. Measure between the E2 terminal and terminal 6 of assumes that battery voltage is sufficient (at least 12.2
the TR1, the DMM should indicate 240 VAC. VDC).
a. If 240 VAC was NOT measured, replace
transfer relay. Procedure/Results
1. Set the controller to OFF.
b. If 240 VAC was measured, proceed to Step 10.
2. Set the DMM to measure DC voltage.
10. Measure between the E2 terminal and the top
terminal of SW3 the DMM should indicate 240 3. See Figure 3-56 or Figure 3-57. Disconnect and
VAC. isolate Wire 23 from the transfer switch side of the
terminal block in the generator. Observe the
a. If 240 VAC was NOT measured, repair or transfer switch.
replace Wire 205.
a. If the transfer relay (TR1) DID NOT de-
b. If 240 VAC was measured, proceed to Step 11. energize and the Transfer Switch DID NOT
return to Utility, proceed to Step 7.
Diagnostic Repair Manual 101
Section 3.4 Diagnostic Tests
b. If the transfer relay (TR1) de-energized and the 9. If DC Voltage was measured, proceed to the next
Transfer Switch returned to Utility, proceed to step.
the next step.
4. Set the controller to the AUTO mode. Utility
Voltage must be present. Verify that Utility is
present at N1 and N2 Terminal Block in the
generator.
5. Using the appropriate menu map, access the
OUTPUTS display (Figure 3-55) via the DEALER
menu (Evolution) or DEBUG menu (Nexus) on the
controller. N1 N2 T1 0 194 23
6. See Figure 3-55. Digital Output 8 is the Wire 23
output from the controller (Figure 3-55)
a. If Output 8 is displaying a “1”, the control board
is grounding Wire 23. Replace the controller.
002525
b. If Output 8 is displaying a “0”, the control board A A.Terminal Block
is NOT grounding Wire 23, proceed to the next B
B.Terminal Strip - Customer Side
step.
Figure 3-57. Transfer Relay Test Points – Evolution
GN
NE
relay (TR1).
B A
N1 N2 T1
209 210 0 194 23
003469
A A.Terminal Block B
8. Connect the positive meter test lead to Wire 194 at Figure 3-58. Transfer Relay Test Points – Evolution
the terminal block in the generator and connect the 2017
negative meter test lead to the ground lug. Verify
that DC Voltage is present.
a. If DC Voltage was not measured, refer back to
the flowchart (Test 22).
Test 26 – Test Utility Control Circuit b. If 240 VAC is not measured proceed to Step 9.
7. Checking coil continuity:
General Theory a. If continuity is measured proceed to Step 8.
See Figure 3-59. The utility coil (C1) requires 240 VAC to b. If there is no continuity, replace the coil.
energize. When the transfer relay (TR1) de-energizes, 8. Measure the voltage across point C (Wire N2A
240 VAC is applied to the C1 coil. Once energized, the previously removed) and B, the DMM should
coil will pull the CONTACTOR up to the “Utility” position. indicate 240 VAC.
Once in the UTILITY position, the limit switch (SW2) will
a. If 240 VAC was NOT measured, repair or
open, removing AC voltage from the C1 coil.
replace Wire N2A.
Procedure b. If 240 VAC was measured, proceed to Step 9.
1. Set the controller to OFF. Disconnect Wire 194 9. Measure for voltage between the N2 lug and the
from the transfer switch terminal strip. F1 terminal A. The DMM should indicate 240 VAC.
2. Set DMM to measure AC voltage. a. If 240 VAC was NOT measured, repair or
replace Wire N1A.
3. Disconnect Utility supply voltage from the transfer
b. If 240 VAC was measured, proceed to Step 10.
switch.
10. Measure for voltage from the N2 lug and Terminal
4. Verify the transfer switch is in the STANDBY
7 of the TR1, the DMM should indicate 240 VAC.
position.
a. If 240 VAC was NOT measured, repair or
5. Turn on Utility supply voltage to the transfer switch.
replace Wire N1A.
a. If transfer to Utility occurs, the transfer relay
b. If 240 VAC was measured, proceed to Step 11.
(TR1) was energized preventing a re-transfer
to Utility. Proceed to Test 25 – Check Wire 23. 11. Measure for voltage between the N2 lug and
terminal 1 of the TR1, the DMM should indicate
b. If transfer to Utility does NOT occur, proceed to
240 VAC.
Step 7.
a. If 240 VAC was NOT measured, replace
6. Remove two wires from the utility coil and check for
transfer relay.
240 VAC.
b. If 240 VAC was measured, proceed to Step 12.
a. If 240 VAC is measured check utility coil for
continuity.
126
N2A H
A
F TR1 C
1 2
N2A
1 2
3 4 C1
5 6 A
E 7 8 I N1 N2
N1A
SW2 B
G
N1A SW1
SW3
D
E1 E2
A A A
B T1 T2
C2
F1 F2 F3 1 2
*Refer to the appropriate schematic
for the unit being worked on.
B B B
002526
Figure 3-59. Typical Utility Control Circuit Test Points
12. Measure for voltage between the N2 lug and the 10. Manually actuate the CONTACTOR to the “Utility”
bottom terminal of the SW2. The DMM should position. Measure and record the resistance.
indicate 240 VAC. 11. Repeat Step 4 and 5 several times and verify the
a. If 240 VAC was NOT measured, repair or DMM reading at each switch position.
replace Wire 126.
Coil Nominal Resistance: 480-520k ohms
b. If 240 VAC was measured, proceed to Step 13.
13. Measure for voltage between the N2 lug and the Results
top terminal of the SW2. The DMM should indicate 1. If the DMM indicated CONTINUITY in Step 4 and
240 VAC. 10 and INFINITY in Step 5 and 9 the limit switches
a. If 240 VAC was not measured, verify the limit are good. Refer back to flowchart.
switch (SW2) is wired correctly and proceed to 2. If the DMM did NOT indicate CONTINUITY in Step
Test 27 – Test Limit Switches. 4 or 10 and INFINITY in Step 5 or 9 the limit
b. If 240 VAC was measured, proceed to Step 14. switch(es) are bad. Repair or replace appropriate
14. Measure for voltage between the N2 lug and switch(es).
terminal 2 of the C1 coil. The DMM should indicate
240 VAC. Test 28 – Check Fuses F1 and F2
a. If 240 VAC was not measured, repair or
General Theory
replace Wire A.
b. If 240 VAC was measured, replace the C1 coil. Fuses F1 and F2 are connected in series with the N1 and
N2 circuits, respectively. A blown fuse will open the
applicable circuit and will result in (a) generator startup
Test 27 – Test Limit Switches and transfer to the “Standby”, or (b) failure to re-transfer
General Theory back to utility source.
With the controller set to OFF, the generator main circuit 4. Inspect and test fuses for an OPEN condition with
breaker “Open”, and Utility Voltage disconnected from the a DMM set to measure resistance. CONTINUITY
transfer switch, test limit switches SW2 and SW3 as follows. should be measured across the fuse.
General Theory A
Procedure
1. On the generator panel, set the controller to OFF.
2. Disconnect Utility from the transfer switch.
3. Remove fuse F3 from the fuse holder.
4. Inspect and test fuses for an OPEN condition with
a DMM set to measure resistance. CONTINUITY
D
should be measured across the fuse.
E F
002448
Results A. Line Side D. Load Side
1. Replace blown fuse as needed. B. 11 E. E1
C. 44 F. E2
Figure 3-61. Main Line Circuit Breaker
Test 30 – Check Main Circuit Breaker
General Theory Test 32 – Check N1 and N2 Wiring
Often the most obvious cause of a problem is over- General Theory
looked. If the generator main line circuit breaker (MLCB)
is set to “Open”, the electrical loads will not receive A shorted Wire N1 or N2 to ground can cause fuse F1 or
power. If the connected loads are not receiving voltage a F2 to blow.
possible cause could be, the MLCB has failed OPEN.
Procedure
Procedure 1. On the generator panel, set the controller to OFF.
The generator main line circuit breaker (MLCB) is located 2. Turn off the utility power supply to the transfer
underneath the control panel side cover. If loads are not switch, using whatever means provided.
receiving power, verify the breaker is set to the “Closed” 3. Remove fuses F1, F2, and F3 from the fuse holder.
position. If the beaker is suspected to have failed, test it 4. Remove the generator control panel cover.
as follows. Disconnect the connector that supplies the
1. Set the DMM to measure resistance. controller T1 located in the control panel.
2. With the generator shutdown, disconnect all wires 5. Set DMM to measure resistance.
from the MLCB terminals, to prevent interaction. 6. Connect the positive meter test lead to Wire N1 at
the terminal block in the control panel.
3. See Figure 3-61. Connect one meter test lead to
the Wire 11 terminal on the breaker and the other a. Connect the negative meter lead to the ground
test lead to the E1 terminal. lug. INFINITY should be measured.
4. Set the breaker to its “Closed” position; the DMM b. Connect the negative meter lead to Wire 23 at
should indicate CONTINUITY. the terminal strip. INFINITY should be
measured.
5. Set the breaker to its “Open” position; the DMM
c. Connect the negative meter lead to Wire 194
should indicate INFINITY.
at the terminal strip. INFINITY should be
6. Repeat Step 4 and 5 with the DMM meter leads measured.
connected across the Wire 44 terminal and the E2
d. Connect the negative meter lead to Wire 0 at
terminal.
the terminal strip. INFINITY should be
measured.
Results
e. Connect the negative meter lead to Wire N2 at
1. If the circuit breaker tests good, refer back to the
the terminal block. INFINITY should be
flow chart.
measured.
2. If the breaker failed Steps 4 or 5, replace the f. Connect the negative meter lead to the neutral
breaker. connection. INFINITY should be measured.
7. Connect the positive meter test lead to Wire N2 at Test 34 – Check Utility Sensing
the terminal block in the control panel. Voltage at the Circuit Board
a. Connect the negative meter lead to the ground
lug. INFINITY should be measured. General Theory
b. Connect the negative meter lead to Wire 23 at If the generator starts and transfer to STANDBY occurs in
the terminal strip. INFINITY should be automatic mode when acceptable UTILITY source
measured. voltage is available at the terminal block, the next step is
c. Connect the negative meter lead to Wire 194 to determine if sensing voltage is reaching the controller.
at the terminal strip. INFINITY should be
measured. NOTE: The System Ready LED will flash in AUTO or
UTILITY LOST will display on the panel.
d. Connect the negative meter lead to Wire 0 at
the terminal strip. INFINITY should be Procedure
measured.
1. Set the controller to OFF.
e. Connect the negative meter lead to the neutral
2. Disconnect the harness connector containing
connection. INFINITY should be measured.
Wires N1 and N2 from the controller.
Results 3. Set a DMM to measure AC voltage.
4. Connect one meter test lead to Wire N1. Connect
If a short is indicated in Step 6 or Step 7, repair wiring and
the other meter test lead to Wire N2. Approximately
repeat test.
240 VAC should be measured.
Results Procedure
Refer to Flow Chart. With utility source voltage available to terminal lugs N1 and
N2, use a DMM to test for utility source line-to-line voltage
across terminal locations N1 and N2 terminals. Normal
240 VAC line-to-line utility source voltage should be indicated.
Results
C 1. If voltage reading across the N1 and N2 terminals
is zero or low, refer to Flow Chart.
2. If voltage reading is good, refer to Flow Chart.
002527
A. N1
B. N2
C. Test Points
Figure 3-62. Terminal Block Test Points
Results
1. If the DMM indicated INFINITY in Steps 4a -4e,
replace the controller.
2. If the DMM indicated CONTINUITY, repair or
replace the wiring in the appropriate circuit.
UT
GN
NE
D
This section will familiarize the reader with the various
components that make up the Engine and DC Control
systems.
Topics covered in this section are:
• Customer Connections
• Controller
N1 N2 T1
• Menu System Navigation 209 210 0 194 23
• LED Display
• Battery Charger
• AUTO-OFF-MANUAL
• 7.5 Amp Fuse 209 210 0 194 23
003162
• Starter Contactor Relay
Figure 4-1. Nexus Customer Connections
• Common Alarm Relay
• Connector Pin Descriptions
Customer Connection
The terminals of this terminal strip connect to identically
numbered terminals in the transfer switch. The terminal
block provides the electrical connection for the controller
at the following connection points:
• UTILITY N1 (Utility Sensing)
• UTILITY N2 (Utility Sensing)
• LOAD T1 (Internal Battery Charger) - 60 Hz Unit 004920
• LOAD T2 (Internal Battery Charger) - 50 Hz Unit Figure 4-2. 2017 Evolution Customer Connections
• Wire 194 (Transfer Relay)
• Wire 23 (Transfer Relay)
C 0
DC COMMON
Table 4-2. Ground and Neutral Connections
D 194 1 Large Neutral Lug Torque Spec 2/0 TO 14 AWG 120 in-lb (13.56 N-m)
+12 VDC
E 23 2 Large Ground Lug Torque Spec 2/0 TO 14 AWG 120 in-lb (13.56 N-m)
TRANSFER
Ground and Neutral Bus Bar Torque Specs:
2
4-6 AWG 35 in-lb (3.95 N-m)
3
8 AWG 25 in-lb (2.82 N-m)
10-14 AWG 20 in-lb (2.26 N-m)
Note: A 25 in-lb (2.82 Nm) torque should be applied to the ground wire
and neutral wire connection to the ground/neutral bar.
000914
B
T1 D BLACK #3 0 - DC (-) Common Ground Wire
VAC LOAD
SUPPLY
C T2 E RED #4 194 - DC (+) 12 VDC for Transfer Controls
VAC LOAD
SUPPLY
F WHITE #5 23 - Transfer Control Signal Wire
000620
Controller
The controller is responsible for all standby electric Table 4-5. Digital Inputs and Outputs
system operations including (a) engine startup, (b)
Position Digital Inputs Digital Outputs
engine running, (c) automatic transfer, (d) automatic re-
transfer, and (e) engine shutdown. In addition, the 1 Not Used/Aux Shutdown* Not Used
controller performs the following functions:
2 Low Oil Pressure Not Used
• Automatic voltage regulation.
3 High Temperature Not Used
• Starts and exercises the generator once every
seven days. 4 Not Used Battery Charger Relay
• Automatic engine shutdown in the event of low oil 5 Wiring Error Detect Fuel
pressure, high oil temperature, over speed, no
RPM sense, over crank, or low battery. 6 2-Wire Start Starter
LED Display
Located next to the right side lock cylinder on the
generator, the LED Display provides a visual indication
the generators status. The LED Display has three LEDs:
110 Diagnostic Repair Manual
Section 4.1 Description and Major Components
Battery Charger
The charger operates at one of three battery charging
voltage levels depending on ambient temperature.
• 13.5 VDC at High Temperature
• 14.1 VDC at Normal Temperature
• 14.6 VDC at Low Temperature
The battery charger is powered from a 120 VAC Load
connection through a fuse (F3) in the transfer switch.
This 120 VAC source must be connected to the Figure 4-5. Nexus Auto-Off-Manual Switch
Generator in order to operate the charger.
NOTE: 50 Hz units use fuses F3 and F4 and a 220 VAC
supply to the battery charger.
During a Utility failure, the charger will momentarily be
turned off until the Generator is connected to the Load.
During normal operation, the battery charger supplies all
the power to the controller; the Generator battery is not
used to supply power.
The battery charger will begin its charge cycle when
battery voltage drops below approximately 12.6V. The
charger provides current directly to the battery dependent
on temperature, and the battery is charged at the
appropriate voltage level for 18 hours. At the end of the
18 hour charge period battery charge current is 000425
measured when the Generator is off. If battery charge
current at the end of the 18 hour charge time is greater Figure 4-6. Evolution controller Off-Manual-Auto
than a pre-set level, or the battery open-circuit voltage is Buttons
less than approximately 12.5V, an “Inspect Battery”
(Nexus) or “Charger Warning” (Evolution) warning is Fuse
raised. If the engine cranks during the 18 hour charge
The fuse protects the controller against excessive
period, then the 18 hour charge timer is restarted.
current. If the fuse has blown, engine cranking and
At the end of the 18 hour charge period the charger does operation will not be possible. Should fuse replacement
one of two things. If the temperature is less than become necessary, use only an equivalent 7.5 amp
approximately 40 ºF the battery is continuously charged replacement fuse.
at a voltage of 14.1V (i.e. the charge voltage is changed
from 14.6V to 14.1V after 18 hours). If the temperature is
above approximately 40 ºF then the charger will stop
charging the battery after 18 hours.
The battery has a similar role as that found in an
automobile application. It sits doing nothing until it either
self-discharges below 12.6V or an engine crank occurs 002438
(i.e. such as occurs during the weekly exercise cycle). If
Figure 4-7. Typical 7.5 Amp Fuse
either condition occurs the battery charge will begin its 18
hour charge cycle.
Diagnostic Repair Manual 111
Section 4.1 Description and Major Components
Starter Contactor Relay/Solenoid On 2017 Evolution units the connections are made to the
controller via Wires 209 and 210 by connecting to the
(V-Twins and units with 426cc Engine) dedicated wire connections.
Y Y 818 Grounded by the controller to turn on NOTE: If the ENTER key is not pressed to save the new
Alarm (Red) LED setting, it will only be saved temporarily. The next time
Y Y 819 Grounded by the controller to turn on the battery is disconnected, the setting will revert back to
the Maintenance (Yellow) LED the old setting.
Y Y 820 Positive voltage (5VDC) for status
LEDs
N Y J1 Model ID Resistor
Y N R1 Model ID Resistor
Y N R3 Model ID Resistor
ESC
Running Manual
Running-Utility Lost
Running-Remote Start ENTER SYSTEM DATE/TIME
Running-2 Wire Start
Running - Exercise
Switched Off Battery Condition ENTER
Stopped - Auto BATTERY SUB MENUS
Stopped - Alarm “Good” “Inspect Battery” or “Check Battery” ESC
ENTER ESC
ENTER ENTER
- 1 thru 50 + - Run Log + “Run Log” ENTER
ESC ESC HISTORY
- 1 thru 50 + - Alarm Log + “Alarm Log” ESC
ENTER ENTER
Warning Message(s)
DEALER
Charger Warning
Charger Missing AC ENTER
Low Battery
Battery Problem
Exercise Set Error
USB Warning
Language ENTER Language Language Language
Download Failure + + +
ESC
FIRMWARE ERROR-9 Å English Æ + English - - + Espanol - - + Francais -
Overload Cooldown
SEEPROM ABUSE
Fuel Warning ESC
Fuel Selection ENTER Fuel Selection
ESC
Å NG or LP Æ + NG or LP -
Alarm Message(s)
High Temperature
Low Oil Pressure ESC
Cold Smart Start? ENTER Cold Smart Start?
Overcrank
ESC
Overspeed Å YES or NO Æ - YES or NO +
Overvoltage
Undervoltage
Overload ESC ESC
Underspeed
RPM Sensor Loss Time ENTER Current Date/Time ENTER Select Month (1-12) ENTER
Controller Fault ESC
Å Manual or AUTO Æ Å 2/13/16 13:00 Æ - 2 +
Wiring Error
Stepper Overcurrent
FIRMWARE ERROR-7
ESC ESC
Overload Remove Load
Low Volts Remove Load Exercise Time ENTER Select Frequency ENTER Quiet Test Mode ? ENTER
Stepper Over Current ESC
Å 14:00 Wednesday Æ - WEEKLY + - YES or NO +
Fuse Problem*
- BIWEEKLY +
- MONTHLY + Quiet Test Mode only
*“Fuse Problem” on Firmware on certain models
1.11 and older ONLY
ESC
ENTER
DOWN ARROW = -
Run Hours (H)
0.0
ESC ENTER
ENTER
Maint. Log Scheduled
- 1 thru 50 + EXAMPLE:
"Battery Maintained" Inspect Battery 200 RnHr or 12/27/13
"Schedule A Serviced"
and
+ Language + "Schedule B Serviced"
Next Maintenance 200 RnHr or 12/27/13
"Maintenance Reset"
- + Portuguese -
"Inspect Battery"
"Service Schedule A"
"Service Schedule B"
Select “Yes” then Press “Enter” to continue or Press “ESCAPE” to escape out of updating.
During update process the Blue “Manual” light flashes, then the Green “Auto” light flashes.
Sequence does this twice. When update is complete the unit returns to Install Wizard menu.
When the controller powers up the very first screen displays the version number for a few seconds.
When update is complete remove Thumb Drive, then follow the Install Wizard Menu.
Select Date (1-31) ENTER Select Year (0-99) ENTER Select Hour (0-23) ENTER Select Min (0-59)
- 13 + - 16 + - 13 + - 0 +
Possible Message(s)
Corrupted File "Current:V XXXX " ENTER "Are You Sure?"
Invalid File
File Not Found "USB: V XXXX" ESC "- Yes or No +"
Unsupported Device 005615
Power Up Unit
FIRMWARE V 1.01
Use UP and DOWN arrows to select fuel type then press “ENTER”
HARDWARE V 1.05
ENTER
Activated Unit
ESC
Cold Smart Start? ENTER Cold Smart Start?
Å YES or NO Æ - YES or NO +
To activate go to
www.activategen.com
Note: If language was previously
programmed this goes directly to
“Select Hour”
Language + Language + L
Serial 1234567890
PASSCODE xxxxx + _______ - - + English - - +
ENTER
Use up and down arrows to change selection 0 Defaults to
thru 9. Press "Enter" to acccept selection and English if not
to move to the next digit. If passcode is correct selected.
goes to "Install Wizard." If not correct goes to
the message below.
Select Hour (0-23) ENTER Select Min (0-59) ENTER
- 14 + - 0 +
Wrong Passcode
* *
Try Again * Holding the Up or Down arrow
button for 2 seconds will speed dial
through the selections
Select F
“NOT ACTIVATED!” Install Wizard ENTER Quiet Test Mode ? ENTER
- WEE
Hours of Protection
Set Exercise - YES or NO + - BIWE
0 (H)
- MON
UP ARROW = +
DOWN ARROW = -
ESC
ENTER Select Month (1-12) ENTER Select Date (1-31) ENTER Select Year (0-99)
- 2 + - 13 + - 13 +
* * *
Select Frequency
ENTER Select Hour (0-23) ENTER Select Min (0-59) ENTER Select Day
- WEEKLY +
- BIWEEKLY + - 14 + - 0 + - Wednesday +
- MONTHLY +
* * *
000429
ESC
ENTER ESC
HISTORY MAIN
EDIT DEALER
ENTER
- Language +
ESC
English
Fuel Selection
ESC
NG or LP
Possible Message(s)
"Corrupted File"
"Invalid File"
EXERCISE TIME "File Not Found"
ESC "Unsupported Device"
14:00 Wednesday
"Insert USB"
Firmware Update
System not in the OFF position
Disabled Press OFF
UP ARROW = +
DOWN ARROW = -
000430
* 50 Hz Display
HISTORY MAINT
*
ENTER ESC
Util Recovery Volts Util Recovery Volts
ESC
Å 190 - 216 Æ Å 175 - 198 Æ
* DEALER:
ENTER
Calibrate Current1 DEALER EDIT
Current 0.0
ESC
Å 1186 - 1780 Æ Å 1640 Æ
*
Calibrate Current 1, Calibrate Current 2,
Calibrate Current2 Current 0.0 Calibrate Volts. Special note: Press Enter
ESC to modify use the Up and Down arrows to
Å 1186 - 1780 Æ Å 1640 Æ make the change. Pressing Enter or ESC
* saves the changes. This is different from all
the others under Dealer Edit.
Calibrate Volts Calibrate Volts
ESC
Å 750 - 1280 Æ Å 1120 Æ
*
ENTER
(Performs Segment
2 Wire Start Select test of the display)
ESC
ESC
Å No or Yes Æ EcoGen Only
* Off Grid Mode
Yes or No
Reset Maintenance
ESC
Å No or Yes Æ UP ARROW = +
*
DOWN ARROW = -
“Battery Voltage”
ESC
0 - 13.7
“Charging Status”
ESC
“Charging” or “Not Charging”
Output Volts”
ESC
0
DISPLAY
Utility Input Volts
ESC
T TEST 0
FIRMWARE V 1.01
ESC
HARDWARE V 1.05
OUTPUTS:Gen. 0 V
ESC
0 0 0 0 0 0 0 0
Commands:
Bootloader V0.2
ESC “Running Manual”
EEPROM V1.01
To Test Displays “Running - Utility Loss”
ESC
Press Enter “Running - Remote Start”
COMMAND:
ESC “Running - 2-wire Start”
Switched Off
“Running - Exercise”
IN AUTO PRESS
ESC “Switched Off”
ENTER FOR QT-TEST
Node Hz Volts “Stopped - Auto”
ESC
15 KW 60 120/240 “Stopped - Alarm”
ENTER ESC or ENTER
PRESS ENTER TO Note: Units equipped with Quiet Test only. Unit
ESC
STOP Quiet Test must be in AUTO and have Utility available in order
to view this screen and test the Quiet Test function.
000431
RESET
ALARM LOG RUN LOG STATE DISPLAY COMMAND VERSIONS MAINTENANCE
INPUTS OUTPUTS DISPLAYS QT TEST
EXERCISE If so equipped
ESC SOFTWARE
TIME
HARDWARE
and rest for a preset time limit. It will then stop cranking 5. Once the control board sees an rpm signal it will
and the LCD screen will indicate an “Overcrank” condition. energize the fuel solenoid, drive the throttle open
and continue the crank sequence.
NOTE: If the fault is not repaired, the overcrank fault will
6. Starter motor will disengage when speed reaches
continue to occur.
starter dropout.
Cyclic cranking is controlled as follows: 16 second crank, 7. If the generator does not reach 2200 rpm within 15
seven (7) second rest, 16 second crank, seven (7) second seconds, a rest and re-crank cycle will occur.
rest followed by three (3) additional cycles of seven (7)
8. If engine stops turning between starter dropout and
second cranks followed by seven (7) second rests.
2200 rpm, the board will go into a rest cycle for
Choke Operation (Nexus controller only) seven (7) seconds then re-crank (if additional
crank cycles exist).
This is defined as any of the following occurrences during
9. Once started, the generator will wait for a hold-off
cranking.
period before starting to monitor oil pressure and
1. The 990/999cc engines have an electric choke in oil temperature (refer to the Alarm Messages
the air box that is automatically controlled by the section for hold-off times).
electronic control board.
10. During cranking, if the controller is in the OFF
2. The 530cc engines have an electric choke on the mode, cranking stops immediately.
divider panel air inlet hose that is automatically
11. During Auto mode cranking, if the Utility returns,
controlled by the electronic control board.
the cranking cycle does NOT abort but continues
3. The 410cc engines have a choke behind the air until complete. Once the engine starts, it will run for
box that is automatically controlled by the one (1) minute, and then shut down.
electronic control board.
NOTE: Evolution and Evolution 2.0 units do not utilize a Under-Frequency
choke mechanism.
After starting, if the generator stays under a set
Failure to Start frequency for more than 30 seconds, it will shutdown.
This is defined as any of the following occurrences during
cranking. Table 4-8. Evolution Under-frequency Shutdown Settings
1. Not reaching starter dropout speed within the Unit Hertz Shutdown Frequency
specified crank cycle. Starter dropout speed is 50 Hz 40 Hz
defined as four (4) engine cycles at 1,500 rpm
60 Hz 55 Hz
(1,800 rpm for 8 kW units).
2. Reaching starter dropout speed, but then not
reaching 2200 rpm within 15 seconds. In this case
the control board will go into a rest cycle for seven (7)
seconds, then continue the rest of the crank cycle.
3. During a rest cycle the start and fuel outputs are
de-energized and the magneto output is shorted to
ground.
Cranking Conditions
The following notes apply during the cranking cycle.
1. Starter motor will not engage within five (5)
seconds of the engine shutting down.
2. The fuel output will not be energized with the
starter.
3. The starter and magneto outputs will be energized
together.
4. Once the starter is energized the control board will
begin looking for engine rotation via the magnetos
and Wire 18 into the control panel. If it does not
see an rpm signal within three (3) seconds it will
shut down and latch out on “RPM Sensor Loss.”
Clearing an Alarm
Table 4-9. Nexus Under-frequency Shutdown Settings When the generator is shut down due to a latching alarm,
Unit Hertz Shutdown Frequency the controller must be set to the OFF mode and the
“Enter” key pressed to unlatch any active fault and clear
50 Hz 40 Hz
the corresponding fault alarm message.
60 Hz with 0H6680A Controller 50 Hz
60 Hz with 0H6680B Controller 55 Hz
Low Oil Pressure 5 seconds 8 seconds 2 looks Digital input Digital input Hard Lockout
3 seconds 2 Re crank, Hard
RPM Sensor Loss 1.1 seconds Continuous Timed signal loss Timed signal loss
4 sec (8 kW only) Lockout
100 ms
Wiring error 0 seconds 7.5% of 100 ms sample 7.50% None Hard Lockout
periods
High temp. 10 seconds 1 second 2 looks Digital input Digital input Auto Reset
Underspeed 5 seconds 30 seconds Continuous None 55 Hz/3300 RPM Hard Lockout
Overspeed Instant 50
0 seconds .1 second Continuous 62.5 Hz/3750 RPM None Hard Lockout
Hz
Overspeed Slow 50 Hz 0 seconds 3 seconds Continuous 60Hz/3600 RPM None Hard Lockout
Overspeed Instant 0 seconds .1 second Continuous 75 Hz/4500 RPM None Hard Lockout
Overspeed Slow 0 seconds 3 seconds Continuous 72 Hz/4320 RPM None Hard Lockout
15 Volts or no zero 2 Re crank, Hard
Undervoltage Fast* 10 seconds 2 seconds Continuous None
crosses detected Lockout
2 Re crank, Hard
Undervoltage Slow* 5 seconds 10 seconds Continuous None 80% of nominal
Lockout
Overvoltage fast * 5 seconds 1/5 second Continuous 130% nominal None Hard Lockout
Overvoltage slow * 5 seconds 3 seconds Continuous 110% nominal None Hard Lockout
Stepper Overcurrent 0 seconds Instant Continuous NA NA Hard Lockout
Overload Alarm 0 seconds 20 seconds Continuous 102% rated current NA Hard Lockout
80% of nominal
Overload
5 seconds 10 seconds Continuous NA after Overload Hard Lockout
Undervoltage
Alarm
As long as battery
Low Battery 60 seconds Continuous NA 12.1 V or less Warning
is <12.1 VDC
12.5 V at end of
Charger Warning 0 seconds NA Continuous NA Warning
charge cycle
Continuous
As long as AC is
Charger Missing AC 15 seconds except NA NA Warning
missing
cranking
N1 240VAC
UTILITY
N2 INPUT
120VAC
T1
LOAD SUPPLY
N1 220VAC
1 2 3 4 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
UTILITY
N1
J3 J2 INPUT
N2
N2
J8 T1
TO PCB
J9 T1
220VAC
MAIN LOAD SUPPLY
14 15 16
F1 CONTROLLER T2
J8 T1
Ready to Run J9 T2
J1
T1 and T2 220VAC for
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Battery Charger 50Hz only.
N1
N2
N1
N2
N2
N1
003213
Figure 4-20.
1 2 3 4 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
J3 J2 J8
TO PCB J9
MAIN
F1 CONTROLLER
Ready to Run
J1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
13
13
0
13
13
13
13
13
0
12V SCR
BATTERY
16
13
0
SC
16 SC SM 13
SC BATTERY
SM
003214
Figure 4-21.
Utility Dropout
N1 240VAC
UTILITY
N2 INPUT
120VAC
T1
LOAD SUPPLY
1 2 3 4 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
J3 J2
N1
N2
J8 T1
TO PCB
J9
MAIN
F1 CONTROLLER
N2
N1 003222
Figure 4-23.
4
0
4
FIELD
BOOST
DIODE
4A
18
4A
14
56
209
4A
18
18
14
14
56
56
6
0
2
4
1 2 3 4 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
J3 J2 J8
J5 J9
TO PCB
GOVERNOR MAIN
ACTUATOR F1 CONTROLLER
Cranking
J1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
817
194
820
13
13
86
23
85
85
86
820
18
14
56
86
85
817
13
23
HOT LOP
SCR FS
0
0
0
0
0
18
13
0
13
13
13
0
194
SCR 23
12V
BATTERY
18 IM1 SP1
16
13
0
SC
SM 18 IM2 SP2
SC
16 SC SM 13
BATTERY
003223
Figure 4-25.
44S
POWER CB1
WINDING
44 44 44
240VAC
GENERATOR
33 OUTPUT
STATOR 22 11 11
11 11 CB2
POWER
WINDING 11C
ROTOR 11S 33 33
BA EXCITATION 22 22
NEUTRAL
WINDING 00
11S 00
6
0
2
4
6
2
4
0
4
FIELD
BOOST
DIODE
4A
4A
11C
120VAC
ACCESSORY
00
POWER
OUTPUT
11S
44S
4A
00
6
0
2
4
1 2 3 4 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 FOR APPLICABLE
MODELS ONLY
J3 J2 J8
J5 J9 00
TO PCB
GOVERNOR MAIN
ACTUATOR F1 CONTROLLER
Running/Warming Up
J1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
003224
Figure 4-27.
Transfer to Standby
In Figure 4-30 the Generator is running, the controller's “engine warm-up” timer has expired and generator AC output
is available to the transfer switch Terminal Lugs E1 and E2 and to the open contacts on the transfer relay. Transfer to
Standby may be briefly described as follows:
• 12 VDC is delivered to the transfer relay coil (TR1 - Terminal A) via Wire 194. The 12 VDC circuit is completed
back to the controller via Wire 23 (TR1 - Terminal B). However, the controller’s logic holds Wire 23 open from
ground and the TR1 relay is de-energized.
• When the “engine warm-up timer” expires, the controller will take Wire 23 to ground. The TR1 relay energizes
and its normally open contacts close (standby position).
• While running, the pulsing AC speed reference from the ignition magneto(s) to the controller via Wire 18 will be
used for the following functions:
a. governor speed control to maintain frequency through different loads
b. overspeed
c. underspeed
• With no, or a light load, the stepper motor will control the throttle position of the smaller venturi. As the load
demand increases and with the smaller venturi nearly wide open, it will start to open the larger venturi as needed
for load/fuel demand.
• With loads applied, CT1 - Wires 398A/399A and CT2 - Wires 398B/399B deliver approximately 0- 1.5 VAC based
on percentage of Amps (load).
Approximate Values (when back-probed at connector):
25 Amps = 0.380 mVAC
50 Amps = 0.755 mVAC
75 Amps = 1.133 VAC
100 Amps = 1.510 VAC
DANGER
Electrocution. Lethal voltage may be present
at current transformers (CTs). Do not touch
CTs while primary current is applied. Doing so
will result in death or serious injury. (000310)
1 2 3 4 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
J3 J2 J8
TO PCB
J9
MAIN
F1 CONTROLLER
Running
J1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
194
23
0
23
0 0 DC COMMON
Figure 4-29.
Utility Pickup
N1 240VAC
UTILITY
N2 INPUT
120VAC
T1
LOAD SUPPLY
1 2 3 4 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
N1
J3 J2
N2
J8 T1
TO PCB
J9
MAIN
F1 CONTROLLER
Running/Cooling Down
J1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
N1
N2
23
N2
N1
TRANSFER
003226
Figure 4-31.
Engine Shutdown
Following re-transfer back to the Utility source an “engine cool-down timer” on the controller starts timing. When the
timer has expired (approximately one minute), the controller will de-energize the internal run relay removing fuel from
the engine. The following events will occur:
• Wire 14 (run circuit) will de-energize and the fuel solenoid will close to terminate the fuel supply to the engine.
• The controller’s logic will connect the engine’s ignition magnetos to ground via Wire 18. Ignition will terminate.
• Without fuel flow and without ignition the engine will shut down.
18
18
14
14
1 2 3 4 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
J3 J2 J8
TO PCB
J9
18
MAIN
FS F1 CONTROLLER
Stopping
J1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
18 IM1 SP1
18 IM2 SP2
003227
Figure 4-33.
120 VAC
T1 T1
LOAD SUPPLY
N1 00 2 44 0 6
T1 N2 11 4 BATTERY CHARGER
1 2 3 4 5 6 7 8 9 10 11 12 13 14
Running - Utility Loss
J5
CONTROLLER
PRINTED CIRCUIT BOARD
J4
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 003243
Figure 4-35.
1 2 3 4 5 6 7 8 9 10 11 12 13 14
Ready to Run
J5
TO PCB
CONTROLLER
PRINTED CIRCUIT BOARD
F1
J3
J4
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
0 13
13 13 13
BATTERY
SCR
0 16
SC
SM
003244
Figure 4-36.
OPTIONAL
BATTERY WARMER
1 240Vac 2 NEUTRAL
CONNECT
N1A N2A
OPTIONAL
OIL WARMER
N1B 1 240Vac 2 N2B
CONNECT 00 WHT
N1 N2
00
6
4
0 T1A
11 MOV
N1 N1 240 VAC
44 UTILITY
N2 N2 INPUT
120 VAC
T1 T1
LOAD SUPPLY
N1 00 2 44 0 6
T1 N2 11 4 BATTERY CHARGER
1 2 3 4 5 6 7 8 9 10 11 12 13 14
Utility Dropout
J5
Pausing 10 seconds
CONTROLLER
PRINTED CIRCUIT BOARD
J4
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 003246
Figure 4-38.
1 2 3 4 5 6 7 8 9 10 11 12 13 14
Crank Atempt # 1
J5
TO PCB
CONTROLLER
PRINTED CIRCUIT BOARD
4 0
GOVERNOR
F1
ACTUATOR
J3
FIELD BOOST
DIODE J4
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
90 0 13 818 85 14 86 18 56 194
56 817 819 820 210 209 23
56 56
820
817
56 85 818
819
A
SCR HTO
86
B 14 CS
0 0
14
LOP FS
14
0 0
0
0 0
SP1
IM1 18
13 13 13
BATTERY
12V
SCR
0 16 SP2
SC
IM2 18
SM
003247
Figure 4-40.
CB1
POWER
WINDING
44 44
240 VAC
GENERATOR
STATOR 22
33
11
OUTPUT
CB2
11
11
POWER
WINDING 11 44
ROTOR 33
BA EXCITATION 22
0 4 2 6 WINDING
NEUTRAL
C1
PIN # 6 5 4 3 2 1
0 4 2 6 11 44
00 00 WHT
00
6 6
4 4
0 0 T1A
11 MOV
44
4
120 VAC
T1 T1
LOAD SUPPLY
0 00 2 44 0 6
FIELD BOOST T1 11 4 BATTERY CHARGER
DIODE
1 2 3 4 5 6 7 8 9 10 11 12 13 14
Running - Utility Loss
J5 11C
J4
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 003248
Figure 4-42.
Transfer to Standby
In Figure 4-45 the Generator is running, the controller's “engine warm-up” timer has expired and generator AC output
is available to the transfer switch Terminal Lugs E1 and E2 and to the open contacts on the transfer relay. Transfer to
Standby may be briefly described as follows:
• 12 VDC is delivered to the transfer relay coil (TR1 - Terminal A) via Wire 194. The 12 VDC circuit is completed
back to the controller via Wire 23 (TR1 - Terminal B). However, the controller’s logic holds Wire 23 open from
ground and the TR1 relay is de-energized.
• When the “engine warm-up timer” expires, the controller will take Wire 23 to ground. The TR1 relay energizes
and its normally open contacts close (standby position).
• Generator voltage is now delivered to the standby closing coil (C2), via Wire E1 and E2, the now closed TR1
contacts, Wire 205, the limit switch (SW3), Wire B, and a bridge rectifier. The standby closing coil energizes and
the main current carrying contacts of the transfer switch are actuated to the “Standby” position.
• As the main contacts move to the “Standby” position, a mechanical interlock actuates SW3 to its open position
and limit switch (SW2) to the “Utility” position. When SW3 opens the C2 coil de-energizes.
• Generator voltage is now available to the LOAD terminals (T1 and T2) of the transfer switch.
1 2 3 4 5 6 7 8 9 10 11 12 13 14
Running - Utility Loss
CONTROLLER
PRINTED CIRCUIT BOARD
J4
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
194
23
194 + BATTERY
TR1
23 TRANSFER 003249
Figure 4-44.
OPTIONAL
BATTERY WARMER
1 240Vac 2 NEUTRAL
CONNECT
N1A N2A
OPTIONAL
OIL WARMER
N1B 1 240Vac 2 N2B
CONNECT 00 WHT
N1 N2
00
6
4
0 T1A
11 MOV
N1 N1 240 VAC
44 UTILITY
N2 N2 INPUT
120 VAC
T1 T1
LOAD SUPPLY
N1 00 2 44 0 6
T1 N2 11 4 BATTERY CHARGER
1 2 3 4 5 6 7 8 9 10 11 12 13 14
Running / Cooldown
J5
CONTROLLER
PRINTED CIRCUIT BOARD
J4
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 003250
Figure 4-46.
Engine Shutdown
Following re-transfer back to the Utility source an “engine cool-down timer” on the controller starts timing. When the
timer has expired (approximately one minute), the controller will de-energize the internal run relay removing fuel from
the engine. The following events will occur:
• The DC circuit to Wire 14 and the fuel solenoid will open. The fuel solenoid will de-energize and close to
terminate the fuel supply to the engine.
• The controller’s logic will connect the engine’s ignition magnetos to ground via Wire 18. Ignition will terminate.
• Without fuel flow and without ignition the engine will shut down.
1 2 3 4 5 6 7 8 9 10 11 12 13 14
Utility Good –
Engine Shutdown
CONTROLLER
PRINTED CIRCUIT BOARD
J4
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
18
SP1
IM1 18
SP2
IM2 18
003251
Figure 4-48.
Overloaded
Overload Check for Overloaded
ALARM 2103 Unit has run and attempted to accept load 10 times, could not accept due to
Remove Load condition on unit
overload condition
ENGINE DOES
NOT CRANK TEST 50 – CHECK
GOOD FUEL SUPPLY AND
PRESSURE
BAD GOOD
BAD
REPAIR OR
REPAIR OR REPLACE SHORTED
REPLACE WIRE 18 OR CIRCUIT
BOARD
TEST 60 – CHECK
PROCEED TO PROBLEM 16
NO SIGNAL IGNITION
MAGNETOS
IMPORTANT NOTE: Clear any faults in the controller before proceeding with any running diagnostic steps!
Problem 15 – Engine Will Not Crank When Utility Power Source Fails
ON ENGINE DOES
NOT CRANK
SWITCH IS “OFF”
BAD
REPLACE CONTROLLER
ASSEMBLY
Problem 16 – Engine Will Not Crank When Controller Switch is Set to MANUAL
TEST 46 – CHECK
TEST 45 – CHECK GOOD GOOD
TEST 44 – CHECK GOOD WIRE 56 VOLTAGE
7.5 AMP FUSE BATTERY
GOOD
BAD RECHARGE / BAD
BAD
REPLACE V-TWIN SINGLE
CYLINDER
UNITS
UNITS
REPLACE
REPLACE
CONTROLLER
ASSEMBLY TEST 47 – CHECK
BAD
STARTER
CONTACTOR
TEST 42 – TEST
RECHECK RELAY (SCR)
GOOD AUTO-OFF-MANUAL
TEST 46
MODE
BAD
WA R N I N G : D O N O T R O TAT E
GOOD TEST 49 – TEST GOOD
ENGINE WITH ELECTRIC STARTER
STARTER MOTOR
WITH SPARK PLUGS REMOVED.
ARCING AT THE PLUG ENDS MAY
IGNITE THE LP OR NG VAPOR BAD REPLACE BAD
EXITING THE SPARK PLUG HOLE.
IMPORTANT NOTE: Clear any faults in the controller before proceeding with any running diagnostic steps!
BAD
BAD BAD
BAD BAD
TEST 55 –
TEST 57 – TEST 63 – TEST 58 –
CHECK FOR
GOOD CHECK SPARK GOOD CHECK AND GOOD CHECK ENGINE
IGNITION
PLUGS ADJUST VALVES COMPRESSION
SPARK
BAD
BAD
GOOD BAD
BAD
CLEAN,
REGAP OR READJUST
REPLACE
CHECK
FLYWHEEL REPLACE FUEL
KEY REGULATOR
BAD
BAD
IMPORTANT NOTE: Clear any faults in the controller before proceeding with any running diagnostic steps!
Problem 18 – Engine Starts Hard and/or Runs Rough / Lacks Power / Backfires / Hunting /
Erratic Operation
BAD READJUST
BAD
TEST 60 – CHECK
IGNITION MAGNETOS
CLEAN, REGAP
OR REPLACE GOOD
BAD
ADJUST OR
REPLACE
IMPORTANT NOTE: Clear any faults in the controller before proceeding with any running diagnostic steps!
TEST 65 – TEST
EXERCISE
FUNCTION
REPLACE CONTROLLER
BAD BAD
GOOD
GOOD REPAIR
OR
TEST 81 – CHECK REPAIR REPLACE
T1/T2 VOLTAGE IN BAD OR
TRANSFER SWITCH REPLACE
REPLACE STOP TESTING. BATTERY
CONTROLLER CHARGER IS
GOOD FUNCTIONING PROPERLY
IMPORTANT NOTE: Clear any faults in the controller before proceeding with any running diagnostic steps!
Results
Test 41 – Try a Manual Start 1. If controller failed either Step 2 or Step 3, replace
General Theory the controller assembly.
2. If the controller passed Step 2 and Step 3, refer
The first step in troubleshooting for an “Engine Won’t
back to flow chart.
Crank” condition is to determine if the problem is related
to automatic operations only or if the engine will not crank
manually either. Test 43 – Test Auto Operations of
Controller (Evolution and Nexus)
Procedure
1. Set the controller to OFF.
General Theory
2. Set the main line circuit breaker (MLCB) to the Initial Conditions: The generator is in AUTO, ready to run,
“Open” position. and voltage is being supplied by Utility. When Utility fails
3. Set the controller set to MANUAL. (below 65% of nominal), a 10 second (optionally
a. The engine should crank cyclically through its programmable) line interrupt delay time is started. If the Utility
“crank-rest” cycles until it starts. is still gone when the timer expires, the engine will crank and
start. Once started a 10 second “engine warm-up timer” will
b. Let the engine stabilize and warm up for a few
be initiated. When the warm-up timer expires, the controller
minutes after it starts.
will transfer the load to the generator. If Utility voltage is
Results restored (75% of nominal) at any time from the initiation of the
engine start until the generator is ready to accept a load (5
1. If the engine cranks manually, but does not crank
second warm-up time has not elapsed), the controller will
automatically, refer back to flow chart.
complete the start cycle and run the generator through its
2. If the engine does not crank manually proceed to normal cool down cycle; however, the voltage will remain on
Problem 16. the Utility source.
Results
Refer back to the flow chart.
3. Verify all cable clamps are tight. The Red battery NOTE: Connect positive cable first.
cable from the starter contactor (SC) must be
securely attached to the positive (+) battery post. Procedure E.Test Battery State of Charge
The Black cable from the frame ground stud must (Non-Maintenance Free Battery Only)
be tightly attached to the negative (-) battery post. 1. Use an automotive type battery hydrometer to test
Procedure C. Perform a Conductance Test with a battery state of charge.
Conductance Type Battery Tester 2. Follow the hydrometer manufacturer’s instructions
1. Remove 7.5 amp fuse from the controller. carefully. Read the specific gravity of the
2. Remove the T-1 fuse from the Transfer Switch to electrolyte fluid in all battery cells.
disable the battery charger. 3. If cells are low, distilled water can be added to refill
3. Connect the test leads to the positive and negative cell compartment.
posts of the battery being tested, and follow the 4. If the hydrometer does not have a “percentage of
battery tester manufacturer’s instructions. Battery charge” scale, compare the reading obtained to the
Test results should not indicate anything lower than following:
60% of the battery’s rated CCA. a. An average reading of 1.260 indicates the
battery is 100% charged.
b. An average reading of 1.230 means the battery
is 75% charged.
c. An average reading of 1.200 means the battery
is 50% charged.
d. An average reading of 1.170 indicates the
battery is 25% charged.
I
NOTE: Disconnect negative cable first. Figure 4-56. Using a Battery Hydrometer
4. Test the load capability of the battery using a lead 5. Test Battery Condition:
acid battery load tester. a. If the difference between the highest and
lowest reading cells is greater than 0.050 (50
points), battery condition has deteriorated and
the battery should be replaced.
b. If the highest reading cell has a specific gravity
of less than 1.230, the test for condition is
questionable. Recharge the battery to a 100
percent state of charge, then repeat the test for
condition.
002408
Figure 4-58. The Output Screens
002411 5. Navigate to the Digital Output Screen using the
A. Liquid Level menu system for the controller being worked on.
a. See Figure 4-58. Digital Output 6 is Wire 56
Cell # Specific Gravity output from the board.
1 1.255 6. Set the controller to MANUAL and observe digital
output Number 6. If the controller is working
2 1.260 HIGH READING correctly output Number 6 will change from a “0” to
3 1.235
a “1”. Observe and record the change in state.
35 POINTS DIFFERENCE a. Nexus Controller - Move to MANUAL position
4 1.250
to view change of state.
5 1.240 LOW READING b. Evolution Controller - Press MANUAL button
to view change of state.
6 1.225
c. If the controller indicated a “1” then proceed to
Figure 4-57. Reading a Battery Hydrometer the next step.
7. Nexus with Amp (black) connectors: go to step 9.
Test 46 – Check Wire 56 Voltage 8. Evolution and Nexus with Molex (white)
General Theory connectors: Set a DMM to measure DC volts. Use
one meter lead to back probe Wire 56 at the
During an automatic start or when starting manually, an controller connector, leaving the connector
internal crank relay energizes. Each time the crank relay connected to the controller. Connect the other
energizes, the controller should deliver 12 VDC to a starter meter lead to ground. Set the controller to
contactor relay (SCR), or starter contactor (SC) and the MANUAL and measure the voltage.
engine should crank. This test will verify (a) that the crank a. If battery voltage is measured go step 8.
relay on the controller is energizing, and (b) that the
b. If no voltage is measured replace the
controller is delivering 12 VDC to the SCR relay or the SC.
controller.
NOTE: If the unit does not crank the Alarm Log will 9. Set a DMM to measure resistance.
display, “Stopped-Alarm RPM Sense Loss.” 10. Remove 7.5 amp fuse.
Procedure 11. Disconnect the harness connector from the
controller.
1. Set the DMM to measure DC voltage.
12. Remove Wire 56 from the starter contactor relay
2. Locate and disconnect Wire 56 from the SCR on V-
(V-twin units) or from the starter contactor (single
Twin units and the SC on single cylinder units.
cylinder units).
3. Connect one meter test lead to Wire 56 and the
13. Connect one meter test lead to disconnected Wire
other meter test lead to the battery negative
56 and connect the other meter test lead to the
terminal.
controller side of the harness (Wire 56), measure
4. Set the controller to MANUAL. Observe the meter. and record the resistance.
The DMM should indicate battery voltage. If battery
voltage was measured, stop testing and refer back Results
to the flow chart. If voltage was NOT measured, 1. If the DMM indicated battery voltage in Step 4,
proceed to Step 5. refer back to the flow chart.
NOTE: If controller is in an Alarm State, digital output will 2. If the Digital Output in Step 5 did not change,
not change. Clear the fault prior to performing Step 5. replace the controller.
Diagnostic Repair Manual 167
Section 4.6 Diagnostic Tests
3. If the DMM did NOT indicate CONTINUITY in Step 10. Disconnect Wire 0 from the SCR.
13, repair or replace Wire 56 between the controller 11. Connect one meter test lead to Wire 0 and connect
side of the harness and the relay or contactor. the negative meter test lead to common ground,
4. If wire did have continuity and the controller measure and record the resistance.
indicated “1” in step 6 then replace controller.
Results
Test 47 – Test Starter Contactor Relay 1. If battery voltage was NOT measured in Step 3, repair
(V-Twin Engine) or replace Wire 13 between the SCR and the SC.
2. If battery voltage was NOT measured in Step 7 and
General Theory CONTINUITY was measured in Step 11, replace
The starter contactor relay (SCR) located in the control the SCR.
panel must energize for cranking to occur. Once 3. If CONTINUITY was NOT measured in Step 11,
energized the normally open contacts of the SCR will repair or replace Wire 0.
close and battery voltage will be available to Wire 16 and 4. If battery voltage was measured in Step 6, refer
to the starter contactor (SC). back to flow chart.
16
13 Test 48 – Test Starter Contactor
General Theory
The coil in the starter contactor (SC) must energize and
13 16
its normally open contacts close or the engine will not
COM NO
crank. This test will determine if the SC is working.
Procedure
56
0 Carefully inspect the starter motor cable that runs from the
56 0 battery to the starter motor. Cable connections must be
002407 clean and tight. If connections are dirty or corroded, remove
Figure 4-59. Starter Contactor Relay (V-Twin Engine) the cable and clean cable terminals and terminal studs.
Procedure Replace any cable that is defective or badly corroded.
1. Set a DMM to measure DC voltage. See Figure 4-60 and Figure 4-61 for Test Points.
2. Disconnect Wire 13 from the SCR located in the A A C
control panel.
3. Connect the positive meter test lead to Wire 13 and
B B
connect the negative meter test lead to a common
ground. Measure and record the voltage.
4. Connect Wire 13 to the SCR. D
5. Disconnect Wire 16 from the SCR.
6. Connect the positive meter test lead to the
002406
terminal on the SCR from which Wire 16 was A. Test Point A C. Starter Contactor
removed and connect the negative meter test lead B. Test Point B D. Starter Motor
to a common ground. Figure 4-60. Starter Contactor (V-Twins and units
with 426cc Engine)
IMPORTANT NOTE: Do not test wire.
56 16
7. Set the controller to MANUAL. Measure and record
the voltage.
a. If voltage is measured, stop testing and go to
B
the results of this test procedure.
b. If voltage is not measured, continue to the next
step.
A
8. Set the DMM to measure resistance.
9. Remove Wire 56 and Wire 0 from the SCR.
Measure and record the resistance at the terminals 13
A. Test Point A
where Wire 56 and Wire 0 were removed. If B. Test Point B
0
resistance was not measured replace the SCR. If 13
003270
resistance was measured go to Step 10. Figure 4-61. Starter Contactor (410cc Single Cylinder
Engine Units Only)
168 Diagnostic Repair Manual
Section 4.6 Diagnostic Tests
Checking The Pinion • The gaseous fuel system must be properly tested
for leaks following installation and periodically
When the starter motor is activated, the pinion gear
thereafter. No leakage is permitted. Leak test
should move and engage the flywheel ring gear. If the
methods must comply strictly with gas codes.
pinion does not move normally, inspect the pinion for
binding or sticking. DANGER
Explosion and fire. Fuel and vapors are extremely
flammable and explosive. No leakage of fuel is
permitted. Keep fire and spark away. Failure to do
so will result in death or serious injury.
(000192)
IMPORTANT NOTE: Verify that the fuel selector is
A properly set for the supplied fuel type.
002403
Procedure
A. Pinion
Figure 4-64. Check Pinion Gear Operation (V-Twins A water manometer or a gauge that is calibrated in
and units with 426cc Engine) “inches of water column” should be used to measure the
fuel pressure. Fuel pressure at the inlet side of the fuel
solenoid valve should be between 3.5-7 inches
A (Evolution) or 5-7 inches (Nexus) water column for natural
gas (NG), or 10-12 inches water column for LP gas.
1. See Figure 4-66, Figure 4-67, and Figure 4-68 for
the gas pressure test point on the fuel regulator. The
fuel pressure can be checked at Port 1 (A) on all fuel
regulators, and at Port 3 (B) on 12-20 kW units.
2. With the manometer connected properly, crank the
003272
A. Pinion
engine. Nominal fuel pressure should be
measured. If pressure is not measured while
Figure 4-65. Check Pinion Gear Operation (410cc cranking refer back to flow chart.
Single Cylinder Engine Units Only)
NOTE: Where a primary regulator is used to establish
Test 50 – Check Fuel Supply and fuel inlet pressure, adjustment of that regulator is usually
Pressure the responsibility of the fuel supplier or the fuel supply
system installer.
General Theory
NOTE: The static pressure port (before solenoid) is
The air-cooled generator was factory tested and adjusted ALWAYS closest to the solenoid, regardless of the
using natural gas as a fuel. If desired, LP (propane) gas demand regulator/plenum tank configuration.
may be used. However, when converting to propane,
some minor adjustments are required. The following Units with a Plenum Tank Only
conditions apply for a unit to operate correctly:
The Port 3 (B) below the fuel solenoid may be used to take a
• An adequate gas supply and sufficient fuel pressure fuel pressure reading before the fuel solenoid. Consistent
must be available or the engine will not start. pressure should be measured at this port both while the
• Minimum recommended gaseous fuel pressure at the generator is running and when the generator is off.
generator fuel inlet connection is 5 inches water
column (Nexus) or 3.5 inches (Evolution) for natural
Results
gas (NG) or 10 inches water column for LP gas on 1. If fuel supply and pressure are adequate, but
Nexus and Evolution. engine will not start refer back to the flow chart.
• Maximum gaseous fuel pressure at the generator 2. If generator starts but runs rough or lacks power,
fuel inlet connection is 7 inches water column for repeat the above procedure with the generator
natural gas or 12 inches water column for LP gas. running and under load. The fuel supply system must
be able to maintain between 3.5-7 inches (Evolution)
• When propane gas is used, only a “vapor or 5-7 inches (Nexus) water column for natural gas
withdrawal” system may be used. This type of (NG), or 10-12 inches water column for LP gas. If
system utilizes the gas that forms above the liquid proper fuel supply and pressure is maintained, refer
fuel. The vapor pressure must be high enough to to Problem 18 – Engine Starts Hard and/or Runs
ensure engine operation. Rough / Lacks Power / Backfires / Hunting /
Erratic Operation.
002414
Figure 4-69. The Output Screens
003274 7. Output 5 is Wire 14 out from the controller. If the
Figure 4-67. Gas Pressure Test points (10 kW) controller is functioning properly, Output 5 will
change from a “0” to a “1” while the unit is cranking.
a. If the DMM did NOT indicate voltage in Step 5
A
and output did not change in Step 7, replace
the controller.
b. If the DMM did NOT indicate voltage in Step 5
and the output in Step 7 changed, proceed to
Step 11.
B 8. Disconnect the 7.5 amp Fuse.
9. Disconnect the appropriate harness connector
from the controller.
10. Set a DMM to measure resistance.
002413 11. Connect one meter test lead to Wire 14
Figure 4-68. Gas Pressure Test points (12-20 kW) (disconnected in Step 3). Connect the other meter
test lead to Wire 14 at the controller side of the
Test 51 – Check Controller Wire 14 harness connector (Wire 14). See “Appendix A” for
proper wire and connector pin identification.
Outputs
a. If the DMM indicated CONTINUITY repeat
General Theory Step 5 and then retest.
During any crank attempt, the controllers crank relay and b. If CONTINUITY is not measured, repair or
run relays both are energized. When the run relay replace Wire 14 between the controller
energizes, its contacts close and 12 VDC is delivered to harness connector and the fuel solenoid.
the Wire 14 circuit and to the fuel solenoid. The solenoid Results
energizes open to allow fuel flow to the engine. This test
will determine if the controller is working properly. Refer back to flow chart.
Test 52 – Check Fuel Solenoid is de-energized, and closed when the choke solenoid is
energized.
General Theory
8 kW: See Figure 4-73. A choke solenoid (A), located on
In Test 51, if battery voltage was delivered to Wire 14, the the air box, energizes only during cranking to assist starting.
fuel solenoid should have energized open. This test will When energized the solenoid is closes the choke plate (B).
verify whether or not the fuel solenoid is operating.
6 kW EcoGen: A Choke Solenoid is located below the air
box and only energizes during cranking to assist starting.
Fuel Solenoid FS1 Nominal Resistance 15-16 ohms When energized, the solenoid is closed.
Fuel Solenoid FS2 Nominal Resistance 29 ohms
A
Procedure: 8 and 12-20 kW Units
1. See Figure 4-66 or Figure 4-68. Install a
manometer to Port 2 on the fuel regulator.
2. Set the controller to MANUAL.
3. Proper gas pressure should be measured during
cranking. If gas pressure is measured, the fuel B
solenoid is operating. If gas pressure is not
measured, repair or replace the fuel solenoid.
Procedure: 10 kW Units
1. See Figure 4-67. Remove the hose from fuel Figure 4-70. Solenoid De-Energized, Choke Closed
solenoid (FS2) and install a manometer to Port 2 12-20 kW Units
on the fuel regulator.
2. Set the controller to MANUAL.
3. Proper gas pressure should be measured during
cranking. If gas pressure is measured, both fuel
solenoids are operating. Discontinue testing.
4. If gas pressure was not measured in Step 3,
remove fuel solenoid FS2 and install a manometer A
to the bottom port of the fuel regulator.
5. Set the controller to MANUAL.
6. Proper gas pressure should be measured during
cranking. If gas pressure is measured, fuel B
solenoid FS1 is operating. Replace fuel solenoid
FS2. If gas pressure is not measured, repair or
replace fuel solenoid FS1. Figure 4-71. Solenoid Energized, Choke Open
12-20 kW Units
Results
If fuel pressure was measured in any of the preceding C
tests it indicates that the fuel solenoid is operating
properly. Refer back to the flow chart for the next test.
90 56 56 90
2 1 1 2
2 1 1 2
FEMALE SIDE MALE SIDE 003285
FEMALE SIDE MALE SIDE 003288
Figure 4-74. C3 Choke Solenoid Connector Figure 4-75. CS Choke Solenoid Connector
6. Set the controller to MANUAL. While cranking, the 6. Set the controller to MANUAL. While cranking, the
DMM should indicate battery voltage cyclically. DMM should indicate battery voltage.
a. If the DMM did NOT indicate battery voltage, a. If the DMM did NOT indicate battery voltage,
verify CONTINUITY of Wire 90 between the verify CONTINUITY of Wire 90 between the
connector and controller side of Wire 90 and connector Pin 1 J4 (Wire 90) and verify
verify CONTINUITY of Wire 14 between the CONTINUITY of Wire 14 between the
connector and controller side of Wire 14. connector Pin 9 J4 (Wire 56). Repair or replace
Repair or replace any wiring as needed. any wiring as needed.
Diagnostic Repair Manual 173
Section 4.6 Diagnostic Tests
b. If the DMM indicated battery voltage proceed 11. With the generator running at a rated speed of
to Step 7. approximately 60 Hz, verify that the choke is de-
7. Set the controller to MANUAL. While cranking, the energized and the choke plate is open.
DMM should indicate battery voltage.
Results
8. Set a DMM to measure resistance.
1. If the DMM did NOT indicate battery voltage in
9. Connect one meter test lead to Pin 1(Wire 56) on
Step 6 and wire CONTINUITY was good, replace
the male side of the CS connector and the other
the controller.
meter test lead to Pin 2 (Wire 90). Measure and
2. If the DMM did NOT indicate approximately 3.7
record the resistance.
ohms (10 kW units) and 6-7 ohms (EcoGen 6 kW
10. Connect the choke solenoid.
units) in Step 9, replace the choke solenoid.
1=CHOKED
Note: The first second of each crank cycle is equal to two (2) revolutions of the engine.
0=OPEN
Seconds
Crank Cycle 1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
10 kW/EcoGen 6 kW 0 1 1 1 1 1 1 1 0 0 1 1 1 1 1 1
12 kW-20 kW 0 1 1 0 0 1 1 1 0 0 0 1 1 1 1 1
10 kW/EcoGen 6 kW 1 1 1 0 1 1 1 1 0 0 1 1 1 1 1 1
12 kW-20 kW 0 1 1 0 0 0 0 0 0 0 0 1 1 1 1 1
10 kW/EcoGen 6 kW 0 0 0 0 1 1 1
12 kW-20 kW 0 0 1 1 1 1 1
10 kW/EcoGen 6 kW 0 1 1 1 1 1 1
12 kW-20 kW 0 1 0 0 0 0 0
10 kW 0 1 1 1 1 0 0
12 kW-20 kW 0 0 0 0 1 1 1
Test 55 – Check for Ignition Spark 7. See Figure 4-78. To determine if an engine miss is
ignition related, connect the spark tester in series
General Theory with the spark plug wire and spark plug. Then,
If the engine cranks but will not start, one cause might be crank and start the engine. A spark miss will be
that an ignition system failure has occurred. A special readily apparent. If spark jumps the spark tester
spark tester can be used to check for ignition spark. gap regularly, but the engine miss continues, the
problem is in the spark plug or in the fuel system.
V-Twin Only
8. Repeat Step 1 through 7 on the second cylinder.
NOTE: A sheared flywheel key may change ignition timing
but sparking will still occur across the spark tester gap.
Procedure
See Figure 4-79 for types of engine related spark plug
problems.
1. Remove spark plug(s) and inspect for any visible
damage.
Figure 4-77. Checking Ignition Spark
2. Replace any spark plug having burned electrodes NOTE: Always check the specifications of the unit you
or cracked porcelain. are working on for correct plug and settings.
3. See Figure 4-80. Using a wire feeler gauge set the
gap on new or used spark plugs as per Table 4-12. Test 58 – Check Engine / Compression
A C
Test / Cylinder Leak Down Test
Introduction
Performing the following test procedures will accurately
diagnose some of the most common problems:
• Will not start • Vibration
• Lack of power • Overheating
• Runs Rough • High Oil Consumption
Check Compression
B
General Theory
D
Lost or reduced engine compression can result in a failure
of the engine to start, or rough operation. One or more of
the following will usually cause loss of compression:
• Blown or leaking cylinder head gasket.
• Improperly seated or sticking-valves.
• Worn piston rings or cylinder (this will also result in
high oil consumption).
002418 For air-cooled engines, the minimum allowable
A. Normal C. Misfires
compression pressure for a cold engine is typically 150
PSI. Compression values are based on accurate process
B. Pre Ignition D. Detonation and proper procedure. However, testing has proven that
an accurate indication of compression in the cylinder can
Figure 4-79. Spark Plug Conditions
be obtained by using the following procedure.
Results
NOTE: Battery and starting system must be in good
1. Clean, re-gap or replace plugs as necessary, condition to get accurate results.
repeat test.
2. If spark plugs are good, refer back to flow chart. IMPORTANT NOTE: Valve adjustment is critical to
proper compression testing. Verify valve adjustment
is correct before proceeding with test.
Procedure
1. Shut off the fuel supply to the unit.
2. Remove both spark plugs.
3. Place a jumper wire from the spark plug boot wire
terminal to ground, OR ground Wire 18 at the
000211
magneto lead connects to harness connection to
Figure 4-80. Checking Spark Plug Gap disable spark.
4. Unplug the stepper motor connector from the
Table 4-12. Spark Plug Gap controller and open the throttle to wide open.
5. Insert a compression gauge into the cylinder.
Engine kW Recommended
Plug Gap Manufacturer 6. Crank the engine until there is no further increase
Size Rating Plug
in pressure.
410 cc 8 0.030 inch RC12YC Champion
7. Record the highest reading obtained.
426 cc 9 0.020 inch RC12YC Champion
8. Repeat the procedure for the remaining cylinder if
530 cc 10 0.030 inch BPR6HS NGK applicable and record the highest reading.
990 cc 12-17 0.040 inch RC14YC Champion NOTE: See Specifications in Section 1.1 for acceptable
999 cc 20 0.030 inch RC12YC Champion compression values.
5. To remove the thickness gauge, rotate the flywheel 12. Connect one meter test lead to one of the wires
(manually). removed from the ignition magneto(s). Connect the
other test lead to an engine ground. INFINITY
A
should be measured. If CONTINUITY is measured,
replace the shutdown harness.
B
C
B
D
002422
A. 0.008-0.012” Gauge
B. Magneto A. Remove leads D. Wire 18 to circuit board
B. Engine wire harness E. Spark plug
Figure 4-86. Setting Ignition Magneto Air Gap C. Stud connector
6. Repeat the above procedure for the second Figure 4-87. Engine Ground Harness
magneto.
13. Check the flywheel magnet by holding a
7. Repeat Test 55 – Check for Ignition Spark and screwdriver at the extreme end of its handle and
check for spark across the spark tester gap. with its point down. When the tip of the screwdriver
a. A spark test may be conducted with unit is moved to within 3/4 inch (19 mm) of the magnet,
disassembled by following this procedure. the blade should be pulled in against the magnet.
b. Battery must be connected. 14. For rough running or hard starting engines check
c. The harness connector must be connected to the flywheel key. The flywheel's taper is locked on
the controller. the crankshaft taper by the torque of the flywheel
d. Remove Wire 56 from the SCR located nut. A keyway is provided for alignment only and
beneath the controller. theoretically carries no load.
NOTE: Verify all debris is cleared from the engine NOTE: If the flywheel key becomes sheared or even
compartment and all body parts are clear from flywheel partially sheared, ignition timing can change. Incorrect
before proceeding. timing can result in hard starting or failure to start.
e. Refer to Test 55 – Check for Ignition Spark. NOTE: As stated earlier, the armature air gap is fixed for
f. Connect a jumper wire to the 194 terminal single cylinder engine models and is not adjustable.
block. Connect the other end to where Wire 56 Visually inspect the armature air gap and hold down
was disconnected in Step 7d. The engine bolts.
should crank once the jumper from 194 is Results
connected.
8. If spark was not indicated, replace magnetos. If sparking still does not occur after adjusting the
armature air gap, testing the ground wires and
NOTE: If gap is only adjusted, properly test the performing the basic flywheel test, replace the ignition
magnetos by cranking the engine before reassembly. magneto(s).
Spark should be present on both cylinders.
Procedure, Replacing Magnetos:
9. If air gap was not out of adjustment, test ground
wires. 1. Follow all steps of the Major Disassembly
procedures that are located in Section 6.
10. Set a DMM to the measure resistance.
2. Once the magnetos are visible, make note of how
11. See Figure 4-87. Disconnect the engine wire
they are connected.
harness from the ignition magnetos.
• Evolution Units and Nexus Single Cylinder NOTE: Each magneto has its own part number. Verify
Units – See Figure 4-82, Figure 4-84 and Figure the part number prior to installation.
4-85. Disconnect Wire 18 at the bullet connector. 3. See Figure 4-88. Cylinder one is the back cylinder.
• Nexus V-twin units – See Figure 4-83. Remove 4. See Figure 4-89. Cylinder two is the front cylinder.
Wire 18 from the stud located above the oil cooler.
Results
1. If the switch operated properly and proper oil
pressure was measured, and Wires 86 and 0
tested good, and/or the Input would not change on
the controller, replace the controller.
F
E
002432 001812
Figure 4-95. Testing the Oil Temperature Switch Figure 4-96. Valve Clearance Adjustment (9 kW -
426cc engine)
002380
Figure 4-97. Valve Clearance Adjustment (8 kW, 11-22
kW - 530cc through 999cc)
NOTE: Hold the rocker arm jam nut in place as the pivot
ball stud is turned.
5. When valve clearance is correct, hold the pivot ball
stud (D) in place with a wrench and tighten the rocker
arm jam nut. Tighten the jam nut according to the
Figure 4-98. Wire 18 Connection – Nexus V-Twin
following torque specifications: Units
7-8 kW 174 in-lbs (19.68 Nm)
9 kW 53 in-lbs (6.0 Nm)
11 kW 72 in-lbs (8.2 Nm)
16–22kW 174 in-lbs (19.68 Nm)
6. After tightening the jam nut, check valve clearance
again to verify it did not change.
7. Install new valve cover gasket.
8. Install the valve cover. Tighten fasteners in a cross
pattern to:
7-8 kW 48 in-lbs (5.4 Nm)
Figure 4-99. Wire 18 Connection Evolution V-Twin and
9 kW 80 in-lbs (9.0 Nm) Single Cylinder Units and Nexus Single Cylinder Units
11–22kW 60 in-lbs (6.8 Nm)
5. Disconnect Wire 18 from the stud on the Nexus V-
9. Repeat the process for the other cylinder if unit is a V- twin unit. On the Evolution V-twin and single
Twin. cylinder units, or Nexus single cylinder unit,
disconnect Wire 18 from magneto sensing lead.
Test 64 – Check Wire 18 Continuity a. Connect one meter test lead to an engine
ground and connect the other meter test lead
General Theory
to the magneto lead terminal.
During cranking and running, the controller receives a b. Set the controller to MANUAL and while unit is
pulse from the ignition magneto(s) via Wire 18. During cranking measure and record the voltage.
cranking, this signal has an AC voltage of approximately 3- c. If the DMM indicated approximately 3-6 VAC
6 Volts on V-twin engines, and approximately 2-3 Volts on for V-Twin and 2-3 VAC for single cylinder,
single cylinder engines. If the controller does not receive proceed to Step 6.
this signal, the unit will shut down due to no rpm sensing.
d. If the DMM did NOT indicate the appropriate
Procedure voltage, go back to the flow chart (Problem 14)
1. Set the DMM to measure AC voltage. and follow “No Signal” (Test 60).
2. See Figure 4-98 and Figure 4-99. 6. Set the DMM to measure resistance.
7. Disconnect the harness connector containing Wire
• On a Nexus V-twin unit, connect one meter test
18 from the controller.
lead to Wire 18 at the stud connector. Connect the
other meter test lead to an engine ground. 8. Connect one meter test lead to an engine ground
and connect the other meter test lead to Wire 18.
• On Evolution V-twin and single cylinder units and a. If the DMM indicated low resistance (.01),
the Nexus single cylinder units back probe the
check for a short to ground in the Wire 18
harness connector.
circuit.
184 Diagnostic Repair Manual
Section 4.6 Diagnostic Tests
Results
1. In all models, if the unit starts in MANUAL, but fails
002434
to exercise without any ALARMS present, replace
Figure 4-100. The Exercise Screen the controller.
Procedure: 8 kW-14 kW
NOTE: Utility voltage must be present.
Test 66 – Test Cranking and Running
Circuits
Make a record of the date and time the generator is set to
exercise. General Theory
1. Record the current date and time of the unit. This test will check all of the circuits that are “Hot” with
2. Navigate to the Exercise settings screen of the battery voltage and which could cause the Main Fuse to
controller being worked on. blow. Refer to Table 4-14 throughout the procedure for
3. Press “Enter”. the known resistance values of components.
4. Adjust exercise time to 5 minutes ahead of the date Figure 4-101 shows the DMM in two different states. The
and time noted in Step 1. left DMM indicates an OPEN circuit or INFINITY. The
5. Return to the Main Display where “READY TO right DMM indicates a dead short or CONTINUITY.
RUN” is displayed. The controller must be in AUTO Throughout the troubleshooting, refer to Figure 4-101 as
mode for the unit to exercise. needed to understand what the meter is indicating about
6. Watch the generator display and note the time. the circuit being tested.
When the date and time reaches the time that was
programmed for exercise the unit should crank and
run. “Running in Exercise” will display if the
exercise feature is working properly.
Results
2 1 1 2
1. Compare the results of Step 3 with Table 4-15.
a. If the DMM indicates less than the value in table FEMALE SIDE MALE SIDE 003285
4-16 at Test Point 1 proceed to Test 67 – Test Figure 4-102. C3 Choke Solenoid Connector
Run Circuit.
b. If the DMM indicates less than the value in Results
table 4-16 at Test Point 2 proceed to Test 68 – 1. If the DMM indicated less than 15 ohms in Step 3,
Test Crank Circuit. replace the FS solenoid.
c. If the DMM indicated proper resistance values 2. If the DMM indicated less than 30 ohms in Step 4,
at all Test Points, refer to FB3 (Evolution) or replace the FS2 solenoid.
FB4 (Nexus) Diode Test. 3. If the DMM indicated less than 3 ohms in Step 5,
replace the CS solenoid.
Test 67 – Test Run Circuit 4. Refer to Table 4-15 and if the DMM indicated the
correct resistance for the component, a short to
General Theory ground exists on Wire 14. Repair or replace Wire
Wire 14 provides 12 VDC during cranking and running. If the 14 as needed.
DMM indicated less than 15 Ohms in the previous test, one
possible cause could be a faulty harness or solenoid.
Procedure: 12 kW - 20 kW
1. Set a DMM to measure resistance.
Procedure: 8 kW 2. Disconnect Wire 14 from the fuel solenoid (FS) and
1. Set a DMM to measure resistance. the choke solenoid (CS).
2. Disconnect Wire 14 from the fuel solenoid (FS). 3. Connect one meter test lead to the FS terminal
3. Connect one meter test lead to the FS terminal from which Wire 14 was removed. Connect the
from which Wire 14 was removed. Connect the other meter test lead to the ground terminal.
other meter test lead to the ground terminal. Measure and record the resistance.
Measure and record the resistance.
186 Diagnostic Repair Manual
Section 4.6 Diagnostic Tests
4. See Figure 4-102. Connect one meter test lead to 2. Disconnect Wire 56 and 0 from the starter
Pin 1 on the male side of the CS connector. contactor relay (SCR).
Connect the other meter test lead to Pin 2. 3. Connect one meter test lead to the SCR terminal
Measure and record the resistance. from which Wire 56 was removed. Connect the
other meter test lead to the terminal from which
Results Wire 0 was removed. Measure and record the
1. If the DMM indicated less than 15 ohms in Step 3, resistance.
replace the FS solenoid. 4. See Figure 4-103. Connect one meter test lead to
2. If the DMM indicated less than 30 ohms in Step 4, Pin 1 on the male side of the CS connector.
replace the FS2 solenoid. Connect the other meter test lead to Pin 2.
3. Refer to Table 4-15 and if the DMM indicated the Measure and record the resistance.
correct resistance for the component, a short to
ground exists on Wire 14. Repair and replace Wire Results
14 as needed. 1. If the DMM indicated less than 155 ohms in Step 3,
replace the SCR relay.
Test 68 – Test Crank Circuit 2. If the DMM indicated less than 3 ohms in step 4
replace the CS solenoid.
General Theory 3. Refer to Table 4-14 and if the DMM indicated the
Wire 56 provides 12 VDC during cranking only. If the correct resistance for the component, a short to
DMM indicated less than 8 ohms (8 kW) at the starter ground exists on Wire 56. Repair and replace Wire
contactor or less than 155 ohms (10-20 kW) at the starter 56 as needed.
contactor relay in the previous test, one possible cause
could be a faulty relay or solenoid. Test 70 – Check to See If Low Speed
Function is Enabled
Procedure: 8 kW (Available only on certain models)
1. Set a DMM to measure resistance.
2. Disconnect Wire 56 from the starter contactor (SC)
General Theory
and on Nexus units disconnect the choke solenoid Some generators are equipped with a low speed
(CS). exercise function. When enabled, the low speed exercise
3. Connect one meter test lead to the SC terminal function allows the generator to exercise at 2400 rpm.
from which Wire 56 was removed. Connect the When low speed exercise is disabled the generator will
other meter test lead to the ground terminal. exercise at 3600 rpm.
Measure and record the resistance. Procedure – Evolution (If equipped)
4. See Figure 4-103. Connect one meter test lead to 1. From the main display enter the Edit Menu using
Pin 1 on the male side of the CS connector. the menu map.
Connect the other meter test lead to Pin 2.
2. Press UP or DOWN Arrow key until “Exercise
Measure and record the resistance.
Time” is displayed.
90 56 56 90 3. Press ENTER.
4. “Quiet Test Mode? Yes or No” will be displayed.
Press UP or DOWN Arrow key until “Yes” is
displayed.
2 1 1 2 5. Press ENTER to save change.
FEMALE SIDE MALE SIDE 003288 6. Return to Main Display.
Figure 4-103. CS Choke Solenoid Connector
Procedure – Nexus
Results 1. Navigate to the Set Exercise display screen of the
1. If the DMM indicated less than 8 ohms of controller being worked on and check to see if the
resistance in Step 3, a short exists. Repair or exercise function is enabled.
replace as needed.
Results
2. If the DMM indicated less than 3 ohms in step 4
replace the CS solenoid. Enable the exercise function if it is not already enabled.
Refer back to flow chart.
Procedure: 10 kW-20 kW
1. Set a DMM to measure resistance.
Test 75 – Test 120 Volt Input (T1) 60 Hz Test 77 – Check Wire 13 and Wire 0
240 Volt Input (T1 - T2) 50 Hz General Theory
General Theory The previous test indicated that battery voltage was not
The controller requires 120 VAC (60 HZ Unit) or 240 VAC available to the controller and it was operating only off of
(50 HZ Unit) supplied from the LOAD side of the the 120 VAC input from T1.
contactor in the transfer switch to function properly. When Procedure
the circuit is supplied to the controller it will allow the
1. Set DMM to measure DC voltage.
controller to remain ON, but in a disabled mode where it
will not crank or function properly. 2. Remove the 7.5 Amp fuse from the controller.
3. Connect one meter lead to the left side of the fuse
Procedure holder where the fuse was previously connected.
NOTE: “Inspect Battery” alarm may appear while Connect the other meter test lead to battery
performing this test procedure. Ignore this alarm, it is a negative (ground). Measure and record the
symptom of the test procedure. voltage.
4. Disconnect the appropriate harness connector
1. Locate the 7.5 amp fuse on the controller. from the controller.
2. Remove the fuse and observe the LCD screen. 5. Connect one meter test lead to harness connector
Results pin for Wire 13 and the other meter test lead to
harness connector pin for Wire 0. Measure and
1. If the controller remained illuminated or continued
record the voltage.
to show its status after the fuse was removed, the
120 VAC (60 Hz) or 240 VAC (50 Hz) input is good. Results
2. If the controller powered down when the fuse was 1. If the DMM indicated battery voltage in Steps 3 and
removed, the controller is not getting the 120 VAC 5, replace the controller.
(60 Hz) or 240 VAC (50 HZ) input. Return to the 2. If the DMM indicated battery voltage in Step 3, but
flow chart (Test 79). did NOT indicate battery voltage in Step 5, repair or
replace Wire 0 between the harness connector and
the ground stud.
Procedure Results
1. If the DMM indicated 120 VAC, proceed to check
NOTE: A “Low Battery” or “Inspect Battery” alert may be
voltage at the J5 connector, refer back to flow
generated during this test procedure. It will not effect the
chart.
results of the test and can be acknowledged when testing
is complete. 2. If the DMM indicated less than 120 VAC or 0, refer
back to flow chart.
1. Set the controller to MANUAL and crank the engine
for 2 -3 seconds. Test 80 – Check T1 Voltage at
2. Set the controller to OFF. Controller Connector
3. Disconnect the negative cable battery.
4. Set the DMM to measure DC amperage. General Theory
NOTE: Consult the meters owner’s manual to ensure If 120 VAC was available on the customer connection
proper setup of meter and that the internal fuse is good block between T1 and neutral for 60 Hz units, or 240 VAC
before proceeding. between T1 and T2 for 50 Hz units, the problem may be
an open wire or bad connector at the controller harness
5. Connect the positive (Red) meter test lead to the connection.
negative battery post and connect the negative
(Black) meter test lead to disconnected negative Procedure
battery cable. Measure and record the amperage. 1. Disconnect the controller connector at the control
panel.
Results
2. Set the DMM to measure AC voltage.
1. If the DMM indicated positive DC amperage
between 50 milliamps to 2.5 amps, stop testing. a. For 60 Hz units check the voltage at the
The charger is functioning properly. controller harness connector pin between Wire
T1 and the neutral connection on the customer
2. If the DMM indicated negative DC amperage,
connection block. If Voltage is present,
replace the controller.
proceed to Step 3. If voltage is not present
check the T1 wire from the customer
connection block to the controller harness
connector.
b. For 50 Hz units check the voltage at the
controller harness connector pins between T1
002435 and the neutral connection, then between T2
Figure 4-104. Positive DC Amps and the neutral connection on the customer
connection block. If voltage is not present
check the T1/T2 wires from the customer
connection block to the controller harness
connector. If Voltage is present, replace the
controller.
3. For 60 Hz units only, check the voltage between
002436 Wire 00 of the controller harness connector pin and
Figure 4-105. Negative DC Amps T1 at the customer connection block. If voltage is
present inspect and repair the connection pins at
controller harness connector. If voltage is not
available, check the 00 wire from the customer
connection block to the controller harness
connector.
4. If 120 VAC is present between T1 and 00 of the Test 82 – Test F3 Fuse Circuit
controller harness connector, and the pins are in
good condition, then the fault is in the controller. Procedure
Replace the controller. 1. Set a DMM to measure AC voltage.
2. Connect one meter test lead to the top side of the
Test 81 – Check T1/T2 Voltage in T1 fuse holder and connect the other test lead to
Transfer Switch the NEUTRAL connection. Measure and record the
voltage.
General Theory a. If the DMM indicated 120 VAC, proceed to Step 3.
If voltage was not present in the generator, the most b. If the DMM indicated less than 120 VAC or 0,
likely cause is a blown T1/T2 fuse or an open wire. verify that Load voltage is available to the
LOAD side of the CONTACTOR.
Procedure 3. Set the controller to OFF.
1. Set the DMM to measure AC voltage.
4. Disconnect Utility from the transfer switch.
2. Connect one meter test lead to the bottom side of
5. See Figure 4-106. Remove fuse F3 from the fuse
the T1 fuse holder (T1/T2 for 50 Hz units) and the
holder.
other meter test lead to the NEUTRAL connection.
6. Inspect and test fuses for an OPEN condition with
Measure and record the voltage.
a DMM set to measure resistance. CONTINUITY
Results should be measured across the fuse.
1. If the DMM indicated proper voltage, repair or Results
replace faulty wire between the generator and the
1. Replace blown fuse as needed and proceed to
fuse holder.
Problem 10 “Blown T1 Fuse.”
2. If the DMM indicated less than proper voltage or 0,
refer back to the flow chart. N1A N2A T1A N1A N2A T1A T2A
A A A A A A A
F1 F2 F3 F1 F2 F3 F3
B B B B B B B
N1 N2 T1 N1 N2 T1 T2
60 Hz Units 50 Hz Units 003304
Figure 4-106. Transfer Switch Fuse Block
Figure 5-3.
005459
Figure 5-5.
005461
Figure 5-9.
7. Remove Controller Mounting Box On Nexus 9. Loosen Side Panel: See Figure 5-11. Using a 10
Controllers: See Figure 5-11. On units with Nexus mm socket remove the two bolts from the base of
controllers, use an 8 mm socket to remove the two the enclosure side panel.
screws from the rear of the controller mounting 10. Unbolt Enclosure Side Panel Mounting
box. Use a 10 mm socket to remove the two bolts Bracket: See Figure 5-11. Using a 10 mm socket
from under the front of the controller mounting box. remove the two bolts from the enclosure side panel
mounting bracket.
Figure 5-11.
Figure 5-13.
8. Remove Engine Intake Baffle: See Figure 5-11.
Use a 10 mm socket to remove the two bolts from
the engine intake baffle. Pull baffle out carefully,
there are tabs holding the backside of the baffle to
the divider panel.
002644
002643
Figure 5-15.
002645
12. Remove Engine Divider Panel: See Figure 5-16. Figure 5-17.
Use a 10 mm socket to remove the rear 10 mm bolt
from the base of the enclosure. See Figure 5-17. 13. Remove Air Box on Nexus units: See Figure 5-
Remove the front 10 mm bolt from the base of the 18. Use a 6 mm Allen wrench to remove the four
enclosure. intake manifold socket head cap screws. See
Figure 5-19. Use a 4 mm Allen wrench to remove
the four airbox Allen head shoulder bolts. While
removing the airbox remove the four rubber
washers.
Figure 5-22.
Figure 5-23.
002651
Figure 5-25.
Figure 5-24.
002652
Figure 5-26.
2017 HSB Front Access 7. Remove Controls Cover: Use a 4mm Hex Allen
1. Set the controller to OFF. socket to remove the bolts and ground washer
from the controls cover.
2. Remove the 7.5 amp main fuse.
8. Remove the controls cover.
9. Remove the controller.
005459
Figure 5-27.
005465
Figure 5-30.
005467
005468
Figure 5-34.
005466
Figure 5-32.
19. Swing breaker with tray out of the way leaving the
wires on the outlet side of breaker connected.
20. Remove air cleaner cover and rubber inlet duct.
005469
005472
Figure 5-35.
Figure 5-38.
17. Remove the 2 inside cap screws under the breaker
tray connecting to the divider panel. 21. Remove the 2 brass colored mounting screws from
the divider panel to the base.
005470
Figure 5-36.
005473
Figure 5-39.
005471
Figure 5-37.
005476
Figure 5-42.
005474
Figure 5-40.
005477
Figure 5-43.
005475
Figure 5-41.
Major Disassembly
Safety
1. Set the controller to OFF.
2. See Figure 5-44. Remove the 7.5 amp main fuse.
3. Remove the N1 and N2 fuses from the transfer
switch.
Figure 5-46.
Figure 5-47.
Stator/Rotor/Engine Removal
1. Remove Top Exhaust Enclosure Covers: See
Figure 5-46. Use a 10 mm socket to remove the
nine bolts from the exhaust top covers. Remove
covers.
002658
Figure 5-48.
4. Remove Exhaust Flex Pipe: See Figure 5-49. 10. Remove the side panel by sliding it forward then
Use a ½” socket to remove the front and rear re-install the hinge bolt.
muffler clamp. Slide exhaust flex toward engine to
NOTE: The muffler has been removed for better view of
completely expose the muffler flange.
the bolts.
f
Figure 5-49.
002661
002661
5. Muffler Assembly: See Figure 5-50. Depending Figure 5-51.
on the clamp, use a ½” or 10 mm socket to remove
the muffler clamp and flex pipe. Leave muffler
attached to the divider panel.
002662
Figure 5-52.
Figure 5-53.
Figure 5-54.
003159
Figure 5-57.
003156
Figure 5-55.
003160
Figure 5-58. Brushes on Nexus Unit
Figure 5-61.
003163
Figure 5-62.
003164
Figure 5-60.
Figure 5-65.
003165
Figure 5-63.
Figure 5-67.
NOTE: Each model uses a specific rotor bolt. Verify the Figure 5-69.
correct bolt is being used for the rotor being serviced.
31. See Figure 5-70. Using proper lifting equipment
a. Cut 0.5 inches from the rotor bolt. Slot the end remove the engine.
of the bolt to suit a flat blade screwdriver.
b. Slide the rotor bolt back through the rotor and
use a screwdriver to screw it into the crankshaft.
Be sure to thread in a minimum of 3/8” to
ensure enough threads for puller cap screw.
c. Screw a 3” M12x1.75 cap screw into rotor.
d. Apply torque to the 3” M12x1.75 cap screw
until taper breaks free from crankshaft.
Figure 5-70.
Figure 5-68.
Torque Specifications
Introduction
The diagrams in this section are provided for general reference only. For unit specific diagrams refer to the Service and
Support page at the manufacturer’s website.
Introduction
The diagrams in this section are provided for general reference only. For unit specific diagrams refer to the Service and
Support page at the manufacturer’s website.
Introduction
The diagrams in this section are provided for general reference only. For unit specific diagrams refer to the Service and
Support page at the manufacturer’s website.
Section 6.5 0J9961-D WD/SD Air-cooled Pre 2016 HSB Evolution 11-22 kW 60 Hz
Introduction
The diagrams in this section are provided for general reference only. For unit specific diagrams refer to the Service and
Support page at the manufacturer’s website.
3 1
4 2
J3
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8
11 12 13 14 15 16 17 18 19 20
J1 J2 9 10 11 12 13 14 15 16
10 9 8 7 6 5 4 3 2 1 J5
003483
Figure A-6. Evolution 1.0 Air-cooled Panel and Connectors (Harness End)
J1 Connector J1 Connector
Pin Wire Circuit Function Pin Wire Circuit Function
J1-1 13 12 VDC un-fused for the controller J1-11 85 High temperature shutdown: Shutdown
occurs when Wire 85 is grounded by
J1-2 13 12 VDC un-fused for the controller
contact closure in the oil temperature switch
J1-3 820 Positive voltage (5VDC) for status LEDs
J1-12 86 Low oil pressure shutdown: Shutdown
J1-4 23 Switched to ground (internally) to energize occurs when Wire 86 is grounded by loss
the Transfer Relay of oil pressure in the LOP switch
J1-5 178 Not Used, Optional - 2-Wire Start (return) J1-13 0 Common Ground (DC) DC Field Excitation
J1-6 819 Grounded by the controller to turn on the Ground
Maintenance (Yellow) LED J1-14 194 Provides 12 VDC to the transfer relay
J1-7 818 Grounded by the controller to turn on (TR1)
Alarm (Red) LED J1-15 - Not Used - UL Required Spacing
J1-8 817 Grounded by the controller to turn on J1-16 N1 240 VAC Utility sensing voltage
System Ready (Green) LED
J1-17 N2 240 VAC Utility sensing voltage
J1-9 398A Generator Current Sense A2
J1-18 - Not Used - UL Required Spacing
J1-10 399A Generator Current Sense A1
J1-19 11S 240 VAC Generator Voltage Sensing
J1-20 44S 240 VAC Generator Voltage Sensing
J2 Connector J3 Connector
Pin Wire Circuit Function Pin Wire Circuit Function
J2-1 J3-1 0 Common Ground (DC) DC Field Excitation
Ground
J2-2 209 Common Alarm Relay Output
J3-2 4 DC (+) Field Excitation
J2-3 56 12 VDC output to starter contactor relay/
solenoid J3-3 2 DPE Winding (AC Excitation power)
J2-4 14 12 VDC output for engine run condition. J3-4 6 DPE Winding (AC Excitation power)
Fuel solenoid supply voltage.
J5 Connector
J2-5 4A DC (+) Field Excitation (Before Field Boost
Diode) Pin Wire Circuit Function
J2-6 398A Generator Current Sense B2 J5-1 - Not Used
J2-7 18 Ignition Shutdown: The controller grounds J5-2 - Not Used
Wire 18 for ignition shutdown and receives
J5-3 - Not Used
a reference signal for speed control while
cranking and running J5-4 - Not Used
J2-8 R1 Model ID Resistor J5-5 - Not Used
J2-9 - Not Used J5-6 Red Stepper Power
J2-10 - Not Used J5-7 Orange Stepper Motor B2 Coil
J2-11 183 Not Used, Optional - 2-Wire Start J5-8 Yellow Stepper Motor B1 Coil
J2-12 210 Common Alarm Relay Output J5-9 Brown Stepper Motor A2 Coil
J2-13 - Not Used J5-10 Black Stepper Motor A1 Coil
J2-14 399B Generator Current Sense B1
J8-J9 Connector
J2-15 R3 Model ID Resistor
Pin Wire Circuit Function
J2-16 R2 Model ID Resistor
1 T1 120 VAC Power for the Battery Charger
2 00 Neutral Connection for T1 (battery
charger)
Nexus Controller
There are currently three styles of Nexus Air-cooled control panel. The difference in the styles is how the wires are
connected to the panel. The different panel part numbers, connection types, and images of each are shown on the
following pages.
See Figure A-7 – Nexus Air-cooled Panel part number 0H6680 (A) or (B) has two Amp-Seal style connectors on the
back (J4 & J5), one actuator connector (J3), and a connector socket for the remote wireless annunciator (optional
accessory).
J5
BLACK
BROWN
YELLOW
J3
ORANGE
RED J4
EMPTY
Remote Annunciator
Connector
003484
Figure A-7. Nexus Air-cooled Panel Part Number 0H6680 (A) or (B), and Connectors (Harness End)
J3 Connector J4 Connector
Pin Wire Circuit Function Pin Wire Circuit Function
J3-1 Black Stepper Motor A1 Coil J4-1 90 Switched to ground for choke solenoid
operation
J3-2 Brown Stepper Motor A2 Coil
J4-2 0 Common Ground (DC)
J3-3 Yellow Stepper Motor B1 Coil
J4-3 13 12 VDC un-fused for the controller
J3-4 Orange Stepper Motor B2 Coil
J4-4 817 Grounded by the controller to turn on
J3-5 Red Stepper Power
System Ready (Green) LED
J3-6 Empty
J4-5 818 Grounded by the controller to turn on
Alarm (Red) LED
J4-6 819 Grounded by the controller to turn on the
Maintenance (Yellow) LED
J4-7 85 High temperature shutdown: Shutdown
occurs when Wire 85 is grounded by
contact closure in the oil temperature
switch
J4-8 820 Positive voltage (5VDC) for status LED's
J4 Connector (Continued)
J5 Connector
Pin Wire Circuit Function
Pin Wire Circuit Function
J4-9 14 12 VDC output for engine run condition.
Used for fuel solenoid and choke solenoid J5-1 N1
operation on V-Twin Models J5-2 T1
J4-10 210 Common Alarm Relay Output J5-3 00
J4-11 Not used J5-4 Not Used
J4-12 Not used J5-5 2 DPE Winding (AC excitation power)
J4-13 86 Low oil pressure shutdown: Shutdown J5-6 N2 240VAC Utility sensing voltage
occurs when Wire 86 is grounded by loss
of oil pressure in the LOP switch J5-7 Not Used
J4-15 JMP 1 Installed in series with a resistor to identify J5-9 Not Used
the kW to the controller J5-10 44 240VAC Generator voltage sensing
J4-16 18 Ignition Shutdown: The controller grounds J5-11 11 240VAC Generator voltage sensing
Wire 18 for ignition shutdown and receives
J5-12 0 DC Field excitation ground
a reference signal for speed control while
cranking and running J5-13 4 DC (+) Field excitation voltage
J4-17 56 12 VDC output to starter contactor relay/ J5-14 6 DPE Winding (AC excitation power)
solenoid
J4-18 209 Common Alarm Relay Output
J4-19 194 Provides 12 VDC to the transfer relay
(TR1)
J4-20 23 Switched to ground (internally) to energize
the Transfer Relay
J4-21 Not used
J4-22 Not used
J4-23 JMP 1 Installed in series with a resistor to identify
the kW to the controller
See Figure A-8 – Nexus Air-cooled Panel part number 0H6680 (D) has 4 Molex/ETC style connectors on the back (J5,
J8, J9 & J10), one actuator connector (J3), the battery charger connector (J11 & J12), and a connector socket for the
remote wireless annunciator (optional accessory).
J11-J12 2 1
J9 3 4
4 5 6
J10 1 2
1 2 3
BLACK
BROWN
YELLOW
J3
ORANGE 10 11 12 13 14 15 16 17 18
RED
J8
EMPTY J5 1 2 3 4 5 6 7 8 9
1 2 3 4 5
Remote Annunciator
Connector
003485
Figure A-8. Nexus Air-cooled Panel Part Number 0H6680 (D), and Connectors (Harness End)
J3 Connector J5 Connector
Pin Wire Circuit Function Pin Wire Circuit Function
J3-1 Black Stepper Motor A1 Coil J5-1 209 Common Alarm Relay Output
J3-2 Brown Stepper Motor A2 Coil J5-2 194 Provides 12 VDC to the transfer relay
(TR1)
J3-3 Yellow Stepper Motor B1 Coil
J5-3 23 Switched to ground (internally) to energize
J3-4 Orange Stepper Motor B2 Coil
the Transfer Relay
J3-5 Red Stepper Power
J5-4 Not used
J3-6 Empty
J5-5 Not used
J8 Connector J9 Connector
Pin Wire Circuit Function Pin Wire Circuit Function
J8-1 820 Positive voltage (5VDC) for status LED's J9-1 6 DPE Winding (AC excitation power)
J8-2 LMP 1 Installed in series with a resistor to identify J9-2 11 240 VAC Generator voltage sensing
the kW to the controller
J9-3 2 DPE Winding (AC excitation power)
J8-3 85 Low oil pressure shutdown: Shutdown
J9-4 44 240 VAC Generator voltage sensing
occurs when Wire 86 is grounded by loss
of oil pressure in the LOP switch
J8-4 0 Common Ground (DC) J10 Connector
J8-5 JMP 1 Installed in series with a resistor to identify Pin Wire Circuit Function
the kW to the controller J10-1 T1 120 VAC power for the battery charger
J8-6 56 12 VDC output to starter contactor relay/ J10-2 00 Neutral Connection for T1 (battery
solenoid charger)
J8-7 14 12 VDC output for engine run condition.
Used for fuel solenoid and choke solenoid
operation on V-Twin Models
J8-8 18 Ignition Shutdown: The controller grounds
Wire 18 for ignition shutdown and receives
a reference signal for speed control while
cranking and running
J8-9 90 Switched to ground for choke solenoid
operation
J8-10 85 High temperature shutdown: Shutdown
occurs when Wire 85 is grounded by
contact closure in the oil temperature
switch
J8-11 Not used
J8-12 819 Grounded by the controller to turn on the
Maintenance (Yellow) LED
J8-13 818 Grounded by the controller to turn on
Alarm (Red) LED
J8-14 817 Grounded by the controller to turn on
System Ready (Green) LED
J8-15 Not used
J8-16 210 Common Alarm Relay Output
J8-17 Not used
J8-18 13 12 VDC un-fused for the controller
See Figure A-9 – Nexus Air-cooled Panel part number 0H6680 (T) has 3 Amp/Tyco style connectors on the back (J4,
J5 & J6) the actuator connector (J3), and a connector socket for the remote wireless annunciator (optional accessory).
J6
J4
BLACK
BROWN
YELLOW
J3
ORANGE
RED J5
EMPTY
Remote Annunciator
Connector
003486
Figure A-9. Nexus Air-cooled Panel Part Number 0H6680 (T), and Connectors (Harness End)
J5 Connector (Continued)
J3 Connector
Pin Wire Circuit Function
Pin Wire Circuit Function
J5-6 819 Grounded by the controller to turn on the
J3-1 Black Stepper Motor A1 Coil Maintenance (Yellow) LED
J3-2 Brown Stepper Motor A2 Coil J5-7 85 High temperature shutdown: Shutdown
J3-3 Yellow Stepper Motor B1 Coil occurs when Wire 85 is grounded by
contact closure in the oil temperature
J3-4 Orange Stepper Motor B2 Coil switch
J3-5 Red Stepper Power J5-8 820 Positive voltage (5VDC) for status LED's
J3-6 Empty J5-9 14 12 VDC output for engine run condition.
Used for fuel solenoid , and choke
J5 Connector solenoid operation on V-Twin Models
Pin Wire Circuit Function J5-10 210 Common Alarm Relay Output
J5 Connector J6 Connector
Pin Wire Circuit Function Pin Wire Circuit Function
J5-1 JMP 1 Installed in series with a resistor to identify J6-1 N1 240 VAC Utility sensing voltage
the kW to the controller
J6-2 T1 120 VAC power for the battery charger
J5-2 18 Ignition Shutdown: The controller grounds
J6-3 00 Neutral Connection for T1 (battery
Wire 18 for ignition shutdown and receives
charger)
a reference signal for speed control while
cranking and running J6-4 2 DPE Winding (AC excitation power)
J5-3 56 12 VDC output to starter contactor relay/ J6-5 N2 240 VAC Utility sensing voltage
solenoid J6-6 44 240 VAC Generator voltage sensing
J5-4 209 Common Alarm Relay Output J6-7 11 240 VAC Generator voltage sensing
J5-5 19423 Provides 12 VDC to the transfer relay J6-8 0 DC (-) Field excitation voltage
(TR1)
J6-9 4 DC (+) Field excitation voltage
J5-6 23 Switched to ground (internally) to energize
the Transfer Relay J6-10 6 DPE Winding (AC excitation power)
J5-7 J6-11
J5-8 J6-12
355.6mm
[14"]
700mm
AIR FILTER BOX
ENGINE [27 5/8"]
177.8mm
[7"]
OIL
FILL
38.1mm
VALVE [1 1/2"] 203.2mm
COVER [8"]
279.4mm
980mm
[11"]
[38 5/8"] OIL
TANK
50.8mm 177.8mm
[2"] [7"]
CHECK
VALVE SCAVANGER 350mm
PROBE [13 3/4"]
MAX OIL
LEVEL PROBE
SUMP
003493
Figure B-1. Eco Gen Oil Make-Up System
Pump 1 Pump 2
Pump 1 Operation
OIL =
VENT =
PULSE = 355.6mm
VENT LINE [14"]
355.6mm
[14"]
700mm
AIR FILTER BOX
ENGINE [27 5/8"]
177.8mm
PUMP 1 [7"]
OIL
FILL
38.1mm
VALVE [1 1/2"] 203.2mm
COVER [8"]
279.4mm
980mm
[11"]
[38 5/8"] OIL
TANK
50.8mm
50 8 177.8mm
177 8
[2"] [7"]
CHECK
VALVE SCAVANGER 350mm
PROBE [13 3/4"]
MAX OIL
LEVEL PROBE
SUMP
003494
Figure B-5. Eco Gen Oil Make-Up System – Pump 1 Operation
Pump 1 draws oil from reservoir tank to replenish sump with the pulse being controlled by the scavenger probe and the
max oil level probe. When the scavenger and max oil probes are submersed in oil, the pulse to pump 1 is stopped.
Pump 2 Operation
OIL = 355.6mm
VENT LINE [14"]
VENT =
PULSE = 355.6mm
PUMP 2 [14"]
700mm
AIR FILTER BOX
ENGINE [27 5/8"]
177.8mm
[7"]
OIL
FILL
38.1mm
VALVE [1 1/2"] 203.2mm
COVER [8"]
279.4mm
980mm
[11"]
[38 5/8"] OIL
TANK
50.8mm 177.8mm
[ ]
[2"] [7"]
CHECK
VALVE SCAVANGER 350mm
PROBE 3/4 ]
[13 3/4"]
MAX OIL
LEVEL PROBE
SUMP
003495
Figure B-6. Eco Gen Oil Make-Up System – Pump 2 Operation
Pump 2 draws oil from engine crankcase to the reservoir tank, essentially keeping the crankcase full. The scavenger
probe must be submerged in the crankcase oil for it to pull oil from the crankcase. This stops the flow of oil from the
reservoir tank to the engine crankcase.
250 Diagnostic Repair Manual
Appendix B EcoGen Drawings
I R I E Current Resistance
Voltage
003003 I Decrease Decrease