Contents

Chapter 1.Summarize
1. 1. Foreword •••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••1
1. 2. Inspection and Safety Precautions • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • 1
1. 3. Specification Sheet • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •4
1. 4. Braking Uni t and Braking Resistor • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • 6

Chapter 2.Installation and Wiring


2. 1. Case Structure and Size • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • 7
2. 2. Installation Requirements • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •9
2. 3. Wiring Requirements • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • 10
2. 4. Wiring Instructions • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • 10

Chapter 3. Running Operation


3. 1. Digi tal Keypad Operati on • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • 15
3. 2. Keyboard Instructions • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • 15
3. 3. Display Content Instructions • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • 16
3.4.Parameter Modification Method •••••••••••••••••••••••••••••••••••••• 17
3. 5. Start Up • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • 17

Chapter 4. Function Parameter Instructions • • • • • • • • • • • • • • • • • • • • • • 19


Attached Table 1. Attached table 1. On-off state of mul ti-step speed for first,
second or third, and the correspondence between the frequency table ••••• 52

Attached table 2. On-off state of acceleration & deceleration time choose first
or second and the correspondence between the accel & decel time
table •••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• 52
Chapter 5.Troubleshooting Measures
5. 1. Maintenance Inspection Precautions • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • 53
5. 2. Periodi e Inspection I tems • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • 53
5.3.Fault Information and Troubleshooting•••••••••••••••••••••••••••••• 54
5. 4. Faul t and Anal ys i s • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • 56
5.5.Common Anomalies and Countermeasures •••••••••••••••••••••••••••••• 58

Chapter 6. RS485 Communication Agreement • • • • • • • • • • • • • • • • • • • • • • • • • 60

Chapter 7. Commi tment to Quali ty • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • 67


Chapter 1 Summarize
1. 1. Foreword
FC300 series inverter is fora variety of special occasions and designed
a mul ti-functional high-performance products. Debugging parameters simple and
practical, only one key settings can be changed to your needs special models,
plus parameter copy function, so you use the inverter becomes extremely simple.
Make sure you read before using this manual so that you can better use this
drive, after reading Keep on future maintenance, maintenance and other
occasions to use a very good help.
If have problem can' t be solved when you use, please feel free to contact
our company at any time. For your safety, please be sure to be qualified
prof essional mechanical and electrical engineering installation and debugging
and modification of parameters. This manual have Danger, Notice and other
symbols to remind you when handling, installation, operation and check the
inverter' s safety, please cooperate so that the inverter using the more secure.

1.2.Inspection and safety precautions


FC300 series inverter has been rigorously tested and quality inspection
before delivery. After the purchase, pls check the product package before
unpacking it for careless transportation losses. Product specifications and
models is the right that your ordered. If in doubt please contact our company.
1.2.1 After unpacking inspection
C!)Includes a manual,a warranty card and a certificate.
®Check the nameplate on the side of the inverter to make sure the product
in your hands is the right that you ordered.
lnverter nameplate explaination
BEST lnverter
Model number--+ Model number, FC300-2.2-T4
technica l lnpul 1 Three--pt,ases380V 50-60Hz
pa ramete rs ~ Outputi Three--phasu 0..J&0VO·~OOOH:z:
Current1 S.SA Power: 2.2KW

Ch nr. ,.1Bn t llwrlul Terbnolo[!' Ct..Lld


lnverter model explaination
FC300 - 2.2 - T4
Produci serial NO. I
Power 2.2KW, see model speclfication
sheet fordetails

T4 :three- hase 380Vin ut T2 :sin le- hase220Vln ut


1.2.2.Safety precautions

I ,Il DANGER Incorrect use may result in casualties.

,&. NOTICE Incorrect use may result in damage to the inverter or the
mechanical system.
Noti ce: Depending on the circumstances, "notice" level issues may also cause
serious consequence,please follow the precautions of both levels,they are
very important to our personal safty.
,Il DANGER
eBe sure to turn off the power when wiring.
eOff AC power in ten minutes, is still very dangerous for inverter internal
pressure,do not touch the internal circuit and spare parts.
eon working, please do not check and touch parts on circuit boards and signal
lines.
eoo not disassemble or change the inverter internal connection lines and
spare parts.
eDo not switch button with wet hands to prevent electric shock.
einverter ground terminals must be correctly grounded.
e Prohibited unauthorized alterations, replacement panels and
parts,otherwise will have electric shock,explosionor or other dangerous.
,&NOTICE
ein case of power inverter, do not open the drive cover, but do not touch
circuit board components,these components are presented with hypertension,
beware died of electric shock! ! !
e Do not perform a wi thstand vol tage parts inside the inverter testing, these
semiconductor parts susceptible to pressure damage.
eNever connect the inverter output terminals UVW connected to AC power.
eBeing energized or power-off,the inverter and braking resistor is hot, do
not touch them in arder to avoid burns.
eApplied to each terminal voltage can only be added by using them on anual
to prevent burst and damage etc.
ecMOS, IC on inverter main circui t board are susceptible to static electrici ty
and damage,do not touch the main circuit board.
erhere can only be a qualified professional installation, debugging and
maintenance of the inverter.
erhe inverter scrap pls click industria! waste disposal, incineration is
2
strictly prohibited.
eLong-term storage, inverter shall be inspected and test run before use.
einverter easily be run at high speed setting, before change the setting,
check the motor and mechanical characteristics whether there is sufficient
capacity to adapt to high-speed operation.

1.2.3 Handling and placing precautions

/1\ NOTICE
ewhen carrying the inverte~ not pull the front cover,should move the
inverter base to prevent the front cover off,fall on the ground, causing
personal injury or damage.
e Install the inverter on fire-retardant materials as metal to prevent fires.
ePls select a safe areato install the inverter to prevent high temperature
and direct sunlight,avoid moisture and water droplets.
ePls prevent children or unrelated person close to the inverter.
eThe inverter can only be used in places approved by the company,use in
unauthorized environment may result in fire, explosion, electric shock or
other accidents.
e If several inverters are installed in the same control cabinet, pls provi de
cooling fan in additional, keep the temperature below 40 ·e, to prevent
overheating or fire and so on.
ePls make sure the power is off, then remove or install the keyboard and hold
the front cover to avoid poor contact, cause operator or display failure.
eoo not install the inverter in an environment containing explosive gas,
otherwise there is danger of explosion.
e The area which altitude over 1000 meters, the inverter effect of heat
dissipation become worse,pls downshift.
ePlease do not install air swi tch and contactors and others swi tching element
at the output side. If due to process and other aspects need to install, you
must ensure that the inverter has no output switching. In addition,do not
install the output side of the power factor improvement capaci tors or
lightning with varistor. Otherwise, the will cause the inverter failures, such
as jump protection or components damaged.
ePlease use a separate power, absolutely avoid together with a power supply
wi th welding machines, etc., otherwise i t will lead the inverter to
protection or damage.
&,NOTICE

3
Before power on
ePower supply vol tage rnust be chosen wi th the sarne specifications as the
inverter input voltage.

~ syrnbol is ground terminal, rnake sure the rnotor and the inverter are
properly grounded to ensure safety.
e When the contactor is installed between the power supply and the
inverter, please do not use contactor to control the start or stop, otherwise, i t
will affect the service life of the inverter.
eMain circuit connections rnust be correct,R.S.T (L.N) is power input
terrninals, never connect on the U. V. W, otherwise when power on, i t will cause
the inverter darnage.
Power on
e It is prohibited to insert or extract the inverter connector when power
on,this is avoid control board surge arising due to plug into,darnage the
inverter. Cover up the cover before power on to prevent electric shock causing
personal injury.
In operation
e The rnotor uni t is prohibi ted to input or separate when inverter
operation, otherwise i twill cause inverter over-current trip, or even burn the
inverter rnain circuit.
e Do not rernove the front cover when power transrnit in order to prevent
electric shock causing casualties.
e When fault restart function is turned on,the rnotor is running will
autornatically restart after stop, do not close to the rnachine to avoid
accidents.
estop switch function rnust be setto be valid, the use of it is difficult
frorn the ernergency stop switch, pls use carefully.

1.3.Specification sheet

Three-phase 440V level


Power KW o. 75 1. 5 2.2 3.0 3. 7 5.5 7.5 11 15 18.5
Adaptive
rnotor o. 75 1. 5 2.2 3.0 3. 7 5.5 7.5 11 15 18.5
voltage KW
I Rated 4.0 6.3 8.2 12 14.5 19 25 33 46 52
n curre
p nt A

4
li Volta Three-phase 380V±15%
t ge V
Rate 50/60Hz
HZ
Rated 2. 7 4. 2 5.5 8.0 9.5 13 18 24 32 38
curre
nt A
o Volta Three-phase 0-380V
li
ge V
t
Rate 0-lO00Hz
p
HZ
li
t 0verl 200% Overcurrent Irnmediately
oad 150% One minute
prote
ction

Single-phase 230V level


Power KW o. 75 1. 5 2.2 3.0 3. 7 5.5 7.5 11 15 18.5
Adaptive
motor o. 75 1. 5 2.2 3.0 3. 7 5.5 7.5 11 15 18.5
voltage KW
Rated 7.5 11 16 22 27 36 49 73 96 111
I curre
n nt A
p Volta Single-phase 220V±15%
li ge V
t Rate 50/60Hz
HZ
Rated 5.0 7.0 11 15 18 25 33 49 65 75
curre
nt A
o
Volta Three-phase 0-220V
li
ge V
t
Rate 0-lO00Hz
p
HZ
li
t 0verl 200% Overcurrent Irnmediately
oad 150% One minute
prote
ction
5
(Remark)
1) Maximum applicable motor refers to the Maximum power light load motor which the inverter
can drive,and 4-pole motor is standard.
2) Rated output current refers to the output current when the output vol tage is 380V (or 220V).
3) 0verload capacity is represented by over-current to the inverter rated current ratio of
the percentage (%), when used repeatedly must wai t temperature below when inverter and motor
down to 100%.
4) The max output voltage can not exceed the supply voltage, under the power supply voltage
can be arbi trarily set the output voltage (The peak value of the inverter output voltage is
DC vol tage).
5) Power capaci ty change according to the value of impedance (including the input reactor and
wire)aside the power.

1.4.Braking unit and braking resistor

Inverter Braking unit Braking resistor


fower KW Configu Specifica Configura Specificatio ~Oli
Voltage Amount
ration tion tion n nt
o. 75 preset 1 outlay 80W /150 Q 1
Single-p 1. 5 preset 1 outlay 200W/100Q 1
hase
2.2 preset 1 outlay 200W/70 Q 1
220V
3.0 preset 1 outlay 500W/90Q 1
3. 7 preset 1 outlay 600W/100Q 1
o. 75 preset 1 outlay 150W /400 Q 1
1. 5 preset 1 outlay 200W/300 Q 1
2.2 preset 1 outlay 250W/200 Q 1
3.0 preset 1 outlay 260W/200 Q 1
Three-ph
ase 380V 3. 7 preset 1 outlay 400W/150 Q 1
5.5 preset 1 outlay 500W/90Q 1
7.5 preset 1 outlay 800W/60Q 1
11 inlay 1 outlay 1000W/47Q 1
15 inlay 1 outlay 1500W/36 Q 1
18.5 inlay 1 outlay 2500W/47 Q 1

6
Chapter 2.Installation and wiring
This chapter provides basic product "Installation and Wiring" , read precautions
of this chapter carefully before use.
2. 1.Case structure and size
FC300 case outline as below:
w

=
=
=
=

:e :e

FC300 plastic case outline as below:

7
V
o VI


5: :e

FC300 series dirnensions of inverter as below:


Dirnension Installation dirnension
Inverter model
W(mm) H(mm) D(mm) Wl (mm) Hl (mm) d(mm)
FC300-0. 75T2
FC300-l. 5T2
FC300-0. 75T4 108 152 130 94 139 4
FC300- l. 5T4
FC300-2. 2T4
FC300-2. 2T2
FC300-3. 0T2
FC300-3. 7T2
140 205 156 125 191 5
FC300-3. 0T4
FC30-3. 7T4
FC30-5.5T4
FC300-7. 5T4 170 280 184 110 266 6
FC300- 11T4
210 338 200 192 319 7
FC300-15T4
FC300-18. 5T4 248 375 228 160 356 8

8
2.2. Installation requirements
As the inverter is a precision power electronic products,good or bad of the installation
enviromnent will directl y affect the normal work and life of the inverter, so demands as below:
2. 2. l Using environment
IPlease install the inverter in the absence of water droplets, steam, dust or oily dust
location.
I No corrosion, flammability of gaseous,, liquid;
I No floating dust and metal parti cl es;
IRugged place wi thout vibration;
I No electromagnetic noise interference place;
IThe temperature of using enviroment is - 10'C~+40'C;
2. 2. 2 The inverter uses plast ic parts, pls do not use excessi ve force on the cover, careful
installation to avoid damage.
2. 2. 3 Pls allow the back of the inverter or heatsink install outside the cabinet if
possible, this can greatly reduce the temperature generated inside the cabinet.
2. 2. 4 Install the inverter in a clean place as possible as you can, or install in a closed
panel which can block any suspended matter.
2. 2. 5 Use screw install the inverter on the mounting plate vertically and firmly.
2. 2. 6 Pay attention to the cooling method when inverter installed in a control cabinet
When two or more inverters and fan are installed in a cabinet, should pay attention to
the correct installation position to ensure that the inverter ambient temperature
wi thin the allowable value. If the installation locati on is incorrect, i t will make
the ambient temperature of inverter rises, reducing ventilation.
2. 2. 7 Pls install on a nonflammable objects. Inverter may reach very high temperatures (about
80'C ), Meanwhile, in order to make heat easy to distribute should be sufficient space
around it. (See attached picture)

Abow aoo below lhe


Coollng
lnverter shoùd leave airflow
enough space IO ensure
good Yefllia1ion

Cooling
fan inside

ml
t
2. 3.iiring requirements
9
2. 3. 1 Installation wiring should be separated from power cables and contro! cables, such as
using separate trunking, etc. If the contro! circuì t and the power cab le line must
cross, cross wiring should be 90 degrees.
2. 3. 2 Use shielded wires or twist ed pair connection contro! circuì ts, to ensure the unshielded
place as short as possible, should be used for cab le sleeve if condi tions permi tted.
2. 3. 3 Avoid inverter gravity line(Output and input line)and signal lines parallel wiring and
cluster wiring, should be disperse and cross wiring.
2. 3. 4 Inverter and contro! signal cables should be used shielded twisted pair cable, the skin
of shielded cable connect to the COM terminal.
2. 3. 5 Ground wire of inverter, motor and others should grounded on the same point.
2. 3. 6 Add data line fil ters to the signal line.
2. 3. 7 Connecting line of the detector and the shield of control signal line should be ground
wi th cable clamp metal.
2.4.Wiring instructions

2.4.1 Main circuit terminal explanation


Terminal mark Jerminal name Explanation
Connect to the frequency power supply
L, N
~C power input Single-phase AC220V 50-60Hz
R, S, T Three-phase AC230V or 380V50-60 Hz
U, V, W Inverter output Connect to three-phase Asynchronous motor
~onnect to brakini Between P+, PB, connect to barking resistor (under
P+, PB
lresistor 15KW)
PE ~rounded Inverter grounding, must be proper ly grounded.

2.4.2 The contro! loop terminals explanation


Terminal mark Terminal name bplanation
llrequency setting Input 0-lOV, PID given or feedback
AVI
voltage input
llrequency setting Input 4-20mA, PID given or feedback
ACI
voltage input
AFM OV-lOV output Osed to indicate the frequency,current,speed,etc.
l<'requency setting ~nd AVI, COMO connected potentiometer (4. 7K-10K)
lOV
auxi liary power
Multifunction input llunction set by parameter P091, the factory defaul ts is
Xl
terminals 1 "forward start"
Multifunction input llunction set by parameter P092, the factory defaul ts is
X2
terminals 2 "reverse start"
Multifunction input llunction set by parameter P093, the factory defaul ts is
X3
terminals 3 "stop"
Multifunction input llunction set by parameter P094, the factory defaul ts is
X4
terminals 4 "forward jog"
Multifunction input llunction set by parameter P095, the factory defaul ts is
X5
terminals 5 "muti-step speed No. l"
Multifunction input llunction set by parameter P096, the factory defaul ts is
X6
terminals 6 "muti-step speed No.2"
Multifunction input llunction set by parameter P097, the factory defaul ts is
X7
terminals 7 "muti-step speed No. 3"
Multifunction input llunction set by parameter P098, the factory defaul ts is
X8
terminals 8 "external fault"
Y2A, Y2B Relay contact output ~2A, Y2B is normally open contact
Relay contact output ~lA, YlB is normally open contact, YlB, YlC is normally
YlA, YlB, YlC
closed contact
COM, 24V Aux i li ary power ~OM, +24V ~ 50mA, COM is analog input, output ano
11
fuulti-functional tenninals of common land

2.4.3 Main circuit wiring explanation


1) The power supply and screw terminals of electrical wiring,pls use the terminals with
insulation tube.
2) Remember that the power must not be connected to the inverter output tenninals(U, V,
W), otherwise it will damage the inverter.
3) After wiring, cuts must be cleaned, wire offcuts may cause the inverter abnormalities,
failure or damage, must always be kept clean. When drilling holes on the console, be careful
not to make powder and other debris into the inverter.
4) To make the vol tage pressure drop wi thin 2%, please use the appropriate type of cab le wiring.
when the wiring distance between the inverter and motor is too long, especially in the
case of low-frequency output,the main circuit cable voltage drop will cause the motor
torque to decrease.
5) Cable distance up to 500 meters, especially long-distance wiring, because inrush current
that generateci by wiring parasi tic capaci tance can cause over-current protection ation. the
device connected to the output may meet abnormal or failure operation. Therefore, the
maximum wiring distance in the following table. (When the inverter is connected to two or
more motors, the wiring length should not exceed 500 meters)

Inverter capacity Under O. 75KW 2.2KW Pver 4. OKW


Non-low noise mode 300M 500M bOOM
c,OW noise mode 300M 500M bOOM
6) Between P+,B- terminal,is recommended to connect the braking resistor option.
7 ) Electromagnetic interference: inverter input and output circui t contains harmonic
components, in high demand situations,please install radio noise filter at the input to
minimize interference.
8) Do not install electric power capacitance,surge suppressors and radio noise filter at
the output of the inverter,it will cause inverter failure or damage to the device.
9) After power on or runing, to change the wiring operati on, first you must shut off the power
after more than 10 minutes, using a mul timeter check the vol tage, after power-off in a peri od
of time, the capaci tor still has a dangerous high vol tage.
10) Ground tenninal must be grounded.
.A.Since the inverter have leakage current, to prevent electric shock, the inverter and
the motor must be proper ly grounded.
.A.Grounding with separate ground tenninal(Do not use screws in the shell, chassis, etc.
Instead).

12
Othtr Equipmfnl lnverter

The Best Well

à Try to use thick grounding cab le wire, ground wire close to the inverter as short as
possible.
à Motor at inverter terminal ground, use one of four- core cab le grounding in which
specifications same as i nput cables.

2.4.4 Inverter main circuit terminal block:

0.75~1 .5KW220V, L N PE u V w PB P+
2.2~ 3.7KW220V: L N PB P+ u V w PE
5.5KW220V: L N PB P+ P- u V w PE I
0.75~2.2KW380V, 8 s T PE u V w PB P+
3.0~5.5KW380V, 8 s T PB P+ u V w PE
7.5KW380V, P- P+ PB B s T u V w PE I
11 ~ 15KW380V: P- P+ PB 8 s T u V w PE I
18 .5KW380V: 8 s T P+ P- u V w PE
Remark:
àDifferent models may have difference, pls see the subject product.
àWhen wiring, the inverter terminals(P +, P-) should marked same as braking uni t, wrong
connection may damage the inverter.
àCabling distance between Braking uni t and braking resistor uni t should be wi thin 5 meters,
even using twisted pair can not be more than 10 meters.
à if t he transistor in braking uni t is damaged (shorted), t he resistance will be very hot
and cause a fire. Therefore, the input of the inverter install a magnetic contactor, cut
off the power in case of fail ure.
I. The cabl e must be 75°C copper wire, 2. Tighten the screws at a certain intensity. No
tightening can cause a short circuit or malfunction, tighten overdone will damage screws
and terminal, also cause a short circui t or malfunction.
2.4.5 Tbe control loop wiring
1) "COM" terminal is control signal common terminal, do not public grounded.
2) The wiring of control circuit terminals should use shielded or twisted pair, and must be

13
the wiring separately from main circuit and strong electrical circuit.
3) Since the frequency input signals of control circuit are micro current, in the occasion
of contact input, in arder to prevent poor contact, please use the two side contacts or twin
contacts.
4) Control loop is recommended O. 75 mm' cable wiring.
5) High voltage can not enter into control loop, otherwise it will damage the inverter.

2.4. 6: Inverter control loop terminal block


lOV AVI COM ACI AFM Y2A Y2B YlA YlB YlC
COM Xl X2 X3 X4 X5 X6 X7 X8 +24V

Remark:
àDifferent models may have difference, pls see the subject product.

14
Chaper 3 Running operation
This chapter provides basic product "running operation" , read details of this
chapter carefully before use.
3.1.0peration panel
Operator panel is the interface between people and machine, i t consists of key section and
display section, keys for the user to input control commands, the display section displays the
parameter data and the different operating state. I ts appearance as below pie ture:

- Working light

- Parameter enter and cancel key


Up and down keys
Jogkey-> - Parameters enter key

- Stop and reset key

Run key

3. 2.Keyboard instructions
Symbol Key name Functional explaination
he inverter starts running when press this key, i
Run key set to an external terminal control, press this ke
is invalid.
he inverter reversal running when press this key, i
~ Reverse key set to an external terminal control or "P067" is set
~ to O, the operation can not be reversed.
he inverter stops running when press this key, afte
stop/reset key fault alarm, press this key to reset system. Sto
utton is always acti ve.
ress this button to enter the function settin
Set key status, after modification, press this key to exi t th
function setting status.
In setting state press this key to confirm th
Enter key function code, after modified parameters contents,
ress again to preserve the modified data; in standb
15
or running state press to sequentially display DC
~ol tage, output current, output vol tage, speed, etc.
see 3. 3 display content description for details.
~he function code and parameter data values will

© Up key
increase when press t his key. In t he run or standby
mode, press this key to increase t he operating
frequency.
~he function code and parameter data values will

0 Down key
decrease when press t his key. In the run or standby
mode, press t his key to reduce t he operating
frequency.
Modify parameters in setting state, i t can be

® Jog key displaced. In standby mode (P025 = 1) press to perforn


jog operation.

o Pane1 encoder
(Non- standard)
Equivalent to keyboard up,down key

3. 3.Display content instructions


Display
Status Instructions
content
FWD Light Motor forward during FWD operation
REV Light Motor reserve during FWD operati on
STOP Light Motor stop during FWD operation

Display content code Function


H Given frequency
F Output frequency
A Output current
u Busbar vo l tage
li Output voltage
r Motor speed
y PIO gived quantity
L PIO feedback quantity
J The current count value
d Factory test reserved

16
3. 4.Parameter modification method
If you need to modify the parameter, first enter into the function code which needs to be
modified, and then re-set parameter values, specific steps are as follows:
No 0peration Instruction

1
Press
@ e
Key
Enter the parameter setting mode, the inverter displays the
current parameter number, example "P000";

2 Press - y

~djust to the required parameters, example "P087";


Key

3
Press
@ r
Key
Inverter displays the current value of the parameter, example
"O";

4 Press - y

~djust to the required value, example "101";


Key

5
Press
@ r
Key
~onfirm this action, storing data;

6
Press
@ e
Key
Exi t setting mode and return to standby or running state

Remark:
1: Press"ESC" to enter the parameter setting mode, if you press "ESC" for
3seconds before being released into the special mode only can display
and modify non- factory value parameter.
2: When setting the parameters, just press "ESC" key to exi t the parameters
setting mode can back to standby mode.

3. 5.Start up
3.5.1 Focus on examination before running
e Whether pick the wrong line, in particular, should check the power
supply if connected to UVW terminals incorrectly.
Pls note:power supply should input by R. S. T(L.N) terminal.
e Whether residual metal shaving or wire easily cause a short circuit
on inverter substrate and wiring terminals.
e Check if screws are locking, connectors are loose.
e If output section occur short circuit or short circuit to ground.
17
3.5.2 Start up method
As control method of FC300 seri es inverter is set operator mode of operation
at the factory, on test run, you can use the jog key on keyboard to move,
generally test run can be used 5.0Hz.

18
Chapter 4 Function parameter instructions

No. Function Function description Factory


settings
POOO Inverter type Setting range: Factory
code o ' O. 75KW/220V; 1 ' setting,
identification O. 75KW/380V; only for
2 ' 1. 5KW/220V ; 3 ' read.
1. 5KW/380V;
4 ' 2. 2KW/220V ; 5 '
2.2KW/380V;
6, 3.0KW/220V; 7 '
3.0KW/380V;
8 ' 3. 7KW/220V ; 9 '
3. 7KW/380V;
10 ' 5. 5KW/220V ; 11 '
5.5KW/380V;
12 , 7. 5KW/220V ; 13 ,
7.5KW/380V;
14 , 11KW/220V ; 15 ,
11KW/380V;
16 , 15KW/220V ; 17 ,
15KW/380V;
18, 18.5KW/220V; 19,
18.5KW/380V;
POOl Motor rated Setting range : 20-110% Depending on
current inverter rated current. type
Setting based on the actual
19
motor rated current. Drive
more than one motor, can not
protect the motor, then
please install protection
relay for all motors.
P002 Motor rated Setting range: 50-460Vo 220V
voltage Setting based on the actual (380V)
motor rated voltage.
P003 Motor rated Setting range: 20. 0-1000. 0Hz 50.0Hz
frequency Setting based on the actual
motor rated frequency.
P004 Motor load Setting range: 20%-50% 40
current Motor no-load current and the
motor rated current ratio
will affect the amount of slip
compensati on.
P005 Reserved
P006 Reserved
P007 Torque Setting range : Depending on
Upgrade 0-30%(Depending on type) type
This parameter sets minimum
starting voltage value of V/F
curve. set this parameter
appropriately can improve the
low starting torque.
P008 Reserved
P009 Reserved

20
POlO Reserved
P011 Reserved
P012 Starting Setting range: 1. OHz-Maximum 1.0
frequency operating frequency
The frequency will accelerate
to the target frequency when
start inverter. If this value
is set too large, it may
result in over-current
protection action.
P013 Starting Setting range: 0.0-600.0S o.o
Delay Press the start frequency
output when start inverter,
to maintain this set time to
the target frequency
acceleration. This function
is used to improve the motor
starting characteristics, to
ensure that the motor can be
fully activated within a set
time.
P014 Stop mode Setting range: o
O,after deceleration, DC
braking;
l,freely stop
This function is used to
select the motor stop mode.
When selecting the
21
deceleration stop, inverter
recei ves a stop command, after
the motor decelerates to a DC
braking starting frequency
P015, press P018 DC braking
vol tage and POl 7 stop braking
time to brake stop; when
choose freely stopping,after
inverter receive stop
command, cut off the output
immediately,the motor freely
inertial stop;
P015 DC braking Setting range: 1.0-1000.0Hz 3.0 Hz
starting When stop, slow down to this
frequency frequency, start DC braking.
P016 Prestart Setting range : 0.0-600.0 O.Osecond
Braking time seconds
When the motor started, first
DC braking click
according to this time, and
then accelerateci to the
target frequency.
P017 Stop braking Setting range : O.Osecond
time 0.0-600.0seconds

P018 DC braking Setting range : 1


voltage 0-30%( Depending on type)
Output voltage for DC
22
barking, set this parameter,
be sure to gradually increase
until sufficient braking
torque.
PO19 Reserved
PO2O Reserved
PO21 Setting range: minimum 6O.OHz
Maximum operating
frequency frequency-1OOO.OHz
Setting the maximum allowable
frequency of the motor, all
operational frequencies are
affected by this frequency
limit.
PO22 Minimum Setting range : o.o O.OHz
operating Hz-Maximum operating
frequency frequency, setting operable
minimum frequency.
PO23 Minimum output Setting range : o.o 1. OHz
frequency Hz-Maximum operating
frequency,
Setting minimum output
frequency that motor
permissible . If the operating
frequency setting under this
frequency, the inverter stop
output. applicable far Water
Supply System.
23
P024 Reserved
P025 Keyboard jog Setting range: 1
control O,Prohibit keyboard jog
operati on
1, Allow keyboard jog
operati on
P026 Jog frequency Setting range : Minimum 5.0Hz
operating frequency-Maximum
frequency, output frequency
value when set the inverter
receives jog command.
P027 Jog relative This parameter is four 0002
parameters hexadecimal number D3, D2,
Dl, DO, Represent different
functions.
DO Jog direction
control:
O,forward:
l,reversal;
2(or others),can forward
or reversal;
Dl, Jog accelerate &
deceleration time selection:
1-4,respectively
corresponding to the first to
fourth accelerate &
deceleration time;
O(or others), Selected by
24
an external control signal;
P028 Reserve
P029 Reserve
P030 First Setting range : Minimum 50.0Hz
frequency operating frequency-maximum
frequency
When the speed command (P064)
is O,this frequency as the
first speed in operati on.
This parameter can be
directly through the control
panel .À., Tkeys to modify,
recall automatically when
power off.
P031 Second Setting range : Minimum 2.0Hz
frequency operating frequency-maximum
frequency
P032 Third Setting range : Minimum 3.0Hz
frequency operating frequency-maximum
frequency
P033 Fourth Setting range : Minimum 4.0Hz
frequency operating frequency-----maximum
frequency
P034 Fifth Setting range : Minimum 5.0Hz
frequency operating frequency-----maximum
frequency
P035 Sixth Setting range : Minimum 6.0Hz
frequency operating frequency-----maximum
25
frequency
P036 Seventh Setting range : Minimum 7.0Hz
frequency operating frequency-maximum
frequency
P037 Eighth Setting range : Minimum 8.0Hz
frequency operating frequency-maximum
frequency
P038 Acceleration Setting range: o. 1-3000. O 10. O
time 1 seconds
This pararneter is used to set
time that inverter output
frequency from o up to max
frequency.
P039 Deceleration Setting range : 10. O
time 1 O. 1-3000.0seconds
This pararneter is used to set
time that inverter output
frequency from max frequency
down to o.
P040 Acceleration Setting range: o. 1-3000.0 10. O
time 2 seconds
P041 Deceleration Setting range: o. 1-3000.0 10. O
time 2 seconds
P042 Acceleration Setting range: o. 1-3000.0 10. O
time 3 seconds
P043 Deceleration Setting range: o. 1-3000.0 10. O
time 3 seconds
P044 Acceleration Setting range: o. 1-3000.0 10. O
26
time 4 seconds
P045 Deceleration Setting range : O. 1-3000. O 10. O
time 4 seconds
P046 Accel & decel Setting range: 1-100. 100
frequency When adjusting the frequency
speed control of the operation panel.À., T
of operation buttons,decrease this
panel pararneter can reduce the
frequency growth rate.
P047 Accel & decel Setting range: 1-20000. 100
frequency time When adjusting the frequency
gap of external by external
terminal terminals, incerase this
pararneter can reduce the
frequency growth rate.
P048 Frequency Setting range: 1
memory O,do not recall;
1, recall;
2,Memory frequency before
start;
After power off, setting
first frequency(P030)
whether memory or not.
P049 outages Setting range: o
handling O,Report lowvoltage fault,
and lock;
1 reportlowvoltage
fault,automatically reset
27
after power is restored,does
not start;
2, Slow down when close to the
lowvol tage.
3, Reserved
4, Reserved
Settings inverter operation
when power off and power on
again.
P050 Quick setting O, when the PID function
operati on effecti vely and quick setting
panel PID target values(Pl22),or
quick setting first
frequency(P030)
l,quick setting count
preset (Pl27)
P051 0verheat Setting range:0-1023 130
protection A/D According to the NTC
value temperature sensor and
overheating protection to
calculate.
Factory setting,for read
only.
P052 Fan start A/D Setting range:0-1023 308
value According to the NTC
temperature sensor and
overheating protection to
calculate.
28
Factory setting,for read
only.
P053 Analog output Setting range: o
select O, output frequency of analog
inverter , O - maximum
frequency corresponds O -
lOV;
1, output current of analog
inverter , O- 2times rated
current corresponds to O-
lOV;
This function is used to
connecting a DC voltmeter or
other equipments between AFM
and COM terminals. remote
monitoring inverter output
frequency,output current.
AFM terminal maximum output
voltage is lOVo
2. Output vol tage of analog
inverter,0-2 times the rated
motor voltage corresponding
to 0-lOV.
P054 the minimum Setting range: 0.00-3.00V o.o
analog terminal signal size when
corresponds to setting minimum analog(OHz or
output OA) .
P055 the maximum Setting range: 5.00-20.00V 10. 00
29
analog terminal signal size when
corresponds to setting maximum analog(max
output frequency or 2 times inverter
rated current).
Notice, This parameter is used
to revise the size of the
analog output, AFM terminal
actual maximum output val tage
is lOVo
P056 start display Setting range: o
selection O, frequency (H, F);
1, motor current (A);
2, bus voltage (U);
3, output voltage (u);
4,Approximate mechanical
speed=output frequency*speed
frequency ratio (r);
5, PID gived amount(y);
6, PID feedback amount (L);
7, count value(J);
8, Factory testing Reserved
Cd);
P057 speed Setting range: 0.01-100.00 30.00
frequency This function is used to set
ratio the speed display and
operating frequency ratio. so
that the speed display
matches the actual speed.
30
P058 carrier Setting range : 0-5 1
frequency corresponding to 3K, 5K, 7K,
9K, llK, 13K
The higher carrier frequency,
the lower motor noise, the
electrical interference
greater, the greater heat
inverter, the leakage current
increases, the efficiency
dropso The carrier frequency
is lower, contrary to the
above.
P059 Desired Setting range: 0.0-1000.0Hz O.OHz
frequency When the inverter output
attained frequency is greater or egual
to this setting value, the
inverter can be output signal
through the multi-function
output terminals.
P060 Reserved
P061 Hopping Setting range: 3.0-100.0Hz 20.0
frequency Used to avoid mechanical
starting point resonance point.
P062 Jump frequency Setting range: 0.0-5.0Hz o.o
width Used to avoid mechanical
resonance point.
P063 Undervoltage Setting range: 170
protection 220V: 150-250VDC; (320)
31
voltage 380V: 300-450VDCa
P064 Frequency Setting range: 3
Cornmand source O. Control panel digital
setting setting;
1. AVI terminal 0-lOV setting;
2.ACI terminal 4-20mA
setting;
3.Control panel digital
setting, automatically
switch to 4 if detected 0-lOV
signal from AVI terminal.
4. AVI terminal 0-lOV setting,
when AVI signal is O,
automatically switched to 3
if detects panel .._ , T
operati on.
5.Panel potentiometer
P065 Run cornmand Setting range: 5
source setting O. Operation panel Controls
( forward rotation start,
Reverse rotation start ,
stop);
1. External terminal control
( forward/stop ,
reversal/stop);
2. External terminal control
start/stop
reversal/forward);
32
3. External terminal control
( Forward rotation start ,
Reverse rotation start, stop
(Normally closed));
4. External terminal control
( Forward rotation start ,
Reverse rotation star, stop
(Normally open));
5 . Above 0-3 automatically
adapt;
This function is used to
select the inverter start and
stop control mode o The
following description
assumes that Xl terminal is
set to forward, X2 terminal is
setto reversal, X3 terminal
is set to stop.
When you select the
operation panel control (O),
the external terminal control
invalid.the motor start and
stop controled by run key RUN,
reversal key REV,stop key
STOP on the control panel.
When selecting an
external terminal control
(1), Xl (forward) and COM
connected forward start,
33
disconnect the stop; X2
(reversal) and COM connected
reversal start, disconnect
the stop.
When selecting an
external terminal control
(2), Xl (forward) and COM
connect to start, disconnect
the stop; X2 (reversal)
decide the run direction, X2
and COM connected reversal
start, disconnect to forward.
When selecting an
external terminal control
(3), X3 (stop) and COM
connected to stop button
normally closed contact, Xl
(forward) and COM connected
to forward button normally
open contact,X2(reversal)
and COM connected to reversal
button normally open contact.
When selecting an
external terminal control
(4), X3 (stop) and COM
connected to stop button
normally open contact, Xl
(forward) and COM connected
to forward button normally
34
open contact,X2(reversal)
and COM connected to reversal
button normally open contact.
When you select 0-3
automatically adapt (5) ,the
inverter can operate at
0-3.Note:Xl,X2 are connected
with COM, the motor reversal
start.
Special Note: In the case
of may lead to personal
safety, production loss or
damage to the equipment, be
sure to correctly set this
parameter to prevent
accidents.
P066 Steering Setting range: 2

Control O, forward, whether running


command is forward or
reversal, the motor
output is forward.
1, reversal, whether running
command is forward or
reversal, the motor
output is reversal;
2, Can forward and reversal.
if running command is
forward, the motor output

35
is forward; if running
command is reversal, the
motor output is reversal.
Used to set the run direction
of the motor, automatic
memory after power failure.
Forward and reversal trigger
function will change this
parameter.
PO67 reversion Setting range: 1
control O, Prohibit motor reversal;
1, allow motor reversal;
2, allow motor reversal, and
allows keyboard inversion
start;
Used to limit the reverse,
in some situations do not
allow motor reversal, the
parameter should be set to O,
to prevent accidents.
PO68 Reserved
PO69 Special This parameter is four
funtion 1 hexadecimal number D3, D2,
Dl, DO, represent different
functions.
DO, Dl,reserved
D2,Program runs reset mode
O,Automatically reset at the
36
start of each, start run from
the first speed.
1, When start, continues to
run the frequency when the
last shutdown.reset by the
external terminal, start run
from the first speed.
P070 Special This parameter is four Ox4000
Function 2 hexadecimal number D3, D2,
DL DO, represent different
functions.
DO, Two-wire DC braking:
O, invalid; 1, effective.
Dl Multi-step speed
'
command simultaneously
wi th forward command: o,
Not included ; 1
'
includedo
D2 AVI,ACI analog
'
forward and reversal: o'
invalid ; 1
'
effective >50% is
forward.
D3, incremental of
operation panel encoder
accelerate control
automatically: Set
smaller, faster
37
acceleration.
P071 Fault record 1 o, No fault o
1, Serious overcurrent (HoC) (Read only)
2, Overcurrent (oC) Remark:fault
3, Overvoltage (oU) record can
4, lowvoltage (LU) not be
5, overload (oL) modified,so
6, Overheat (oH) may leave
7, external fault (EF) test records
8, memory error (EEP) before
9, data error (dEr) factory.
10, CPU fault (CPU)
11, code error (CodE)
12, lack of input phase (LP)
13, lack of output phase (oP)
14, reserve
P072 Fault history (same as above) o
2
P073 Fault history (same as above) o
3
P074 Accumulative (day) (Read only)
boot time
P075 reserved
P076 reserved
P077 Torque motor This parameter is the
voltage limit relative proporti on of the
value of motor rated
voltage, setting
38
range : 10%-100%.
Function:Limiting the
minimum voltage which output
to the torque
motor.Example:P077=50,P002=
380V, so P380*50%=190V,mean
motor voltage can adjust
between 190-380V.
P078 Middle voltage 1/3 Motor rated frequency o
corresponding output
voltage.0-50%,0
representatives of this power
is invalid.
P079 reserved
P080 reserved
P081 reserved
P082 reserved

P083 reserved
P084 reserved
P085 reserved o
P086 User password Setting range, 0-655350 O: o
lnvalid; 65535: lnvalid;
When a password is not set,
the P086 is set to a new
password, and then the P087 is
set to 2, the password becomes
effective.
39
When a password is set, you
must enter the corre et
password in P086 before
changing parameters, if P087
is setto 3, the password is
cleared.
P087 Special Set this parameter, can o
operati on perform some special
operati on sequence, the
operati on is completed
automatically returns to O,
no memory.
Setting range:
O, no operation;
1, restare factory settings;
2, remember user password;
3, clear user password;
4, upload parameters;
5,downdload parameters ;
(notice: download from the
same version of the software;
the user required to consider
the compatibility if copies
between the different power
specifications)
others: reserve, Can not set
arbi trarily;
P088 Braking Setting range: 360V
40
resistor 220V inverter: 350-400V or
discharge 380V inverter: 650-720V 660V
starting
voltage
P089 response Setting range: 380V
points against 220V inverter: 350-420V or
overvoltage 380V inverter: 650-760V 730V
P090 response Setting range : 100-190% 150
points against motor rated current
overcurrent
P091 Xl function Setting range: 8
selection o, no effect;
1 first multi-speed ;
'
(attached table 1)
2 second multi-speed ;
'
(attached table 1)
3 third multi-speed ;
'
(attached table 1)
4, Frequency rises;
5, Frequency decreases;
6, forward jog;
7, reverse jog;
8, forward;
9, reversal;
10, forward trigger;
11, reverse trigger;
12, stop;
13, freely shutdown;
41
14, Forced shutdown;
15, Forced inversal;
16, Counter is cleared;
17, Counter input;
18, Program run reset;
19, External fault;
20, External reset;
21,Accelerate & decelerate
time choosing first ;

(attached table 2)
22, accelerate & decelerate
time choosing second ;

(attached table 2)
23, accelerate and decelerate
pause;
24,Forced ACI passage
effective.
P092 X2 Function (Same as above) g

selection
P093 X3 Function (Same as above) 12
selection
P094 X4 Function (Same as above) 6
selection
P095 X5 Function (Same as above) 1
selection
P096 X6 Function (Same as above) 2
selection
P097 X7 Function (Same as above) 3
42
selection
P098 X8 Function (Same as above) 19
selection
P099 reserved
PlO0 reserved
PlOl Yl Function Setting range: 4
selection o, no effect;
1, running;
2, target frequency reach;
3, random frequency reach;
4, fault;
5, lack of voltage;
6, count to;
7, count to warning;
8, stoping;
9, motor commutation delay;
P102 Y2 Function (Same as above) 4
selection
P103 Y3 Function (Same as above) 4
selection
P104 reserved
P105 reserved
P106 AVI Analog Setting range: 0.01-2.00 0.30
input filter
P107 ACI Analog Setting range: 0.01-2.00 0.30
input filter
P108 Analog input Setting range: 0-100% 98

43
corresponding For setting corresponding
to Maximum relationship between analog
frequency (PID quanti ty and target frequency
maximum target (PID target value).
value) For example, when AVI terminal
input lOV*98%=9.8V
frequency value reaches the
maximum frequency (P021)
P109 Analog input Setting range: 0-100% 2
corresponding For setting corresponding
to Minimum relationship between analog
frequency (PID quanti ty and target frequency
minimum target (PID target value)
value) For example, when AVI terminal
input 10V*2%=0.2V, frequency
value reaches the minimum
frequency (P022).
Pll0 reserved
Plll reserved
P112 Run Mode Setting range: o
O, Normal operation;
1, PID mode, control panel .... ,
Tset the target value, AVI
terminal input the amount of
feedback;
2, PID mode, control panel .... ,
Tset the target value, ACI
terminal input the amount of
44
feedback;
3, AVI terminal set the target
value, ACI terminal input
the amount of feedback;
4, ACI terminal set the target
value, AVI terminal input the
amount of feedback;
5-9, reserve;
10, Program run, shut down
after a single cycle;
11, Program run, run for last
frequency after a single
cycle
12, Program run, reciprocating
cycle run;
This parameter selects the
run mode of the inverter.
Pll3 PID Max target Setting range Min 10000
value target-10000
This function is used to set
the maximum target value when
PID run.the decimal point
position that displays on
operator panel is set by Pl21.
Pl 14 PID Min target O-Max target o
value This function is used to set
the minimum target value when
PID run.
45
P115 PID Maximum Setting range: 0-100% 100
target value Used for setting maximum
corresponds to target value corresponds to
the amount of the sensor feedback quantity.
feedback
P116 PID Minimum Setting range: 0-100% o
target value Used for setting minimum
corresponds to target value corresponds to
the amount of the sensor feedback quantity.
feedback
P117 ratio Setting range: 0.01-10.00 1. 00
coefficient The greater ratio
coefficient, the fast
response, but too much prone
to oscillation. The smaller
ratio coefficient, the slow
response.
P118 Integral Setting range: o. 01-10. 00 0.50
coefficient The greater integral
coefficient, the fast
response
P119 differential Setting range: o. 01-10. 00 0.50
coefficient The greater differential
coefficient, the fast
response, but too much prone
to oscillation. The smaller
differential coefficient,
the slow response.
46
P120 Feedback Setting range : o. 1-20.0 0.3
sampling seconds
period This parameter set time
interval for next respond of
PID controller.
P121 PID reference This parameter is four Ox0002
parameters hexadecimal number D3, D2,
DL DO, represent different
functions. o

DO, decimal place setting of


PID display value:
Setting range: 0-30
Dl, the relationship between
motor speed and the amount of
feedback:
O, Motor speed increase,
the amount of feedback
increase;
1, Motor speed increase,
the amount of feedback
decrease;
P122 PID target Setting range: PID Min target 5000
value value-PID Max target value
automatically memory when
power off.
P123 reserved
P124 reserved
Pl25 reserved
47
P126 Setting range: 0-65000 o
Current count This parameter sets the count
value of the counter current,
an external pulse signal
cause the parameter count
increments up.
P127 count to preset Setting range: 0-65000 100
This function is used to set
the counter preset value,
when the count value is egual
to the count preset value, the
system according to P129.
P128 Count to Setting range: 1-65000 90
warning This function is used to set
the counter preset value, in
order to do well preparations
of next step before counting
arrive. when counter to the
warning value, the system can
output the signal through the
terminal.
P129 Count to action Setting range: o
selection O, close output;
1, Continues to output;

P130 program run O: second; 1: second; 2: o


time unit hour

48
P131 First speed 0-6553.0 o
run-time
P132 Second speed 0-6553.0 o
run-time
P133 Third speed 0-6553.0 o
run-time
P134 Fourth speed 0-6553.0 o
run-time
P135 Fifth speed 0-6553.0 o
run-time
P136 Sixth speed 0-6553.0 o
run-time
P137 Seventh speed 0-6553.0 o
run-time
Pl38 Eighth speed 0-6553.0 o
run-time
P139 First This parameter is four Ox0002
speed-related hexadecimal number D3, D2,
parameters D1, DO, represent different
functions:
o, forward;
1, reversal;
2 (others), can forward
and reversal;
D1, accelerate & deceleration
time selection:
1-4 respectively
'
corresponding to the first to
49
fourth accelerate &
deceleration time;
O (or others), Selected by an
external control signal;
P140 Second (Same as above) Ox0002
speed-related
parameters
P141 Third (Same as above) Ox0002
speed-related
parameters
P142 Fourth (Same as above) Ox0002
speed-related
parameters
P143 Fifth (Same as above) Ox0002
speed-related
parameters
P144 Sixth (Same as above) Ox0002
speed-related
parameters
Pl45 Seventh (Same as above) Ox0002
speed-related
parameters
P146 Eighth (Same as above) Ox0002
speed-related
parameters
P147 reserved
P148 reserved
P149 reserved
50
P150 Communication This parameter is four Ox0301
Settings hexadecimal number D3, D2,
Dl, DO, specific functions as
belows:
Dl DO the local address:
Two hexadecimal means local
address,
Range 01-FF, is decimal 1-255
D2:baud rate
0:4800
1 :9600
2: 19200
3:38400
D3:Data format
O: 1-8-2 mode, no parity
1 : 1-8-1 mode, even parity
2: 1-8-1 mode, odd parity
P151 reserved
P152 reserved
P153 reserved
P154 reserved
P155 reserved
P156 reserved
P157 reserved
P158 reserved
P159 reserved

Remark 1: Some models do not have the X5-X8, Yl-Y3, AVI, ACI, AFM etc. terminals
51
and functions, please referto the specific model or consulting firm.
Remark 2: Some parameters can not be modified when the motor is running;

Attached table 1. Attached table l.On-off state of multi-step speed for


first,second,third, and the correspondence between the frequency table
Third Second First multi-step Target frequency
multi-step multi-step speed
speed speed
OFF OFF OFF First frequency
OFF OFF ON Second frequency
OFF ON OFF Third frequency
OFF ON ON Fourth frequency
ON OFF OFF Fifth frequency
ON OFF ON Sixth frequency
ON ON OFF Seventh frequency
ON ON ON Eighth frequency

Attached table 2. On-off state of acceleration & deceleration time choose first
or second and the correspondence between the acceleration & deceleration time
table
accel & decel time accel &decel time target accel on & decel time
setting choose setting choose
second first
OFF OFF first accel & decel time
OFF ON second accel & decel time
ON OFF third accel & decel time
ON ON fourth accel & decel time

52
Chapter 5 troubleshooting easures

Maintenance and inspection in regularly to make your inverter keep in


normal state fora long time.
5.1.Maintenance inspection precautions
e Maintenance inspection, be sure to cut off the input power to the
inverter.
e Make sure the power is cut off, maintenance and inspection after the
display disappears 10 minutes.
e During the inspection process, definitely not uproot and mismatches
the internal power supply, wire and cable, otherwise will cause
inverter does not work or damage it.
e Screws and other accessories can not be stay inside the inverter when
installed to avoid circuit boards causing a short.
e To keep the inverter clean and avoid dust, oil mist, moisture
intrusion after installation.
5.2.Periodic inspection items
e Confirm if supply voltage compliance with the required voltage of
inverter;
(Particular attention if the power line and motor damaged)
e If wiring terminals and connectors become flexible;
(If power lines, terminal connection cable are broken strand)
e Whether there is dust, iron and corrosive liquids inside the inverter.
e Prohibit to measure insulation resistance of inverter.
e Check output voltage, output current, output frequency;
(Measurement gap is not too large)
e Check if the around temperature is between -10·c~4o·c, if installation
environment is well ventilated;

53
e Humidity maintained at 90% or less;
(Can not have the phenomenon of water droplets)
e run without abnormal sound or abnormal vibration phenomena;
(Inverter can not be placed where have large vibration)
e You should regularly clean the vent.
5.3.Fault information and troubleshooting
FC300 series inverter with very perfect protection function, possess
overload, phase short circuit, ground short circuit, lowvoltage, overheat,
overcurrent etc. pls identify the cause according to the following table when
inverter meet protection. Start running after these, if can not handle, please
contact the company.

Fault displayFault content and Handling method


description
1: Check if the motor for short circuit or
partial short circuit, if output wire
insulation is good;
2: extend the accelerate & decelerate time;
3 : inverter configuration unreasonable,
increase the inverter capacity;
serious 4: Reduce the torque boost setting;
HoC
overcurrent 5: Check whether the motor stall, the
mechanical load has sudden change;
6: Whether have a mutation of power system
voltage;
7: DC braking is too big, reduce the amount of
DC braking;
8: machine faul t, send to factory for overhaul.
54
1: Power system voltage is too high, Check if
generate sudden voltage;
ou Over-voltage 2: if the input voltage is wrong;
3: Load inertia is too large;
4: Deceleration time is too short.
1:check if the input voltage is normal;
2:check if the load have sudden change;
LU Low-voltage
3:Check the line is too far away or too small;
4: i f lack of phase.
1: Check whether the fan stall and the heat sink
have foreign matter;
2:if surrounding temperature is normal;
OH overheat 3:if have adequacy ventilation and air
convection
4:Temperature sensor is damaged or inverter
fault, send to factory for overhaul.
1:Check whether the inverter capacity match
small, otherwise increase capacity;
2: Check if the mechanical load has stuck
OL Overload phenomenon;
3: V/F curve setting is poor, reset;
4:DC braking time is too long when start or
stop, reduce braking time
1: Acceleration time too fast, appropriate to
increase the acceleration time;
oC Over-current 2: motor serious overload;
3: control panel bad, send to factory for
overhaul.
55
CodE Code errar Inverter fault, send to factory for overhaul.

Lack of input Check whether input terminal lack of phase or


LP
phase disconnection
Lack of output
oP Inverter fault, send to factory for overhaul.
phase
CPU CPU fault Inverter fault, send to factory for overhaul.
EEP Memory errar send for repair
EF Exteral fault External equipment failure
Set the pararneters correctly
Pararneter setting Notice: It is possible because the causes of
dEr
errar accidents lead to pararneter errar, please
check the pararneters strictly before running.
5.4.Fault and anlaysis
5.4. 1 Press run button, the motor does not turn
1) Run mode setting wrong ,that is to say if run mode under the control
of external terminals,use panel to start;or run mode under the control of
operator,use external terminal to start.
2) Frequency cornrnand is too low or not giveno
3) External wiring errors, such as two-wire, three-wire connection and
the pararneter setting is incorrect.
4) Multi-function input terminal setting errar CExternal control cases) .
5) Inverter fault protection status
6) motor fault.
7) inverter fault.
5.4.2 Parameters can not be set
1) User password lock, pls reset after decryption.

56
2) inverter is running.
3) Connector connect abnormally, digi tal operator communication unusual,
remove the operator after power off, reloading up and try again.
5.4.3 The motor can not reversal
See if P067 is equal to 1, if equal to O then reversal are prohibit.
5.4.4 Motor run in the apposite direction
Motor output line wiring error, set P066 steering control to the opposi te
direction or exchange any two wires of the U, V, W.
5.4.5 motor deceleration is too slow
1) Deceleration time is too long, reduce deceleration time
2) Installation of the braking resistor.
3) Plus DC braking.
5.4.6 Motor overheating
1) The load is too large, the actual torque already exceed the rated torque
of the motor, we recommend increasing the motor capacity.
2) The temperature is too high, in the high temperature environment, the
motor will burn pls lower the temperature around the motor.
3) Withstand voltage shortage between motor phase.
Inverter switching action will produce a shock wave between the motor
windings, usually the maximum impulse voltage will reach three times with the
inverter input power, use the motor which impulse withstand voltage between
motor phase higher than maximum impulse voltage.
5.4. 7 Inverter starts,interfering with other contro! devices.
1) Lower carrier frequency, reduce the number of switching operation
2) Set noise filter at the power input side of the inverter.
3) Set noise filter at the output side of the inverter.
4) Pls correct grounding the inverter and motor.
5) Put metal pipe on the outside of the cable, proceed shielding.

57
6) Main circuit wiring and control lines are wiring separately.
5. 4. 8 When fan start, the inverter has been found overcurrent and stall.
1) When start, the fan is in idle condi tion, pls set DC braking when start.
2) Already set DC braking when start, pls increase the value of the DC
braking.
5.4.9 The machine has vibration or roar
1) Vibration frequency of mechanical systems occurs resonance wi th carrier,
adjust the carrier to avoid resonance point.
2) Vibration frequency of mechanical systems occurs resonance wi th output
frequency of the inverter.
3) a.Set skip frequency function, avoiding the resonance point; b. Set
rubber vibration insulatoron on the motor baseboard.
5.5.Common anomalies and countermeasures
Common anomalies analysis and countermeasures reference to the following
table
abnormal phenomena
Possible reason and countermeasures

no display on Check if power failure, if input power lack of


keyboard phase, if input power connect in a wrong way
Detection if have some problems with the wire and
no display on
Motor sockets which related to keyboard, measuring inside
keyboard, but the
does control supply and voltage,to confirm whether the
inside fan still at
not output voltage of the switching power supply input
work
run to the control board

Inside fan is not Switching power supply or rectifier circuit is


working broken, send to factory for overhaul.

58
~otor has drone
Motor load is too heavy, try to reduce the load
sound
Confirm whether trip or not reset after trip, if in
power-down and then start state, if keyboard re-set,
whether enter into the program running status,
multi-speed running status,set by operating status
Wound no anomalies or non-operating status.

Can try to restare the factory value.

Confirm whether the run command is given

Check if the running frequency is setto zero


1---~----------1
acceleration and deceleration time setting
inappropriate
mo tor can not
Current limits set too small
acceleration and
overvoltage protection when slow down
deceleration smoothly
Carrier frequency setting inappropriate,overloaded
or oscillation
V/F features select improperly
V/F features standard select wrong,reset
The motor speed is too motor rated vol tage is not standard or non-standard
high or too low power supply voltage is too low
frequency setting signal gain set errar
output frequency set errar

59
Chapter 6 RS485 Communication agreement

1 Support agreement
Support Modbus agreement, RTU mode. Broadcast address O, slaves address
can be set 1~2550
2 lnterface mode
RS485: asynchronous, half duplex, the least significant bit sent
priority.High byte in the front, low byte at the back.
The default data format: 1-8-N-2, 38400 bps o
Function parameters: Pl50, Communication configuration. Composed by the
four hexadecimal[ D3 D2 Dl DO], default Ox0301, the role of members as following
table shows:
D3 D2 Dl I DO
Data format Baud rate Two hexadecimal
o 1-8-2 mode, No parity o 4800 mean address of the
1 1-8-1 mode, even parity 1 9600 mach i ne, range 01- FF,
2 1-8-1 moede, odd parity 2 19200 mean decimal 1- 2550
3 38400

3 Agreement format

,::---:-:--7:....---~

~
Startofframe
sp_a_c_
ing
_~-4~ ~
_ characters
Slaves aGB
- ------ ADU -------:'~ - - ~
- - ~ Function code
address Data
Endofframe
Check and ~_ characters
s-pa_c_
ing_~-4~

+ -- - PDU - --

60
ADU (Application Data Unit) check is the CRC16 check of the first three
parts of ADU and obtain through exchange high and low byte. If the operation
request fails, PDU (Protocol Data Unit) reply for error code and exception
code. Error code is equal to the function code +ox80, Exception code indicates
the specific cause of the errore Exception code listed as below:

Exception code Significance shown


OxOl Illegal function code
Ox02 Illegal Address
Ox03 Illegal data
Ox04 Slave operation failed
Ox05 Framing error

4Functional Explanation

♦ Function 0x03 read inverter multi-functions parameters and status word, at

most 5.

Content Data length (bytes) Range


Request:
Function code 1 Ox03
Register Start 2 OxOOOO~OxFFFF
Address
Register data 2 OxOOOl~OxOOlO
Reply:
Function code 1 Ox03
Read the bytes 1 2* Number of registers
Read the contents 2* Number of
registers
61
♦ Funct i on 0x06 rewr i te i nverter si ng I e funct i on code and contro I parameters

Content Data length (bytes) Range


Request:
Function code 1 0x06
Register address 2 0x0000~0xFFFF
Register data 2 0x0000~0xFFFF
Reply:
Function code 1 0x06
Register address 2 0x0000~0xFFFF
Function data 2 0x0000~0xFFFF

5 lnverter register address distribution

0x0000-0x0fff Inverter functional parameters


0x8000 Virtual Terminal Low 16
0x8001 Virtual Terminal high 16
0x8100 Inverter status word
0x8101 Setting frequency
0x8102 Output frequency
0x8103 Output current
0x8104 Bus voltage
0x8105 Output voltage
0x8106 Mechanical revolving speed
0x8107 PID gived quantity
0x8108 PID feedback quantity
0x8109 Current count

The role ofthe Virtual Terminal


62
The inside of inverter has an 32-bit virtual terminal, and its low 16 (bit0-bit15)'s
address is Ox8000, high 16 (bit16-bit31)'s address is Ox8001. This virtual terminals and
Xl-X8 (Specific functions specified by the parameter) have an effect in parallel.

32 virtual terminal functions corresponding to various specific input functions, such as


function of bit8 is 8-Forward; function of bit9 is 9-reversal. Reference to
Xl-X8multi-function input.
inverter status word (Ox8100) bits are defined as follows:
Position Meaning
1 O: normai input voltage 1: lowvoltage
3 O: non-jogrun 1: jogrun
4 O: non-reversal run 1: reversal run
5 O: non-forward run 1: forwardrun
11-15 fault status in current, reference to fault recording and code

6 CRC16 Function

unsigned int crc16(unsigned char *data, unsigned char length)

int i, crc_result=Oxffff;
while (length-)
{
crc_resultA=*data++;
for (i=O; i<S; i++)

if ( crc_result&Ox01)
crc_result= (crc_result>>1) AQxa001;

else
crc_result=crc_result>>1;

63
return (crc_result= ( (crc_result&Oxff) «8) I (crc_result»S));
//exchange CRC16 check and high & low byte

7 Modbus Conmin i cat i on Contro I Examp I e

Start 1# inverter forward:


Request: 0x0l 0x06 0x80 0x00 0x0l 0x00 CRCH CRCL
Reply: 0x0l 0x06 0x80 0x00 0x0l 0x00 CRCH CRCL

Remark: 0x8000: virtual terminal low 16;


0x0lO0: Set the virtual terminal bit8=1, forward command is valid.
CRCH = Al; CRCL = 9Aa
01 06 80 00 01 00 Al 9A

Start 1# inverter reversal:


Request: 0x0l 0x06 0x80 0x00 0x02 0x00 CRCH CRCL
Reply: 0x0l 0x06 0x80 0x00 0x02 0x00 CRCH CRCL
Remark: 0x0200: Set the virtual terminal bit9=1, reversal command is valid.
CRCH = Al; CRCL = 6Aa

1# lnverter stopping:
Request: 0x0l 0x06 0x80 0x00 0x00 0x00 CRCH CRCL
Reply: 0x0l 0x06 0x80 0x00 0x00 0x00 CRCH CRCL
Remark: 0x0000: Set the virtual terminal bit8=bit9=0, forward and reversal command is
invalid.
CRCH = A0; CRCL = 0Aa
01 06 80 00 00 00 A0 0A

1# Inverter speed setting for 50.0Hz:


64
Request: OxOl Ox06 OxOO Oxle OxOl Oxf4 CRCH CRCL
Reply: OxOl Ox06 OxOO Oxle OxOl Oxf4 CRCH CRCL
Remark: OxOOle: decimal 30, represents P030(First frequency);
Ox01f4: decimal 500, inverter inside unit is O. lHz, scilicet 50.0Hzo
CRCH = E9; CRCL = DBo
38HZ: 01 06 00 lE 01 7C E9 BD

Read 1# inverter output frequency, inverter reply output frequency is 50.0Hz:


Request: OxOl Ox03 Ox81 Ox02 OxOO OxOl OxOd Oxf6
Reply: OxOl Ox03 Ox02 OxOl Oxf4 Oxb8 Ox53
Remark: Ox8102: Output frequency;
OxOOOl: Read a word;
Ox02: Return two bytes;
Ox01f4: Decimal 500, inverter inside unit is O. lHz, scilicet 50.0Hzo

Read 1# inverter status, inverter reply on forward run, no fault:


Request: OxOl Ox03 Ox81 OxOO OxOO OxOl Oxac Ox36
Reply: OxOl Ox03 Ox02 OxOl OxaO Oxb9 Oxac
Remark: Ox8100: inverter status words;
OxOOOl: read a word;
Ox02: return two bytes;
OxOlaO: BIT5=1, inverterforwardrun

8 C011111.1nications network set up


♦ One inverter connected to the computer

65
Shielded Twisted Pair
-- , ✓ ----- , /

)( ~<
- -✓ '----- ✓ '

GND 485+ 485-

Rs232cable
up to 15 Meters

Computer Station number 1

♦ Multiple inverters connected to the computer


Shielded Twisted Pair

GNO 485+ 485- GNO 485• 485- GNO 485+ 485-

RsZ32cable
uplo 15 Meters

Computer SlalionlU1'lber1 S1a1mrumber2 S1a1m rumbe< N

Notice: Only the most distant inverter require to connect to termination


resistors.240 OHM)

66
Chapter 7 Commitment to quality
This chapter provides the product "Conmitment to quality• if have quality
problem,we will handle according to follow regulations, pls read this chapter
carefully before use.

Commitment to Quality Regulations of the product


7.1 Warranted range: Inverter itself
7.2 Warranted start time: On the day of user opening
7.3 Warranted commitment: The products implement three guarantees
1. 1 Return wi thin a week after purchase if have non-human quali ty problems
1.2 Replacement Within a month after purchase if have non-human quality
problems
1.3 Guaranteed fora year
7. 4 Subject to the following causes of failure, even within the warranty but
needs maintenance fee:
1. 1 Problems caused by incorrect operation or unauthorized repair and
transform.
1.2 Problems caused by use inverter beyond the standard specifications
requirement.
1. 3 Damage cause by broken after purchase or improper placement (such as
water, etc. ) .
1. 4 Failure that due to use does not meet the requirements of this
specification environment.
1.5 Inverter damage caused by wiring errors.
1. 6 Failure that due to earthquake, fire, lightning, abnormal voltage or
other caused by force majeure.
7.5 Sales in China and agencies of the company can provide service for this
product.
67
~~~ ~ Best EleciricalT!(hnology Guarantee Card
Mode l : Factory No . :

Buy day:

User name ~
: _________ Company name : _ _ _ _ _ _ _ _ _ __

Address:

Zip code : E- mail :

Tel : Fax:
lf any quallty probtems occured under appropriate operation ,we previde 1 week
replacement and 12 months free main tenance service when presenting lhis warranty
card for the produci purchased.
Add :Building A6,Lugu lnternational Industriai Zone ,No. 229
of West Tongzipo Road ,Gaoxin Area ,Changsha,Hunan,China
Changsha Best Elrctrical Technology Co.,Ltd Website:www.best-cn.cn
Mailbox:best_ cs@126 .com
Tel:0731-88719138 Fax:0731-88719238

Please leave your comments and suggestions