0% found this document useful (0 votes)
32 views1 page

KrugerVentProject 20240419 113611

The document provides details on selecting an axial fan for a ventilation project including the required volume, pressure, fan specifications, recommended motor, and sound levels. Key details are the required air volume of 9000 cubic meters per hour at a pressure of 350 Pascals and the selected TDA 450/9AA/5-5/30° (145) fan that can provide 9109 cubic meters per hour at 359 Pascals.

Uploaded by

tivina1987
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
32 views1 page

KrugerVentProject 20240419 113611

The document provides details on selecting an axial fan for a ventilation project including the required volume, pressure, fan specifications, recommended motor, and sound levels. Key details are the required air volume of 9000 cubic meters per hour at a pressure of 350 Pascals and the selected TDA 450/9AA/5-5/30° (145) fan that can provide 9109 cubic meters per hour at 359 Pascals.

Uploaded by

tivina1987
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Date 19/04/2024 Kruger Ventilation Industries (Vietnam) Co.

Ltd
Company Lot A7.2‑4 C2 Road
Customer Ref. Thanh Thanh Cong IZ
Trảng Bàng Dist
Project
Tay Ninh Province
Reference
Tel: 84‑276 3585200/01/02 Fax: 84‑276 3585199
Line Website: www.krugerfan.com

Tag:
Fan Selection
Fan Type Axial Fan
Unit TDA 450/9AA/5‑5/30° (145)
Operating Conditions Ducted
Required Volume 9000 m³/h
Required Pressure (Ps) 350 Pa
Air Volume 9109 m³/h (101.0 %)
Static Pressure 359 Pa (102.0 %)
Velocity Pressure 150 Pa
Total Pressure 508 Pa
Outlet Velocity 15.9 m/s
Fan Total Efficiency 60.7 %
Fan Static Efficiency 42.8 %
Fan Speed 2850 rpm
Air Temperature 20 °C
Altitude 0.0 m
Fan Absorbed Power 2.12 kW
FEG
Motor Selection
Recommended Motor 2.2kW(2P D90L)
Motor Speed 2850 rpm
Service Factor 4%
Belt Selection
Fan Pulley / Bush
Motor Pulley / Bush
Belt Length
Number of Belts
Bearing Life (L10/L50) ‑ / ‑ hours
Hz 63 125 250 500 1k 2k 4k 8k Overall
Starting Torque
Lwi(Lin) 88 95 95 91 90 88 85 82 100 dB
Operating Limits
Lwi(A) 62 79 86 88 90 89 86 81 95 dB(A)
Max. Absorbed Power 10.00 kW
Lpi(A) 44 61 69 70 72 72 68 63 78 dB(A)
Max. Fan Speed 3600 rpm
* Sound data is for the inlet side * Sound Pressure Level 3.0 m, Room Conditions

ØA ØB ØC D KG* N°xØ
450 490 530 400 14 12x10
*weight excludes motor and drive All dimensions in mm.
Version 1 Build 1 (December 2023)