en Operating Instructions Ultrasonic Heat and Cooling Meter Translation
ULTRAHEAT®T550 (UH50...)
ULTRACOLD®T550 (UH50…)
T550 (UH50...)
Note: These operating instructions remain with the end user following installation.
Note: In the following text, the term meter refers to
both the heat meter, the cooling meter and the flow Do not lift the meter by the electronic unit.
meter, unless they are otherwise differentiated.
Be aware of sharp points on the edges, flange and
measuring tube.
1. General Only personnel, trained in the installation and opera-
1.1 Use tion of meters in heating and cooling systems, may
install and remove the meter.
The T550 (UH50…) is used as a meter for heating or cooling
Only install or remove the meter when the pipes are
32 16 101 003 j
consumption measurement in systems with water.
pressure-less.
The meter consists of two temperature sensors and an elec-
tronic unit that calculates the energy consumption from the After installing the meter, check the leak-tightness of
volume and temperature difference. the system.
1.2 General notes Guarantee and calibration validity will lapse if the
calibration relevant security seals are broken.
The meter left the factory in a faultless condition where safety
Only clean the meter from outside with a soft, lightly
is concerned. The manufacturer will provide additional tech-
wetted cloth. Do not use any spirit or cleaning solvent.
nical support on request. Calibration relevant security seals on
the meter must not be damaged or removed. Otherwise, the The 110 V / 230 V connections may only be made by
warranty and calibration validity of the meter will no longer an electrician.
apply. The meter may only be powered up once the installa-
• Keep the packaging so that you can transport the meter in tion has been completed. There is otherwise a danger
its original packaging following expiry of the calibration va- of electronic shock on the terminals.
lidity. A defective or obviously damaged appliance must be
• Lay all cables at a minimum distance of 500 mm to high disconnected from the power supply immediately and
voltage and high frequency cables. replaced.
• A relative humidity of < 93 % at 25 °C is permissible (with- As far as disposal is concerned, the meter is a waste
out condensation). electronic appliance in the sense of European Di-
• Avoid cavitation in the whole system due to overpressure rective 2012/19/EU (WEEE) and it must not be dis-
i.e. at least 1 bar at qp and approx. 3 bar at qs (applies for posed of as domestic waste. The relevant national,
approx. 80 °C). legal regulations must be observed as the appliance
• At a heat meter or combined heat/cold meter the mounting must be disposed of via the channels provided for this
place of the flow sensor cold side is equivalent to return. purpose. The local and currently valid legislation must
The mounting place of the flow sensor hot side is equiva- be observed.
lent to flow. The meter contains lithium batteries. Do not dispose of
• At a cooling meter the mounting place of the flow sensor the meter and the batteries with domestic waste. Ob-
hot side is equivalent to the return. The mounting place of serve the local stipulations and laws on disposal.
the flow sensor cold side is equivalent to flow. You can return the lithium batteries to the manufactur-
er for appropriate disposal following use. When ship-
2. Safety Information ping please observe legal regulations, in particular,
those governing the labelling and packaging of haz-
The meter may only be used in building service engi- ardous goods.
neering systems and only for the applications de- Do not open the batteries. Do not bring batteries into
scribed. contact with water or expose to temperatures above
The local regulations (installation etc.) must be ad- 80 °C.
hered to. The meter does not have any lightning protection.
The operating conditions according to the type plate Ensure lightning protection via the in-house installa-
must be complied with during use. Non-compliance tion.
can result in hazardous situations and the expiry of all Only fit one compartment for the power supply. Do not
claims arising from liability for defects as well as liabil- remove the red locking hatch.
ity based on any expressly granted guarantees.
Requirements for circulating water (CEN/TR 16911:
2016).
The meter is only suitable for circulating water in heat-
ing systems.
The meter is not suitable for drinking water.
Landis+Gyr GmbH Subject to change without prior notice 08.11.2018 1
3. Operating The LCD displays the following values one after the other:
Energy accumulated with tariff status
3.1 Operating elements Tariff register 1 (optional)
Volume accumulated
8 1 Segment test
Head of the loop
In case of error: message with error code
2
3
Service loop 1 “LOOP 1“
Service loop 1 displays the details of the current measurement.
4
The LCD shows the following values one after the other:
5 Head of the loop
Current flow
Current power
7 6
TV current temperature hot side,
TR current temperature cold side;
in 2-sec. cycles
Operating time
Number Description Operating time with flow
1; 6; 7; 8 Cover lugs Missing time
2 Button 1
3 Button 2 Property number, 8-digit
4 LCD Date
5 Security seal
Yearly set day (DD.MM)
Note: Both display range and data displayed can differ Energy: previous year on set day
from the description depending on the appliance pa- Volume: previous year on set day
rameterisation. Certain button functions can also be
blocked. Firmware version
3.2 Displaying current meter status Service loop 2 “LOOP 2“
The meter displays the current meter status in kWh, MWh, MJ Service loop 2 displays the measurement period for establish-
or GJ. ing the maximum.
Note: In order to prevent reading errors, the decimal The LCD shows the following values one after the other:
places of the values displayed are marked with a Head of the loop
frame. Measurement period for establishing the maximum
Note: Calibrated values can be recognised by an
additionally displayed star symbol. Service loop 3 “LOOP 3“
Display values Service loop 3 displays the monthly values.
• In order to display the monthly values, press button 2.
Switch to the service loops to display the values. Proceed as The set day of the current month is displayed.
follows:
• To select the desired month, press button 1.
• To switch from the user loop into the service loops press
button 1. Head of the loop
The displays of the meter are arranged in several levels … …
(LOOPs). Set day for July 2011
• To switch the LCDs between the loops press button 1. • To request the associated values, press button 2.
The LCD shows the following values one after the other: The LCD displays the following values one after the other:
Service loop 1 Energy on the set day
Service loop 2 Tariff register 1 on the set day
... ... Volume on the set day
User loop
Max. flow on the set day,
After the last loop is displayed, the user loop “LOOP 0” comes
in 2-sec. cycles with date stamp
up again.
Max. power on the set day,
Switching in a loop in 2-sec. cycles with date stamp
Proceed as follows to switch to the next display value within a
loop: Max. temperatures on the set day,
• Press button 2. in 2-sec. cycles with date stamp
The first display value will appear again after the final display MV for hot side or MR for cold side
value.
User loop “LOOP 0“ Missing time count on the set day
After the last display the previously selected set day is dis-
The meter is located in the user loop “LOOP 0“. played once again.
• To switch to the next display value press button 2. • To select the next set day, press button 1.
Landis+Gyr GmbH Subject to change without prior notice 08.11.2018 2
Stop “LOOP 3“ 4. Error Messages
To go into the next loop early, proceed as follows: The meter continuously runs a self-diagnosis and can thus
• Select a monthly value with button 2. recognise and display various installation or meter error mes-
• Press button 1. sages.
The error message F0 means that no flow measurement is
Service loop 4 “LOOP 4“ possible, due to air in the volume measurement unit for exam-
ple; the system must be vented carefully.
Service loop 4 displays appliance parameters.
The error message F4 means the battery must be replaced.
The LCD displays the following values one after the other:
When any of the error messages F1, F2 or F5, F6, F8 are
Head of the loop displayed, the temperature sensors are defective. The mes-
Current tariff, sages F3, F7, F9 mean a defect in the electronic.
in 2-sec. cycles with threshold value 1 Contact the service department in all these cases.
Measurement interval flow
Measurement interval temperature 5. Functional Details
Module 1: M-Bus module If the respective operation thresholds are exceeded and flow
M-Bus primary address 1 and temperature difference are positive, the meter summates
M-Bus secondary address 8-digit the energy and the volume. All segments of the display are
switched on for control purposes during the segment test.
Module 2: Pulse module; channel 1 = energy, On the yearly set day, the meter status for energy and volume,
channel 2 = volume; in 2-sec. cycles
the values for the maxima and flow and missing hours are
Value for energy pulses *) logged in the previous year’s archive.
Value for volume pulses *) Flow, power and temperature difference are recorded with the
appropriate +/- signs. If the operation threshold has dropped a
Pulse duration in in ms *)
“u“ is displayed in front. The current temperatures are dis-
*) for “fast pulse“ played to an accuracy of 0.1 °C.
3.3 Previous year’s values For maximum formation the power and flow over the meas-
urement period (of e.g. 60 mins.) are averaged. The maximum
The meter saves the following values on the yearly set day values of the average value formation are marked with “Ma“ in
• Energy (meter status) front. The maximum values of the temperatures are marked
• Volume (meter status) with “MV“ or “MR“.
The 8-digit property number (also the secondary address for
• Tariff register (meter status)
M-Bus operation) can be set in the parameterisation mode.
• Missing time (meter status) The meter number is issued by the manufacturer.
• Flow measurement time (meter status) The operating time is counted from the first connection of the
and the maxima with date stamp for power supply. Missing hours are summated if there is an error
• Flow and the meter is thus unable the measure. The date is incre-
• Power mented on a daily basis.
• Temperature difference The type of modules installed is displayed. If an M-Bus module
is installed, the primary and secondary address is displayed in
• Temperature hot side
the subsequent lines.
• Temperature cold side The number for the firmware version is issued by the manufac-
3.4 Monthly values turer.
The meter stores the following values for 60 months on the
monthly set day
• Energy (meter status)
• Volume (meter status)
• Tariff register (meter status)
• Missing time (meter status)
• Flow measurement time (meter status)
and the maxima with date stamp for
• Flow
• Power
• Temperature difference
• Temperature hot side
• Temperature cold side
The monthly values can be read via the optical and the 20 mA-
interface.
Note: Central European Time (CET) applies as the
standard time. During summer time the storage takes
place at the corresponding times.
Landis+Gyr GmbH Subject to change without prior notice 08.11.2018 3
6. Technical Data
Note: The information on the meter must be observed!
General
Measuring accuracy Class 2 or 3 (EN 1434)
Environment class A (EN 1434) for indoor installation
Mechanical class M1 *)
Electromagnetic class E1 *)
*) according to 2014/32/EU Directive on Measuring Instruments
Ambient humidity < 93 % rel. humidity at 25 °C, without condensa-
tion
Max. height 2000 m above sea level
Storage temperature -20 … 60 °C
Electronic unit
Ambient temperature 5 … 55 °C
Housing protection rating IP 54 according to EN 60529
Safety class
Line 110 / 230 V AC II according to EN 61558
Line 24 V ACDC III according to EN 61558
Operation threshold f. T 0.2 K
Temperature difference T 3 K … 120 K
Temperature measurement 2 ... 180 °C
range
LCD 7 digits
Optical interface Standard, EN 62056-21
Communication Optional, e.g. M-Bus
Separability Always, optional cable length
Sensor
Type Pt 500 or Pt 100
According to EN 60751
Temperature range 0 ... 150 °C (up to 45 mm overall length)
0 ... 180 °C (from 100 mm overall length)
Volume measurement unit
Protection class IP 54 / IP 65 according to EN 60529
IP 68 (at qp 150) according to EN 60529
Mounting place Hot side / cold side
Installation position Any
Flow straightening None
Measuring range 1:100
Temperature range 5 … 130 °C
National type approvals may be different.
recommended...
...heating application 10 … 130 °C
...cooling application 5 … 50 °C
Maximum overload 2.8 × qp
Nominal pressure PN16 (PS16), PN25 (PS25)
Landis+Gyr GmbH Subject to change without prior notice 08.11.2018 4