Product datasheet
Specifications
on-delay timing relay - 1 s..100 h -
24..240 V AC/DC - solid state
output
RE17LHBM
Main
Range Of Product Harmony Timer Relays
Product Or Component Type Single function relay
Discrete Output Type Solid state
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Width 17.5 mm
Component Name RE17L
Time Delay Type Interval
Time Delay Range 1...10 s
1...10 h
0.1...1 s
6...60 s
6...60 min
1...10 min
10...100 h
Nominal Output Current 0.7 A
Complementary
Control Type Selector switch front panel
[Us] Rated Supply Voltage 24...240 V AC 50/60 Hz
Voltage Range 0.85...1.1 Us
Supply Frequency 50...60 Hz +/- 5 %
Release Of Input Voltage 9V
Control Signal Pulse Width 0.05 s typical
Insulation Resistance 100 MOhm at 500 V DC conforming to IEC 60664-1
[Uimp] Rated Impulse Withstand 5 kV during 1.2/50 µs
Voltage
Power On Delay 100 ms
Connections - Terminals Screw terminals, 1 x 0.5...1 x 3.3 mm² (AWG 20...AWG 12) solid without cable end
Screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end
Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 14) flexible with cable end
Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end
Tightening Torque 0.6…1 N.m conforming to IEC 60947-1
Dielectric Strength 2.5 kV 1 mA/1 minute 50 Hz conforming to IEC 61812-1
Housing Material Self-extinguishing
Repeat Accuracy +/- 0.5 % conforming to IEC 61812-1
Temperature Drift +/- 0.05 %/°C
Voltage Drift +/- 0.2 %/V
Price is “List Price” and may be subject to a trade discount – check with your local distributor or retailer for actual price.
Apr 22, 2024 1
Setting Accuracy Of Time Delay +/- 10 % of full scale at 25 °C conforming to IEC 61812-1
Reset Time 350 ms on de-energisation typical
On-Load Factor 100 %
Power Consumption In Va 0…3 VA at 240 V AC
Maximum Power Consumption In 1.5 W at 240 V DC
W
Breaking Capacity 0.5 A AC conforming to UL
0.7 A AC at 20 °C
Operating Frequency 10 Hz
Maximum Output Current 20 A
Minimum Switching Current 10 mA
Maximum Leakage Current 5 mA
Maximum Switching Voltage 250 V AC
Maximum Voltage Drop <4 V 3-wire
<8 V 2-wire
Electrical Durability 100000000 cycles
Marking CE
Creepage Distance 4 kV/3 conforming to IEC 60664-1
Safety Reliability Data MTTFd = 353.8 years
B10d = 320000
Mounting Position Any position in relation to normal vertical mounting plane
Mounting Support 35 mm DIN rail conforming to IEC 60715
Net Weight 0.068 kg
Time Delay Type H
Functionality On-delay timing
Number Of Functions 1
Compatibility Code RE17
Environment
Immunity To Microbreaks 20 ms
Derating Factor 5 mA/°C
Standards 2006/95/EC
IEC 61000-6-1
IEC 61000-6-3
IEC 61000-6-2
IEC 61812-1
IEC 61000-6-4
2004/108/EC
Product Certifications cULus
CSA
GL
Ambient Air Temperature For -30…60 °C
Storage
Ambient Air Temperature For -20…60 °C
Operation
Ip Degree Of Protection IP20 (terminal block) conforming to IEC 60529
IP40 (housing) conforming to IEC 60529
IP50 (front panel) conforming to IEC 60529
Vibration Resistance 20 m/s² (f= 10…150 Hz) conforming to IEC 60068-2-6
Shock Resistance 15 gn for 11 ms conforming to IEC 60068-2-27
2 Apr 22, 2024
Relative Humidity 93 % without condensation conforming to IEC 60068-2-30
Electromagnetic Compatibility Electrostatic discharge immunity test: (in contact), level 3, 6 kV, conforming to IEC
61000-4-2
Electrostatic discharge immunity test: (in air), level 3, 8 kV, conforming to IEC
61000-4-2
Susceptibility to electromagnetic fields: (80 MHz to 1 GHz), level 3, 10 V/m,
conforming to IEC 61000-4-3
Electrical fast transient/burst immunity test: (capacitive connecting clip), level 3, 1 kV,
conforming to IEC 61000-4-4
Electrical fast transient/burst immunity test: (direct), level 3, 2 kV, conforming to IEC
61000-4-4
1.2/50 µs shock waves immunity test: (differential mode), level 3, 1 kV, conforming to
IEC 61000-4-5
1.2/50 µs shock waves immunity test: (common mode), level 3, 2 kV, conforming to
IEC 61000-4-5
Conducted RF disturbances: (0.15...80 MHz), level 3, 10 V, conforming to IEC
61000-4-6
Voltage dips and interruptions immunity test: (1 cycle), 0 %, conforming to IEC
61000-4-11
Voltage dips and interruptions immunity test: (25/30 cycles), 70 %, conforming to IEC
61000-4-11
Conducted and radiated emissions: , class B, conforming to EN 55022
Packing Units
Unit Type Of Package 1 PCE
Number Of Units In Package 1 1
Package 1 Height 2.700 cm
Package 1 Width 8.000 cm
Package 1 Length 9.500 cm
Package 1 Weight 69.000 g
Unit Type Of Package 2 S02
Number Of Units In Package 2 40
Package 2 Height 15.000 cm
Package 2 Width 30.000 cm
Package 2 Length 40.000 cm
Package 2 Weight 3.244 kg
Apr 22, 2024 3
Sustainability
Green PremiumTM label is Schneider Electric’s commitment to delivering products with best-in-
class environmental performance. Green Premium promises compliance with the latest regulations,
transparency on environmental impacts, as well as circular and low-CO2 products.
Guide to assessing product sustainability is a white paper that clarifies global eco-label
standards and how to interpret environmental declarations.
Learn more about Green Premium arrow2_right
Guide to assess a product’s sustainability arrow2_right
Transparency RoHS/REACh
Well-being performance
Mercury Free
Rohs Exemption Information Yes
Certifications & Standards
Reach Regulation REACh Declaration
Eu Rohs Directive Pro-active compliance (Product out of EU RoHS legal scope)
China Rohs Regulation China RoHS declaration
Environmental Disclosure Product Environmental Profile
Circularity Profile End of Life Information
4 Apr 22, 2024
Product datasheet RE17LHBM
Dimensions Drawings
Width 17.5 mm
Apr 22, 2024 5
Product datasheet RE17LHBM
Connections and Schema
Internal Wiring Diagram
6 Apr 22, 2024
Product datasheet RE17LHBM
Wiring Diagram
Apr 22, 2024 7
Product datasheet RE17LHBM
Technical Description
Function H : Interval Relay
Description
On energisation of the relay, timing period T starts and the output(s) R close(s). At the end of the timing period T, the
output(s) R revert(s) to its/their initial state. The second output can be either timed or instantaneous.
Function: 1 Output
Function: 2 Outputs
2 timed outputs (R1/R2) or 1 timed output (R1) and 1 instantaneous output (R2 inst.)
8 Apr 22, 2024
Product datasheet RE17LHBM
Legend
Relay de-energised
Relay energised
Output open
Output closed
C Control contact
G Gate
R Relay or solid state output
R1/R2 2 timed outputs
R2 inst. The second output is instantaneous if the right position is selected
T Timing period
Ta - Adjustable On-delay
Tr - Adjustable Off-delay
U Supply
Apr 22, 2024 9