Fire-Fighting-System Design Forn Power Plant

The document provides a design basis report for the fire fighting system of a 120MW combined cycle power plant. It details the scope of work, regulations considered, system description including water storage, pumps, hydrant and sprinkler systems. It also analyzes six cases considering different component operations and flow rates.

Uploaded by

yerrisiddappa K
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
296 views12 pages

Fire-Fighting-System Design Forn Power Plant

The document provides a design basis report for the fire fighting system of a 120MW combined cycle power plant. It details the scope of work, regulations considered, system description including water storage, pumps, hydrant and sprinkler systems. It also analyzes six cases considering different component operations and flow rates.

Uploaded by

yerrisiddappa K
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 12

DOC. NO.

-
100-1101-L1L-R00
GAJANAN AND SONS CLIENT:
FIRE SAFETY PVT. LTD. Rev –0
M/s KDL 120MW COMBINED CYCLE POWER
PLANT PROJECT SHEET NO 1 of 12

FIRE FIGHTING
DESIGN BASIS REPORT

CLIENT: M/s KDL 120MW COMBINED CYCLE POWER


PLANT PROJECT

REVISION NO. R-0


ISSUED FOR ENGINEERING
PREP. BY/DATE 16/08/12
CHKD. BY/DATE 16/08/12
APPRO. BY/DATE 16/08/12
DOC. NO.-
100-1101-L1L-R00
GAJANAN AND SONS CLIENT:
FIRE SAFETY PVT. LTD. Rev –0
M/s KDL 120MW COMBINED CYCLE POWER
PLANT PROJECT SHEET NO 2 of 12

SR.NO. DESCRIPTION PAGE NO.


INDEX
1. SCOPE OF WORK 4

2. FIRE PROTECTION & DETECTION SYSTEM 5

3. SPECIFICATION & MAKES 12


DOC. NO.-
100-1101-L1L-R00
GAJANAN AND SONS CLIENT:
FIRE SAFETY PVT. LTD. Rev –0
M/s KDL 120MW COMBINED CYCLE POWER
PLANT PROJECT SHEET NO 3 of 12

While making this DBR, following regulations are considered

NFPA 10 portable Fire Extinguisher

NFPA 12 Carbon Dioxide Extinguishing Systems

NFPA 13 sprinklers

NFPA 14 Installation of Standpipe, private Hydrants, and Hose System

NFPA 15 Water Spray fixed system for fire Protection

NFPA 24 Yard hydrants

NFPA 30 Flammable and combustible Liquids Code

NFPA 70 National Electrical Codes

NFPA 72D9E National fire Alarm Code

NFPA 850 Recommended Practice for Fire Protection for Eclectic Generating plants and
High Voltage Direct Current Converters Stations.

ANSI B31.1 Power Piping

ASME VIII Pressure Tank

IEEE 383 Fire retardant Cable


DOC. NO.-
100-1101-L1L-R00
GAJANAN AND SONS CLIENT:
FIRE SAFETY PVT. LTD. Rev –0
M/s KDL 120MW COMBINED CYCLE POWER
PLANT PROJECT SHEET NO 4 of 12

UTILITY WORKS:

1. SCOPE OF WORK

Fire Protection system:


- Hydrant System.
- Sprinkler system.
- Deluge system.
- Fire Fighting Pump sets.
- Portable first aid & fire extinguishers.
- Automatic Fire Extinguishers for Electrical Panels
- Photo luminescent safety signages.
- Fire rated sealant.
- Analogue Type Fire detection & Alarm system.
DOC. NO.-
100-1101-L1L-R00
GAJANAN AND SONS CLIENT:
FIRE SAFETY PVT. LTD. Rev –0
M/s KDL 120MW COMBINED CYCLE POWER
PLANT PROJECT SHEET NO 5 of 12

2. FIRE PROTECTION & DETECTION SYSTEM

System Description

Water shall be drawn from fire reserve tanks by electrically driven jockey
pumps & fire pumps. A standby diesel engine driven pump for fire hydrants,
deluge system and sprinkler system is provided. All pumps have separate suction
lines from the suction header and delivery is connected to the system. The
function of pumps is to maintain 3.5 Kg/Sq.cm at the farthest hydrant. Diesel
engine driven fire pump shall be of the same capacity and shall back up the
electrically operated fire hydrant / sprinkler pump, as per fire regulations. This
pump is operated in case of total electrical power or electrical pump failure.
Jockey pump is operated intermittently in order to take care of hydraulic losses in
the system and to maintain the minimum pressure.

- A/g Fire Water Storage Tank : 250 M3

Pumps:

- Main Pump (For Hydrant/Sprinkler) - 1 No, 273 M3/Hr, Head 71 m.


Elect. Driven Pump

- Standby Pump - 1 No, 273 M3/Hr ,Head 88 m


- Diesel Engine Driven Pump

- Jockey Pump Set - 1 No,10.8 M3/Hr ,Head 71 m.

Fire Hydrant System:

The Plant shall be provided with separate fire hydrant riser connected to the
hydrant landing valve with fire hose cabinet consisting of swinging hose reels,
fire man’s axe, 63 mm dia canvas hose and nozzles.
Externally, a fire fighting ring main shall be provided around the Plant.
External yard hydrants shall be suitably located at 30 meter centers. Necessary
DOC. NO.-
100-1101-L1L-R00
GAJANAN AND SONS CLIENT:
FIRE SAFETY PVT. LTD. Rev –0
M/s KDL 120MW COMBINED CYCLE POWER
PLANT PROJECT SHEET NO 6 of 12

hose pipe and nozzle shall be placed in a closed cabinet with glass shutters at
these yard hydrants.

We had design system for 6 cases in which the capacity for reservoir has
been taken as 250 m3. One electric driven pump of capacity 273 m 3 /hr , 71 m
Head and one diesel engine driven pump of capacity 273 m3/hr , 88 m Head
along with one jockey pump of capacity 10.8 m3/hr, 71 m Head have been
installed.

Working pressure:

1. The mains are always kept pressurized at 7.1 kg/cm 2. If the pressure reduces from
7.1 kg/cm2 due to leakage of line or deluge valve, the jockey pump operates and
automatically cut off at 7.1 kg/cm2.
2. When pressure reduce below 6 kg/cm 2, the Electric operated pumps (273 m3/hr)
operates and automatically cut off at 7.1 kg/cm2.
3. Still if pressure drops below 5.0 bars due to opening of several fire hydrant
points, electrical pump (273 m3/hr) will start ( along with diesel pump 273
m3/hr )

Design basis:

1) Flow rate consideration for Single hydrant (SH), Water Monitor (WM) & Fire
escape hydrant (FEH): 900 lpm. Flow rate consumption for single spray
nozzle considered as 90 lpm, there are 3 Deluge valves operating in whole the
system with 96 spray nozzles each. Flow rate consideration for single
sprinkler is depending on K Factor of that sprinkler and operating pressure at
that time. In our case we had considered as 40 sprinklers for Admin building
at 2 bar pressure having k factor 80 and for Warehouse sprinklers k factor will
be 360.
2) For analysis purpose we had considered, Furthermost point (Remotest
Hydrant) and remotest sprinkler.

CASE: 1

When all 3 pumps are in working conditions and only Hydrant to open and
no any sprinkler and Deluge valve will operate.

Flow rate for pumps = 556.8 m3/hr =0.1546 m3/s


Flow rate dedicated required for Sprinkler System = 0 m3/hr = 0 m3/s
Flow rate dedicated required for Deluge System = 0 m3/hr=0 m3/s
DOC. NO.-
100-1101-L1L-R00
GAJANAN AND SONS CLIENT:
FIRE SAFETY PVT. LTD. Rev –0
M/s KDL 120MW COMBINED CYCLE POWER
PLANT PROJECT SHEET NO 7 of 12

Flow rate available for SH /FEH = 556.8 m3/hr - 0 m3/h - 0 m3/hr = 556.8 m3/hr
= 0.1546 m3/s

Maximum Flow rate for Single Hydrant / FEH = 900 lpm = 0.015 m3/sec

FLOWRATE FOR PUMPS


Number of hydrants =
Maximum Flow rate for Single Hydrant∨FEH

= 0.1546 / 0.015
= 10.3
Therefore,
The total number of active hydrants = 11 Nos. with no sprinklers will operate

CASE: 2

When all 3 pumps operating and all Admin sprinklers is in operating


condition &
No Deluge valve is operating

Flow rate for pumps = 556.8 m3/hr = 0.1546 m3/s


Flow rate dedicated required for Sprinkler System = 270 m3/hr=0.075 m3/s
Flow rate dedicated required for Deluge System = 0 m3/hr=0 m3/s

Flow rate available for SH /FEH =556.8 m3/hr - 270 m3/hr = 376.8 m3/hr =
0.1046 m3/s

Maximum Flow rate for Single Hydrant / FEH = 900 lpm = 0.015 m3/sec

FLOWRATE FOR PUMPS


Number of hydrants =
Maximum Flow rate for Single Hydrant∨FEH

= 0.1046 / 0.015
= 6.97
Therefore,
The total number of active hydrants = 7 with all Sprinklers in admin area in
Active mode.
DOC. NO.-
100-1101-L1L-R00
GAJANAN AND SONS CLIENT:
FIRE SAFETY PVT. LTD. Rev –0
M/s KDL 120MW COMBINED CYCLE POWER
PLANT PROJECT SHEET NO 8 of 12

CASE: 3

When all 3 pumps operating and all Warehouse sprinklers is in operating


condition & no Deluge system is operating.

Flow rate for pumps = 556.8 m3/hr =0.1546 m3/s


Flow rate dedicated required for Sprinkler System = 305.5 m3/hr = m3/s
Flow rate dedicated required for Deluge System = 0 m3/hr = 0 m3/s

Flow rate available for SH /FEH = 556.8 m3/hr - 305.4 m3/hr = 251.4 m3/hr =
0.0698 m3/s

Maximum Flow rate for Single Hydrant / FEH = 900 lpm = 0.015 m3/sec

FLOWRATE FOR PUMPS


Number of hydrants =
Maximum Flow rate for Single Hydrant∨FEH

= 0.0698 / 0.015
= 4.65
Therefore,
The total number of active hydrants = 5 with all Warehouse sprinkler
System in Active mode.

CASE: 4

When all three pumps are operating and one Deluge Valve system is in
operating condition and no sprinklers will operate.

Flow rate for pumps = 556.8 m3/hr =0.1546 m3/s

Flow rate dedicated required for Sprinkler System = 0 m3/hr = 0 m3/s


Flow rate dedicated required for whole Deluge System = 518.4 m3/hr=0.144 m3/s

Maximum Flow rate for Single Hydrant = m3/sec

FLOWRATE FOR PUMPS


Number of hydrants =
Maximum Flow rate for Single Hydrant∨FEH
DOC. NO.-
100-1101-L1L-R00
GAJANAN AND SONS CLIENT:
FIRE SAFETY PVT. LTD. Rev –0
M/s KDL 120MW COMBINED CYCLE POWER
PLANT PROJECT SHEET NO 9 of 12

= 0.0106 / 0.015
= 0.71

Therefore,
The total number of active hydrants = 1.

Above mentioned all calculations are done at extreme operating conditions of


each individual system, Hence we can conclude that pump selected for whole
system delivers required flow rate and pressure satisfactorily.

Deluge System:

Deluge system design shall be compliant with the requirements of NFPA


15. Deluge valves are supplied from the appropriate firewater ring main at two
separate points to maintain supply under most foreseeable scenarios. Deluge
systems shall be of dry type downstream of the deluge valves and shall be
provided with both automatic and manual release actuation facilities.
Each deluge circuit shall have a manual release facility which shall be
located outside the area being protected. All deluge circuits shall have the
capability to be operated automatically from the F&G system (on detection of a
Confirmed Fire in the area), or by remote manual activation from the PCR (via the
F&G system). Release of a deluge circuit by any means shall be considered to be
a Confirmed Fire and shall be signalled to the F&G system via PSL (system
activated) and PSH (deluge valve open) pressure switches. The operation of
deluge places large quantities of water on the ground floor. Drains shall be
provided to evacuate this water and to prevent hydrocarbon release spilling over
the water and possibly spreading the fire.

Automatic Deluge system is considered for following areas


1 Main power Transformers for GTG 1, GTG2, STG
2 Unit Auxiliary transformers.
3 Turbine oil tank and oil treatment Area.
For Gas turbine combustion Chambers Dry powder type portable
extinguishers are considered.
For Diesel Driven fire water Pump, electrical motor driven pump and
jokey pump – Dry powder type portable extinguishers are considered.

Portable Fire Extinguishers:


DOC. NO.-
100-1101-L1L-R00
GAJANAN AND SONS CLIENT:
FIRE SAFETY PVT. LTD. Rev –0
M/s KDL 120MW COMBINED CYCLE POWER
PLANT PROJECT SHEET NO 10 of 12

The portable fire extinguisher shall be suitably distributed in the entire plant in
accordance with IS : 2190 and with respect to the requirement under Fire
Prevention and life safety measures act (NFPA 10).
As per design ‘ABC’ Powder type & ‘CO2’ type Fire Extinguishers will be stored
in each 100 M2 floor area, inside the building for minor Fire Extinguishing needs.
The type of extinguisher (Powder / Gas etc) will be defined by the activity carried
in that area.
 15 nos. of CO2 type extinguishers and
 25 nos. ABC powder type are designed to be installed at various required
place.

Sprinkler System:

Sprinkler system rated at 70 Degree Celsius.


Sprinklers with Alarm valve shall be provided in entire floor area, ware house &
office area.
Sprinkler piping will be of CS Pipe of IS 1239 Pipes with fittings. Each
sprinkler required will be installed about 3m between each other.
Design sprinklers are provided in various areas as per below, Sprinkler systems
will be standard Response Pendant Type.
40 Nos sprinklers of type K80 (K5.6) are provided for admin area.
21 Nos sprinklers of type K360 (K25.4) are provided for admin area.
96 Nos Spray nozzle for equipments size of 1/2" orifice with 90 deg angle.

Smoke detector System:

The smoke detector can be used in all areas where Photoelectric Smoke Detectors
are required.The wide range smoke chamber makes the PS24 well suited for fires ranging
from smoldering to flaming fires. SB Series Style bases may be used with the PS24.
Current interchangeable/compatible devices are the IS24 ionization detector.

Optical Smoke Detector (office area & store area) - 50 Nos.

Following area’s are covered in this System


1 Gas Turbine Enclosures
2 Gas and Lube oil Containers
3 Steam turbine Enclosures
4 Fuel area including gas metering station
5 operating office
DOC. NO.-
100-1101-L1L-R00
GAJANAN AND SONS CLIENT:
FIRE SAFETY PVT. LTD. Rev –0
M/s KDL 120MW COMBINED CYCLE POWER
PLANT PROJECT SHEET NO 11 of 12

*Alarm Panels
Detection system consists of
1 control panel location in main room
2 local Alarm panels provided
- Main power Transformers
- T.G Bearings
- Turbine Lube oil reservoirs and conditioners

*Fire warning devices

1 Fire detection warning Horns- These are provided at suitable locations in plant
& and connected to main panel. These are to provide effective warning, ensuring
the safety of people and environment.
2 Rotating Light or strobe beacons - These are provided at suitable locations in
plant and it should be visible from every location of plant. It shall be placed at the
topmost part of the building. These are actually high efficient LEDs or Xenon
flash tubes and accompany sounders to ensure alarm is recognized.
3 Manual Pull station for manual initiation of fire alarm.

Details of fire detection and fire fighting system for each of following areas.

1. Electrical and administration & control Building - For this area sprinkler,
portable extinguisher and smoke detectors are considered.
2. Ware house and workshop- For this area sprinkler, portable extinguisher and
smoke detectors are considered.
3. Electrical switchyard Building - For this area smoke detector and automatic
extinguishers are considered.
4. Temporary Guard House - For this area CO2 portable extinguisher is
considered.
5. Power Building - For this area portable extinguisher is considered.
6. Analyzer Building - For this area dry powder type portable extinguisher is
considered.
7. Maintenance and loading area - For this area dry powder type portable
extinguisher is considered.
DOC. NO.-
100-1101-L1L-R00
GAJANAN AND SONS CLIENT:
FIRE SAFETY PVT. LTD. Rev –0
M/s KDL 120MW COMBINED CYCLE POWER
PLANT PROJECT SHEET NO 12 of 12

3. SPECIFICATIONS & MAKES.

Sr. No Description Material / Specs. Makes.


A Fire Protection System
1 Fire pumps CI Kirloskar/Mather & Platt
2 Diesel engine Cummins/Graves/KOEL
3 Motors Kirloskar/Siemence/BB
4 Pipes GI/MS ‘B’ class (IS- Tata / Jindal
1239)
5 Landing Valves Gun Metal New Age/Safe guard
6 Hose pipe RRL canvas New Age/Safe guard
7 Hose Reel Rubber New Age/Safe guard
8 Hose Box MS
9 Control valve New Age/HD/Tyco
10 Sprinkler heads UL/FM Approved New Age/Tyco/viking
11 Flow switch Honeywell/ Spray safe
12 Butterfly Valves CI Audco/Intervalve
13 Ball valves Gun Metal RB / Zoloto
14 Fire extinguishers Mimimax /safeguard