Multi-Turn Actuators Profox PF-M25 - PF-M100: Assembly and Commissioning Operation Instructions
Multi-Turn Actuators Profox PF-M25 - PF-M100: Assembly and Commissioning Operation Instructions
PROFOX
PF-M25 – PF-M100
Target group:
This document contains information for assembly, commissioning and maintenance staff.
2
PF-M25 – PF-M100
Table of contents
3
PF-M25 – PF-M100
Safety instructions
1. Safety instructions
1.1. Prerequisites for the safe handling of the product
Standards/directives The end user or the contractor must ensure that all legal requirements, directives,
guidelines, national regulations and recommendations with respect to assembly,
electrical connection, commissioning and operation are met at the place of installation.
Depending on the actuator version, this includes:
● Applicable configuration guidelines for fieldbus applications.
● Applicable configuration guidelines for network applications.
Safety instructions/
All personnel working with this device must be familiar with the safety and warning
warnings
instructions in this manual and observe the instructions given. Safety instructions
and warning signs on the device must be observed to avoid personal injury or property
damage.
Qualification of staff Assembly, electrical connection, commissioning, operation, and maintenance must
be carried out by suitably qualified personnel authorised by the end user or contractor
of the plant only.
Prior to working on this product, the staff must have thoroughly read and understood
these instructions and, furthermore, know and observe officially recognised rules
regarding occupational health and safety.
Commissioning Prior to commissioning, imperatively check that all settings meet the requirements
of the application. Incorrect settings might present a danger to the application, e.g.
cause damage to the valve or the installation. The manufacturer will not be held
liable for any consequential damage. Such risk lies entirely with the user.
Protective measures The end user or the contractor are responsible for implementing required protective
measures on site, such as enclosures, barriers, or personal protective equipment
for the staff.
Maintenance To ensure safe device operation, the maintenance instructions included in this manual
must be observed.
Any device modification requires prior written consent of the manufacturer.
1.2. Range of application
AUMA multi-turn actuators are designed for the operation of industrial valves, e.g.
globe valves, gate valves, butterfly valves and ball valves.
Other applications require explicit (written) confirmation by the manufacturer.
4
PF-M25 – PF-M100
Safety instructions
Information The term Information preceding the text indicates important notes and information.
5
PF-M25 – PF-M100
Safety instructions
6
PF-M25 – PF-M100
Short description
2. Short description
Multi-turn actuator Definition in compliance with EN 15714-2/EN ISO 5210:
A multi-turn actuator is an actuator which transmits torque to a valve for at least one
full revolution. It is capable of withstanding thrust.
AUMA multi-turn actuators PF-M25 – PF-M100 are driven by an electric motor. For
control in motor operation and for processing the actuator signals, controls are
integrated within the housing. Push buttons allow for local actuator operation. A
handwheel is provided for occasional manual operation. Manual operation is possible
without change-over.
Switching off in end positions may be either by limit or torque seating.
The self-locking of the actuator is ensured by means of the braking function. As soon
as the actuator is at standstill, the motor takes over the brake function for the first
20 seconds. This period is defined through a parameter which can be set via
Bluetooth. After this, the locking brake takes over the brake function by disconnection
from power and renewed engagement. Brake engagement generates a clicking noise
and is part of the standard operational behaviour.
The actuator performs a torque measurement. The measured values can be read
by means of the AUMA Assistant App or AUMA CDT. Measured values are only
generated during motor operation. No measured value is generated during manual
operation. The last measured value remains frozen and is displayed. This is not the
case when starting from the torque seating end position. In this case, the value is
set to zero and also displayed as zero.
AUMA multi-turn actuat- Figure 1: PF-M50
or
PROFOX PF-M50
Information Only smaller sizes without handwheel function are equipped with a manual drive
option via Allen key, located below the screw plug for manual emergency operation
[5].
Using the AUMA CDT software for Windows-based computers (notebooks or tablets)
and the AUMA Assistant App, actuator data can be uploaded and read, settings
can be modified and stored. The connection between computer and AUMA actuator
is established wireless via Bluetooth interface. With the AUMA Cloud, we provide
an interactive platform to collect and assess e.g. detailed device data of all actuators
within a plant.
7
PF-M25 – PF-M100
Short description
AUMA CDT AUMA CDT is a user-friendly setting and operation program for AUMA actuators.
Connection between computer (notebook, tablet) and actuator is wireless via
Bluetooth interface.
AUMA CDT software can be downloaded free of charge from our website
www.auma.com.
The AUMA Cloud is the driving element of the digital AUMA world, acting as
interactive platform for efficient maintenance of AUMA actuators at moderate cost.
AUMA Cloud The AUMA Cloud collects all device data of all actuators within one site and provides
a clear overview at a glance. Detailed analysis provides valuable information on
potential maintenance requirements. Additional functions foster smooth asset
management.
8
PF-M25 – PF-M100
Name plate
3. Name plate
Figure 4: Name plate arrangement
9
PF-M25 – PF-M100
Name plate
Order number The product can be identified using this number and the technical data as well as
order-related data pertaining to the device can be requested.
Please always state this number for any product inquiries.
On the Internet at http://www.auma.com > Service & Support >myAUMA, we offer
a service allowing authorised users to download order-related documents such as
wiring diagrams and technical data (both in German and English), inspection certificate
and the operation instructions when entering the order number.
Data Matrix code When registered as authorised user, you may use our AUMA Assistant App to scan
the Data Matrix code and directly access the order-related product documents without
having to enter order number or serial number.
Figure 6: Link to AUMA Assistant App:
10
PF-M25 – PF-M100
Transport and storage
Suspended load!
Death or serious injury.
→ Do NOT stand below suspended load.
→ Attach ropes or hooks for the purpose of lifting by hoist only to housing and NOT
to handwheel.
→ Actuators mounted on valves: Attach ropes or hooks for the purpose of lifting
by hoist to valve and NOT to actuator.
→ Actuators mounted to gearboxes: Attach ropes or hooks for the purpose of lifting
by hoist only to the gearbox using eyebolts and NOT to the actuator.
→ Respect total weight of combination (actuator, gearbox, valve)
→ Secure load against falling down, sliding or tilting.
→ Perform lift trial at low height to eliminate any potential danger e.g. by tilting.
Information Please refer to the technical data sheet for actuator weights.
4.2. Storage
Long-term storage For long-term storage (more than 6 months), observe the following points:
1. Prior to storage:
Protect uncoated surfaces, in particular the output drive parts and mounting
surface, with long-term corrosion protection agent.
2. At an interval of approx. 6 months:
Check for corrosion. If first signs of corrosion show, apply new corrosion protec-
tion.
11
PF-M25 – PF-M100
Assembly
5. Assembly
The product described in this document can be operated without restriction in any
mounting position.
5.2. Fit ball handle to handwheel
To avoid damage during transport, the ball handle is fitted at the rear of the
handwheel.
Prior to commissioning, mount the ball handle into correct position:
1. Remove cap nut [1] and pull out ball handle [2].
2. Insert ball handle [2] in correct position and fasten with cap nut [1].
Information The end position detection can be modified by rotating the handwheel even if the
actuator is not mounted to a valve.Therefore, we recommend refraining from rotating
the handwheel several times prior to mounting the actuator to the valve.
12
PF-M25 – PF-M100
Assembly
Assemble valve and actuator in the same end position. As standard, the actu-
ator is supplied in end position CLOSED.
→ Recommended mounting position for butterfly valves: End position CLOSED.
→ Recommended mounting position for ball valves: End position OPEN.
Assembly steps 1. If required, move actuator in same end position as valve using the handwheel.
2. Clean mounting faces, thoroughly degrease uncoated mounting surfaces.
3. Apply a small quantity of grease to the valve shaft [2].
13
PF-M25 – PF-M100
Assembly
4. Place coupling [1] onto valve shaft [2] and secure against axial slipping by using
a grub screw [3] or a clamping washer and a screw with curved spring lock
washer [4]. Thereby, ensure that dimensions X, Y or L are observed (refer to
figure and table <Mounting positions for coupling>).
Figure 8: Examples: Fit coupling
[1] Coupling
[2] Valve shaft
[3] Grub screw
[4] Clamping washer and screw with curved spring lock washer
Figure 9: Mounting positions for coupling
Table 3:
Mounting position of the coupling within fitting dimensions according to AUMA definition
Dimensions M25 M50 M100
[mm]
EN ISO 5211 F05 F07 F10 F05 F07 F10 F07 F10
X max. 3 3 3 3 3 3 4.5 4.5
Y max. 2 2 2 2 2 2 4.5 4.5
L max. 381)/40 381)/40 381)/40 381)/40 381)/40 381)/40 50 50
14
PF-M25 – PF-M100
Assembly
6. Fit actuator. If required, slightly turn actuator until splines of coupling engage.
Figure 10: Mounting the actuator onto valve
15
PF-M25 – PF-M100
Electrical connection
6. Electrical connection
6.1. Basic information
Wiring diagram/terminal The pertaining wiring diagram/terminal plan (in German or English) is attached to
plan the device in a weather-proof bag, together with these operation instructions. It can
also be requested from AUMA (state order number, refer to name plate) or
downloaded directly from the Internet (http://www.auma.com).
Permissible networks The actuators are suitable for use in TN and TT networks. For IT network, a suitable,
(supply networks) approved insulation monitor measuring the pulse code is required.
Current type, mains Type of current, mains voltage and mains frequency must match the data on the
voltage, mains fre- name plate.
quency For short-circuit protection and for disconnecting the actuator from the mains, fuses
and disconnect switches or circuit breakers have to be provided by the customer.
For circuit breakers, the following sizing/characteristics are recommended:
Sizing/
Number of actuators characteristics
1 B06
2 B10
4 C13
10 D16
Refer to electric data for the maximum current values of individual models and
versions.
16
PF-M25 – PF-M100
Electrical connection
Safety standards Safety measures and safety equipment must comply with the respectively valid
national on site specifications. All externally connected devices shall comply with
the relevant safety standards applicable for the place of installation.
Connecting cables, ● We recommend using connecting cables and connecting terminals according
cable glands, reducers, to rated current (IN) (refer to motor or electrical data sheet).
blanking plugs ● For device insulation, appropriate (voltage-proof) cables must be used. Specify
cables for the highest occurring rated voltage.
● To avoid contact corrosion, we recommend the use of sealing agents for cable
glands and blanking plugs made of metal.
● Use connecting cable with appropriate minimum rated temperature.
● For connecting cables exposed to UV radiation (outdoor installation), use UV
resistant cables.
● For the connection of position transmitters, screened cables must be used.
Cable installation in ac- Signal and fieldbus cables are susceptible to interference. Motor cables are
cordance with EMC interference sources.
● Lay cables being susceptible to interference or sources of interference at the
highest possible distance from each other.
● The interference immunity of signal and fieldbus cables increases if the cables
are laid close to the earth potential.
● If possible, avoid laying long cables and make sure that they are installed in
areas being subject to low interference.
● Avoid parallel paths with little cable distance of cables being either susceptible
to interference or interference sources.
6.2. Open terminal compartment
Figure 11: Open terminal compartment (example of I/O interface)
[1] Cover
[2] Screws
[3] Cable entry
[4] Blanking plug
[5] Cable gland (not included in scope of delivery)
17
PF-M25 – PF-M100
Electrical connection
3. Tighten cable glands and blanking plugs with the appropriate torque in compli-
ance with the manufacturer's specifications.
6.3. Cable connection
Cable arrangement
The shown cable arrangement is only applicable for actuators with I/O interface!
For actuators with fieldbus interface, please refer to appropriate short instructions
(if available).
[1] Cable arrangement for one mains cable and one signal cable
[2] Cable arrangement for one mains cable and two additional cables
1. Insert signal cable into cable gland on the right and push upward until the cable
is visible.
18
PF-M25 – PF-M100
Electrical connection
2. In case a further signal cable is connected: Insert second signal cable into
middle cable gland and push upward until the cable is visible.
3. Insert mains cable into left cable gland and also push upward until the cable is
visible.
4. Remove cable sheathing.
5. Strip wires.
→ Controls approx. 6 mm, power supply unit approx. 10 mm
6. For flexible cables: Use wire end sleeves according to DIN 46228.
PE connection
7. Fasten PE using spade lugs or wire end sleeves at protective earth connection
( ) as shown. Do not completely loosen screw!
Figure 14: Protective earth connection (example)
Table 5:
Terminal cross sections and tightening torques of PE connection
Designation Terminal cross sections Tightening torques
2
Protective earth connection (PE) 1.0 – 6 mm (flexible) via spade lug or 3 – 4 Nm
wire end sleeve
2
1.5 – 2.5 mm (flexible) directly
2
1.5 – 6 mm (rigid) directly
19
PF-M25 – PF-M100
Electrical connection
Damage to push-in terminals by jamming of wire end sleeves with the housing!
Replacement of the complete component is required.
→ Use wire end sleeves with smooth surface.
→ Always press the push-in terminals completely down using a screwdriver and
always carefully remove signal cables.
→ It must be possible to pull out the signal cable without resistance when the push-
in terminal held down.
Table 7:
Terminal cross sections
Designation Wire type Cross section
min. [mm²] max. [mm²]
I/O signal cable solid 0.2 1.5
flexible 0.2 1.5
flexible with wire end 0.2 1.5
sleeve without plastic
sleeve
AWG AWG 24 AWG 16
10. For shielded cables: Link the cable shield end via the cable gland to the housing
(earthing).
11. If the PE conductor has been removed from the cover, it must be tightened
applying 2.2 Nm tightening torque prior to re-placing the cover.
12. Fasten cable glands with the torque as specified by the manufacturer to ensure
respect of required enclosure protection.
13. Connect power supply.
If the end position setting is carried out with the internal operation buttons
following the connection to the power supply: Do not close cover!
20
PF-M25 – PF-M100
Electrical connection
[1] Cover
[2] Screws
[3] O-ring
Standard version: Without earth connection, with plastic plate and screw only.
Option: With earth connection consisting of metal plate and hex. socket cap head
screw with shaft bearing race.
21
PF-M25 – PF-M100
Electrical connection
Information The earthing cable must be attached between the U-bracket and the metal washer
resting on the housing.
Information Strip powder from actuator surface below the U-bracket (file down).
Table 8:
Terminal cross sections and earth connection tightening torques
Conductor type Terminal cross sections Tightening torques
solid 2.5 mm² to 6 mm² 3 – 4 Nm
flexible 1.5 mm² to 4 mm² 3 – 4 Nm
For fine stranded (flexible) wires, connection is made via cable lugs/ring terminals. When connecting
two individual wires with a U-bracket, cross sections have to be identical.
22
PF-M25 – PF-M100
Commissioning
7. Commissioning
Commissioning is made in three steps:
1. End position setting
2. Position indicator setting
3. Configuration of further parameters
Besides end position settings, all other settings have already been made in
the factory in compliance with the order.
If correctly ordered, only end position setting is required.
The following table shows the most important parameters and how they can be
configured.
Step Setting Parameter/desig- At the actuator AUMA Assistant AUMA CDT Page
nation App
End position set- Positions End position Yes Yes Yes page 24, Set end
ting CLOSED setting position CLOSED
End position OPEN Yes Yes Yes page 25, Set end
setting position OPEN
Position indicator Indication for the Indication end posi- Yes No No page 27, Position
setting end positions tion CLOSED indicator setting
Indication end posi- Yes No No
tion OPEN
Configuration of Type of seating End position No Yes Yes —
further parameters CLOSED
End position OPEN No Yes Yes
Torque switching Tripping torque No Yes Yes
CLOSE
Tripping torque No Yes Yes
OPEN
Speeds Speed No Yes Yes page 28, Speed
setting
Many further parameters can be configured using the AUMA Assistant App or AUMA
CDT. Refer to Manual “PROFOX Parameters and functions”.
7.1. End position setting (via push buttons)
When setting the end positions, the actuator acts in accordance with the selected
type of seating:
Limit seating
The final position of the end position is set to the exact current position. Once the
final position is reached, the actuator switches off.
Torque seating
The final position of the end position is set to <1 % before the current position. Once
the torque is reached, the actuator switches off.
23
PF-M25 – PF-M100
Commissioning
The end positions may also be set using the AUMA Assistant App or the AUMA
CDT software.
3. Once the desired end position CLOSED has been reached, release the push
button .
➥ The LED continues flashing in blue for approx. 10 seconds. This time span al-
lows for end position setting.
24
PF-M25 – PF-M100
Commissioning
4. While LED is flashing in blue, hold down push button for at least two seconds
until the LED is illuminated in red.
Figure 19: Example with I/O interface
25
PF-M25 – PF-M100
Commissioning
2. Operate in direction OPEN via push button until complete valve opening.
3. Once the desired end position OPEN has been reached, release the push button
.
➥ The LED continues flashing in blue for approx. 10 seconds. This time span al-
lows for end position setting.
4. While LED is flashing in blue, hold down push button for at least two seconds
until the LED is illuminated in green.
Figure 21: Example with I/O interface
26
PF-M25 – PF-M100
Commissioning
The position indicator shows the valve position by means of a yellow position
indication disc moving up and down. The white end position indication ring shows
the end position OPEN and the bottom final point of the position indication shows
the end position CLOSED.
Figure 22: Mechanical position indicator
27
PF-M25 – PF-M100
Commissioning
During first operation in direction OPEN, the yellow position indication disc pushes
the white end position indication ring until reaching the end position.
Figure 24: Operation in direction OPEN
During operation in direction CLOSE, only the yellow position indication disc is
moving. The white end position indication ring remains in end position OPEN.
After having changed the end position OPEN, it is possible to open the position
indicator and readjust the white end position indication ring using a screw-
driver.
Information In case of problems with the mechanical position indicator, refer to Corrective action
chapter.
7.3. Configuration of further parameters
Either the AUMA Assistant App or AUMA CDT software is required to use the
complete range of configuration options.
The user level defines which parameters are displayed or can be changed.
Information For further information relating to user levels and passwords, please refer to page
33, Table 16
Table 9: Assignment of power levels to the motors and power supply units used
Power level Motor Power supply unit
V1 18 W 65 W
V2 25 W 65 W
V3 50 W 85 W
28
PF-M25 – PF-M100
Commissioning
29
PF-M25 – PF-M100
Commissioning
30
PF-M25 – PF-M100
Operation
8. Operation
The handwheel allows actuator operation even in case of power failure. Handwheel
operation is only provided for occasional manual valve operation.
The handwheel does not rotate during motor operation. Change-over from motor
operation to manual operation is not required.
31
PF-M25 – PF-M100
Operation
Menu Description
Diagnostics Display of all available warnings and faults including
respective details.
Actuator diagnostics and detailed diagnostics
Operation function Operation in direction of end positions
Resetting the fault log
Setting end positions Setting the positions for end positions CLOSED and
OPEN
Device ID Device designation
Order number, serial number
Configuration Configuration of all parameters
Service functions Factory settings
Rebooting the actuator
32
PF-M25 – PF-M100
Operation
User level User level (1), (2), (3), ... defines which menu items or parameters can be displayed
or modified by the active user.
6 different users/user levels are available. User level (1), (2), (3), ... is indicated in
the top display row.
Figure 26: User level display (example user level 4)
Password A specific password is assigned to each user level and allows different actions. The
password must comprise 6 characters.
Operation mode REMOTE is the preliminary condition for actuator control via binary
signals, analogue signals or via fieldbus.
The operation mode can be activated via AUMA Assistant App or AUMA CDT
software:
AUMA Assistant App DIS_53 Configuration
DIS_2919 Operation mode
PRM_5535 Selector
Or directly via the Remote operation menu in DIS_2250 Operation function.
Default setting: Operation mode = REMOTE
AUMA CDT DIS_53 Configuration
DIS_2919 Operation mode
33
PF-M25 – PF-M100
Operation
PRM_5535 Selector
Or directly via the tool bar in the “Device” tab in PRM_5535 Selector or Remote
control.
Default setting: Operation mode = REMOTE
Information The actuator only reacts to the currently selected command source. However, the
command source can be changed during running operation. The OPEN/CLOSE
operation is usually performed via the digital inputs. The setpoint control (e.g. for
modulating duty) can only be performed via the analogue inputs or the fieldbus.
34
PF-M25 – PF-M100
FOX-EYE indication light and status indication
Various profiles can be selected for the FOX-EYE indication light. Depending on the
profile, colours and states of the indication light provide a different signal.
Use the following menu for active profile setting:
DIS_53 Configuration
DIS_2269 Indication
DIS_2684 Actuator internal control unit
PRM_5506 Configuration FOX-EYE (blinking behaviour/colours)
The following profiles can be selected by means of the AUMA Assistant App or AUMA
CDT:
Default value: CUSTOMER
Setting values: CUSTOMER, AUMA, NAMUR, FLEXIBLE
Information The “Flexible” profile allows setting of colours and states of the signals as required.
Most signals can be activated and deactivated. Also refer to the table at the end of
the section.
35
PF-M25 – PF-M100
FOX-EYE indication light and status indication
36
PF-M25 – PF-M100
FOX-EYE indication light and status indication
Position indicator
37
PF-M25 – PF-M100
Corrective actions
Table 19:
Faults during operation/commissioning
Faults Description/cause Remedy
Actuator operation is either too fast Speed setting is incorrect. Change speed.
or to slow.
Actuator suddenly stops in end posi- Speed reduction switched off or incorrectly set be- Set speed reduction and/or adapt parameter.
tions. fore reaching end positions.
Mechanical position indicator stops; Incorrect position indicator selection when placing Replace position indicator.
however, the actuator continues oper- the order.
ation. This can cause the position in-
dicator to break.
The position indication disc jams at In relation to the actuator stroke range, the position Open blanking plugs with screwdriver.
the upper or lower edge of the posi- indicator has been incorrectly set. This causes the ● Position indication disc jams at the top (end
tion indicator and does no longer position indicator to be pressed to the end stop and position OPEN):
move in the event of a change of dir- the slip clutch is activated. The position indication Briefly turn the spindle shaft with slotted
ection. disc jams in the event of high speeds. screwdriver clockwise.
● Position indication disc jams at the bottom (end
position CLOSED):
Briefly turn the spindle shaft with slotted
screwdriver counterclockwise.
The yellow position indication disc The setting range of the position indication disc is Operate the actuator sufficiently in opposite direc-
stops before the end position indica- larger than the actual stroke range of the actuator. tion.
tion ring. Open blanking plugs with screwdriver.
Press down the end position indication ring using
a screwdriver and approach again the end position,
ensuring that the end position indication ring is
pushed to the end position by the position indication
disc.
Actuator exceeds the end position. Overrun due to excessive speed. Advance electronic end position switch by the
overrun margin or adapt the parameters to an ex-
tended speed reduction curve in the “Speed
red.pr.end pos.” [speed reduction prior to end pos-
ition] section.
Actuator repeatedly corrects the set- Overrun due to excessive speed. Adapt the speed reduction prior to setpoint position
point position during positioning. parameters to an extended speed reduction curve
in the positioner menu or adjust optimally the
parameters for the positioner.
Faults interrupt or prevent the electrical actuator operation. If a fault occurs, the
FOX-EYE indication light is quickly flashing in red.
Warnings have no influence on the electrical actuator operation. They only serve
for information purposes. The FOX-EYE remains white.
Further signals are comprised in collective signals. The FOX-EYE remains white.
For the content of the respective collective signals, refer to the Manual PROFOX
“Parameters and functions”.
Faults and warnings may exclusively be read via AUMA Assistant App or AUMA
CDT software.
38
PF-M25 – PF-M100
Corrective actions
Table 20:
Fault / NAMUR failure
Display (App or CDT) Description/cause Remedy
Torque fault CLOSE The actuator has reached the preset tripping torque Perform one of the following measures:
in direction CLOSE. ● Issue operation command in direction OPEN.
● Reset the fault signal either via AUMA Assistant
App or AUMA CDT software.
● For control via fieldbus: Execute reset command
via fieldbus.
Torque fault OPEN The actuator has reached the preset tripping torque Perform one of the following measures:
in direction OPEN. ● Issue operation command in direction CLOSE.
● Reset the fault signal either via AUMA Assistant
App or AUMA CDT software.
● For control via fieldbus: Execute reset command
via fieldbus.
Thermal fault Motor protection tripped. Perform one of the following measures:
● Cool down, wait.
● If the fault indication display persists after cool-
ing down:
- Reset the fault signal either via AUMA As-
sistant App or AUMA CDT software
- For control via fieldbus: Execute reset
command via fieldbus
● Check fuses.
Fault no reaction No actuator reaction to operation commands within Check movement at actuator.
the set reaction time.
Incorrect rotary direction Contrary to the configured direction of rotation and ● Check operation command control.
the active operation command, the motor turns into ● Check the parameter PRM_5515 Rot. dir. motor,
the wrong direction. whether it is suitable for the gearbox. The fault
may only occur after modification of the actuat-
or/gearbox.
● Check the parameter PRM_79 Closing rotation.
For a 1-phase AC motor, this can be caused by a
defective auxiliary capacitor.
Internal error Collective signal 14: Use AUMA Assistant App or AUMA CDT to visualise
Internal error has occurred. the individual signals by means of the Diagnostics
Different causes can be the reason: Memory over- menu.
flow in firmware, firmware error, electronic sub-as- If a memory overflow occurs, reboot the actuator.
sembly defective. In case the problem persists: Contact AUMA Ser-
vice.
IE logic Check logic.
IE fieldbus Check fieldbus interface.
IE MWG Check MWG.
IE version Check configuration.
IE EEPROM Check configuration.
IE parameter Check configuration.
IE file access Check configuration.
IE registration Check configuration.
IE startup FB Check configuration.
IE CAN Overflow Check configuration.
IE MWG measurement system defective Check configuration.
Wrn signal loss actual position Check configuration.
Configuration error Collective signal 11: Use AUMA Assistant App or AUMA CDT to visualise
A configuration fault has occurred preventing actu- the individual signals by means of the Diagnostics
ator operation. menu.
Check the applicable configuration parameters.
In case the problem persists: Contact AUMA Ser-
vice.
IE parameter configuration Check position transmitter parameters.
39
PF-M25 – PF-M100
Corrective actions
Table 21:
Warning / NAMUR out of specification
Display (App or CDT) Description/cause Remedy
Internal warning Collective signal 15: Use AUMA Assistant App or AUMA CDT to visualise
Device warnings. the individual signals by means of the Diagnostics
The device can still be operated with restrictions. menu.
40
PF-M25 – PF-M100
Corrective actions
Table 22:
Not ready REMOTE / NAMUR function check
Display (App or CDT) Description/cause Remedy
OFF active The actuator is in operation mode OFF. Change operation mode.
Operation mode Local The actuator is in operation mode LOCAL. Change operation mode.
Operating mode Commissioning The actuator is in operation mode Commissioning. End commissioning and change the operation mode.
EMCY behav. active Operation mode EMERGENCY is active (EMER- ● Detect cause for the EMERGENCY signal.
GENCY signal was sent). ● Verify failure source.
0 V are applied at the EMERGENCY input. ● Apply +24 V DC at EMERGENCY input.
Service active Operation via service interface (Bluetooth) and Exit service software.
AUMA CDT service software.
Disabled The actuator is in operation mode Disabled. Check configuration.
I/O interface The actuator is controlled via the I/O interface Check I/O interface.
FailState fieldbus Fieldbus connection available, however no process Verify master configuration.
data transmission by the master.
41
PF-M25 – PF-M100
Corrective actions
42
PF-M25 – PF-M100
Servicing and maintenance
AUMA
AUMA offers extensive service such as servicing and maintenance as well as
Service & Support customer product training. For the contact addresses, refer to our website
(www.auma.com).
The following actions are at least required to ensure safe device function during
operation:
Enclosure protection IP68
After submersion:
● Check actuator.
● In case of ingress of water, locate leaks and repair. Dry device correctly and
check for proper function.
6 months after commissioning and then once a year
● Carry out visual inspection:
Cable entries, cable glands, blanking plugs, etc. have to be checked for correct
tightness and sealing. If required, tighten cable glands and blanking plugs with
torque in compliance with the manufacturer's specifications.
● Check fastening screws between actuator and gearbox/valve for tightness. If
required, fasten screws while applying the tightening torques as indicated in
chapter <Assembly>.
● When rarely operated: Perform test run.
Seals
Preventive actions to ensure the IP protection degree. The seals of seal kit S1 should
be replaced within a period of 4 – 8 years:
After 4 years: In case of outdoor installation (frequent changes of temperature and
humidity, extreme weathers)
After 8 years: In case of indoor installation (constant or virtually constant
environmental conditions)
If original AUMA screw plugs are used, original AUMA seals must also be used.
They are included with the AUMA seal kit S1.The seal kit can be ordered with AUMA.
Lubrication
● Within the device lifetime, no additional lubrication of the gear housing is required
during operation.
Lifetime
The maximum lifetime depends on the number of operating cycles or the number of
starts (refer to technical data) as well as the respectively applicable AUMA load
profiles. Distinction is made between actuators in open-close or modulating duty:
Open-close duty The load is measured by means of the number of operating cycles at a defined torque
(OPEN/CLOSE) characteristics, the AUMA load profile.
One operating cycle corresponds to 25 turns respectively to OPEN and CLOSE.
AUMA load profile:
10 % of the travel at 100 % of maximum torque.
90 % of the travel at 35 % of maximum torque.
43
PF-M25 – PF-M100
Servicing and maintenance
Modulating duty The load is measured by means of the switching frequency, e.g. the number of
starts/hour at a defined torque, the AUMA load profile.
One start corresponds to a movement of 0.25 turns in both directions.
AUMA load profile:
35 % of maximum actuator torque.
Determination Operating cycles and number of starts for PROFOX actuators can be determined
Key figures using the AUMA CDT software.
Operating cycles
The number of operating cycles can be further determined using the AUMA CDT
software and the AUMA Cloud. For this, create an actuator snapshot and upload it
to the AUMA Cloud. The AUMA Cloud menu “My devices” indicates the value for
“Number of Full Stroke Equivalent” for the actuator.
Number of starts
The number of starts in indicated in starts/h. The exact sum of this key figure is made
in the actuator and can be read via AUMA Assistant App or the AUMA CDT software
in “Operational info”.
AUMA recommendation
We recommend contacting the AUMA Service for an inspection of the actuator if one
of the following conditions is reached:
● The actuator life is more than 12 years
● The maximum number of operating cycles has been reached at a lower load
profile than specified by AUMA (for open-close duty).
● The maximum number of starts has been reached at a lower load profile than
specified by AUMA (for modulating duty).
An inspection by the AUMA Service can also be carried out using digital snapshots
from the AUMA Assistant App or the AUMA CDT software.
Mechanical position indicator
Both indicator glass and screw plug of mechanical position indicator are made of
plastic. To ensure enclosure protection and a long lifetime, both components must
be fastened at a defined torque:
Indicator glass cover: 6 Nm (special tool art. no. V004.027-02, available with AUMA)
Screw plug: 1.6 Nm
44
PF-M25 – PF-M100
Disposal and recycling
45
PF-M25 – PF-M100
Technical data
13.1. Technical data Multi-turn actuators with integral controls for open-close and modulating duty
46
PF-M25 – PF-M100
Technical data
47
PF-M25 – PF-M100
Technical data
48
PF-M25 – PF-M100
Technical data
With output drive type A for valve shafts with threads (option)
The stem stroke can be increased by using spacer elements as special solution; available on request.
Service conditions
Mounting position Any position
Installation altitude ≤ 2,000 m above sea level
> 2 000 m above sea level on request
Ambient temperature –30 °C to +70 °C
Humidity Up to 100 % relative humidity across the entire permissible temperature range
Enclosure protection in accordance Standard: IP67
with IEC 60529
Option: According to AUMA definition, enclosure protection IP68 meets the following requirements:
● Depth of water: maximum 8 m head of water
● Continuous immersion in water: maximal 96 hours
● Up to 10 operations during immersion
● Modulating duty is not possible during immersion
49
PF-M25 – PF-M100
Technical data
Service conditions
Pollution degree according to Pollution degree 4 (when closed), pollution degree 2 (internal)
IEC 60664-1
Vibration resistance according to 2 g, from 10 Hz to 200 Hz
IEC 60068-2-6 Resistant to vibration during start-up or for failures of the plant. However, a fatigue strength may not be
derived from this. Not valid in combination with gearboxes.
Seismic resistance according to Test proof for application class 3
IEC 60068-3-3
Corrosion protection Standard: KS
Suitable for use in areas with high salinity, almost permanent condensation, and high
pollution.
Option: KX (upon request)
Suitable for use in areas with extremely high salinity, permanent condensation, and high
pollution.
Coating Double layer powder coating
Two-component iron-mica combination
Colour Standard: AUMA silver-grey (similar to RAL 7037)
Option: Available colours on request
Driving load During operation, accelerating loads up to 15 % of the max. torque may occur.
Lifetime Open-close 10,000 operating cycles OPEN - CLOSE - OPEN
duty: One operation cycle consists of 25 turns in both directions (OPEN-CLOSE-OPEN)
Modulating 1.8 million modulating steps
duty:
The lifetime depends on the load and the number of starts. A high starting frequency will rarely improve
the modulating accuracy. To reach the longest possible maintenance and fault-free operating time, the
number of starts per hour chosen should be as low as permissible for the process.
Further information
EU Directives Machinery Directive 2006/42/EC
Low Voltage Directive 2014/35/EU
EMC Directive 2014/30/EU
RoHS Directive 2011/65/EU
50
PF-M25 – PF-M100
Spare parts
51
PF-M25 – PF-M100
Spare parts
Please state device type and our order number (see name plate) when ordering spare parts. Only original AUMA spare parts should be used.
Failure to use original spare parts voids the warranty and exempts AUMA from any liability. Only the designated spare parts with reference
numbers or spare parts sets for replacement are available for the customer. The are specified in the following list. The parts shown in the
exploded view without reference numbers may only be replaced by AUMA. Representation of spare parts may slightly vary from actual delivery.
1) A special tool is required for disassembly/assembly of mechanical position indicator. This can be ordered from AUMA (parts number:
V004.027-02).
2) The manual emergency operation is only available for models PF-M5 and PF-M10, which are not equipped with a handwheel.
52
PF-M25 – PF-M100
Index
L
Index LEDs (indication lights) 35
Lubrication 43
A
Ambient temperature 9 M
App functions 32 Mains cable 18
Applications 4 Mains connection 16
Assembly 12 Mains frequency 9, 16
Assistant App 10 Mains voltage 9, 16
AUMA Assistant App 8, 10 Maintenance 4, 43, 43
AUMA Cloud 8 Maintenance intervals 43
Manual operation 31
B Mechanical position indcator 27
Blanking plug 17 Mechanical position indicator 35
Bluetooth 8 MODE 34
C Motor operation 31
Cable connection 18 N
Cable glands 17 Name plate 9, 16
Cable path 18
Cables 17 O
CDT 8 OPEN-CLOSE control 33
Change-over between OPEN- 33 Open terminal compartment 17
CLOSE control and setpoint Operating time 9, 28
control Operation 4, 31
Commissioning 4, 23 Operation and display 49
Connecting cables 17 Order number 9, 10
Control inputs Potential 16 Output signals Potential 16
Corrective actions 38
Corrosion protection 11 P
Coupling 12, 13 Password 33
Current type 9, 16 PE connection 18
Position indication 27
D Power supply 18
Data Matrix code 10 Protective measures 4
Directives 4 Push buttons 31
Disposal 45
Q
E Qualification of staff 4
Earth connection 22
Electrical connection 16 R
EMC 17 Range of application 4
EMERGENCY operation 34 rated current 9
End position CLOSED 24 Rated power 9
End position OPEN 25 Recycling 45
End position setting 23 reductions 17
Remote 33
F Remote operation 33
Fault 38 Running indication 35
Features and functions 46, 48
Flange size 10
FOX-EYE 35
Further information 50
Fuse 16
H
Handwheel 12
I
Indication lights 35
Input signals Potential 16
Inspection certificate 10
53
PF-M25 – PF-M100
Index
S
Safety instructions 4
Safety instructions/warnings 4
Safety measures 17
Safety standards 17
Screw plugs 17
Serial number 9, 10
Service 43
Service conditions 50
Setpoint control 33
Short description 7
Signal cable 18
Size 10
Spare parts 51
Speed 28
Speed range 9
Speeds 28
Standards 4
Status signals Potential 16
Storage 11
Supply networks 16
Support 43
T
Technical data 46
Terminal compartment: close 21
Terminal plan 16
Torque range 9
Transport 11
Type 10
Type designation 9
Type of duty 9
Type of networks 16
U
User 33
User level 33
W
Wiring diagram 9, 10, 16
Y
Year of manufacture 10
Year of production 10
54