Power System Lab Manual
Power System Lab Manual
Date:
CIRCUIT DIAGRAM:
LIST OF APPARATUS:
MACHINE SPECIFICATION:
THEORY:
ABCD parameter are widely used in analysis of power transmission engineering where they will be
turned as “Generalized circuit parameter” ABCD parameters are also called as Transmission parameter. It
is conventional to designate the input port as sending end and the output port as receiving end while
representing ABCD parameter.
We know that,
𝑉 S = 𝐴 𝑉 R + 𝐵 𝐼R --------------------- (1)
𝐼S = 𝐶 𝑉 R + 𝐷 𝐼R --------------------- (2)
At open circuit condition (IR = 0), we get
A = VS/VR --------------------- (3)
C = IS/VR --------------------- (4)
At short circuit condition (VR = 0), we get
B = VS/IR --------------------- (5)
D = IS/IR --------------------- (6)
PROCEDURE:
OBSERVATIONS:
CALCULATION:
A = VS/VR
C = IS/VR
B = VS/IR
D = IS/IR
RESULTS:
A B C D
CONCLUSION:
LIST OF APPARATUS:
MACHINE SPECIFICATIONS:
CIRCUIT DIAGRAM:
THEORY:
Theory of synchronizing:-
If two like alternators having the same wave form are running with their electromotive force
waves in uniform and are generating the same voltage they may be made to operate in parallel.
This is due to the reversibility of the alternators that is the ability of either to operate as a
synchronous motor in the same direction of rotation if its driving power be removed.
Necessity of synchronization:-
An alternator cannot deliver power to electric power system until its voltage, frequency,
phase sequence and other parameters matches with the network to which the alternator is
connected.
The case of synchronization arises because we are connecting many alternators in parallel
to supply the demand load. So we need to match all the parameter of connected alternator
with bus-bar to deliver power to load.
By synchronization we can match all the other parameters of one alternator with the other
alternator and also with the bus-bar and deliver the required power to load.
Synchronization of alternator is also called as paralleling of alternator
PROCEDURE:
CONCLUSION:
APPARATUS REQUIRED:
CIRCUIT DIAGRAM:
THEORY:
Voltage Regulation of single-phase transformers is the percentage (or per unit value) change in its secondary
terminal voltage compared to its original no-load voltage under varying secondary load conditions. In other words,
regulation determines the variation in secondary terminal voltage which occurs inside the transformer as a result of
variations in the transformers connected load thereby affecting its performance and efficiency if these losses are high and
the secondary voltage becomes too low. When there is no-load connected to the transformers secondary winding, that is
its output terminals are open-circuited, there is no closed-loop condition, so there is no output load current (IL = 0) and the
transformer acts as one single winding of high self-inductance. Note that the no-load secondary voltage is a result of the
fixed primary voltage and the turns ratio of the transformer. Loading the secondary winding with a simple load impedance
causes a secondary current to flow, at any power factor, through the internal winding of the transformer. Thus voltage
drops due to the windings internal resistance and its leakage reactance causes the output terminal voltage to change. A
transformers voltage regulation change between its secondary terminal voltage from a no-load condition when IL = 0,
(open circuit) to a fully-loaded condition when IL = IMAX (maximum current) for a constant primary voltage is given as:
Note that this voltage regulation when expressed as a fraction or unit-change of the no-load terminal voltage can be
defined in one of two ways, voltage regulation-down, (Regdown) and voltage regulation-up, (Regup).
That is when the load is connected to the secondary output terminal, the terminal voltage goes down, or when the load is
removed, the secondary terminal voltage goes up. Thus the regulation of the transformer will depend on which voltage
value is used as the reference voltage, load or non-load value. We can also express transformer voltage regulation as a
percentage change between the no-load condition and the full-load conditions as follows:
So for example, let‟s assume we have a single-phase transformer which has an open-circuit, no-load terminal voltage of
100 volts and the same terminal voltage drops to 95 volts on the application of a resistive load. The transformers voltage
regulation would therefore be: 0.05 or 5%, ((100 – 95)/100)*100%). Then a transformers voltage regulation can be
expressed as either a unit change value, in this example 0.05, or as a percentage change value (5%) of the original no-load
voltage.
PROCEDURE:
CONCLUSION:
Aim: To observe the Ferranti effect and find the Surge Impedance Loading (SIL) in a long
transmission line.
Objective: To observe the Ferranti effect and find the SIL a in a long transmission line using
Transmission Line Protection Simulator.
CIRCUIT DIAGRAM:
Fig. 1 Circuit diagram for Ferranti effect and SIL on a long transmission line.
LIST OF APPARATUS:
MACHINE SPECIFICATION:
THEORY:
During light-load or no-load condition, receiving end voltage is greater than sending end voltage in
medium and long transmission line. This happens due to very high line charging
current. This phenomenon is known as Ferranti effect. A charged open circuit line draws
significant amount of current due to capacitive effect of the line. This is more in HV long
transmission line. Sending end voltage of a TL is: Vs = AVR + BIR .
Under no-load condition; IR = 0, therefore: VR =Vs/A ; Since A<1 so VR is greater than Vs.
The capacitance (and charging current) is negligible in short line but significant in medium
line and appreciable in long line. Therefore this phenomenon occurs in medium and long lines.
Consider the figure given below shows phasor diagram of Ferranti Effect of transmission line.
PROCEDURE:
OBSERVATION:
1 At no load
At load when
2
VS = VR
CONCLUSION:
OBJECTIVE: Formulate the Efficiency curve for a 3 phase transformer and find the maximum
efficiency.
APPARATUS REQUIRED:
MACHINE SPECIFICATION:
CIRCUIT DIAGRAM:
THEORY:
Efficiency Of Transformer
Just like any other electrical machine, efficiency of a transformer can be defined as the output power
divided by the input power. That is efficiency = output / input .
Transformers are the most highly efficient electrical devices. Most of the transformers have full load
efficiency between 95% to 98.5% . As a transformer being highly efficient, output and input are having
nearly same value, and hence it is impractical to measure the efficiency of transformer by using output /
input. A better method to find efficiency of a transformer is using, efficiency = (input - losses) / input = 1
- (losses / input).
Hence, efficiency of a transformer will be maximum when copper loss and iron losses are equal.
That is Copper loss = Iron loss.
PROCEDURE:
CONCLUSIONS:
OBJECTIVE: To find out the dielectric strength of transformer oil using breakdown voltage test
kit.
CIRCUIT DIAGRAM:
LIST OF APPARATUS:
THEORY:
Oil used in the transformer for insulation and cooling purpose. A breakdown test on transformer oil is
crucial for assessing the dielectric strength and overall quality of the oil used in electrical transformers.
This can be done using the breakdown test of transformer oil using the breakdown voltage test kit. The
breakdown strength can be calculated using the equation
Breakdown Strength = (breakdown voltage in KV / Electrode gap distance in mm) × 10 ------ (1)
PROCEDURE:
OBSERVATIONS:
1 2.5
2 4.0
3 6.0
CALCULATION:
Dielectric Strength = (V/d) × 10 =
RESULT:
CONCLUSION:
OBJECTIVE: Perform load test on 3 phase transformer under unbalanced condition & thus find
out per cent total harmonic distortion in both generating and load end
APPARATUS REQUIRED:
MACHINE SPECIFICATION:
CIRCUIT DIAGRAM:
THEORY:
Now, let‟s increase the load on one of the phase of our system. As we have increased the load on one
phase, it will draw more current than the other two phases. And this will create imbalance in the system.
And here you‟ll need the neutral conductor. The waveform is now disturbed in terms of magnitude and
phase shift.
System gets unbalanced because of following reasons.
1. Unbalance in winding of a 3 phase equipment like 3 phase induction motor. If the reactants of the
three windings are not same then it will draw unequal current from the system.
2. Unequal load on the system. This causes more current to flow through one particular phase on which
the load is connected.
These are the two main and the basic causes of unbalance in a system.
Effects of unbalanced system
Heating of the 3 phase machines
Heating will decrease overall life of machine
This imbalance, will also increase the I^2 R losses,
Also, unbalanced system may cause tripping of variable frequency drives used for induction motor.
You‟ll see in our distribution system a neutral is always provided. This is because, load on the phases
is not defined or equal. And hence, different phases draw different current which makes the distribution
system unbalanced.
Properties of an unbalanced system.
1. Waveforms are disturbed in terms of magnitude & phase angle.
2. Current flowing through phases is not same.
3. Neutral in needed.
4. Power losses are more.
PROCEDURE:
CONCLUSIONS:
OBJECTIVE: To compute the regulation and efficiency of a transmission line using Transmission
Line Protection Simulator.
CIRCUIT DIAGRAM:
Fig. 1 Circuit diagram for calculation of regulation and efficiency of a transmission line.
LIST OF APPARATUS:
MACHINE SPECIFICATION:
THEORY:
Due to transmission line resistance there are certain losses in the transmission lines such as copper loss,
corona loss etc. and due to the line resistance and reactance there are certain voltage drops in the
transmission lines. To measure this loss we can find out the efficiency and to find out the drop we can
find out the regulation of the line. To find the efficiency of a transmission line powers at both the ends
can be measured using multifunction meters at both ends and efficiency can be found out using equation
To find the regulation of transmission line voltages at both the ends can be measured using multifunction
meters at both ends and regulation can be found out using equation
PROCEDURE:
OBSERVATIONS:
6
CALCULATION:
CONCLUSION: