VEP A00 Manual
VEP A00 Manual
VEP-A00-P (4 Pipes)
VEP-A00-1P (1 Pipe)
September 2020
Doc. No. 22060_15
Part No. AD30274-000
VESDA-E VEP-A00-P Product Guide
Disclaimer
The contents of this document is provided on an “as is” basis. No representation or warranty (either express or
implied) is made as to the completeness, accuracy or reliability of the contents of this document. The manufacturer
reserves the right to change designs or specifications without obligation and without further notice. Except as
otherwise provided, all warranties, express or implied, including without limitation any implied warranties of
merchantability and fitness for a particular purpose are expressly excluded.
General Warning
This product must only be installed, configured and used strictly in accordance with the General Terms and
Conditions, User Manual and product documents available from Xtralis. All proper health and safety precautions
must be taken during the installation, commissioning and maintenance of the product. The system should not be
connected to a power source until all the components have been installed. Proper safety precautions must be taken
during tests and maintenance of the products when these are still connected to the power source. Failure to do so
or tampering with the electronics inside the products can result in an electric shock causing injury or death and may
cause equipment damage. Xtralis is not responsible and cannot be held accountable for any liability that may arise
due to improper use of the equipment and/or failure to take proper precautions. Only persons trained through an
Xtralis accredited training course can install, test and maintain the system.
Liability
You agree to install, configure and use the products strictly in accordance with the User Manual and product
documents available from Xtralis.
Xtralis is not liable to you or any other person for incidental, indirect, or consequential loss, expense or damages of
any kind including without limitation, loss of business, loss of profits or loss of data arising out of your use of the
products. Without limiting this general disclaimer the following specific warnings and disclaimers also apply:
Fitness for Purpose
You agree that you have been provided with a reasonable opportunity to appraise the products and have made
your own independent assessment of the fitness or suitability of the products for your purpose. You acknowledge
that you have not relied on any oral or written information, representation or advice given by or on behalf of Xtralis
or its representatives.
Total Liability
To the fullest extent permitted by law that any limitation or exclusion cannot apply, the total liability of Xtralis in
relation to the products is limited to:
i. in the case of services, the cost of having the services supplied again; or
ii. in the case of goods, the lowest cost of replacing the goods, acquiring equivalent goods or having the goods
repaired.
Indemnification
You agree to fully indemnify and hold Xtralis harmless for any claim, cost, demand or damage (including legal costs
on a full indemnity basis) incurred or which may be incurred arising from your use of the products.
Miscellaneous
If any provision outlined above is found to be invalid or unenforceable by a court of law, such invalidity or
unenforceability will not affect the remainder which will continue in full force and effect. All rights not expressly
granted are reserved.
www.xtralis.com i
VESDA-E VEP-A00-P Product Guide
Scope
The VESDA-E VEP-A00 Product Guide provides a comprehensive description of the VESDA-E VEP-A00
detector and its accessories.
This guide introduces the VEP-A00 features, technical specifications and gives an understanding of its
components and their function. You will also find instructions on installing, cabling and powering up the
detector.
This guide is for anyone involved with the design, maintenance and purchasing of a VESDA-E system. It is
assumed that anyone using this product has the knowledge and appropriate certification from local fire and
electrical authorities.
Document Conventions
The following typographic conventions are used in this document:
Convention Description
Bold Used to denote: emphasis.
Used for names of menus, menu options, toolbar buttons
Italics Used to denote: references to other parts of this document or other
documents. Used for the result of an action.
Convention Description
Caution: This icon is used to indicate that there is a danger to
equipment. The danger could be loss of data, physical damage, or
permanent corruption of configuration details.
Contact Us
UK and Europe +44 1442 242 330
The Americas +1 800 229 4434
Middle East +962 6 588 5622
Asia +86 10 56697101
Australia and New Zealand +61 3 9936 7000
www.xtralis.com
ii www.xtralis.com
VESDA-E VEP-A00-P Product Guide
DO NOT OPEN
NO SERVICEABLE
PARTS
NE PAS OUVRIR CLASS 1
DISPOSITIFS/PIECES LASER PRODUCT
DANGER NON ECHANGEABLES
PRODUIT LASER
Laser Radiation when Open DE CLASSE 1
AVOID DIRECT EXPOSURE TO BEAM
Rayonnement Laser en cas d’ouverture
EVITEZ TOUTE EXPOSITION DIRECTE AU FAISCEAU
AS1603.8
The performance of this product is dependent upon the configuration of the pipe network. Any extensions or
modifications to the pipe network may cause the product to stop working correctly. All pipe network designs must be
validated using ASPIRE. ASPIRE is available from your authorized representative.
The product is not intended to be mounted in hostile environments but is able to sample from hostile environments.
AS1851.1 2005
Maintenance Standards. Wherever this document and the AS1851.1 differ, AS1851.1 should be followed in
preference to this document.
www.xtralis.com iii
VESDA-E VEP-A00-P Product Guide
These limits should be verified using ASPIRE during the design of the sampling pipe network.
The product is compliant with EN 54-20 flow monitoring requirements provided the following conditions are
met:
l The minor low and minor high flow thresholds should be set at 85% and 115% respectively
l The flow through the detector predicted by ASPIRE must be greater than 20 L/m.
Additional information:
The VESDA-E VEP-A00 passed the EN 54-20 fire tests with the following configurations:
l Class A with 40 holes and a Fire-1 setting of 0.028% obs/m
l Class B with 80 holes and a Fire-1 setting of 0.027% obs/m
l Class C with 100 holes and a Fire-1 setting of 0.072% obs/m
Product Listings
l UL
l ULC
l FM
l ActivFire
l CE
l VdS
l EN 54-20
l ISO 7240-20
l NF
Regional approvals listings and regulatory compliance vary between product models. Refer to www.xtralis.com for
the latest product approvals matrix.
Document: 22060_15
Part Number: AD30274-000
iv www.xtralis.com
VESDA-E VEP-A00-P Product Guide
Scan the QR code to access the latest security advice available from: https://xtralis.com/33252
Commissioning Requirements
l All VESDAnet wiring and connection ports must be secured against unauthorized access.
l Ethernet and Wi-Fi ports must ONLY be connected to networks which are secure and physically or
logically separate from business IT infrastructure.
l VESDA devices including HLIs must not be accessible from the Internet. Any provision of remote
access to VESDA devices must be subjected to a full cyber security risk assessment and regular
review.
l WPA-2 encryption must be used whenever Wi-Fi is enabled.
l Restrict access to HLI devices to authorized personnel only.
l Passwords must be chosen in line with the guidelines in the detector user guide and provided to trusted
users only.
l Default PIN codes must be changed as part of the initial configuration.
www.xtralis.com v
VESDA-E VEP-A00-P Product Guide
vi www.xtralis.com
VESDA-E VEP-A00-P Product Guide
Table of Contents
1 Introduction 3
1.1 Features 3
2 Product Information 5
2.1 Detector Components 5
2.2 How the VEP-A00 works 5
2.3 Front Panel 6
2.4 Internal Buttons 7
2.5 Communication Ports 7
2.6 VESDAnet 8
2.7 Specifications 9
2.8 Dimensions 11
3 Pipe Network Design and Installation 15
3.1 Design Considerations 15
3.2 Installation Considerations 15
3.3 Pipe Inlets 15
3.4 Managing the Exhaust Air 16
4 Installation 17
4.1 Prepare the Detector 17
4.2 Mounting 18
4.3 Wiring 32
4.4 Powering Up 42
4.5 Installation Checklist 43
4.6 Preliminary System Check 44
5 Configuration 45
5.1 Communication between Xtralis VSC and the detector 45
5.2 Connecting to the Detector 49
5.3 Security 51
5.4 Commands 52
5.5 Configuration Options 55
5.6 Factory Default Settings 66
6 Commissioning 69
6.1 AutoLearn Smoke 69
6.2 AutoLearn Flow 70
6.3 Commissioning Smoke Test 70
7 Maintenance 71
7.1 Standby 71
7.2 Open the Door 72
7.3 Replacing the Filter 73
7.4 Remove the Fascia 76
7.5 Replacing the Aspirator 78
7.6 Replacing the Smoke Detection Chamber 80
7.7 Replacing the Sampling Module 84
7.8 Spare Parts 88
8 Troubleshooting 89
8.1 Fault Reporting through Relays 89
8.2 Troubleshooting with Xtralis VSC 90
A Commissioning Forms 91
A.1 VEP-A00 Detector Commissioning Configuration 93
A.2 ASPIRE Data 93
A.3 Smoke Test 93
www.xtralis.com 1
VESDA-E VEP-A00-P Product Guide
2 www.xtralis.com
VESDA-E VEP-A00-P Product Guide
1 Introduction
The VESDA-E VEP-A00 is an aspirating smoke detector (ASD) that provides very early warning of fire
conditions by drawing air samples through an air sampling pipe network.
1.1 Features
The VEP-A00 detector contains the following features:
l Short wavelength laser-based detection
l Inherent absolute calibration
l Clean air barrier for optics protection
l More robust contamination resistance
l Wide sensitivity range
l Flow fault thresholds configurable per port
l Long-life, easy-to-replace air sample filter
l Quiet operation
l Advanced remote diagnostics
l Area coverage:
l up to 2,000 m² (21,520 ft²) (VEP-A00-P)
l up to 1,000 m² (10,760 ft²) (VEP-A00-1P)
l Up to four inlet pipes
l Total maximum pipe length:
l Four pipe VEP-A00-P: 560 m (1,837 ft)
l One pipe VEP-A00-1P: 130 m (427 ft)
l Referencing
l AutoLearn™ Smoke and Flow
l Seven programmable relays
l Two General Purpose Inputs (GPIs), one monitored and one unmonitored
l Ultrasonic flow sensing
l Xtralis VSC, Xtralis VSM4 and ASPIRE PC software support
l IP 40 enclosure (not UL tested)
l Easy mounting with steel support bracket
l Field replaceable aspirator, sampling module, filter and detection chamber
l VESDAnet networking
l Ethernet 100 base T
l Local host mode USB port
l Easy cable termination access
l Event Log (20,000 events)
www.xtralis.com 3
VESDA-E VEP-A00-P Product Guide
4 www.xtralis.com
VESDA-E VEP-A00-P Product Guide
2 Product Information
2.1 Detector Components
The VEP-A00 detector contains field-replaceable Filter, Aspirator and Chamber Assembly components.
These are shown below in Figure 2-1.
Legend
A Fascia
B Filter
C Chamber Assembly
C
D D Aspirator
E Sampling Module
F Base
B E
www.xtralis.com 5
VESDA-E VEP-A00-P Product Guide
Notes:
l The LEDs are tested during the power up cycle. To manually test the LEDs, run the Lamp Test using
Xtralis VSC.
Disabling the detector disables signaling of alarms and faults via the relays. The aspirator remains active.
6 www.xtralis.com
VESDA-E VEP-A00-P Product Guide
Disabled mode is signaled on relay #1 and on the Fault Relay (Relay #3) by default. Refer to sections 4.3.6
and 5.5.9 for further information. The buzzer will beep once every 60 seconds if the beep checkbox for the
Disable condition on the Relay configuration screen (section 5.5.9) is ticked.
l To disable the detector, once all alarms and faults have been acknowledged, press and hold the button
for approximately 4 seconds, until the DISABLED LED illuminates continuously.
l To re-enable the unit, once all alarms and faults have been acknowledged, press and hold the button for
approximately 4 seconds, until the DISABLED LED deactivates continuously.
l While the detector is disabled, any faults or alarms may be acknowledged by pressing this button once.
Connection
Usage?
Use
Use USB Ethernet
www.xtralis.com 7
VESDA-E VEP-A00-P Product Guide
Refer to Section 4.3.4 for information on connecting the Ethernet lead, and Section 5.1.2 for information on
creating connection profiles in Xtralis VSC.
A password is required to access the detector via ethernet connection. It is initially set using Xtralis VSC
during configuration with the USB port, and the user is required to enter it when creating an Ethernet
connection profile in Xtralis VSC. It is also necessary to enter additional PIN codes to access administrative
and distributor functions. Refer to Section 5.3 on page 51 for further information.
2.6 VESDAnet
A VESDAnet network allows:
l the VEP-A00 detector to report alarms and faults to a Fire Panel using a remote display module, remote
relay module or HLI.
l configuration and monitoring of devices from a central computer.
l connection to a reference detector.
8 www.xtralis.com
VESDA-E VEP-A00-P Product Guide
2.7 Specifications
Table 2-2: VEP-A00 Detector Specifications
Specification Value
Supply Voltage 18 to 30 VDC (24 VDC Nominal)
Power Consumption @24 VDC Aspirator Setting 1 Setting 5 Fixed
VEP-P Power (Quiescent) 7.0 W 8.8 W -
Power (In Alarm) 7.8 W 9.6 W -
VEP-1P Power (Quiescent) - - 8.8 W
Power (In Alarm) - - 9.6 W
www.xtralis.com 9
VESDA-E VEP-A00-P Product Guide
Notes:
l UL and ULC: For open area, open area high velocity and
duct protection the fire alarm threshold (setting) that
initiates an evacuation signal must be set such that the
sensitivity of each sampling hole is more sensitive than
10%/m (3.2 %/ft) as determined by the ASPIRE software.
l Refer to Section 5.6 on page 66 for the default settings.
Referencing Reference smoke level source.
10 www.xtralis.com
VESDA-E VEP-A00-P Product Guide
2.8 Dimensions
B C D E F G H
mm inch
A 28.5 1.12
I
B 35.0 1.38
C 45.0 1.77
D 134.0 5.28
E 34.0 1.34
M
F 34.0 1.34
J N
G 34.0 1.34
H 34.0 1.34
I 26.5 1.04
J 350.0 13.78
K 224.0 8.82
L 230.2 9.06
L
M 135.5 5.3
N 132.3 5.21
O 28.5 1.12
P 35.0 1.38
Q 45.0 1.77
R 127.0 5.0
S 143.0 5.63
T 26.0 1.02
O
P Q R S
www.xtralis.com 11
VESDA-E VEP-A00-P Product Guide
A B C F mm inch
A 17.5 0.69
B 315.0 12.4
C 17.5 0.69
D 144.99 5.71
E 77.2 3.04
D F 3.5 0.1
12 www.xtralis.com
VESDA-E VEP-A00-P Product Guide
mm inch
C D E
A 224.0 8.82
B 112.0 4.41
C 40.9 1.61
F
D 268.39 10.57
E 40.71 1.6
F 20.25 0.8
G 183.5 7.22
H 20.25 0.8
A
G
B
H
Figure 2-6: Rear Dimensions with hole locations for direct mounting
www.xtralis.com 13
VESDA-E VEP-A00-P Product Guide
14 www.xtralis.com
VESDA-E VEP-A00-P Product Guide
Refer to the VESDA Pipe Network Design Guide for best design practices.
Notes:
l Sampling holes should be angled between 30° and 45° into the direction of airflow, or point downwards in
static airflow situations.
l Keep the sampling holes evenly spaced.
l For code-specific information, see Codes and Standards Information for Air Sampling Smoke Detection
on page iii.
Refer to the VESDA Pipe Network Installation Guide for best installation practices.
www.xtralis.com 15
VESDA-E VEP-A00-P Product Guide
Note: DO NOT glue the inlet pipes to the pipe inlet manifold.
When configuring the detector ensure that the correct pipes in use are selected as indicated in Table 3-1.
Table 3-1: Preferred use of pipe inlet ports
No. of Pipes Preferred Pipe Inlet Port to use
Pipe 1 Pipe 2 Pipe 3 Pipe 4
VEP-A00-P 1 Inlet 2 or 3 Inlet 2 or 3
2
3 Inlet 1 or 4 Inlet 1 or 4
4
VEP-A00-1P 1
1 2 3 4
16 www.xtralis.com
VESDA-E VEP-A00-P Product Guide
4 Installation
The VEP-A00 detector is shipped with the following components:
l 1 VESDA-E VEP-A00 detector
l Installation Sheet
l Mounting bracket
l Mounting template for directly mounting the detector to the mounting surface
l Exhaust Adaptor (US only)
l 1 End of Line resistor for the monitored GPI
Check all components for damage and refer any concerns to your authorized representative.
Depending on the nature of the installation, it may be necessary to procure the following items:
l The latest revision of this full product guide can be downloaded from the partner extranet at
www.xtralis.com.
l A 24 VDC Power Supply and backup battery, compliant with local fire protection codes and standards.
l Screws and inserts for the mounting bracket that are appropriate for the installation location.
l Type A to Type B USB Interface Lead, required for initial configuration of the detector (Figure 4-1).
l Wrist strap for ESD prevention.
B
A
www.xtralis.com 17
VESDA-E VEP-A00-P Product Guide
4.2 Mounting
The VEP-A00 detector can be mounted in an upright or inverted position. Do not mount the detector with a
sideways orientation as shown in Figure 4-3 below.
Legend
A Min. 50 mm (2 in.) below ceiling
level
A
B Mounting Bracket:
The detector can be mounted
directly against a wall or
B obstruction.
Refer to Section 4.2.2 for
further information.
Direct mounting:
A minimum clearance of 20 mm
(0.8 in.) is required between the
detector and a wall or
obstruction, on both sides of the
detector.
Refer to Section 4.2.3 for
further information.
18 www.xtralis.com
VESDA-E VEP-A00-P Product Guide
www.xtralis.com 19
VESDA-E VEP-A00-P Product Guide
A Legend
A Top cover retaining tabs
B Bottom cover retaining
tabs
20 www.xtralis.com
VESDA-E VEP-A00-P Product Guide
www.xtralis.com 21
VESDA-E VEP-A00-P Product Guide
AB
22 www.xtralis.com
VESDA-E VEP-A00-P Product Guide
o
180
A B
Figure 4-11: Rotate detector and door and move door to right side of fascia
www.xtralis.com 23
VESDA-E VEP-A00-P Product Guide
Figure 4-12: Replacing the door hinge pin - showing correct positioning of door and pin
24 www.xtralis.com
VESDA-E VEP-A00-P Product Guide
Figure 4-14: Correct positioning of door hinge pin when fully in place
8. Re-attach the tethers. Attach at the slots circled in Figure 4-15. Position the tethers in the slots and pull
up as shown in Figure 4-16.
www.xtralis.com 25
VESDA-E VEP-A00-P Product Guide
1 2
3 4
26 www.xtralis.com
VESDA-E VEP-A00-P Product Guide
Legend
A Mounting bracket
B B Sampling Pipes
C Electrical Conduit
C E
D Pipe alignment marks
A F
E 3/4 inch IPS pipe (1.05 inch
OD) depth
F 25 mm pipe depth
D
D
Legend
A Mounting bracket
B Keyholes
B
A
A Legend
A Mounting bracket
B Screwdriver
www.xtralis.com 27
VESDA-E VEP-A00-P Product Guide
5. Insert the remaining three mounting screws (B) and tighten them (Figure 4-20).
Legend
A
A Mounting bracket
B B Mounting screws
A
A
A
Legend
A Mounting buttons
Legend
A Locking screw
28 www.xtralis.com
VESDA-E VEP-A00-P Product Guide
A
Inverted
Detector
C
D
3/4” IPS
25mm
3/4” IPS
25mm
Edge
of Dete
ctor
ctor
of Dete
Edge
25mm
3/4” IPS
25mm
3/4” IPS
D
C
Upright
Detector
3/4” IPS
B
25mm
3/4” IPS
25mm
Edge
of Dete
ctor
B
A
A C
ctor
of Dete
Edge
C
25mm
3/4” IPS
25mm
3/4” IPS
Upright Inverted
Detector Detector 7mm
www.xtralis.com 29
VESDA-E VEP-A00-P Product Guide
A B
Inverted
Detector
C
D 3/4” IPS
25mm
3/4” IPS
25mm
Edge
of Det
ector
ector
of Det
Edge
25mm
3/4” IPS
25mm
3/4” IPS
C D
Upright
Detector B
A
Inverted
Detector
Upright
Detector
Upright Inverted
Detector Detector
30 www.xtralis.com
VESDA-E VEP-A00-P Product Guide
Upright Inverted
Detector Detector
Upright Inverted
Detector Detector
Upright Inverted
Detector Detector
www.xtralis.com 31
VESDA-E VEP-A00-P Product Guide
4.3 Wiring
The screw type terminals located on electrical terminals within the VEP-A00 detector will accept wire sizes
from 0.2 mm² to 2.5 mm² (24 – 14 AWG).
Refer to Codes and Standards Information for Air Sampling Smoke Detection on page iii for code specific
requirements.
Refer to the VESDA System Design Manual for cabling details.
Note: The VEP-A00 detector is IP 40 rated, therefore a suitable cable gland or conduit must be used to
maintain the IP rating. (The IP rating is not UL tested.)
Caution: Electrostatic discharge (ESD) precautions need to be taken prior to removing the fascia from
the detector in order to prevent damage to sensitive electronic components within the VEP-A00.
Attention : Les precausions contre le decharge electrostatique dois etre respecter avant d’ouvrir le panneau
du detecteur afin de prevenir au dommage des composants electroniques a l’interieur du VEP-
A00.
32 www.xtralis.com
VESDA-E VEP-A00-P Product Guide
NO C NC NO C NC NO C NC
NC C NO NC C NO NC C NO NC C NO
F J A Power Out
B Power In
G I
VESDAnet
D
H M C VESDAnet B
SH
L D VESDAnet A
C
SH
Relays
E 1 - Disable (Isolate)
N O F 2 - Minor Fault
G 3 - Urgent Fault
H 4 - Alert
I 5 - Action
J 6 - Fire 1
B
K 7 - Fire 2
Comms
A
L USB
M Ethernet
GPI
P N Monitored GPI
O Unmonitored GPI
Ground
P Ground Reference
Terminal
Caution: Operating the detector when DC supply voltage is outside the specified voltage range may
cause damage to internal components. For further information refer to the Product
Specifications on page 9.
www.xtralis.com 33
VESDA-E VEP-A00-P Product Guide
PSU
PWR IN
+ PWR OUT PWR IN PWR OUT PWR IN PWR OUT
+
+
+
_
_
_
_
Detector 1 Detector 2 Detector 3
Ethernet
The Ethernet port is used for permanent network connection to the VEP-A00. An Ethernet lead can be routed
through the cable entry ports and plugged into the Ethernet port.
Use a standard Ethernet lead when connecting the VEP-A00 to a network switch, router or directly to a PC or
laptop.
4.3.5 VESDAnet
VESDAnet is a bidirectional data communication network between connected VESDA-E devices. VESDAnet
connectivity is available on the VEP-A00 detector. Refer to Section 2.6 for further information.
It is recommended that RS 485 (Belden 9841 - 120 Ohm) twisted pair cables be used for including the devices
in the network.
The network cables are terminated at the VESDAnet A and B Terminals. Cabling from one VESDA-E device
is brought into the detector at one terminal and looped out to another device on VESDAnet from the other
terminal.
Notes:
l The polarity of the data wires must be maintained throughout the network.
l In order for the detector to be able to detect ground faults on the VESDAnet wiring, the Ground Reference
Terminal (Figure 1-1) must be connected to the local ground.
34 www.xtralis.com
VESDA-E VEP-A00-P Product Guide
Shield Shield
A- A-
A+ A+
Shield Shield
B- B-
B+ B+
Module 5 Module 4
Figure 4-36: Closed loop for standalone detectors with VESDAnet capability
Note: Refer to the VESDA-E Communications Guide for further information.
www.xtralis.com 35
VESDA-E VEP-A00-P Product Guide
4.3.6 Relays
The relays, located on the main processor card, interface to the Fire Alarm Control Panel (FACP) to
communicate faults, alarms and disabled states. The relays can be programmed using Xtralis VSC. Relays 3
and 6 are permanently set for Urgent Fault and Fire 1 respectively. Table 4-22 below illustrates the default
assignments of functions (conditions) to relays and summarizes the default behavior of each relay. Section
5.5.9 describes how to configure the relay behavior using Xtralis VSC. It is possible to assign more than one
condition to a relay.
Fire 1 Relay
If a detector relay is to be used to signal fire alarm to the Fire Alarm Control Panel (FACP) then the Fire 1 relay
must be used.
Fault and Fire 1 Relay Terminals
The Urgent and Minor Fault relays are energized during normal operation while the Fire 1 relay is only
energized when a Fire 1 is detected. The operation of the relays are summarized in the following table.
Table 4-1: Typical Relay Operation
36 www.xtralis.com
VESDA-E VEP-A00-P Product Guide
www.xtralis.com 37
VESDA-E VEP-A00-P Product Guide
38 www.xtralis.com
VESDA-E VEP-A00-P Product Guide
www.xtralis.com 39
VESDA-E VEP-A00-P Product Guide
Legend
A External device (1 to N)
B End of Line Resistor at device end of
wiring
C GPI Pin 1
D GPI Pin 2
40 www.xtralis.com
VESDA-E VEP-A00-P Product Guide
Note: It is recommended that batteries be inspected and changed as per manufacturer’s specifications or
as per local codes and standards.
To facilitate the calculation of the backup battery size, a Battery Calculation Sheet is included below.
Table 4-3: Calculating the size of backup battery
Equipment Normal loads @ 24 V DC Full alarm load @ 24 V DC
Load (A) Qty Total Load (A) Qty Total
Detector set to Fan Speed 1 0.29 0.33
Detector set to Fan Speed 5 0.37 0.40
Other 24V Loads Total Total
(A) (A)
X X
Normal Hours Alarm Hours
=
Normal Capacity Alarm Capacity
Total Capacity =
Normal + Alarm
Multiply by battery
factor X1.25
www.xtralis.com 41
VESDA-E VEP-A00-P Product Guide
4.4 Powering Up
After installing the detector it is necessary to power up the system. The power up sequence lasts
approximately 15 seconds.
The VEP-A00 detector does not have a power switch i.e it is an "always on" device which is activated by
applying powered cabling to the power input terminal on the main board (Figure 4-33). This process must only
be performed by Xtralis accredited personnel.
If the system fails to power up, check all power wires are secured to their terminals and that the polarity is
correct.
On power up:
l The Power LED illuminates and the detector runs a series of self-diagnostic tests.
l If there is a fault, the Fault LED illuminates. To identify the fault, check the Active Event List for the
detector using Xtralis VSC.
l The aspirator starts up and air may be felt flowing out of the exhaust port.
It is normal for the detector to display airflow faults immediately after the first power up and until the air flow
normalization step is done. Reset the detector by pressing the reset button on the front of the unit. This will
unlatch the relays and turn off the Fault LED. Any remaining faults will cause the Fault LED to illuminate
again. Proceed with the preliminary system check.
42 www.xtralis.com
VESDA-E VEP-A00-P Product Guide
Address
Name of Installer
Signature
Date
Perform the following checks listed below to ensure that all the necessary items are completed before handing
over to a commissioning engineer.
www.xtralis.com 43
VESDA-E VEP-A00-P Product Guide
44 www.xtralis.com
VESDA-E VEP-A00-P Product Guide
5 Configuration
This chapter describes a number of configuration options, user functions and security features of the VEP-
A00 detector that the installer and users must to be familiar with. These include:
l defining connections and connecting to the detector
l security
l detector commands
l configuration options
l relay options
l GPI functions
l default settings
The VEP-A00 detector is initially configured using Xtralis VSC software installed on a PC directly connected
to the USB port. It is necessary to connect to the detector in order to configure it. The procedure for
connecting to the detector is described in Section 5.1.1 below.
USB is used for initial configuration, however it must not be used for permanent connection. Permanent
connection for secondary monitoring must only be done with Ethernet.
For example, the installer would connect directly to a VEP-A00 using the USB port with a laptop running
Xtralis VSC in order to configure the detector to enable Ethernet, the parameters of which could be unique for
each installation. A connection profile would need to be defined for the temporary USB connection, and then
for the permanent connection using VESDAnet, Ethernet.
Note: Refer to the VESDA Communications Guide for further information.
www.xtralis.com 45
VESDA-E VEP-A00-P Product Guide
46 www.xtralis.com
VESDA-E VEP-A00-P Product Guide
2. Enter a unique name for the Connection or accept the pre-generated name, then select Finish
(Figure 5-4).
www.xtralis.com 47
VESDA-E VEP-A00-P Product Guide
3. Enter a unique name for the Connection or accept the pre-generated name, then select Finish
(Figure 5-7).
48 www.xtralis.com
VESDA-E VEP-A00-P Product Guide
l Connect to the detector using USB following the procedure described in Section 5.2.1.
l In the Ethernet tab for the detector:
l For dynamic IP addresses, set Automatically obtain IP Address to on. Once it has been
successfully allocated, record the IP Address for use in connection profiles. It can be found on the
www.xtralis.com 49
VESDA-E VEP-A00-P Product Guide
D Legend
A PC or Laptop
installed with
Xtralis VSC
B Router or access
point
A C D C VEP-A00 used as a
gateway to the
D VESDAnet
D Other VESDA-E
detectors on the
VESDAnet
Define a new Connection Profile (USB or Ethernet connection between the PC and the detector
which is acting as a gateway)
1. For VESDA-E detectors, follow the steps in Section 5.1.2 and add a USB or Ethernet connection.
50 www.xtralis.com
VESDA-E VEP-A00-P Product Guide
5.3 Security
The VEP-A00 has two levels of protection against unauthorized access. For connection via Ethernet, a
password of at least 8 characters must be used. After connection, a four digit PIN is used to control the
access level.
www.xtralis.com 51
VESDA-E VEP-A00-P Product Guide
5.4 Commands
The following commands are able to be issued to the detector. As indicated below in Table 5-2, a small
number of basic commands can be executed from the detector via buttons, while the full range of commands
can be executed using the Xtralis VSC software.
Table 5-2: Detector Commands
52 www.xtralis.com
VESDA-E VEP-A00-P Product Guide
www.xtralis.com 53
VESDA-E VEP-A00-P Product Guide
54 www.xtralis.com
VESDA-E VEP-A00-P Product Guide
Authentication
l Change Password: The password used to authenticate Ethernet access. Refer to Section 5.3.1 on
page 51 for further information.
www.xtralis.com 55
VESDA-E VEP-A00-P Product Guide
56 www.xtralis.com
VESDA-E VEP-A00-P Product Guide
www.xtralis.com 57
VESDA-E VEP-A00-P Product Guide
58 www.xtralis.com
VESDA-E VEP-A00-P Product Guide
These settings should be confirmed in the ASPIRE design of the sampling pipe network.
Note: Refer to Section 5.6 for the default settings.
Note: The number of pipes able to be configured matches the number of pipes supported by the
detector.
l Significant Flow Change: The amount of airflow change at which an event is recorded in the event log.
l Delay: The length of time between the air flow fault threshold being reached and the fault relay operation.
l Pipes in Use: The pipes that are actually being used. Refer to Section 3.3 on page 15 for further
information. This setting is not available for the VEP-A00-1P.
l Aspirator: Select the required Aspirator Speed setting 1 through 5, as determined using ASPIRE. This
setting is not available for the VEP-A00-1P.
www.xtralis.com 59
VESDA-E VEP-A00-P Product Guide
60 www.xtralis.com
VESDA-E VEP-A00-P Product Guide
www.xtralis.com 61
VESDA-E VEP-A00-P Product Guide
62 www.xtralis.com
VESDA-E VEP-A00-P Product Guide
Monitored GPI
l The detector is held Standby mode
Closed
(see Section 7.1) while contact is
Standby
closed. Open
l The detector exits Standby mode Reset Enabled
when the contact opens.
5 VDC. Enabled
l The detector is enabled on a 5 VDC
to 0 VDC falling edge.
www.xtralis.com 63
VESDA-E VEP-A00-P Product Guide
Monitored GPI
Closed
l The detector uses night-time
thresholds while the contact is Open
closed. Day or Night Night Day or Night
Notes:
l When using the standby or disable options it is recommended that all remote displays on VESDAnet are
configured to have the Isolate button locked out.
l When the detector is disabled or set to standby via the GPI, the status cannot be changed through the
normal enable / disable function on the front panel or via Xtralis VSC or a remote display. Refer to
Section 2.3.2 on page 6 for further information.
l When the night-time thresholds are invoked via the GPI, the clock settings for day-start and night-start
are overridden.
64 www.xtralis.com
VESDA-E VEP-A00-P Product Guide
In the Normally De-energized mode no drive is applied to the relay coil until the assigned condition such as
Alert or Fire 1 occurs. The Normally Energized mode is the opposite. Drive is removed from the relay coil
when the condition occurs.
The default mode of the relays is listed in Table 4-2.
Latching: If the cause of a condition is removed (for example, smoke decreases below the threshold) and
latching is enabled, the detector “remembers” the condition and holds the corresponding relays and displays in
the active state as though the cause of the condition were still active.
Latching can be enabled for any alarm condition or for urgent or minor fault by checking the corresponding
latching checkbox to the right of the condition.
Beep: The detector's buzzer can be configured using the checkboxes under heading "Beep". If checked the
buzzer will beep when the condition occurs.
www.xtralis.com 65
VESDA-E VEP-A00-P Product Guide
66 www.xtralis.com
VESDA-E VEP-A00-P Product Guide
1 The Xtralis VSC software forces the user to move the detector to a valid zone number.
2 The user must set the password the first time. There is no default password.
3 Default value set in factory. Not modified by return to factory defaults command.
www.xtralis.com 67
VESDA-E VEP-A00-P Product Guide
68 www.xtralis.com
VESDA-E VEP-A00-P Product Guide
6 Commissioning
The VEP-A00 has been designed to simplify commissioning processes. The AutoLearn function allows the
unit to assess its environment and setup appropriate alarm and flow thresholds.
The detector is programmed using the Xtralis VSC software.
Once the VEP-A00 detector has been commissioned, it will report alarms and faults according to the
parameters defined during installation.
Note: Detectors should be commissioned with a smoke test.
Prior to commissioning the detector:
1. Check that the pipe network is clean and correctly fitted with all joints correctly seated and sealed
(except the endcaps and the pipe which enters the detector which must not be glued). Ensure that the
relevant pipes are selected as in use in Xtralis VSC.
2. Check that the power is connected and on. Ensure that the pipe flow rates comply with the minimum
requirements listed in Section 3.1. Ignore any faults during this time.
3. Set the Pipes in Use value in the Airflow configuration options.
4. Set the aspirator setting to the value used when designing the system in ASPIRE to achieve the required
transport time.
5. Normalize the airflow. This takes approximately 3 minutes, after which the pipe flow rates (%) should be
close to 100%.
6. Reset the detector after normalization. It should now be running without faults, providing the flow rates
are maintained as indicated in Section 3.1.
It is important that the protected environment is working under normal operating conditions when operating the
AutoLearn processes.
Xtralis recommends that a 14 day period is used.
After AutoLearn is complete, review to confirm that the thresholds are within the range allowed by local codes
and standards.
For code-specific information, see Codes and Standards Information for Air Sampling Smoke Detection on
page iii.
www.xtralis.com 69
VESDA-E VEP-A00-P Product Guide
70 www.xtralis.com
VESDA-E VEP-A00-P Product Guide
7 Maintenance
To maintain the VEP-A00 detector at its peak performance level, the recommended maintenance schedule
shown in Table 7-1 below should be followed.
Table 7-1: Recommended maintenance schedule for the VEP-A00 detector
Notes:
l The above maintenance steps are preventative maintenance.
l Maintenance can be conducted by the original installer or an authorized distributor or service contractor.
l The required frequency of maintenance checks may vary depending upon local codes and standards and
the environment of the installation.
l When smoke testing is done, follow the site procedures for preventing false alarms to monitoring
services.
Caution: While the detector is disabled or put into Standby mode, no fire warnings will be annunciated by
the detector. Prior to any maintenance or testing:
Attention : Pendant que le detecteur ou la zone est desactivee, aucun feu d’indication va etre emis par le
detecteur. Avant tout entretien ou tester:
7.1 Standby
When maintenance is performed on the pipe network or sample points it is recommended that you temporarily
set the detector to Standby in order to turn off the aspirator. Setting the VEP-A00 to Standby mode
deactivates the aspirator and stops all detection of alarms (but not detection and signaling of faults). Standby
mode is signaled on relay #1 by default. Other relays may also be configured to signal standby mode. Refer to
sections 4.3.6 and 1.0.1 for further information. For example, standby mode may be also signaled as an
additional condition on the Fault Relay (Relay #3).
To set the detector to Standby mode using Xtralis VSC, select Go to Standby from the Device menu. The
Disabled LED will blink and the aspirator will turn off. If configured the buzzer will beep once per minute if the
Standby beep checkbox on the Relay configuration screen (section 1.0.1) is ticked.
To re-activate the unit, select End Standby from the Device menu.
www.xtralis.com 71
VESDA-E VEP-A00-P Product Guide
72 www.xtralis.com
VESDA-E VEP-A00-P Product Guide
www.xtralis.com 73
VESDA-E VEP-A00-P Product Guide
3. Tilt the filter towards the left-hand side of the detector (Figure 7-3). The filter has hinge pins at its base
which allow it to be tilted on the chamber manifold.
Figure 7-3: Tilt Filter towards the left-hand side of the detector
4. Lift the filter out of the detector case (Figure 7-4).
74 www.xtralis.com
VESDA-E VEP-A00-P Product Guide
www.xtralis.com 75
VESDA-E VEP-A00-P Product Guide
Caution: Electrostatic discharge (ESD) precautions need to be taken prior to removing the fascia from
the detector. A wrist strap must be connected to the case of the detector (Figure 7-7).
Attention : Les precausions contre le decharge electrostatique dois etre respecter avant d’ouvrir le panneau
du detecteur. Un bracelet doit être raccordé au panneau du détecteur (Figure 7-7).
76 www.xtralis.com
VESDA-E VEP-A00-P Product Guide
www.xtralis.com 77
VESDA-E VEP-A00-P Product Guide
Attention : Les precausions contre le decharge electrostatique dois etre respecter avant d’ouvrir le panneau
du detecteur. Un bracelet doit être raccordé au panneau du détecteur (Figure 7-7).
Ensure the area surrounding the aspirator is clear of dirt and debris prior to replacement.
Care must be taken during aspirator replacement. The aspirator must be correctly seated; it is essential to
ensure that the gaskets are not damaged or dislodged from the underside of the aspirator.
Remove the Aspirator
1. Turn off the 24V DC power to the detector.
2. Open the front door and remove the front fascia. Refer to Sections 7.2 and 1.1 for further information.
3. Disconnect the aspirator cable (A) (Figure 7-10).
78 www.xtralis.com
VESDA-E VEP-A00-P Product Guide
www.xtralis.com 79
VESDA-E VEP-A00-P Product Guide
3 4
2
1
80 www.xtralis.com
VESDA-E VEP-A00-P Product Guide
www.xtralis.com 81
VESDA-E VEP-A00-P Product Guide
Looms beside
module
82 www.xtralis.com
VESDA-E VEP-A00-P Product Guide
3. Re-install the chamber as shown in Figure 7-18. Be careful to hold looms (A) and (B) in the position
shown so that the looms are not caught between the chamber and other parts of the detector.
www.xtralis.com 83
VESDA-E VEP-A00-P Product Guide
Attention : Les precausions contre le decharge electrostatique dois etre respecter avant d’ouvrir le panneau
du detecteur. Un bracelet doit être raccordé au panneau du détecteur (Figure 7-7).
Ensure the area around the Sampling Module is clear of dirt and debris prior to replacement.
Care must be taken during Sampling Module replacement. The Sampling Module must be correctly seated in
order for a correct seal to be established between the Sampling Module and the rest of the detector. It is
essential to ensure that the rubber seal on the underside of the Sampling Module is correctly in place.
Removing the Sampling Module
1. Turn off the 24V DC power to the detector.
2. Open the front door and remove the front fascia. Refer to Sections 7.2 and 1.1 for further information.
3. Disconnect the Sampling Module cable (Figure 7-19).
84 www.xtralis.com
VESDA-E VEP-A00-P Product Guide
4. Press on the lever on the connector to release the catch (Figure 7-20).
www.xtralis.com 85
VESDA-E VEP-A00-P Product Guide
86 www.xtralis.com
VESDA-E VEP-A00-P Product Guide
6. Remove the Sampling Module. Be sure to include the rubber seal on the base of the Sampling Module
(Figure 7-22).
www.xtralis.com 87
VESDA-E VEP-A00-P Product Guide
88 www.xtralis.com
VESDA-E VEP-A00-P Product Guide
8 Troubleshooting
If the VEP-A00 detector identifies a fault condition, the Fault LED on the front of the detector illuminates and
an event containing details of the condition is written to the Xtralis VSC active event list and the detector's
event log. The buzzer will beep once every 30 seconds if the Urgent fault beep and Minor fault beep
checkboxes on the Relay configuration screen (section 5.5.9) are ticked.
The Xtralis VSC software can be used to obtain specific information on the event to enable further
investigation and correction of the fault. The Xtralis VSC Online Help contains descriptions of each fault and
recommended corrective actions.
www.xtralis.com 89
VESDA-E VEP-A00-P Product Guide
The fault is removed from the active event list once it is cleared.
90 www.xtralis.com
VESDA-E VEP-A00-P Product Guide
A Commissioning Forms
This is the main commissioning form for each customer site.
Table A-1: VESDA-E commissioning form
Customer Name
Site Address
www.xtralis.com 91
VESDA-E VEP-A00-P Product Guide
Customer's Signature
Date:
Commissioner's Signature
Date:
92 www.xtralis.com
VESDA-E VEP-A00-P Product Guide
Test Results
Test Method
Type of Smoke
Test Date
www.xtralis.com 93
VESDA-E VEP-A00-P Product Guide
94 www.xtralis.com
VESDA-E VEP-A00-P Product Guide
B Glossary
Table B-1: Glossary
Term Description
A Aspirator Impeller type fan used to draw sampled air into the detector.
AutoLearn Smoke A feature which allows the detector to learn its environment
(background pollution, differences between day and night
operations within the facility etc) in order to set appropriate
alarm thresholds for that environment.
AutoLearn Flow A feature which allows the detector to learn its airflow
behavior in the installed environment. This information is
used by the detector to set appropriate airflow trouble
thresholds.
C Capillary Tubes Flexible tubes attached to the sampling pipe network for
sampling specific areas away from the sampling pipe.
Commissioning The process of making a smoke detection system
operational.
Condition For example, Fire 1 condition, Urgent Fault condition. The
detector is said to be in the Fire 1 condition when it has
detected a Fire 1 alarm.
D Disable When the detector is disabled the detector will not signal
alarms and faults via its relays. The detector signals that it is
disabled using Relay 1. (Disable was previously referred to
as isolate.)
E Event Log A data log of events (for example, alarms, troubles, user
commands) which is stored in the detector.
www.xtralis.com 95
VESDA-E VEP-A00-P Product Guide
96 www.xtralis.com
VESDA-E VEP-A00-P Product Guide
Index
A reset 52
return to factory defaults 54
access level
set system date and time 54
ADM 51, 66
standby 52
DST 51, 66
start air flow fault test 54
USR 51
start alarm test 54
accessories
start AutoLearn flow 53
display module 8, 36, 38
start AutoLearn smoke 53
programmer 38, 89
start lamp test 54
action 5-6, 10, 33, 36, 39, 66
start major fault test 53
airflow 59
start minor fault test 54
alert 5-6, 10, 33, 36, 66
start relay test 54
area coverage 3
commissioning 69, 91, 95
aspirator 3, 5-6, 9, 15, 41-42, 44, 52, 54, 59,
63, 69, 71, 78, 88, 95 smoke test 70
autolearn 10 connection 7, 45
add 46
B
ethernet 47, 49
battery 17, 41, 71
USB 46
button
VESDAnet 50
disable 5-6, 38, 52, 62
D
lockout 62, 64
reset 6, 42, 52 detector
invert 19
C
open the door 72
cable entry point 3, 9, 17-18, 32, 34
remove fascia 76
capillary tubes 95
replace aspirator 78
chamber assembly 3, 5, 80, 88
replace chamber assembly 80
checklist
replace sample module 84
air sampling results 93
replacing the filter 73
commissioning 91
set to standby 71
installation 43
dimensions 9, 11
smoke test 93
disable 5-6, 36, 38, 52, 62-64, 71, 95
commands
display module 8, 36, 38
cancel AutoLearn flow 53
E
cancel AutoLearn smoke 53
disable 52 EOL resistor 17, 38-39
normalize air flow 52 ethernet 3, 5, 7-9, 17, 33-34, 47, 51, 56, 62, 66
www.xtralis.com 97
VESDA-E VEP-A00-P Product Guide
isolate 62 options 58
mains OK 62 airflow 59
reset + isolate 62 P
standby mode 62
PIN code 51
unmonitored 3, 33, 38-39, 62, 95
pipe
use night-time threshold 64
airflow 59
H diameter 15
98 www.xtralis.com
VESDA-E VEP-A00-P Product Guide
network 9, 15, 95 S
network design 15-16
sampling module 5, 84, 88
network testing 70
sensitivity 3, 9, 95
size 9
settings 66
pipe flow rate 15, 69
default 66
pipe length 3
significant smoke change 58
pipe network 3, 5, 15, 59
specifications 9
pipes in use 15, 59
alarm range 9
polarity 33-34, 42
dimensions 9
port
power 9
ethernet 33-34, 50
weight 9
Ethernet 7
standby 52, 63, 71, 73, 78, 80
USB 7, 33-34
supply voltage 9, 33
power 6
battery 41 T
cabling 32-33, 43 temperature 9, 41
consumption 9 thresholds 5, 9
GPI supply voltage 38 action 6, 9-10, 66, 69
socket 33 alert 6, 9-10, 66, 69
supply 33, 39 fire 1 6, 9-10, 36, 66, 69
voltage range 33 fire 2 6, 9-10, 66, 69
wiring 33 troubleshooting 89-90
power source 33
U
power supply 17, 33
USB 5, 7-9, 46
monitoring 38
interface lead 17
power up 42, 44
V
R
VESDAnet 5, 8, 34, 38, 43, 50, 55, 62, 64,
referencing 8, 10 66, 93, 95
relays 3, 5-6, 8-9, 33, 36, 39, 42, 52, 62, 65, polarity 34
89, 95
action 33 W
alert 33 weight 9
fault 33, 36 wiring 32, 38-39
fire 33, 36 address loop module 39
isolate 33 FACP 39
options 65 power 33
remote display 8, 55, 89 VESDAnet 34
reset 5-6, 38, 42, 52, 62, 64, 69
Z
zone 53, 55, 71, 95
www.xtralis.com 99
VESDA-E VEP-A00-P Product Guide
100 www.xtralis.com
www.xtralis.com All technical data is correct at the time of publication and is subject to changes without notice. All Intellectual
Property including but not limited to trademarks, copyrights, patent are hereby acknowledged. You agree not
Doc. No. 22060_15 to copy, communicate to the public, adapt, distribute, transfer, sell, modify or publish any contents of this
Part No. AD30274-000 document without the express prior written consent of Xtralis. Installation information: In order to ensure full
September 2020 functionality, refer to the installation instructions as supplied. © Xtralis