Simpson Strong-Tie® Anchoring, Fastening, Restoration and Strengthening Systems for Concrete and Masonry

SET-3G™ High-Strength Epoxy Adhesive

Adhesive Anchors
SET-3G Cure Schedule1, 2
Concrete Temperature Gel Time Cure Time
(°F) (°C) (minutes) (hr.)
40 4 120 192
50 10 75 72
60 16 50 48
70 21 35 24
90 32 25 24
100 38 15 24
For SI: 1°F = (°C x 9/5) + 32.
1. For water-saturated concrete, submerged concrete and water-filled holes, the cure times shall be doubled.
2. For installation of anchors in concrete where the temperature is below 70°F (21°C),
the adhesive must be conditioned to a minimum temperature of 70°F (21°C).

SET-3G Typical Properties


Class B Class C Test
Property
(40°– 60°F) (> 60°F) Method
Consistency Non-sag Non-sag ASTM C881
Hardened to Hardened Concrete, 2-Day Cure 1
3,700 psi 3,300 psi
Bond Strength, Slant Shear Hardened to Hardened Concrete, 14-Day Cure1 3,850 psi 3,350 psi ASTM C882
Fresh to Hardened Concrete, 14-Day Cure2 2,750 psi 2,750 psi
Compressive Yield Strength, 7-Day Cure2 13,000 psi 15,350 psi ASTM D695
Compressive Modulus, 7-Day Cure 2
650,000 psi 992,000 psi ASTM D695
Heat Deflection Temperature, 7-Day Cure2 147°F (64°C) ASTM D648
Glass Transition Temperature, 7-Day Cure2 149°F (65°C) ASTM E1356
Decomposition Temperature, 24-Hour Cure2 500°F (260°C) ASTM E2550
Water Absorption, 24-Hours, 7-Day Cure2 0.13% ASTM D570
Shore D Hardness, 24-Hour Cure2 84 ASTM D2240
Linear Coefficient of Shrinkage, 7-Day Cure2 0.002 in./in. ASTM D2566
Coefficient of Thermal Expansion2 2.3 x 10-5 in./in.°F ASTM C531
1. Material and curing conditions: Class B at 40° ± 2°F, Class C at 60° ± 2°F.
2. Material and curing conditions: 73° ± 2°F.
C-A-2023 © 2023 SIMPSON STRONG-TIE COMPANY INC.

IBC *
SET-3G Installation Information and Additional Data for Threaded Rod and Rebar1
Nominal Anchor Diameter da (in.) / Rebar Size
Characteristic Symbol Units
3/8 / #3 1/2 / #4 5/8 / #5 3/4 / #6 7/8 / #7 1 / #8 1 1/4 / #10
Installation Information
Drill Bit Diameter for Threaded Rod dhole in. 7/16 9/16 11/16 7/8 1 1 1/8 1 3/8

SD
Drill Bit Diameter for Rebar dhole in. 1/2 5/8 3/4 7/8 1 1 1/8 1 3/8
Maximum Tightening Torque Tinst ft.-lb. 15 30 60 100 125 150 200
Minimum Embedment Depth hef, min in. 2 3/8 2 3/4 3 1/8 3 1/2 3 3/4 4 5
Maximum Embedment Depth hef, max in. 7 1/2 10 12 1/2 15 17 1/2 20 25
Minimum Concrete Thickness hmin in. hef + 11/4 hef + 2dhole
Critical Edge Distance cac in. See footnote 2
Minimum Edge Distance cmin in. 1 3/4 2 3/4
Minimum Anchor Spacing smin in. 1 2 1/2 3 6
1. The information presented in this table is to be used in conjunction with the design criteria of ACI 318-19, ACI 318-14 and ACI 318-11.
2. cac = hef (τk,uncr /1,160)0.4 x [3.1 – 0.7(h/hef)], where:
[h/hef ] ≤ 2.4
τk,uncr = the characteristic bond strength in uncracked concrete, given in the tables that follow ≤ kuncr ((hef x f 'c )0.5/(π x da))
h = the member thickness (inches)
hef = the embedment depth (inches)

*See p. 14 for an explanation of the load table icons.


25
Simpson Strong-Tie® Anchoring, Fastening, Restoration and Strengthening Systems for Concrete and Masonry

SET-3G™ Design Information — Concrete


Adhesive Anchors

IBC *
SET-3G Tension Strength Design Data for Threaded Rod 1,7
Nominal Rod Diameter (in.)
Characteristic Symbol Units
3/8 1/2 5/8 3/4 7/8 1 1 1/4
Steel Strength in Tension
Minimum Tensile Stress Area Ase in.2 0.078 0.142 0.226 0.334 0.462 0.606 0.969
Tension Resistance of Steel — ASTM F1554, Grade 36 4,525 8,235 13,110 19,370 26,795 35,150 56,200
Tension Resistance of Steel — ASTM F1554, Grade 55 5,850 10,650 16,950 25,050 34,650 45,450 72,675
Tension Resistance of Steel — ASTM A193, Grade B7 9,750 17,750 28,250 41,750 57,750 75,750 121,125
Tension Resistance of Steel — Stainless Steel ASTM A193, Grade B8 and B8M Nsa lb.
4,445 8,095 12,880 19,040 26,335 34,540 55,235
(Types 304 and 316)
Tension Resistance of Steel — Stainless Steel ASTM F593 CW (Types 304 and 316) 7,800 14,200 22,600 28,390 39,270 51,510 82,365
Tension Resistance of Steel — Stainless Steel ASTM A193, Grade B6 (Type 410) 8,580 15,620 24,860 36,740 50,820 66,660 106,590
Strength Reduction Factor for Tension — Steel Failure φ — 0.755
Concrete Breakout Strength in Tension (2,500 psi ≤ f'c ≤ 8,000 psi)
Effectiveness Factor for Cracked Concrete kc,cr — 17
Effectiveness Factor for Uncracked Concrete kc,uncr — 24
Strength Reduction Factor — Concrete Breakout Failure in Tension φ — 0.655
Bond Strength in Tension (2,500 psi ≤ f'c ≤ 8,000 psi)6
Minimum Embedment hef,min in. 2 3/8 2 3/4 3 1/8 3 1/2 3 3/4 4 5
Maximum Embedment hef,max in. 7 1/2 10 12 1/2 15 17 1/2 20 25

SD
Characteristic Bond Strength
in Cracked Concrete8 τk,cr psi 1,448 1,402 1,356 1,310 1,265 1,219 1,128
Temperature Range A2,4
Characteristic Bond Strength
in Uncracked Concrete8 τk,uncr psi 2,357 2,260 2,162 2,064 1,967 1,868 1,672
Continuous Inspection

Characteristic Bond Strength


in Cracked Concrete8 τk,cr psi 1,201 1,163 1,125 1,087 1,050 1,012 936
Temperature Range B3,4
Characteristic Bond Strength
in Uncracked Concrete8 τk,uncr psi 1,957 1,876 1,795 1,713 1,632 1,551 1,388
Anchor Category Dry Concrete — — 1
Strength Reduction Factor Dry Concrete φdry,ci — 0.655
Water-Saturated Concrete, Water-Filled
Anchor Category — — 3 2
Hole or Submerged Concrete
Water-Saturated Concrete, Water-Filled
Strength Reduction Factor Hole or Submerged Concrete φwet,ci — 0.455 0.555
Characteristic Bond Strength τk,cr psi 1,346 1,304 1,356 1,310 1,265 1,219 1,128

C-A-2023 © 2023 SIMPSON STRONG-TIE COMPANY INC.


in Cracked Concrete8
Temperature Range A2,4
Characteristic Bond Strength
in Uncracked Concrete8 τk,uncr psi 2,192 2,102 2,162 2,064 1,967 1,868 1,672
Periodic Inspection

Characteristic Bond Strength


in Cracked Concrete8 τk,cr psi 1,117 1,082 1,125 1087 1,050 1,012 936
Temperature Range B3,4
Characteristic Bond Strength
in Uncracked Concrete8 τk,uncr psi 1,820 1,744 1,795 1,713 1,632 1,551 1,388
Anchor Category Dry Concrete — 2 1
Strength Reduction Factor Dry Concrete φdry,pi — 0.555 0.655
Water-Saturated Concrete, Water-Filled
Anchor Category — — 3
Hole or Submerged Concrete
Water-Saturated Concrete, Water-Filled
Strength Reduction Factor Hole or Submerged Concrete φwet,pi — 0.455
Reduction Factor for Seismic Tension αN,seis9 — 1.0 0.9 1.0 1.0 1.0 1.0 1.0
1. The information presented in this table is to be used in conjunction with the design criteria of ACI 318-19, ACI 318-14 and ACI 318-11.
2. Temperature Range A: Maximum short-term temperature = 160°F, Maximum long-term temperature = 110°F.
3. Temperature Range B: Maximum short-term temperature = 176°F, Maximum long-term temperature = 110°F.
4. Short-term concrete temperatures are those that occur over short intervals (diurnal cycling). Long-term temperatures are roughly constant
over significant periods of time.
5. The tabulated value of φ applies when the load combinations from the IBC or ACI 318 are used and the requirements of ACI 318-19 17.5.3,
ACI 318-14 17.3.3 or ACI 318-11 D.4.3, as applicable, are met. If the load combinations of ACI 318-11 Appendix C are used, refer to
ACI 318-11 D.4.4 to determine the appropriate value of φ.
6. Bond strength values shown are for normal-weight concrete having a compressive strength of f'c = 2,500 psi. For higher compressive strengths
up to 8,000 psi, the tabulated characteristic bond strength may be increased by a factor of (f'c /2,500)0.35 for uncracked concrete and a factor
of (f'c /2,500)0.24 for cracked concrete.
7. For lightweight concrete, the modification factor for bond strength shall be as given in ACI 318-19 17.2.4, ACI 318-14 17.2.6 or ACI 318-11 D.3.6,
as applicable, where applicable.
8. Characteristic bond strength values are for sustained loads, including dead and live loads.
9. For anchors installed in regions assigned to Seismic Design Category C, D, E or F, the bond strength values must be multiplied by αN,seis.

*See p. 14 for an explanation of the load table icons.


26
Simpson Strong-Tie® Anchoring, Fastening, Restoration and Strengthening Systems for Concrete and Masonry

SET-3G™ Design Information — Concrete

Adhesive Anchors
IBC *
SET-3G Tension Strength Design Data for Rebar 1,7
Rebar Size
Characteristic Symbol Units
#3 #4 #5 #6 #7 #8 #10
Steel Strength in Tension
Minimum Tensile Stress Area Ase in.2 0.11 0.20 0.31 0.44 0.60 0.79 1.27
Tension Resistance of Steel — Rebar (ASTM A615 Grade 60) 9,900 18,000 27,900 39,600 54,000 71,100 114,300
Nsa lb.
Tension Resistance of Steel — Rebar (ASTM A706 Grade 60) 8,800 16,000 24,800 35,200 48,000 63,200 101,600
Strength Reduction Factor for Tension — Steel Failure φ — 0.755
Concrete Breakout Strength in Tension (2,500 psi ≤ f'c ≤ 8,000 psi)
Effectiveness Factor for Cracked Concrete kc,cr — 17
Effectiveness Factor for Uncracked Concrete kc,uncr — 24
Strength Reduction Factor — Concrete Breakout Failure in Tension φ — 0.655
Bond Strength in Tension (2,500 psi ≤ f'c ≤ 8,000 psi)6
Minimum Embedment hef,min in. 2 3/8 2 3/4 3 1/8 3 1/2 3 3/4 4 5
Maximum Embedment hef,max in. 7 1/2 10 12 1/2 15 17 1/2 20 25
Characteristic Bond Strength
in Cracked Concrete8 τk,cr psi 1,448 1,402 1,356 1,310 1,265 1,219 1,128
Temperature Range A2,4
Characteristic Bond Strength τk,uncr psi 2,269 2,145 2,022 1,898 1,774 1,651 1,403
in Uncracked Concrete8

SD
Continuous Inspection

Characteristic Bond Strength


in Cracked Concrete8 τk,cr psi 1,201 1,163 1,125 1,087 1,050 1,012 936
Temperature Range B3,4
Characteristic Bond Strength
in Uncracked Concrete8 τk,uncr psi 1,883 1,781 1,678 1,575 1,473 1,370 1,165

Anchor Category Dry Concrete — — 1


Strength Reduction Factor Dry Concrete φdry,ci — 0.655
Water-Saturated Concrete, Water-Filled Hole
Anchor Category — — 3 2
or Submerged Concrete
Water-Saturated Concrete, Water-Filled Hole φwet,ci
Strength Reduction Factor — 0.455 0.555
or Submerged Concrete
Characteristic Bond Strength
in Cracked Concrete8 τk,cr psi 1,346 1,304 1,356 1,310 1,265 1,219 1,128
Temperature Range A2,4
Characteristic Bond Strength
in Uncracked Concrete8 τk,uncr psi 2,110 1,995 2,022 1,898 1,774 1,651 1,403
C-A-2023 © 2023 SIMPSON STRONG-TIE COMPANY INC.

Characteristic Bond Strength τk,cr


Periodic Inspection

psi 1,117 1,082 1,125 1,087 1,050 1,012 936


in Cracked Concrete8
Temperature Range B3,4
Characteristic Bond Strength
in Uncracked Concrete8 τk,uncr psi 1,751 1,656 1,678 1,575 1,473 1,370 1,165

Anchor Category Dry Concrete — — 2 1


Strength Reduction Factor Dry Concrete φdry,pi — 0.55 5
0.655
Water-Saturated Concrete, Water-Filled Hole
Anchor Category — — 3
or Submerged Concrete
Water-Saturated Concrete, Water-Filled Hole φwet,pi
Strength Reduction Factor — 0.455
or Submerged Concrete
Reduction Factor for Seismic Tension αN,seis9 — 1.0 1.0 1.0 1.0 1.0 1.0 1.0
1. The information presented in this table is to be used in conjunction with the design criteria of ACI 318-19, ACI 318-14 and ACI 318-11.
2. Temperature Range A: Maximum short-term temperature = 160°F, Maximum long-term temperature = 110°F.
3. Temperature Range B: Maximum short-term temperature = 176°F, Maximum long-term temperature = 110°F.
4. Short-term concrete temperatures are those that occur over short intervals (diurnal cycling). Long-term temperatures are roughly constant
over significant periods of time.
5. The tabulated value of φ applies when the load combinations from the IBC or ACI 318 are used and the requirements of ACI 318-19 17.5.3,
ACI 318-14 17.3.3 or ACI 318-11 D.4.3, as applicable, are met. If the load combinations of ACI 318-11 Appendix C are used, refer to
ACI 318-11 D.4.4 to determine the appropriate value of φ.
6. Bond strength values shown are for normal-weight concrete having a compressive strength of f'c = 2,500 psi. For higher compressive strengths
up to 8,000 psi, the tabulated characteristic bond strength may be increased by a factor of (f'c /2,500)0.35 for uncracked concrete and a factor
of (f'c /2,500)0.24 for cracked concrete.
7. For lightweight concrete, the modification factor for bond strength shall be as given in ACI 318-19 17.2.4, ACI 318-14 17.2.6 or ACI 318-11 D.3.6,
as applicable, where applicable.
8. Characteristic bond strength values are for sustained loads, including dead and live loads.
9. For anchors installed in regions assigned to Seismic Design Category C, D, E or F, the bond strength values must be multiplied by αN,seis.

*See p. 14 for an explanation of the load table icons.


27
Simpson Strong-Tie® Anchoring, Fastening, Restoration and Strengthening Systems for Concrete and Masonry

SET-3G™ Design Information — Concrete


Adhesive Anchors

IBC *
SET-3G Shear Strength Design Data for Threaded Rod1
Nominal Rod Diameter (in.)
Characteristic Symbol Units
3/8 1/2 5/8 3/4 7/8 1 1 1/4
Steel Strength in Shear
Minimum Shear Stress Area Ase in.2 0.078 0.142 0.226 0.334 0.462 0.606 0.969
Shear Resistance of Steel — ASTM F1554, Grade 36 2,715 4,940 7,865 11,625 16,080 21,090 33,720
Shear Resistance of Steel — ASTM F1554, Grade 55 Vsa lb. 3,510 6,390 10,170 15,030 20,790 27,270 43,605

SD
Shear Resistance of Steel — ASTM A193, Grade B7 5,850 10,650 16,950 25,050 34,650 45,450 72,675
Reduction factor for Seismic Shear — Carbon Streel αV,seis3 — 0.75 1.0
Shear Resistance of Steel — Stainless Steel ASTM A193, 2,665 4,855 7,730 11,425 15,800 20,725 33,140
Grade B8 and B8M (Types 304 and 316)

Shear Resistance of Steel — Stainless Steel ASTM F593 CW


(Types 304 and 316) Vsa lb. 4,680 8,520 13,560 17,035 23,560 30,905 49,420

Shear Resistance of Steel — Stainless Steel ASTM A193, 5,150 9,370 14,915 22,040 30,490 40,000 63,955
Grade B6 (Type 410)
Reduction factor for Seismic Shear — Stainless Steel αV,seis3 — 0.80 0.75 1.0
Strength Reduction Factor for Shear — Steel Failure φ — 0.652
Concrete Breakout Strength in Shear
Outside Diameter of Anchor da in. 0.375 0.5 0.625 0.75 0.875 1 1.25
Load-Bearing Length of Anchor in Shear le in. Min. of hef and 8 times anchor diameter
Strength Reduction Factor for Shear — Breakout Failure φ — 0.70 2
Concrete Pryout Strength in Shear
Coefficient for Pryout Strength kcp in. 1.0 for hef < 2.50"; 2.0 for hef ≥ 2.50"
Strength Reduction Factor for Shear — Breakout Failure φ — 0.70 2
1. The information presented in this table is to be used in conjunction with the design criteria of ACI 318-19, ACI 318-14 and ACI 318-11.
2. The tabulated value of φ applies when the load combinations from the IBC or ACI 318 are used and the requirements of ACI 318-19 17.5.3,
ACI 318-14 17.3.3 or ACI 318-11 D.4.3, as applicable, are met. If the load combinations of ACI 318-11 Appendix C are used, refer to
ACI 318-11 D.4.4 to determine the appropriate value of φ.
3. The values of Vsa are applicable for both cracked concrete and uncracked concrete. For anchors installed in regions assigned to

C-A-2023 © 2023 SIMPSON STRONG-TIE COMPANY INC.


Seismic Design Category C, D, E or F, Vsa must be multiplied by αVseis for the corresponding anchor steel type.

*See p. 14 for an explanation of the load table icons.


28
Simpson Strong-Tie® Anchoring, Fastening, Restoration and Strengthening Systems for Concrete and Masonry

SET-3G™ Design Information — Concrete

Adhesive Anchors
IBC *
SET-3G Shear Strength Design Data for Rebar1
Rebar Size
Characteristic Symbol Units
#3 #4 #5 #6 #7 #8 #10
Steel Strength in Shear

SD
Minimum Shear Stress Area Ase in.2 0.110 0.200 0.310 0.440 0.600 0.790 1.270
Shear Resistance of Steel — Rebar (ASTM A615 Grade 60) 5,940 10,800 16,740 23,760 32,400 42,660 68,580
Vsa lb.
Shear Resistance of Steel — Rebar (ASTM A706 Grade 60) 5,280 9,600 14,880 21,120 28,800 37,920 60,960
Reduction Factor for Seismic Shear — Rebar (ASTM A615 Grade 60) 0.60 0.8
αV,seis3 —
Reduction Factor for Seismic Shear — Rebar (ASTM A706 Grade 60) 0.60 0.8
Strength Reduction Factor for Shear — Steel Failure φ — 0.65 2

Concrete Breakout Strength in Shear


Outside Diameter of Anchor da in. 0.375 0.5 0.625 0.75 0.875 1 1.25
Load-Bearing Length of Anchor in Shear le in. Min. of hef and 8 times anchor diameter
Strength Reduction Factor for Shear — Breakout Failure φ — 0.702
Concrete Pryout Strength in Shear
Coefficient for Pryout Strength kcp in. 1.0 for hef < 2.50"; 2.0 for hef ≥ 2.50"
Strength Reduction Factor for Shear — Breakout Failure φ — 0.702
1. The information presented in this table is to be used in conjunction with the design criteria of ACI 318-19, ACI 318-14 and ACI 318-11.
2. The tabulated value of φ applies when the load combinations from the IBC or ACI 318 are used and the requirements of ACI 318-19 17.5.3,
ACI 318-14 17.3.3 or ACI 318-11 D.4.3, as applicable, are met. If the load combinations of ACI 318-11 Appendix C are used, refer to
ACI 318-11 D.4.4 to determine the appropriate value of φ.
3. The values of Vsa are applicable for both cracked concrete and uncracked concrete. For anchors installed in regions assigned to
Seismic Design Category C, D, E or F, Vsa must be multiplied by αVseis for the corresponding anchor steel type.

For additional load tables, visit strongtie.com/set3g.


C-A-2023 © 2023 SIMPSON STRONG-TIE COMPANY INC.

Anchor Anchor Designer™ Software


AD

Designer™
for ACI 318, ETAG and CSA
Simpson Strong-Tie® Anchor Designer software accurately
analyzes existing design or suggests anchor solutions
based on user-defined design elements in cracked and
uncracked concrete conditions.

*See p. 14 for an explanation of the load table icons.


29
Simpson Strong-Tie® Anchoring, Fastening, Restoration and Strengthening Systems for Concrete and Masonry

SET-3G™ Design Information — Concrete


Adhesive Anchors

c ≥ cmin.

Concrete edge

c ≥ cmin.

s ≥ smin.

Cast-in-place
reinforcing bars
ld Post-installed
Development length reinforcing bars

IBC *
SET-3G Development Length for Rebar Dowel
Development Length,
in. (mm)
Drill Bit Clear Cover,
Rebar
Diameter in. f'c = 2,500 psi f'c = 3,000 psi f'c = 4,000 psi f'c = 6,000 psi f'c = 8,000 psi
Size
(in.) (mm) (17.2 MPa) (20.7 MPa) (27.6 MPa) (41.4 MPa) (55.2 MPa)
Concrete Concrete Concrete Concrete Concrete

1.125 12 12 12 12 12
#3 1/2
(29) (305) (305) (305) (305) (305)

#4 5/8 1.125 14.4 14 12 12 12


(29) (366) (356) (305) (305) (305)
1.125 18 17 14.2 12 12

C-A-2023 © 2023 SIMPSON STRONG-TIE COMPANY INC.


#5 3/4
(29) (457) (432) (361) (305) (305)

#6 7/8 1.125 21.6 20 17.1 14 13


(29) (549) (508) (434) (356) (330)
2.30 31.5 29 25 21 18
#7 1 (58) (800) (737) (635) (533) (457)

#8 1 1/8 2.30 36 33 28.5 24 21


(58) (914) (838) (724) (610) (533)

#9 1 3/8 2.30 40.5 38 32 27 23


(58) (1,029) (965) (813) (686) (584)

#10 1 3/8 2.30 45 42 35.6 30 26


(58) (1,143) (1,067) (904) (762) (660)

#11 1 3/4 2.30 51 47 41 33 29


(58) (1,295) (1,194) (1,041) (838) (737)
1. Tabulated development lengths are for static, wind and seismic load cases in Seismic Design Category A and B.
Development lengths in Seismic Design Category C through F must comply with ACI 318-19 and ACI 318-14 Chapter 18 or
ACI 318-11 Chapter 21, as applicable.
2. Rebar is assumed to be ASTM A615 Grade 60 or A706 (fy = 60,000 psi). For rebar with a higher yield strength,
multiply tabulated values by fy /60,000 psi.
3. Concrete is assumed to be normal-weight concrete. For lightweight concrete, multiply tabulated values by 1.33.
4. Tabulated values assume bottom cover less that 12" cast below rebars (Ψ1 = 1.0).
5. Uncoated rebar must be used.
6. The value of Κtr is assumed to be 0. Refer to ACI 318-19 Section 25.4.2.4, ACI 319-14 Section 25.4.2.3 or ACI 318-11 Section 12.2.3.

*See p. 14 for an explanation of the load table icons.


30
Simpson Strong-Tie® Anchoring, Fastening, Restoration and Strengthening Systems for Concrete and Masonry

SET-3G™ Design Information — Masonry

Adhesive Anchors
SET-3G Epoxy Anchor Installation Information — *
Fully Grouted CMU Construction — Face of Wall IBC

Nominal Rod Diameter / Rebar Size


Installation Information Symbol Units
3/8" / #3 1/2" / #4 5/8" / #5 3/4" / #6

Drill Bit Diameter — Threaded Rod do in. 7/16 9/16 11/16 7/8

Drill Bit Diameter — Rebar do in. 1/2 5/8 3/4 7/8

Minimum Embedment Depth hef,min in. 3 3 3 3

SET-3G Epoxy Anchor Installation Information — *


Fully Grouted CMU Construction — Top of Wall IBC

Nominal Rod Diameter / Rebar Size


Installation Information Symbol Units
1/2" / #4 5/8" / #5 7/8"

Drill Bit Diameter — Threaded Rod do in. 9/16 11/16 1

Drill Bit Diameter — Rebar do in. 5/8 3/4 —

Minimum Embedment Depth hef,min in. 3 3 3

SET-3G Epoxy Anchor Installation Information — *


Ungrouted CMU Construction IBC

Nominal Rod Diameter


Installation Information Symbol Units
3/8" 1/2" 5/8"

Drill Bit Diameter do in. 9/16 3/4 7/8


C-A-2023 © 2023 SIMPSON STRONG-TIE COMPANY INC.

Embedment Depth hef,min in. 3 1/2 3 1/2 3 1/2

Please see the SET-3G product


page at strongtie.com and
ICC-ES ESR Report for load data.

*See p. 14 for an explanation of the load table icons.


31