Desigo™

Automation stations
PXC7

To automate building automation and control systems


● Modular automation station and system controller for HVAC and building
automation and control systems
● BACnet/IP communication (BTL certified)
● BACnet Secure Connect communication
● Comprehensive management and system functions
● Freely programmable automation stations for maximum flexibility
● Connects TXM input/output modules
● KNX PL-Link bus to connect RDG2..KN room thermostats, sensors, and operator
units (including bus power)
● Integration of M-bus energy meters directly (integrated mini power supply) or via
RS485 level-converter
● Integration of Modbus data points via RTU and / or TCP
● Integration of BACnet MS/TP devices
● WLAN interface for engineering and commissioning
● Operating voltage AC or DC 24 V
● Mounted on standard rails or on the wall
● Plug-in screw terminal blocks
● Building X integration

A6V12505052_en--_e Smart Infrastructure


2024-02-02
Functions
Optimized, flexible automation station for HVAC and building automation and control
systems
● System functions (alarming, scheduling, trending, access protection with individually
definable user profiles and categories)
● System controller for system networks with PXC3, PXC4, PXC5, PXC7 and DXR
controllers over BACnet/IP, BACnet/SC, or BACnet MS/TP
● Integrates data points and/or subsystems via Modbus RTU and/or Modbus TCP
● Integrates MS/TP devices
● Integration of wired M-bus meters via RS485 level-converter or onboard M-bus interface
(EN 13757-2):
– Offline and/or online engineering with ABT Site. No additional M-bus tool required
– Primary and/or secondary device addressing
● The following functions are available with KNX PL-Link bus:
– Communication with RDG2..KN room thermostats, sensors, and operator units
– Plug-and-play connection of Siemens field devices with KNX PL-Link
● Integrated power supply for TX-IO modules
● Integrated AC/DC 24 V power supply for field devices (e.g. actuators and sensors)
● Engineering and commissioning with the ABT Site Tool using graphical function charts
● Freely programmable. All function blocks, available in libraries, can be graphically
connected.
● BTL tested BACnet communication on IP (BACnet/IP or BACnet/SC) or BACnet MS/TP,
in compliance with the BACnet standard including B-BC profile (Rev. 1.16)
● IT security including HTTPS, IEC-62443 4-2 (Security Level 2*), and BACnet Secure
Connect
● BACnet Secure Connect support as BACnet/SC hub
● Generic operation via embedded web interface
● Cloud connectivity to Building X for remote access and data points time series
● 2-port Ethernet switch for low-cost cabling
● WLAN interface for engineering and commissioning
● Operating voltage AC 24 V or DC 24 V
● DIN rail or screw mounting
● Plug-in screw terminal blocks

* For details about network and physical setup, refer to the Desigo Cybersecurity Guidelines.

2
Siemens Schweiz AG A6V12505052_en--_e
Smart infrastructure 2024-02-02
Type summary

Standardized hardware
PXC7.E400S, M, and L are based on the same hardware and all have the same look and
feel. Interfaces like RS485 are enabled and disabled according to the type specification.

PXC7 variants E400S E400M E400L


Order number S55375-C111 1) S55375-C110 1) S55375-C105 1)
Number of TXM inputs and outputs up to 100 up to 200 up to 400
Number of integration data points up to 100 up to 200 up to 400
(M-bus, Modbus TCP and / or RTU)
Total number TXM-I/Os and integration DPs 100 2) 250 2) 600 2)
Number of digital inputs for potential-free contacts for 1 1 1
signaling functions NO or NC (onboard)
Number of BACnet/SC devices connected as nodes up to 100 up to 100 up to 100
Number of BACnet MS/TP devices in a field level network up to 60 3) up to 120 3) up to 240 3)
(2 x 60) (4 x 60)
Number of KNX PL-Link devices up to 64 up to 64 up to 64
Number of configurable RS485 interfaces either for 1 2 4
integration of Modbus RTU, BACnet MS/TP, or M-bus

1)
For details on engineering, see PXC4, PXC5 & PXC7 Planning overview, A6V13054435.
2)
KNX PL-Link data points do not count as integration points. For KNX PL-Link, only the limits on BACnet objects
are considered.
3)
Depending on the behavior of the third-party MS/TP devices.

Onboard inputs

DI Digital inputs for potential-free contacts for signaling functions (NO, NC)

TXM I/O modules

Description Type 1) Data sheet


Digital input module 8 or 16 I/O points TXM1.8D, TXM1.16D CM2N8172
Universal module without / with local operation and LCD TXM1.8U, TXM1.8U-ML CM2N8173
Super universal module without / with local operation and LCD TXM1.8X, TXM1.8X-ML CM2N8174
Relay module without / with local operation TXM1.6R, TXM1.6R-M CM2N8175
Resistance measuring module (for Pt100 4-wire) TXM1.8P CM2N8176
Triac module (only if PXC7.E400 is powered with AC) TXM1.8T CM2N8179
Digital input and relay module TXM1.4D3R CM2N8188
Power module TXS1.12F10 CM2N8183
Bus connection module TXS1.EF10 CM2N8183
Island bus extension module TXA1.IBE CM2N8184

1)
Module series B and higher. In following use cases only series D can be used (available as of 2012):
● I/O bus communication mode "Event"

PXC7 can power TXM extensions modules (see Interfaces [} 9]).


For further details see PXC4, PXC5 & PXC7 Planning overview A6V13054435 and data sheets.

3
Siemens Schweiz AG A6V12505052_en--_e
Smart infrastructure 2024-02-02
KNX PL-Link devices

Description Type Data sheet


Wall-mounted temperature sensor QMX3.P30 CM2N1602
Wall-mounted temperature and humidity sensor QMX3.P40
Wall-mounted temperature, humidity, and CO2 sensor QMX3.P70
Wall-mounted temperature sensor and room operator unit QMX3.P34
Wall-mounted temperature and humidity sensor and room operator QMX3.P44
unit
Wall-mounted temperature, humidity, and CO2 sensor and room QMX3.P74
operator unit
Wall-mounted temperature sensor and room operator unit QMX2.P33 A6V10733768
Wall-mounted temperature and humidity sensor and room operator QMX2.P43
unit
Flush-mounted room sensors base and front modules: CE1N1411
● Base module for temperature and / or humidity measurement 1) ● AQR2570
● Base module for CO2 measurement 1) ● AQR2576
● Front module for base module without sensor ● AQR2530NNW
● Front module for base module with temperature sensor ● AQR2532NNW
● Front module for base module with humidity and temperature ● AQR2535NNW
sensor ● AQR2535NNWQ
● Front module for base module with humidity, temperature
sensor, and CO2 indicator LED
Passive infrared presence detector UP 258D12 A6V10489489
Presence detector WIDE with temperature sensor UP 258D31 A6V11894530
Presence detector WIDE with temperature and humidity sensor UP 258D41
Presence detector WIDE with temperature, humidity, and CO2 UP 258D51
sensor
Presence detector WIDE with temperature sensor and ultrasound UP 258D61
Room thermostat with temperature and humidity sensor RDG200KN A6V11545853
RDG260KN
Room thermostat with temperature, humidity, and CO2 sensor RDG204KN
RDG264KN

1)
Physical data points on the base module AQR257.. for use in HVAC functions:
- 2 x Binary potential-free contacts (NO, NC)
- 1 x Passive sensor NTC10K (Type II / Beta (0-50 °C) = 3892 K)
For details see PXC4, PXC5 & PXC7 Planning overview A6V13054435 and data sheets.

Desigo Control Point

Description Type Data sheet


BACnet touch panels with integrated data storage and web server A6V11664137
functionality: PXM30.E
7.0 " PXM40.E
10.1 " PXM50.E
15.6 "
TCP/IP client touch panels with data storage in web server PXG3.Wx00-2: A6V11664139
7.0 " PXM30-1
10.1 " PXM40-1
15.6 " PXM50-1
BACnet/IP web server with standard functionality PXG3.W100-2 A6V12304192
BACnet/IP web server with extended functionality PXG3.W200-2

4
Siemens Schweiz AG A6V12505052_en--_e
Smart infrastructure 2024-02-02
Technical and mechanical design
The compact build allows for mounting the devices on a standard rail or a wall.

4 Service button (ID on network and WLAN on/off)


5 2-port Ethernet switch
(with 2 LEDs per port for display purposes)
6 Ethernet port (for future use)
7 Plug-in terminal block with screw terminals
KNX PL-Link
8 Plug-in terminal blocks with screw terminals
Power supply
9 Plug-in terminal block with screw terminals
Digital input
10 Data matrix code
11 Connection for TXM modules (island bus)
12 Plug-in terminal block with screw terminals
M-bus
Plug-in terminal block with screw terminals
(M-bus, Modbus, or MS/TP)
13 COM1 interface
14 COM2 interface
15 COM3 interface
16 COM4 interface
Activation of COM 1/2/3/4 depending on Type
(S,M,L)
17 DIP switches for bus termination and polarization
COM
18 QR code for default WLAN access
Description see Technical data [} 8]
19 Date/series and serial number
1 Plastic housing 20 Slider for mounting on DIN rails
2 Battery cover 21 Eyelets for cable ties
3 LEDs for communication and state 22 Holes for wall mounting

5
Siemens Schweiz AG A6V12505052_en--_e
Smart infrastructure 2024-02-02
LED displays

Activity LED Color Activity Function


Ethernet Green Steady ON Link active
Steady OFF No connection
Flashing Network traffic
Yellow Steady ON Link 100 Mbps
Steady OFF Link 10 Mbps

RUN Green Steady ON Device operational


Steady OFF Device not operational
Flashing Start-up or program stop
Red Steady OFF OK
Steady ON HW or SW fault
Rapid flashing Firmware or application missing/corrupted
Blue Steady ON Cloud connection OK
Blinking Cloud connection enabled but no connection
available
Steady OFF Cloud connection disabled
BAT Red Steady OFF Optional battery OK
Steady ON Optional battery empty - replace
TXM Yellow Flashing Communication
Steady OFF No communication with TXM modules
SVC Red Steady OFF OK
Flashing Device not configured
Flashing after wink Device ID after receipt of wink command
command

5 Hz 5 Hz

2s 1s 2s 1s

WLAN Blue Steady OFF WLAN inactive


Steady ON WLAN active and at least one WLAN client
connected
Flashing WLAN active and no WLAN client connected
COM… Yellow Flashing Communication
(TX: Transmit, RX: Receive)
Steady OFF No communication to subsystem
KNX Yellow Flashing Communication
(TX: Transmit, RX: Receive)
Steady OFF No communication to subsystem
M-bus Yellow Flashing Communication
(TX: Transmit, RX: Receive)
Steady OFF No communication to subsystem
Service Press 0.2 ... 1 s ID in the network
button Press 1 ... 3 s WLAN enable/disable
WLAN disables automatically after
10 minutes if no client is connected
Factory reset 1. Power off the device.
2. Power on the device.
3. Wait until all LEDs light up and turn off
again, then press the Service button.
4. Keep the Service button pressed until all
LEDs light up, then release the button.
All LEDs go off, the device restarts.
5. Wait until the device has fully started –
unconfigured (green RUN LED and red
SVC LED are flashing)

6
Siemens Schweiz AG A6V12505052_en--_e
Smart infrastructure 2024-02-02
Product documentation
Related documents such as the environmental declarations, declarations of conformity, etc.,
can be downloaded from the following Internet address:
www.siemens.com/bt/download

Notes
Safety

CAUTION
National safety regulations
Failure to comply with national safety regulations may result in personal injury and property
damage.
● Observe national provisions and comply with the appropriate safety regulations.

Mounting position and ambient temperature


The devices can be snapped onto standard rails or screwed onto a flat surface.
Plug-in screw terminals connect power and interfaces.

Ambient temperature -5...50 °C (23...122 °F) Ambient temperature -5...45 °C (23...113 °F)
● Wall, horizontal ● Overhead
– From left to right ● Wall, vertically

– From right to left – From top to bottom


– From bottom to top
● On a horizontal surface

CAUTION
Risk of overheating for failure to comply with ambient temperature
Burning and damage to the device
● Ensure sufficient ventilation to comply with the permissible ambient temperature within
the panel or installation box. The temperature must be at least 10 K (18° F) lower
outside the installation box.

Installation

WARNING
Electric shock
Incorrect installation of the device may lead to electric shock injuries when touching the
device!
● Install the device in a lockable cabinet or use terminal covers.
● Do not install the device in locations where children are likely to be present.
● Conductors with a cross-section of 0.5 mm2 (AWG24) or greater shall comply with the
requirements of IEC 60332-1-2 and IEC 60332-1-3 or IEC TS 60695-11-21.

Disposal

7
Siemens Schweiz AG A6V12505052_en--_e
Smart infrastructure 2024-02-02
This symbol or any other national label indicate that the product, its
packaging, and, where applicable, any batteries may not be disposed of as
domestic waste. Delete all personal data and dispose of the item(s) at
separate collection and recycling facilities in accordance with local and
national legislation.
For additional details, refer to Siemens information on disposal.

Warranty
Technical data on specific applications are valid only together with Siemens products listed
under "Equipment combinations". Siemens rejects any and all warranties in the event that
third-party products are used.

Technical data
Power supply

Operating voltage AC 24 V (24 V≃, ⏊, ) AC 24 V -15 / +20 % (PELV)


AC 24 V Class 2 (US)
48…63 Hz
Operating voltage DC 24 V (24 V≃, ⏊, ) DC 24 V -15 / +20 % (PELV)
DC 24 V Class 2 (US)
Functional ground (US) The terminal for the functional ground must be
Functional earth connected on the installation side with the building
grounding system (PE).
Screw terminals for wire cross sections up to Max. 2.5 mm2 (14 AWG)
Internal fusing 4 A irreversible / non-replaceable
External supply line fusing (EU) Non-renewable fuse max. 10 A slow-blow
or
circuit breaker max. 13 A
Tripping characteristic B, C, D per EN 60898
or
Power supply with current limitation of max. 10 A
Protection Reverse connection protection for DC 24 V

Power consumption (for transformer / power supply planning)

Operating voltage Operating voltage


AC 24 V DC 24 V
Full load 71 VA / 3.0 A 66 W / 2.8 A
Base load (without loading by I/O modules TXM, KNX 15.4 VA / 0.64 A 7.8 W / 0.33 A
PL-Link, M-bus, and field devices)
I/O modules TXM supply 15 VA / 0.6 A 8 W / 0.3 A
KNX PL-Link supply 4 VA / 0.17 A 2.2 W / 0.09 A
M-bus supply 3 VA / 0.13 A 1.7 W / 0.07 A
Field device supply V~ Max. 2 A, total of the connected field devices
< 48 VA / 48 W

8
Siemens Schweiz AG A6V12505052_en--_e
Smart infrastructure 2024-02-02
Function data

Hardware information
Processor NXP i.MX8 QuadXPlus, 1.2 GHz
Storage 2 GByte RAM
8 GByte eMMC

Data backup in the event of power failure


Energy reserve (supercapacitor) to support real-time clock (7 days).
Energy reserve to support real-time clock can be extended using optional battery BR2032: depending on the life
time of the battery and use, typically 10 years.
(Battery safety requirement and specification for BR2032 according to IEC 60086-4 or UL1642.
Battery must be rated for ambient temperature 85 °C (185 °F))
Low power of battery will be indicated by LED and a system alarm will be generated.
Data available if stored to flash memory: Every 5 minutes.
The interval of 5 minutes is only valid for change log but not for trending.
In case of a power failure, trend log data can be lost up to 30 minutes.

Interfaces

Ethernet interface
Plug 3 x RJ45, shielded
Interface type 10Base-T / 100Base-TX, IEEE 802.3 compatible
Bit rate 10/100 Mbps, autosensing
Protocol BACnet/IP on UDP/IP, BACnet/SC on TCP/IP, and
HTTPS on TCP/IP
Cabling (in-house cabling only), cable type 10 Mbps: Min. CAT3, shielded cable is recommended
100 Mbps: Min. CAT5, shielded cable is recommended
Cable length Max. 100 m (330 ft)

The COM interfaces can be used either for M-bus, Modbus, or for MS/TP, according to type
and configuration.

M-bus interface on COM interface (RS485)


Interface type EIA-485, electrically isolated
Baud rate 300, 600, 1200, 2400, 4800, 9600, 19200, 38400.
The maximum baud rate is depending on the
configuration of M-bus-S devices (subordinate devices)
and M-bus repeater.
Internal bus termination 120 Ohm, switchable with DIP switch
Internal bus polarization 270 Ohm pull-up/pull-down resistances, switchable with
DIP switch
Cabling (in-house cabling only) 3-wire cable, shielded cable recommended (shield must
Cable length be connected to building earth in the mounting panel)
Max. 1000 m (3300 ft)
Protection Short-circuit proof
Protection against faulty wiring with AC 24 V and
DC 24 V
M-bus level converter including power supply (required) Configuration examples (simple M-bus loads à 1.5 mA):
● Up to 2 M-bus devices: STV Electronic, MPW-2 1
● Up to 6 M-bus devices: STV Electronic, MPW-6 1
● Up to 60 M-bus devices: Relay GmbH, PW60 1
● Up to 250 M-bus devices: Siemens, WTX631-
GA0090

1
For STV Electronic level converters, refer to https://www.stv-electronic.de/. For Relay GmbH level converters,
refer to https://www.relay.de/.
The use of these products is a recommendation only. Siemens cannot guarantee functionality nor take over any
warranty for third-party products. This information is subject to change without notice.

9
Siemens Schweiz AG A6V12505052_en--_e
Smart infrastructure 2024-02-02
Modbus RTU interface
Interface type EIA-485, electrically isolated
Baud rate 300, 600, 1200, 2400, 4800, 9600, 19200, 38400,
57600, 76800, 115200 (depending on the configuration)
Internal bus termination 120 Ohm, switchable with DIP switch
Internal bus polarization 270 Ohm pull-up/pull-down resistances, switchable with
DIP switch
Cabling (in-house cabling only) 3-wire cable, shielded cable recommended (shield must
Cable length be connected to building earth in the mounting panel)
Max. 1000 m (3300 ft)
Protection Short-circuit proof
Protection against faulty wiring with AC 24 V and
DC 24 V

BACnet MS/TP interface


Interface type EIA-485, electrically isolated
Baud rate 9600, 19200, 38400, 76800, 115200 (depending on the
configuration)
Internal bus termination 120 Ohm, switchable with DIP switch
Internal bus polarization 270 Ohm pull-up/pull-down resistances, switchable with
DIP switch
Cabling (in-house cabling only) 3-wire cable, shielded
Distance between 2 devices Max. 500 m (1650 ft)
Length of the MS/TP line Max. 1000 m (3300 ft)
Protection Short-circuit proof
Protection against faulty wiring with AC 24 V and
DC 24 V

WLAN interface
Interface type Wireless access point
Supported standards IEEE 802.11b/g/n
Frequency band 2.412…2.462 GHz
WLAN channels 1…11
Maximum radio-frequency power 16.4 dBm
Distance (unobstructed field) Min. 5 m (16 ft)
Device pairing Activation / deactivation with service button
Automatic switch off after 10 minutes if no WLAN-client
is connected.
Optionally, for cyber security reasons, the WLAN can be
permanently disabled via configuration.
Default SSID and WLAN password: Scan the QR code.
It will display something like WIFI:S:PXC7.E400_0000550;T:WPA;P:1400052738;;
Then SSID = PXC7.E400_0000550 and password = 1400052738
Determine manually: Use the information from the Date/Series/SN block It will display something like:
Date/Series: 202104230000550
S/N: 1400052738
SSID = <ASN>_<Running number after the series letter> and password = <S/N>

10
Siemens Schweiz AG A6V12505052_en--_e
Smart infrastructure 2024-02-02
M-bus manager with integrated power supply
Interface type M-bus manager according to EN 13757-2 for max.
7.5 mA, galvanically isolated
Max. 4 M-bus meters as subordinates (4 simple M-bus
loads à 1.5 mA)
Baud rate 300, 2400 (default), 9600.
The maximum baud rate is depending on M-bus device
configuration and M-bus repeater.
Cabling (in-house cabling only) 2-wire cable, interchangeable according to M-bus
Cable length standard
Max. 100 m (330 ft)
Protection Short-circuit proof
Protection against faulty wiring with AC 24 V and
DC 24 V
M-bus level converter used as repeater (optional) to Configuration examples (simple M-bus loads à 1.5 mA):
extend number of connected M-bus-S devices ● Up to 60 M-bus-S devices: WTV531-GA5060
● Up to 250 M-bus-S devices: WTX631.GA0090

ABT Site checks the number of data points and not the number of M-bus-S devices. The
max. number of devices per network depends on the individual load of each device and the
given power supply by the M-bus manager (PXC4/5/7) or converter.

KNX PL-Link interface


Type KNX TP1 PL-Link, galvanic isolation
Baud rate: 9.6 kbps
Cabling (in-house cabling only) 2-wire cable, 0.75 mm2 / AWG20
or 1 mm2 / AWG18
Cable length With internal supply: Max. 80 m (262 ft)
With external supply: Max. 1000 m (3300 ft)
Internal bus power Max. 50 mA
When using external bus power for KNX PL-Link, switch
off the internal bus power via the ABT Site Tool.

I/O modules TXM bus interface


Nominal voltage DC 24 V
Supply current for I/O modules TXM Max. 300 mA
Connectable in parallel with DC 24 V power supply For details, see: TX-I/O- engineering and installation,
module TXS1.12F4 CM110562
Protection Short-circuit proof
TXM I/O module plug: No protection against faulty No electric protection.
wiring with AC 24 V Use cover

Field device supply (I/O module TXM)


AC 24 V output current (terminal V~ on the TXM Max. 2 A, short-circuit proof (only if PXC7 is powered by
module) AC voltage)
If PXC7 is powered by DC voltage, the field device
supply on terminal V~ of the TXM modules is also DC
voltage.

Screw terminals, plug-in


Cu-wire or Cu-strand with wire end sleeve 1 x 0.6 mm ∅ to 2.5 mm2 (22 to 14 AWG)
or 2 x 0.6 mm ∅ to 1.0 mm2 (22 to 18 AWG)
Cu-strand without wire end sleeve 1 x 0.6 mm ∅ to 2.5 mm2 (22 to 14 AWG)
or 2 x 0.6 mm ∅ to 1.5 mm2 (22 to 16 AWG)
Stripping length 6...7.5 mm (0.24...0.29 in)
Screwdriver Slot screws, screwdriver size 1 with shaft ø = 3 mm
Max. tightening torque 0.6 Nm (0.44 lb ft)

11
Siemens Schweiz AG A6V12505052_en--_e
Smart infrastructure 2024-02-02
Conformity

Ambient conditions and protection classification


Classification as per EN 60730
Automatic action Type 1
Control function Class A
Pollution degree 2
Overvoltage category I
Protection against electric shock Protection class III
Protection degree of housing to EN 60529
Front parts in DIN cut-out IP30
Terminal part IP20
Climatic ambient conditions
● Storage / Transport (packaged for transport) as per ● Class 1K22 / 2K12
IEC EN 60721‑3‑2 Temperature -25...70 °C (-13...158 °F)
Air humidity 5...95 % (non-condensing)
● Operation as per IEC/EN 60721-3-3 ● Class 3K23
Operation in enclosed dry locations, having no
temperature or humidity control
Temperature -5...50 °C (23...122 °F)
(for details see chapter Mounting)
Air humidity 5...95 % (non-condensing)
Mechanical ambient conditions
● Transport per IEC/EN 60721-3-2 ● Class 2M4
● Operation as per IEC/EN 60721-3-3 ● Class 3M11

Standards, directives, and approvals


Product standards IEC/EN 60730-1
Product family standard IEC/EN 63044-x
Electromagnetic compatibility (EMC) For residential, commercial, and industrial environments
EU conformity (CE) See CE declaration 1)
UK conformity (UKCA) See UK declaration 1)
EAC conformity Eurasian compliance
RCM conformity See RCM declaration 1)
UL/cUL certification (US / Canada) UL916, http://ul.com/database
UL94, housing material meets classification V-0 2)
CSA certification C22.2, http://csagroup.org/services-industries/product-
listing
FCC CFR 47 Part 15C
BACnet Profile: B-BC
Revision: 1.16
Detailed information on BACnet certificates, BTL
listings, and PICS can be found on the BACnet website
(filtered for Siemens products)
AMEV profile (BACnet 2017) AS-B
KBOB profile (BACnet 2017) AS-CH 3)
1)
Environmental compatibility The product environmental declaration 1) contains data
on environmentally compatible product design and
assessments (RoHS compliance, materials
composition, packaging, environmental benefit,
disposal).
OSHPD seismic certification Product meets OSHPD Special Seismic Certification
Preapproval (OSH-0217) under California Building
Code 2022 (CBC 2022)4)

1)
Documents can be downloaded at www.siemens.com/bt/download.
2)
Material level
3)
AS-CH pending

12
Siemens Schweiz AG A6V12505052_en--_e
Smart infrastructure 2024-02-02
4)
When installed within the following Siemens enclosures: PXA-ENC18, PXA-ENC19, or PXA-ENC34.

European Union conformity


Contact for regulatory topics: (EU) Siemens AG, Berliner Ring 23, DE-76437 Rastatt

United Kingdom conformity assessed


Contact for regulatory topics: (GB) Siemens plc, Sir William Siemens House, Princess Road,
Manchester, M20 2UR

FCC Statement
This equipment has been tested and found to comply with the limits for a Class B digital
device, pursuant to part 15 of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference in a residential installation. This
equipment generates, uses and can radiate radio frequency energy and, if not installed and
used in accordance with the instructions, may cause harmful interference to radio
communications. However, there is no guarantee that interference will not occur in a
particular installation. If this equipment does cause harmful interference to radio or television
reception, which can be determined by turning the equipment off and on, the user is
encouraged to try to correct the interference by one or more of the following measures:
● Reorient or relocate the receiving antenna.
● Increase the separation between the equipment and receiver.
● Connect the equipment into an outlet on a circuit different from that to which the receiver
is connected.
● Consult the dealer or an experienced radio/TV technician for help.
This device complies with Part 15 of the FCC rules. Operation is subject to the following two
conditions:
1. This device may not cause harmful interference, and
2. this device must accept any interference received, including interference that may cause
undesired operation
FCC Caution: Changes or modifications not expressly approved by Siemens Switzerland
Ltd. could void user authority to operate the equipment. United States representative
https://new.siemens.com/us/en/products/buildingtechnologies/home.html

Industry Canada statement


This device complies with ISED’s license-exempt RSSs. Operation is subject to the following
two conditions:
1. This device may not cause interference, and
2. This device must accept any interference received, including interference that may cause
undesired operation.

Radiofrequency radiation exposure statement


This equipment complies with FCC and IC radiation exposure limits set forth for an
uncontrolled environment. This equipment should be installed and operated with a minimum
distance of 20 cm between the radiator and your body.
This transmitter must not be co-located or operated in conjunction with any other antenna or
transmitter.
Housing

Color top / bottom 2003 Ti-Grey / 804 Black


Dimensions per DIN 43880, see Dimensions
Weight without / with packaging 516 g / 581 g

13
Siemens Schweiz AG A6V12505052_en--_e
Smart infrastructure 2024-02-02
Connection terminals

3 4 5 6 7 10 11

66 67 68 69 70 71 72 73 74 75 76 77 78 79

Terminal Symbol Description


1A, 1B 2 x RJ45 interface for Ethernet with switch

2 1 x RJ45 interface (for future use)

3, 4 KNX KNX PL-Link


5, 6 ≃,⏊ Operating voltage AC 24 V or DC 24 V
7 Functional ground (must be connected on the installation side with the building
grounding system (PE)).
10, 11 D, ⏊ Digital input
Term on, off Switch for bus termination
Polar on, off Switch for polarization
66, 67 MBUS M-bus interface
68, 69, 70 COM1 Interface EIA-485 (M-bus, Modbus RTU, BACnet MS/TP)
71, 72, 73 COM2 Remark: Activation of COM1/2/3/4 depending on Type (S, M, L)

74, 75, 79 COM3


77, 78, 79 COM4
Right side of Interface for connecting TXM I/O modules
device

14
Siemens Schweiz AG A6V12505052_en--_e
Smart infrastructure 2024-02-02
Dimensions
All dimensions in mm and inches.

PXC7
198 (7.80") 3 (0.12") 74.5 (2.93")

183 (7.20") 7 (0.28") 48.6 (1.91")

117 (41.61")

124 (4.88")

110 (4.33")
45 (1.77")

67 (2.64")
4.1 (0.16") 26.6 (1.05")

PXC7 with four TXM modules


198 (7.80") 64 (2.52") 64 (2.52") 64 (2.52") 64 (2.52") 7 (0.28")
124 (4.88")

90 (3.54")
461 (18.15")

15
Siemens Schweiz AG A6V12505052_en--_e
Smart infrastructure 2024-02-02