Ecowatt® Drive K354 Series
Quick Setting Manual
OVERVIEW: This is a basic installation and commissioning steps that must be adhere for quick installation and commissioning.
STEP 1 - UNPACK INSPECTION STEP 2 - INSTALLATION CONFIRMATION STEP 3 - BASIC COMMISSIONING
Check the following after receiving the product. If found Check the following before VFD installation. Complete the basic commissioning below before the actual use
abnormalities, please contact the local dealer or Kruger office. of the VFD. (See more details in page no. 2)
2.1 Ensure that the grid voltage meets input power of VFD.
1.1 Check if the packing box is damaged. 2.2 Ensure that the output power from VFD is matched with the
1.2 Check if the interior surface of the packing box is abnormal. motor spec.
For example, in wet condition or whether the enclosure of the 2.3 Ensure that the environments of installation area are not over
VFD is damaged or cracked. the VFD specified limits.
1.3 Check if the accessories inside the packing box are complete
(including the manual and keypad). Upper PC
Check the following after the 3.1 MOTOR SETTING
1.4 Check if the VFD nameplate is consistent with the model LCD keypad software
VFD installation. & AUTO TUNING
identifier on the exterior surface of the packing box and your 485+
RS485–
purchased model. 485-
RS232
converter
PC
2.4 Ensure that the correct
Standard
accessories are selected for
Power supply
-
the VFD. The accessories
PB + +
Breaker
are correct and properly
P1 installed, and the
Model: K354-5R5P-4 IP54 +
installation cables meet the
Power: 5.5kW
DC reactor
requirements of all
Input: AC 3PH 380(-15%)~400V(+15%) 19.5A components (including the
Input reactor
Brake
47Hz~63Hz
resistor
Earth
Brake unit
reactor, input filter, output
Output: AC 3PH 0-Uinput 14A 0-400Hz Input filter reactor, output filter, DC
Output filter reactor, braking unit and
S/N: Made in China braking resistor).
Output reactor
2.5 Ensure that all control
Kruger Ventilation Industries Asia Co., Ltd. Motor cables and power cables are 3.2 CONTROL
run separately and the METHOD & SETTING
Earth
routing complies with EMC
requirements.
2.6 Ensure that all grounding systems are properly grounded
according to the requirements of the VFD.
2.7 Ensure that the external connection terminals of the VFD are
tightly fastened and the torque on the bolts are appropriate.
2.8 Ensure that there are screws, cables, or other conductive
items are cleared from the VFD. If no, clear them out. CAUTION: The K354 should ONLY be installed by a
qualified electrician.
DANGER! Improper wiring can and will cause bodily
1/2 harm as well as damage to the equipment.
Ecowatt® Drive K354 Series 3. BASIC COMMISSIONING (CONTINUE)
You can perform various operations on the VFD by using the
Quick Setting Manual keypad, including entering/exiting menus, parameter selection,
list modification and parameter addition.
3.1 MOTOR SETTING & AUTO TUNING 3.2 CONTROL METHOD SETTING
1. Select the motor type 1. Select Start/Stop command method 2. Select Speed command method
Push Manu => Parameter setting => Motor and Encoders Push Manu => User defined parameter setting => P00.01: Run CMD channel Push Manu => User defined parameter setting
parameter setting => Motor1 param => P02.00 motor type (0: Keypad, 1: Terminal, 2: Communication) => P00.06: A Freq CMD
(0: Asynchronous motor, 1: Synchronous motor) (0: Set via Keypad, 1: Set via AI1 )
P00.01 = 0 : Start/Stop via Keypad
2. Set motor parameters follow Motor’s nameplate - You can Push or on Keypad directly. P00.06 = 0 : Set via Keypad
- Asynchronous motor_P02.01 to P02.05 - You can adjust motor speed / frequency from the
Example of setting Digital Operator on Keypad directly.
P00.01 = 1 : Start/Stop via Terminal 16:02:35 Forward Local Ready 01: K354 16:02:35 Forward Local Ready 01: K354
- Connect 3 switch to terminal S1, S2, S3, COM, PE below.
P02.01: Rated Power (3.0 kW)
Set frequency Set frequency
P17.00 Hz 50.00 50.00
Hz
P02.02: Rated Frequency (50 Hz) DC bus voltage
P17.11 V 540.0
P02.03: Rated Speed (2880 rpm) Digital input terminal state
0.00 630.00
0x0000
P02.04: Rated Voltage (400 V) P17.12
Return
Monitoring About Menu Homepage
P02.05: Rated Current (5.7 A)
P00.06 = 1 : Set via AI1
- Synchronous motor _P02.15 to P02.19 - Speed reference from external terminals
Example of setting (Potentiometer or Analog Signal)
Connect cable to 10V, AI1, GND, PE below.
P02.15: Rated Power (4.77 kW)
P02.16: Rated Frequency (50 Hz)
P02.17: Number of Pole Pair (1)*
P02.18: Rated Voltage (400 V)
P02.19: Rated Current (12.5 A)
* 2 pole = 1 pole pair P00.01 = 2 : Start/Stop via Communication (Modbus)
- Connect control cable to 485+, 485-, 485G below.
3. Auto tuning
De-couple the load from motor before start autotuning.
Push Manu => Motor parameters auto tuning => 485+ 485- 485G
1: Rotary auto tuning => Push RUN to start auto tuning
=> Waiting until tuning completed
Note: If cannot be de-coupled motor from the load,
please select to perform 2: Static autotuning. Shieled cable
4. Check rotating direction
Push Jogging for 5sec to run motor and check whether
the motor rotational direction is correct. If not, change the
rotation direction by swapping UW wires of the motor.
or change P00.13 from 0 to 1: Run in reverse direction.
RS485 connect to
Controller 2/2