Electrical Interview Questions On Protection
Electrical Interview Questions On Protection
If all Current Transformers,all having the same ratio are mounted on every circuit
connected to the busbar and are connected in parallel then a fault external to the busbar
will result in a balance of all CT currents which will not initiate the high impedance
relay,but if the fault is on the busbar then the protection will operate. Additionally to this
where the design of the switchboard allows for a bus section switch which divides the
switchgear into two sections.a fault on either side will trip that section only and leave the
healthy section intact. It should be noted that in the bus section switch the CT`s are cross
connected ie those on one side are connected to the other side and vice versa.This ensures
that all the busbar,including the bus section switch itself will result in a complete loss of
busbar. I hope this helps,let me know?
55. Reply to this post...
56.
57.
Posted by samo on 1 August, 2008 - 12:56 am
58. Kevinr...
Everyone can read the T.Davies book on industrial power systems. Any ideas of your
own?
59. Reply to this post...
60.
61.
Posted by Subhro Roy on 7 May, 2007 - 10:23 pm
62. Hello,
Bus zone protection is a unit protection (meaning a protection with a restricted zone,
therefore does not need to be coordinated with other time based protections) specifically
for MV/HV switchgear protection of Busbars and Circuit Breakers. Generally always
Circuit Breakers are included in the zone of Busbar protection. They are of two types
from point of view of principle of operation: High impedance and Low impedance types.
From the point of view of zones of protection they are classified into discriminating and
check zone protections.
High impedance differential protection for the MV Switchgear Bus bar protection use the
principle of comparison of currents by paralleling the secondaries of identical (both ratio
and parameters) current transformers to a current operated relay and a stabilizing resistor
in series, with a voltage limiting device across the combination. It is a very simple,
reliable and fast operating scheme provided CTs and stabilizing resistors have been
selected properly for stability against operation by through fault currents outside the zone
of operation. For HV switchgears with more than one bus bars and switching isolators
etc, the low impedance differential relay is used which is a costlier solution. However, it
permits different CT ratios. These are numerical protection relays.
Please refer to the litrature of MCAG. MFAC and Micom P740 Relays from Alstom
T&D web site for more details of High and low impedance Bus zone protection.
64.
65.
Posted by SIKANDER on 12 April, 2008 - 3:17 am
In HV switchgear the zone of protection is segregated according to the position of the bus
section or bus coupler. Mainly the selection of zone should be overlapping each other.
Then only it will protect the system entirely from wherever the fault occurs.
For example, we have one bus coupler & 6 cable feeders on either side of the bus
coupler. In this condition we need to provide 2 zones & 1 check zone. We have two trip
relays on 2 different zones (zone 1 & 2). The CT connected to the corresponding zone
will give initiation to the particular zone trip relay. Then the breaker will get trippped