HGM1791_HGM1791CAN
GENSET CONTROLLER
USER MANUAL
Registered trademark
No. 28 Xuemei Street, Zhengzhou, Henan, China
Tel: +86-371-67988888/67981888/67992951
+86-371-67981000(overseas)
Fax: +86-371-67992952
Web: www.smartgen.com.cn/
www.smartgen.cn/
Email: [email protected]
All rights reserved. No part of this publication may be reproduced in any material form (including
photocopying or storing in any medium by electronic means or other) without the written
permission of the copyright holder.
SmartGen reserves the right to change the contents of this document without prior notice.
Table 1 Software Version
Date Version Note
2023-12-15 1.0 Original release.
HGM1791_HGM1791CAN Genset Controller User Manual Page 2 of 41
Table 2 Notation Clarification
Sign Instruction
Highlights an essential element of a procedure to ensure correctness.
NOTE
Indicates a procedure or practice, which, if not strictly observed, could
CAUTION! result in damage or destruction of equipment.
Indicates a procedure or practice, which could result in injury to personnel
WARNING! or loss of life if not followed correctly.
HGM1791_HGM1791CAN Genset Controller User Manual Page 3 of 41
CONTENT
1 OVERVIEW ................................................................................................................................................ 6
2 PERFORMANCE AND CHARACTERISTICS .............................................................................................6
3 OPERATION .............................................................................................................................................. 9
3.1. FRONT PANEL DESCRIPTION ............................................................................................................9
3.2. INDICATOR DESCRIPTION ................................................................................................................. 9
3.3. PANEL KEYS ........................................................................................................................................9
3.4. AUTO START/STOP OPERATION ....................................................................................................10
3.5. MANUAL START/STOP OPERATION .............................................................................................. 11
4 PROTECTION ..........................................................................................................................................12
4.1. SHUTDOWN ...................................................................................................................................... 12
4.2. WARNINGS ........................................................................................................................................13
5 WIRING CONNECTION ...........................................................................................................................15
6 PARAMETER RANGE AND DEFINITION ............................................................................................... 17
6.1. PARAMETERS CONTENTS AND RANGE ........................................................................................ 17
6.2. DEFINABLE CONTENTS OF RELAY OUTPUTS ............................................................................... 24
6.3. DEFINABLE CONTENTS OF DIGITAL INPUTS ................................................................................ 24
6.4. SENSOR SELECTION ........................................................................................................................ 25
6.5. CONDITIONS OF CRANK DISCONNECT SELECTION .................................................................... 26
7 CONTROLLER FUNCTION SETTING ..................................................................................................... 27
7.1. SETTING ............................................................................................................................................ 27
7.2. PARAMETER SETTING .....................................................................................................................27
7.3. LANGUAGE ........................................................................................................................................28
7.4. EVENT LOG ....................................................................................................................................... 28
7.5. CONTROLLER INFO .......................................................................................................................... 28
8 SENSOR SETTINGS ................................................................................................................................29
9 COMMISSIONING ...................................................................................................................................30
10 TYPICAL APPLICATION .........................................................................................................................31
11 INSTALLATION .......................................................................................................................................32
11.1. FIXING CLIPS .................................................................................................................................... 32
11.2. OVERALL DIMENSION ......................................................................................................................32
12 FAULT FINDING ......................................................................................................................................34
13 CONNECTIONS OF CONTROLLER WITH J1939 ENGINE ....................................................................35
13.1. CUMMINS-ISB/ISBE ......................................................................................................................... 35
13.2. CUMMINS QSL9 ................................................................................................................................35
13.3. CUMMINS QSM11 ............................................................................................................................ 35
13.4. CUMMINS QSX15-CM570 ................................................................................................................36
13.5. CUMMINS QSM11 ............................................................................................................................ 36
HGM1791_HGM1791CAN Genset Controller User Manual Page 4 of 41
13.6. CUMMINS QSZ13 ............................................................................................................................. 36
13.7. DETROIT DIESEL DDEC III / IV ......................................................................................................... 37
13.8. DEUTZ EMR2 .....................................................................................................................................37
13.9. JOHN DEERE .....................................................................................................................................37
13.10.MTU MDEC ........................................................................................................................................38
13.11.MTU ADEC (SMART MODULE) .......................................................................................................... 38
13.12.MTU ADEC (SAM MODULE) ............................................................................................................... 38
13.13.PERKINS ............................................................................................................................................ 39
13.14.SCANIA ..............................................................................................................................................39
13.15.VOLVO EDC3 .....................................................................................................................................39
13.16.VOLVO EDC4 .....................................................................................................................................40
13.17.VOLVO-EMS2 .................................................................................................................................... 40
13.18.YUCHAI ..............................................................................................................................................40
13.19.WEICHAI ............................................................................................................................................ 41
HGM1791_HGM1791CAN Genset Controller User Manual Page 5 of 41
1 OVERVIEW
HGM1791_HGM1791CAN genset controller is suitable for single unit automation and
monitoring control (also can be used for pumping unit). It can realize manual start/stop of genset,
and it can also automatically start/stop genset by remote start signal. HGM1791_HGM1791CAN
controller can monitor and protect genset operation by collecting and analyzing genset data like
generation voltage, current, water temperature, oil pressure and so on, and it can indicate fault
conditions and do maintenance as soon as possible. The controller uses LCD display to show
Chinese and English languages. Touch-button operation makes it clear and intuitive. Moreover,
parameter threshold and delay value can be adjusted via front panel or USB port (communicated
with PC software).
2 PERFORMANCE AND CHARACTERISTICS
— 128x64 LCD display (with backlight), Chinese and English operation interface to be set by
on-site engineer for commissioning and testing;
— Hard screen acrylic material is used to protect screen.
— Silicone panel and buttons are adopted to increase high and low temperature adaption
ability;
— Power supply range DC (8~35)V, compatible with 12V or 24V starting batteries;
— Generator single phase voltage, current, frequency, power and load percentage parameters
are measured and displayed:
Generator Voltage V Generator Frequency Hz
Generator Power kW Generator Current A
Load Percentage %
— Precision measured and displayed parameters of engine:
Oil Pressure kPa Temperature ºC
Fuel Level % Total Running Time H (max. 65535 hours)
Battery Voltage V Engine Speed RPM
Accumulated Start Times (max. 65534 times)
— With genset fault protection and display functions.
— 3 working modes: manual, auto, stop;
— Compatible with multiple temperature, pressure, fuel level sensors, which can be
user-defined and used directly; temperature sensors, pressure sensors can be used in parallel
with annunciator, providing analog quantity and increasing protection level at the same time;
— Multiple crank disconnection conditions to select (engine speed sensor, oil pressure,
HGM1791_HGM1791CAN Genset Controller User Manual Page 6 of 41
generator frequency);
— 3 configurable input ports which can be set as digital input or sensor input;
— 2 fixed relay outputs (fuel relay, start relay);
— 3 configurable output ports which can be set as common alarm output, preheat output or
idle control output;
— Parameters can be set and modified by users, and they will not be lost in case of power off.
Parameters of the controller can be modified by the front panel and all parameters can be
adjusted by PC software via Type-C USB port;
— Digital regulation of all parameters to make control more reliable and stable;
— Modular design, self-extinguishing ABS plastic enclosure, pluggable terminal
blocks/connectors, embedded installation way, small size and compact structure for easy
mounting.
HGM1791_HGM1791CAN Genset Controller User Manual Page 7 of 41
Table 3 Technical Parameters
Item Content
Working Voltage DC8.0V to 35.0V, Continuous Power Supply
Power Consumption <1.8W (Standby mode: ≤0.8W)
Alternator Voltage Input AC 15V ~ AC 360 V (ph-N)
Alternator Frequency 50Hz/60Hz
Speed Sensor Voltage 1V to 24V (RMS)
Speed Sensor Frequency Max. 10,000Hz
Start Relay Output 1A DC28V DC power supply
Fuel Relay Output 1A DC28V DC power supply
Aux. Output 1 1A DC28V DC power supply
Aux. Output 2 1A DC28V DC power supply
Aux. Output 3 1A DC28V DC power supply
Programmable Digital Input Active when connected to B-
Case Dimensions 96mm x 86mm x 467mm
Panel Cutout 78mm x 66mm
CT Secondary Current Rated value: 5A
Working Temperature (-25~+70) ºC
Working Humidity (20~93) %RH
Storage Temperature (-30~+80) ºC
IP65: When waterproof rubber gasket will be installed between the
Protection Level
controller and panel fascia.
Attach AC2.2kV voltage between AC high voltage terminal and low
Insulation Intensity
voltage terminal (leak current below 3mA in 1 minute).
Weight 0.17kg
HGM1791_HGM1791CAN Genset Controller User Manual Page 8 of 41
3 OPERATION
3.1. FRONT PANEL DESCRIPTION
Fig.1 HGM1791_HGM1791CAN Front Panel
3.2. INDICATOR DESCRIPTION
Stop status indicator light: genset in stop mode.
Auto status indicator light: genset in auto mode.
Manual start indicator light: only light up when genset starts and is in manual mode.
Alarm indicator light: blink slowly (1 time/s) when warn alarm occurred; blink fast (5 times/s)
when shutdown alarm occurred.
3.3. PANEL KEYS
Table 4 Key Descriptions
Key Definition Description
In auto/manual mode, pressing it will shut down the genset;
If genset is in stop status, reset shutdown alarms by pressing it;
Test indicator lights and LCD screen when press it for over 3s in
Stop/Reset
stop mode;
Stop immediately if press this button again during stop process;
Quick exit parameter setting menu if press this button.
Pressing this button will make the module into auto mode, and
genset is controlled by remote start input signals in this mode;
Auto/Decrease
In settings menu, it can move page up or reduce the set value;
When cursor disappears, pressing it can quit the current menu.
Pressing this button will start genset;
Start/Confirm
In settings menu it can move cursor or confirm the setting.
HGM1791_HGM1791CAN Genset Controller User Manual Page 9 of 41
Key Definition Description
Using this button can scroll pages of the LCD monitor;
Page Down/
Enter settings menu after press it over 3s;
Increase
In settings menu, it can move page down or increase the set value.
3.4. AUTO START/STOP OPERATION
Auto mode is selected by pressing button, and the LED indicator beside the button will light
up to confirm the operation.
Automatic Start Sequence:
1) When “Remote Start” is active (Input terminal configuration is “Remote Start”), “Start Delay”
timer is initiated, then the status on LCD screen will be “Start Delay” countdown;
2) When start delay is over, preheat relay energizes (if configured), “Preheat Delay” starts to count,
then the status on LCD screen will be “Preheat Delay XXs”.
3) After the preheat delay, the Fuel Relay is energized, and one second later, the Start Relay is
engaged. If the genset fails to fire during “Cranking Time”, then the fuel relay and start relay stop
to output; “Crank Rest Time” begins and wait for the next cranking attempt.
4) After setup number of cranking attempts, if genset fails to start, the start sequence will be
terminated, and “Fail to Start” alarm will be displayed on LCD screen, and meanwhile alarm
indicator light is blinking.
5) In case of successful crank attempt, the “Safety On” timer is activated, Low Oil Pressure, High
Temperature and other alarms are inactive during the period. As soon as this delay is over,
“Start Idle” delay is initiated (if configured).
6) During “Start Idle” delay, under speed, under frequency, under voltage alarms are inhibited. When
this delay is over, “Warming up” delay is initiated (if configured).
7) When “Warming up” delay is over, if power generation runs normal, the power generation
indicator will light up. When generator voltage and frequency meet load requirement, the
generation switch-on relay will output, then genset start to load and power supply indicator
lights up, which means genset starts normal running; if generator voltage or frequency is
abnormal, shutdown alarm signals will be sent by the controller (alarm page on LCD screen will
show power generation alarm).
Automatic Stop Sequence:
1) When the “Remote Start” signal doesn’t work, “Stop Delay” is initiated;
2) Once this “Stop Delay” has expired, the “Cooling Delay” is then initiated.;
3) During “Stop Idle” Delay (if configured), idle relay is energized;
4) When “ETS Delay” begins, ETS relay switches on while fuel relay switches off.;
HGM1791_HGM1791CAN Genset Controller User Manual Page 10 of 41
5) When genset enters “Wait Stop Time”, it automatically detects whether genset stops
completely;
6) Genset enters standby status after it stops completely. Otherwise, the controller enters stop
failure and issues “Stop Failure” warning.
NOTE:
a) When press stop button in auto start status, genset will stop and enter into stop mode simultaneously.
b) In process of crank rest delay, ETS output is energized when fuel output is de-energized and crank rest
time countdown is less than 7s. After crank rest delay, ETS output is de-energized, fuel relay starts
output, and preheat output switches off before crank.
3.5. MANUAL START/STOP OPERATION
1) MANUAL START: Press button to start the genset (Please refer to No.2~7 of Automatic
Start Sequence for detail procedures). With high temperature, low oil pressure, over speed
and abnormal voltage during generator running, controller can protect genset to stop quickly.
2) MANUAL STOP: Press button can shut down the running genset. (Please refer to No.2~6
of Automatic Stop Sequence for detail procedures).
HGM1791_HGM1791CAN Genset Controller User Manual Page 11 of 41
4 PROTECTION
4.1. SHUTDOWN
When controller detects shutdown warning signals, it switches off to stop at once and issues
warning type.
Table 5 Controller Shutdown Alarms
No. Type Description
When controller detects emergency stop alarm signal, it
1 Emergency Stop
issues emergency shutdown alarm signal.
When controller detects engine speed is over preset over
2 Over Speed Shut
speed stop threshold, it issues shutdown alarm signal.
When controller detects engine speed is under preset over
3 Under Speed Shut
speed stop threshold, it issues shutdown alarm signal.
When controller detects speed is 0, and speed signal loss
4 Loss of Speed Signal
action is "Shutdown", it issues shutdown alarm signal.
Genset Over Frequency When controller detects genset frequency is over preset over
5
Shut frequency stop threshold, it issues shutdown alarm signal.
Genset Under Frequency When controller detects genset frequency is under preset over
6
Shut frequency stop threshold, it issues shutdown alarm signal.
Genset Over Voltage When controller detects genset voltage is over preset over
7
Shut voltage stop threshold, it issues shutdown alarm signal.
Genset Under Voltage When controller detects genset voltage is under preset over
8
Shut voltage stop threshold, it issues shutdown alarm signal.
When engine fails to start after pre-set start attempts,
9 Failed to Start
controller issues shutdown alarm signal.
When controller detects genset current is over preset over
10 Genset Over Current Shut
current stop threshold, it issues shutdown alarm signal.
When controller input port is set to High Temp Shutdown Input
11 High Temp. Shut IN
and it is active, it issues shutdown alarm signal.
When controller input port is set to Low Oil Pressure
12 Low Oil Pressure Shut IN Shutdown Input and it is active, it issues shutdown alarm
signal.
When controller detects ECU temperature value is above
13 High Temp. Shut ECU
pre-set shutdown value, it issues shutdown alarm signal.
Low Oil Pressure Shut When controller detects ECU oil pressure is below pre-set
14
ECU shutdown value, it issues shutdown alarm signal.
When controller detects ECU temperature value is below
15 Low Temp. Shut ECU
pre-set shutdown value, it issues shutdown alarm signal.
High Oil Pressure Shut When controller detects ECU oil pressure is above pre-set
16
ECU shutdown value, it issues shutdown alarm signal.
Aux. Temp. Sensor X Set sensor X as temperature sensor, when controller detects
Open sensor is open, and action type is “Shutdown”, it issues
17
(X can be 1~3, the below shutdown alarm signal.
same)
Set sensor X as temperature sensor, when controller detects
Aux. Sensor X High
18 sensor value is above pre-set shutdown upper limit value, it
Temp.
issues shutdown alarm signal.
Set sensor X as temperature sensor, when controller detects
Aux. Sensor X Low
19 sensor value is below pre-set shutdown lower limit value, it
Temp.
issues shutdown alarm signal.
Set sensor X as oil pressure sensor, when controller detects
Aux. Oil Pressure Sensor
20 sensor open, and action type is “Shutdown”, it issues
X Open
shutdown alarm signal.
HGM1791_HGM1791CAN Genset Controller User Manual Page 12 of 41
No. Type Description
Set sensor X as oil pressure sensor, when controller detects
Aux. Oil Pressure Sensor
21 sensor value is above pre-set shutdown upper limit value, it
X High
issues shutdown alarm signal.
Set sensor X as oil pressure sensor, when controller detects
Aux. Oil Pressure Sensor
22 sensor value is below pre-set shutdown lower limit value, it
X Low
issues shutdown alarm signal.
Set sensor X as level sensor, when controller detects sensor
Aux. Level Sensor X
23 open, and action type is “Shutdown”, it issues shutdown alarm
Open
signal.
Set sensor X as level sensor, when controller detects sensor
24 Aux. Sensor X High Level value is above pre-set shutdown upper limit value, it issues
shutdown alarm signal.
Set sensor X as level sensor, when controller detects sensor
25 Aux. Sensor X Low Level value is below pre-set shutdown lower limit value, it issues
shutdown alarm signal.
When controller is set as ECU genset, if it detects
26 ECU Comm. Failure
communication failure, it issues communication failure signal.
When controller detects shutdown alarm signal from ECU, it
27 ECU Shutdown
issues shutdown alarm signal.
When controller input port is set as shutdown alarm, and it is
28 Input Shutdown
active, it issues shutdown alarm signal to the same input port.
NOTE:
a) Shutdown signal is latched signal, and press the “Stop” button can clear the alarm; Warning signal will not
be latched.
b) If shutdown alarm delay time is set, after the time is over, then controller issues shutdown alarm signal.
4.2. WARNINGS
When controller detects warning signal, it only issues warning without shutdown.
Table 6 Warnings
No. Type Description
When controller detects speed is above the pre-set over speed
1 Over Speed Warn
warning threshold, it issues warning signal.
When controller detects speed is under the pre-set under
2 Under Speed Warn
speed warning threshold, it issues warning signal.
When controller detects speed is 0, and speed signal loss
3 Loss of Speed Signal
action is “Warning”, it issues warning signal.
Genset Over Frequency When controller detects genset frequency is over preset over
4
Warn frequency stop threshold, it issues warning signal.
Genset Under Frequency When controller detects genset frequency is under preset over
5
Warn frequency stop threshold, it issues warning signal.
Genset Over Voltage When controller detects genset voltage is over preset over
6
Warn voltage stop threshold, it issues warning signal.
Genset Under Voltage When controller detects genset voltage is under preset over
7
Warn voltage stop threshold, it issues warning signal.
Genset Over Current When controller detects genset current is over preset over
8
Warn current stop threshold, it issues warning signal.
When engine stop delay is over and engine doesn't stop
9 Stop Failure
completely, controller issues warning signal.
When controller detects genset battery voltage is above
10 Battery Over Voltage
pre-set threshold, it issues warning signal.
11 Battery Under Voltage When controller detects engine battery voltage is below
HGM1791_HGM1791CAN Genset Controller User Manual Page 13 of 41
No. Type Description
pre-set threshold, it issues warning signal.
When controller receives warning signal of engine by J1939, it
12 ECU Warn
issues warning signal.
When controller detects ECU temperature value is above
13 High Temp. Warn ECU
pre-set shutdown value, it issues warning signal.
Low Oil Pressure Warn When controller detects ECU oil pressure is below pre-set
14
ECU shutdown value, it issues warning signal.
When controller detects ECU temperature value is below
15 Low Temp. Warn ECU
pre-set shutdown value, it issues warning signal.
High Oil Pressure Warn When controller detects ECU oil pressure is above pre-set
16
ECU shutdown value, it issues warning signal.
Set sensor X as temperature sensor, when controller detects
Aux. Temp. Sensor X
17 sensor is open, and action type is “Warning”, it issues warning
Open
signal.
Set sensor X as temperature sensor, when controller detects
Aux. Sensor X High
18 sensor value is above pre-set warning upper limit value, it
Temp.
issues warning signal.
Set sensor X as temperature sensor, when controller detects
Aux. Sensor X Low
19 sensor value is below pre-set warning lower limit value, it
Temp.
issues warning signal.
Set sensor X as oil pressure sensor, when controller detects
Aux. Oil Pressure Sensor
20 sensor open, and action type is “Warning”, it issues warning
X Open
signal.
Set sensor X as oil pressure sensor, when controller detects
Aux. Sensor X High Oil
21 sensor value is above pre-set warning upper limit value, it
Pressure
issues warning signal.
Set sensor X as oil pressure sensor, when controller detects
Aux. Sensor X Low Oil
22 sensor value is below pre-set warning lower limit value, it
Pressure
issues warning signal.
Aux. Level Sensor X Set sensor X as level sensor, when controller detects sensor
23
Open open, and action type is “Warning”, it issues warning signal.
Set sensor X as level sensor, when controller detects sensor
24 Aux. Sensor X High Level value is above pre-set warning upper limit value, it issues
warning signal.
Set sensor X as level sensor, when controller detects sensor
25 Aux. Sensor X Low Level value is below pre-set warning lower limit value, it issues
warning signal.
NOTE: If warning alarm delay time is set, after the time is over, then controller issues warning signal.
HGM1791_HGM1791CAN Genset Controller User Manual Page 14 of 41
5 WIRING CONNECTION
Fig.2 Controller Back Panel
Table 7 Terminals Description
No. Function Cable Size Remarks
1 DC Voltage Input B- 1.5mm 2
Connect to negative of starting battery
Connected to positive of starting battery. If wire
2 DC Voltage Input B+ 1.5mm 2
length is over 30m, better to use double wires in
parallel. Max. 20A fuse is recommended.
B+ voltage input is active, and connected to
3 Emergency Stop Input 1.0mm2
emergency stop normal closed button.
4 Fuel Relay Output 1.0mm 2
B+ is supplied by No.3 point, rated 1A.
5 Crank Relay Output 1.0mm2 B+ is supplied by No.3 point, rated 1A.
Ground connected is active (B-) if it is configured as
digital input.
6 Aux. Input 1 1.0mm2
Connect to resistive sensor if it is configured as
sensor 1.
Ground connected is active (B-) if it is configured as
digital input.
7 Aux. Input 2 1.0mm2
Connect to resistive sensor if it is configured as
sensor 2.
8 Aux. Input 3 1.0mm 2
Ground connected is active (B-) if it is configured as
HGM1791_HGM1791CAN Genset Controller User Manual Page 15 of 41
No. Function Cable Size Remarks
digital input.
Connect to resistive sensor if it is configured as
sensor 3.
If controller model is HGM1791: connect to B-;
9 CANL/MP2 0.5mm2 If controller model is HGM1791CAN: connect to
CANL signal line.
If controller model is HGM1791: connect to speed
sensor, and shielded wire is recommended;
10 CANH/MP1 0.5mm2 Another end of speed sensor is connected to B-.
If controller model is HGM1791CAN: connect to
CANH signal line.
11 Gen Volt Monitoring 1.0mm2 Connect to generator voltage output port. (2A fuse is
12 Input 1.0mm2 recommended)
Load Current (Inlet
13 1.5 mm2
Loop) Connect to secondary coil of current transformer.
Load Current (Outlet (Rated 5A)
14 1.5 mm2
Loop)
15 Aux. Output 1 1.0 mm2 B+ is supplied by No.2 point, rated 1A.
16 Aux. Output 2 1.0 mm2 B+ is supplied by No.2 point, rated 1A.
17 Aux. Output 3 1.0 mm 2
B+ is supplied by No.2 point, rated 1A.
NOTE: Type-C USB port, which can be connected with PC software, is applied for parameter configuration
and data monitoring.
HGM1791_HGM1791CAN Genset Controller User Manual Page 16 of 41
6 PARAMETER RANGE AND DEFINITION
6.1. PARAMETERS CONTENTS AND RANGE
Table 8 Parameter Setting Contents and Range
No. Parameter Range Default Value Description
Timer Setting
Time from remote start signal being
1 Start Delay (0-3600)s 1
active to genset start.
Time from remote start signal being
2 Stop Delay (0-3600)s 1
inactive to genset stop.
Time to pre-energize heat plug before
3 Preheat Time (0-3600)s 0
starter is powered on.
Time to power on the starter for every
4 Cranking Time (3-60)s 8
crank attempt
The waiting time before second power
5 Crank Rest Time (3-60)s 10
on when engine start fails.
Alarms for low oil pressure, high
temperature, under speed, under
6 Safety On Delay (0-3600)s 10
frequency, under voltage and charging
failure are inactive.
7 Start Idle Time (0-3600)s 0 Idle running time after genset starts.
Warming Up Warming time between genset switch
8 (0-3600)s 10
Time on and normal running.
Radiating time before genset stop,
9 Cooling Time (0-3600)s 10
after it unloads.
10 Stop Idle Time (0-3600)s 0 Idle running time after genset stops.
ETS Solenoid The time of powering up the
11 (0-120)s 20
Hold electromagnet during stop procedure.
Time between ending of genset idle
delay and stopped when “ETS Solenoid
Hold” is set as 0;
12 Wait Stop Time (0-3600)s 0
Time between ending of ETS hold delay
and stopped when “ETS Solenoid Hold”
is not 0.
Time from complete stop to standby
13 After Stop Time (0-3600)s 0
status.
Engine Setting
1 Engine Type (0-39) 0 Default: non-ECU genset.
Tooth number of the engine is for
2 Flywheel Teeth (10.0-300.0) 118.0 judging of crank disconnect conditions
and inspecting of engine speed. See
HGM1791_HGM1791CAN Genset Controller User Manual Page 17 of 41
No. Parameter Range Default Value Description
the installation instructions.
Baseline for over speed, under speed
3 Rated Speed (0-6000)RPM 1500
and load speed detection.
It is set for ECU genset to control idle
4 Idle Speed (0-6000)RPM 750
speed.
Set value is percentage of rated speed.
Before load stage if controller detects
5 Load Speed (0-100)% 90
speed is below idle speed, the genset
won’t enter to normal running stage.
Speed Signal Time from detecting speed is 0 to
6 (0-3600)s 5
Loss Delay confirm action.
Speed Signal
7 (0-1) 0 0: Warning; 1: Shutdown.
Loss Action
(0-1) 1 0: Disable; 1: Enable.
Over Speed
8 (0-200)% 114 Set value is percentage of rated speed.
Shutdown
(0-3600)s 2 Delay value.
(0-1) 1 0: Disable; 1: Enable.
Under Speed
9 (0-200)% 80 Set value is percentage of rated speed.
Shutdown
(0-3600)s 3 Delay value.
(0-1) 1 0: Disable; 1: Enable.
(0-200)% 110 Set value is percentage of rated speed.
Over Speed
10 Return value is percentage of rated
Warn (0-200)% 108
speed.
(0-3600)s 5 Delay value.
(0-1) 1 0: Disable; 1: Enable.
(0-200)% 86 Set value is percentage of rated speed.
Under speed
11 Return value is percentage of rated
Warn (0-200)% 90
speed.
(0-3600)s 5 Delay value.
Battery Rated Baseline for battery over/under voltage
12 (0-60.0)V 24.0
Voltage detection.
(0-1) 1 0: Disable; 1: Enable.
Set value is percentage of rated
(0-200)% 120
Battery Over voltage.
13 Voltage Warn Return value is percentage of rated
(0-200)% 115
voltage.
(0-3600)s 60 Delay value.
(0-1) 1 0: Disable; 1: Enable.
Set value is percentage of rated
(0-200)% 85
Battery Under voltage.
14 Voltage Warn Return value is percentage of rated
(0-200)% 90
voltage.
(0-3600)s 60 Delay value.
Maximum start times in case of failed
to start; when this number is reached,
15 Start Attempts (1-10)times 3
controller shall issue Failed to Start
signal.
Please refer to Table 12.
There are three kinds of disconnection
Crank conditions between engine and starter.
16 (0-6) 2
Disconnect They can work separately or together
to separate starter motor and engine
as soon as possible.
HGM1791_HGM1791CAN Genset Controller User Manual Page 18 of 41
No. Parameter Range Default Value Description
Set value is the percentage of rated
generation rated frequency, when
Disconnect
17 (0-200)% 24 frequency is above the set value,
Frequency
starter shall disconnect. Please refer to
the following installation instruction.
Set value is the percentage of rated
speed, when speed is above the set
Disconnect
18 (0-200)% 24 value, starter shall disconnect. Please
Speed
refer to the following installation
instruction.
When Oil Pressure is above set value,
19 Disconnect OP (0-1000)kPa 200 starter shall disconnect. Please refer to
the following installation instruction.
Generator Setting
0: 3P4W;
Power Supply 1: 3P3W;
1 (0-3) 0
System 2: 2P3W;
3: 1P2W.
Numbers of generator poles (even
number). The value could be used for
2 Generator Poles (2-64) 4
calculation of engine speed when there
is no speed sensor.
Baseline for over/under voltage and
load voltage detection. If there is a
3 Rated Voltage (30-30000)V 230
potential transformer(PT), the value
means primary voltage of transformer.
Set value is percentage of rated
voltage. Before load stage if controller
4 Load Voltage (0-200)% 85 detects voltage is below load voltage,
the genset won’t enter to normal
running stage.
Baseline for over/under frequency and
5 Rated Frequency (10.0-600.0)Hz 50.0
load frequency.
Set value is percentage of rated
frequency. Before load stage if
6 Load Frequency (0-200)% 85 controller detects frequency is below
load frequency, the genset won’t enter
to normal running stage.
Potential
7 Transformer (0-1) 0 0: Disable; 1: Enable.
(PT) Setting
Primary Voltage The value means primary voltage of
8 (30-30000)V 100
of PT transformer.
Secondary The value means secondary voltage of
9 (30-1000)V 100
Voltage of PT transformer.
(0-1) 1 0: Disable; 1: Enable.
Generator Over Set value is percentage of rated
10 (0-200)% 120
Voltage Shut voltage.
(0-3600)s 3 Delay value.
(0-1) 1 0: Disable; 1: Enable.
Generator Under
11 Set value is percentage of rated
Voltage Shut (0-200)% 80
voltage.
HGM1791_HGM1791CAN Genset Controller User Manual Page 19 of 41
No. Parameter Range Default Value Description
(0-3600)s 3 Delay value.
(0-1) 1 0: Disable; 1: Enable.
Generator Over Set value is percentage of rated
12 (0-200)% 114
Frequency Shut frequency.
(0-3600)s 2 Delay value.
(0-1) 1 0: Disable; 1: Enable.
Generator Under Set value is percentage of rated
13 (0-200)% 80
Frequency Shut frequency.
(0-3600)s 3 Delay value.
(0-1) 1 0: Disable; 1: Enable.
Set value is percentage of rated
(0-200)% 110
Generator Over voltage.
14 Return value is percentage of rated
Voltage Warn (0-200)% 108
voltage.
(0-3600)s 5 Delay value.
(0-1) 1 0: Disable; 1: Enable.
Set value is percentage of rated
(0-200)% 84
Generator Under voltage.
15 Return value is percentage of rated
Voltage Warn (0-200)% 86
voltage.
(0-3600)s 5 Delay value.
(0-1) 1 0: Disable; 1: Enable.
Set value is percentage of rated
(0-200)% 110
Generator Over frequency.
16 Return value is percentage of rated
Frequency Warn (0-200)% 108
frequency.
(0-3600)s 5 Delay value.
(0-1) 1 0: Disable; 1: Enable.
Set value is percentage of rated
(0-200)% 84
Generator Under frequency.
17 Return value is percentage of rated
Frequency Warn (0-200)% 86
frequency.
(0-3600)s 5 Delay value.
Load Setting
Transformation Transformation ratio of external
1 (5-6000)/5 500
ratio of CT current transformer (CT).
It is rated current of generator, as
2 Rated Current (5-6000)A 500
baseline for load current.
It is rated power of generator, as
3 Rated Power (0-6000)kW 276
baseline for load power.
Over Current
4 (0-1) 1 0: Disable; 1: Enable.
Protection
Set value is percentage of rated
5 Overload Current (0-200)% 120
current.
Over Current
6 (0-1) 1 0: Warning; 1: Shutdown.
Action
Over Current 0: Definite-time Delay;
7 (0-1) 0
Delay Type 1: Inverse-time Delay.
HGM1791_HGM1791CAN Genset Controller User Manual Page 20 of 41
No. Parameter Range Default Value Description
Delay 1 Setting
8 (0-3600)s 10 Delay value.
(Delay Value)
Delay 2 Setting
9 (Multiple Delay (1-36) 36 Multiple value of inverse-time delay.
Value)
Module Setting
1 Power On Mode (0-2) 0 0: Stop; 1: Manual; 2: Auto.
2 Module Address (0-255) 1 Reserved.
0: Simplified Chinese; 1: English;
3 Language (0-2) 0
2: Others.
It is used for advanced parameter
4 Password Set (0-65534) 00318
setting.
Temperature
5 (0-1) 0 0: Controller; 1: ECU.
Sampling Option
Oil Pressure
6 (0-1) 0 0: Controller; 1: ECU.
Sampling Option
Speed Sampling
7 (0-1) 0 0: Controller; 1: ECU.
Option
Analog Sensor Setting
0: Not Used
1: Temperature Sensor
2: Oil Pressure Sensor
1 Sensor 1 (0-4) 1 3: Level Sensor
4: Auxiliary Input 1 (Set the sensor as 4
before configure the input 1 function)
0: Not Used
1: Temperature Sensor
2: Oil Pressure Sensor
2 Sensor 2 (0-4) 2 3: Level Sensor
4: Auxiliary Input 2 (Set the sensor as 4
before configure the input 2 function)
0: Not Used
1: Temperature Sensor
2: Oil Pressure Sensor
3 Sensor 3 (0-4) 3 3: Level Sensor
4: Auxiliary Input 3 (Set the sensor as 4
before configure the input 3 function)
Temperature Sensor
1 Curve Type (0-15) 7 SGX. See table 11.
2 Open Action (0-2) 0 0: Warning; 1: Shutdown; 2: No Action.
(0-1) 1 0: Disable; 1: Enable.
Over Temp. Set value is engine temperature. This
3
Shutdown (-50-300)ºC 98 value will be detected only after safety
on delay.
HGM1791_HGM1791CAN Genset Controller User Manual Page 21 of 41
No. Parameter Range Default Value Description
(0-3600)s 3 Delay value.
(0-1) 0 0: Disable; 1: Enable.
Set value is engine temperature. This
Under Temp.
4 (-50-300)ºC 0 value will be detected only after safety
Shutdown
on delay.
(0-3600)s 0 Delay value.
(0-1) 1 0: Disable; 1: Enable.
Set value is engine temperature. This
(-50-300)ºC 95 value will be detected only after safety
Over Temp. on delay.
5
Warn Return value is engine temperature.
(-50-300)ºC 93 This value will be detected only after
safety on delay.
(0-3600)s 5 Delay value.
(0-1) 0 0: Disable; 1: Enable.
Set value is engine temperature. This
(-50-300)ºC 70 value will be detected only after safety
Under Temp. on delay.
6
Warn Return value is engine temperature.
(-50-300)ºC 75 This value will be detected only after
safety on delay.
(0-3600)s 5 Delay value.
Oil Pressure Sensor
1 Curve Type (0-15) 7 SGX. See table 11.
2 Open Action (0-2) 0 0: Warning; 1: Shutdown; 2: No Action.
(0-1) 0 0: Disable; 1: Enable.
Set value is engine oil pressure. This
High OP
3 (0-1000)kPa 0 value will be detected only after safety
Shutdown
on delay.
(0-3600)s 0 Delay value.
(0-1) 1 0: Disable; 1: Enable.
Set value is engine oil pressure. This
Low OP
4 (0-1000)kPa 103 value will be detected only after safety
Shutdown
on delay.
(0-3600)s 3 Delay value.
(0-1) 0 0: Disable; 1: Enable.
Set value is engine oil pressure. This
5 High OP Warn (0-1000)kPa 0 value will be detected only after safety
on delay.
(0-1000)kPa 0 Return value is engine oil pressure.
HGM1791_HGM1791CAN Genset Controller User Manual Page 22 of 41
No. Parameter Range Default Value Description
This value will be detected only after
safety on delay.
(0-3600)s 0 Delay value.
(0-1) 1 0: Disable; 1: Enable.
Set value is engine oil pressure. This
(0-1000)kPa 124 value will be detected only after safety
on delay.
6 Low OP Warn
Return value is engine oil pressure.
(0-1000)kPa 138 This value will be detected only after
safety on delay.
(0-3600)s 5 Delay value.
Level Sensor
1 Curve Type (0-15) 4 SGH. See table 11.
2 Open Action (0-2) 0 0: Warning; 1: Shutdown; 2: No Action.
(0-1) 0 0: Disable; 1: Enable.
High Level Set value is level value. This value will
3 (0-300)% 0
Shutdown be detected only after safety on delay.
(0-3600)s 0 Delay value.
(0-1) 0 0: Disable; 1: Enable.
Low Level Set value is level value. This value will
4 (0-300)% 8
Shutdown be detected only after safety on delay.
(0-3600)s 5 Delay value.
(0-1) 0 0: Disable; 1: Enable.
Set value is level value. This value will
(0-300)% 0
be detected only after safety on delay.
5 High Level Warn Return value is level value. This value
(0-300)% 0 will be detected only after safety on
delay.
(0-3600)s 0 Delay value.
(0-1) 1 0: Disable; 1: Enable.
Set value is level value. This value will
(0-300)% 10
be detected only after safety on delay.
6 Low Level Warn Return value is level value. This value
(0-300)% 15 will be detected only after safety on
delay.
(0-3600)s 5 Delay value.
Digital Input Ports Setting
Input Port 1 Setting (Set sensor 1 as auxiliary input 1 before configuration)
1 Content Setting (0-7) 0 Not in use. See table 10.
Input Port 2 Setting (Set sensor 2 as auxiliary input 2 before configuration)
HGM1791_HGM1791CAN Genset Controller User Manual Page 23 of 41
No. Parameter Range Default Value Description
1 Content Setting (0-7) 0 Not in use. See table 10.
Input Port 3 Setting (Set sensor 2 as auxiliary input 3 before configuration)
1 Content Setting (0-7) 0 Not in use. See table 10.
Relay Output Ports Setting
Output Port 1 Setting
1 Content Setting (0-10) 3 Idle speed control. See table 9.
Output Port 2 Setting
1 Content Setting (0-10) 2 Energize to Stop. See table 9.
Output Port 3 Setting
1 Content Setting (0-10) 1 Common alarm. See table 9.
6.2. DEFINABLE CONTENTS OF RELAY OUTPUTS
Table 9 Definable Contents of Relay Outputs
No. Items Description
0 Not Used Output is not active if select this option.
Includes all shutdown alarms and warning alarms. Warning alarms are
Common
1 not self-latching, while shutdown alarms are self-latching and will not
Alarm
disappear until they are reset.
Energize to Suitable for the genset with stop electromagnet. The electromagnet
2
Stop closes when stop idle is over. And opens when ETS delay is over.
Used for machines that have idles. Closes during cranking, disconnects
3 Idle Control during warming up, closes during stop idle delay, disconnects after
complete stop.
Preheat
4 It closes before starting and opens before starter is powered on.
Control
5 Closing Gens During normal operation of the generator, closes the breaker.
High Speed Output when entering high speed warming up and disconnect after high
6
Output speed cooling.
Rated Speed
7 Output Output when speed is normal.
Over Speed
8 Output when speed is over the set limit value.
Output
Low Battery Output when controller detects battery voltage is low and issues warning
9
Voltage Warn signal.
Low Level Output when sensor is set as level sensor and there is low level warning
10
Warn signal.
6.3. DEFINABLE CONTENTS OF DIGITAL INPUTS
Table 10 Definable Contents of Digital Inputs (Active When GND (B-) Connected)
No. Description Notes
HGM1791_HGM1791CAN Genset Controller User Manual Page 24 of 41
No. Description Notes
0 Not Used
1 High Temperature Alarm If these signals are activated after safety on delay,
2 Low OP Alarm shutdown alarm will be immediately initiated.
3 Reserved
Shutdown alarm will be immediately initiated if this input
4 Auxiliary Shutdown
is active.
When the genset is working normally and this signal is
active, if there is a high temperature situation, the
High Temperature Cooling controller will first cool down the generator and then stop
5
Shutdown it; if the signal is deactivated and a high temperature
situation occurs, the controller will shut down the genset
without cooling down.
When the controller is in auto mode, if this input is active,
6 Remote Start
the genset will start automatically.
7 Reserved
6.4. SENSOR SELECTION
Table 11 Sensor Selection
No. Items Content Remark
0 Not used
1 User defined resistor curve
2 User defined current curve
3 VDO
4 CURTIS
The range of user-defined resistor type
Temperature 5 VOLVO-EC
1 sensor is 0-6000Ω, and the default
Sensor 6 CURTIS
selection is temperature sensor.
7 SGX
8 SGD
9 SGH
10 SUZUKI
11-15 Reserved
0 Not used
1 User defined resistor curve The range of user-defined resistor type
2 User defined current curve sensor is 0-6000Ω, and the default
Oil Pressure 3 VDO 10Bar selection is pressure sensor. If select
2
Sensor 4 CURTIS voltage or current type sensor, the
5 VDO 5Bar hardware will be changed. And it needs
6 DATCON 10Bar to be specified when order.
7 SGX
HGM1791_HGM1791CAN Genset Controller User Manual Page 25 of 41
No. Items Content Remark
8 SGD
9 SGH
10 VOLVO-EC
11 SUZUKI
12 4-20mA 10Bar
13 0-5V 10Bar
14-15 Reserved
0 Not used
1 User defined resistor curve
2 User defined current curve The range of user-defined resistor type
Fuel Level
3 3 SGD sensor is 0-6000Ω, and the default
Sensor
4 SGH selection is level sensor.
5 SUZUKI
6-15 Reserved
6.5. CONDITIONS OF CRANK DISCONNECT SELECTION
Table 12 Crank Disconnect Conditions Selection
No Content
0 Generator Frequency
1 Speed
2 Speed + Generator Frequency
3 Oil pressure
4 Generator Frequency + Oil pressure
5 Speed + Oil pressure
6 Generator Frequency + Speed+ Oil pressure
1) There are 3 conditions to make starter separate with engine; Speed, generator frequency and oil
pressure can be used separately while oil pressure is recommended to use together with speed
and generator frequency. The aim is to disconnect the starter motor as soon as possible.
2) Speed sensor is the magnetic equipment which be installed in starter for detecting flywheel
teeth.
3) When set as speed, must ensure that the number of flywheel teeth is as same as setting,
otherwise, “over speed shutdown” or “under speed shutdown” may be caused.
4) If genset without speed sensor please don’t select corresponding items, otherwise, “start fail” or
“loss speed signal” maybe caused.
5) If genset without oil pressure sensor, please don’t select corresponding items.
6) If not select generator frequency in crank disconnect setting, controller will not collect and
display the relative electric quantity (can be used in water pump set); if not select speed in crank
disconnect setting, the speed displayed in controller is calculated by generator signal.
HGM1791_HGM1791CAN Genset Controller User Manual Page 26 of 41
7 CONTROLLER FUNCTION SETTING
7.1. SETTING
When the controller is in standby mode, hold and press for 3s to enter into menu interface,
and menu items is listed as follows:
Parameter setting
Language
Event log
Controller information
7.2. PARAMETER SETTING
1) Press or button to change setting option, then press button to enter into
password interface;
2) In password interface, press button to move the cursor, then press or button to
set the password, after finish the setting, press button to confirm;
3) The password of “00318” has the highest authority, after inputting it, you can set all parameter
items. If you change the default password of “00318”, when you set parameters by PC software,
you need to input the same password with controller first. If you want to set more parameters,
such as voltage value and current value, or forget the password, please contact with the
manufacturer.
Attention:
a) Please change the controller parameters when generator is in standby mode only (e. g. crank
disconnect conditions selection, configurable input, configurable output, various delay),
otherwise, shutdown and other abnormal conditions may happen.
b) Upper set value must be higher than lower set value, for example, over voltage set value must
be higher than under voltage set value, otherwise over voltage and under voltage condition
may occur simultaneously.
c) Over speed set value must be higher than under speed set value, otherwise over speed and
under speed condition may occur simultaneously.
d) When you do the alarm setting, please set the correct return value, or it won’t issue warning
successfully. When you set upper alarm value, return value should be less than set value; as
for lower alarm value, return value should be more than set value.
e) Please set the generator frequency value as low as possible when cranking, in order to make
the starter be separated quickly as soon as crank disconnect.
f) Auxiliary input port 1-3 can’t be set as same item, otherwise it won’t function properly.
Auxiliary output port 1-3 can be set as same item.
g) At any time, press can stop current parameter setting immediately.
HGM1791_HGM1791CAN Genset Controller User Manual Page 27 of 41
7.3. LANGUAGE
In language setting interface, the options are simplified Chinese, English and Others. The default
of “Others” will be English.
7.4. EVENT LOG
Event log function can record up to 99 logs. The time of event log will be the cumulative running
time.
7.5. CONTROLLER INFORMATION
a) In this interface, it will show you the development information, such as software version,
hardware version and release date.
b) In this interface, press button to show the status of digital input and output ports.
HGM1791_HGM1791CAN Genset Controller User Manual Page 28 of 41
8 SENSOR SETTINGS
a) Sensors connected to the controller are all resistor type. Parts of build-in standard sensor
curves in the controller can be selected by users. If users want to use defined sensor curve, it
needs to be set via host PC software (see details in table 10).
b) When input the sensor curve, X value (resistance) must be input from small to large,
otherwise, mistake occurs.
c) If sensor type is set as “not used”, sensor curve will not work.
d) The first or last few values in the vertical coordinates can be set as same as below:
Fig.3 Sensor Curve
Table 13 Normal Pressure Unit Conversion Table
N/m2 (pa) kgf/cm2 bar psi
1Pa 1 1.02x10 5 1x10 5 1.45x10 4
- - -
1kgf/cm2 9.8x104 1 0.98 14.2
1bar 1x105 1.02 1 14.5
1psi 6.89x103 7.03x10 2 6.89x10 2 1
- -
HGM1791_HGM1791CAN Genset Controller User Manual Page 29 of 41
9 COMMISSIONING
Please make sure the following checks are made before commissioning;
a) Ensure all the connections are correct and wires diameter is suitable;
b) Ensure that the controller DC power has fuse, controller’s positive and negative correctly
connected to starting battery;
c) Take proper action to prevent engine to crank success (e. g. Remove the connection wire of fuel
valve). If checking is OK, make the starting battery power on; choose manual mode and
controller will executive routine;
d) Set controller under manual mode, press “start” button, genset will start. After the cranking
times as setting, controller will send signal of Start Failure; then press “stop” to reset controller;
e) Recover the action to prevent engine to crank success (e. g. Connect wire of fuel valve), press
start button again, genset will start. If everything goes well, genset will normal running after idle
running (if idle run be set). During this time, please watch for engine’s running situations and AC
generator’s voltage and frequency. If abnormal, stop genset and check all wires connection
according to this manual;
f) Any other questions please contact with SmartGen’s service personnel.
HGM1791_HGM1791CAN Genset Controller User Manual Page 30 of 41
10 TYPICAL APPLICATION
Fig.4 HGM1791_HGM1791CAN Typical Application Diagram
Fig.5 HGM1791_HGM1791CAN 3P3W Application Diagram
Fig.6 HGM1791_HGM1791CAN 2P3W Application Diagram
CAUTION: Crank and fuel output ports should be extended to large capacity relays.
HGM1791_HGM1791CAN Genset Controller User Manual Page 31 of 41
11 INSTALLATION
11.1. FIXING CLIPS
1) Controller is panel built-in design; it is fixed by clips when installed.
2) Withdraw the fixing clip screw (turn anticlockwise) until it reaches proper position.
3) Pull the fixing clip backwards (towards the back of the module) ensuring two clips are inside
their allotted slots.
4) Turn the fixing clip screws clockwise until they are fixed on the panel.
NOTE: Care should be taken not to over tighten the screws of fixing clips.
11.2. OVERALL DIMENSION
Unit: mm
Fig.7 Overall and Cutout Dimensions
— BATTERY VOLTAGE INPUT
HGM1791_HGM1791CAN controller can suit for widely range of battery voltage DC(8~35)V.
Negative of battery must be connected with the engine shell. Diameter of wire that connects from
power supply to battery must be over 1.5mm2. If floating charger configured, please firstly connect
output wires of charger to battery’s positive and negative directly, then, connect wires from battery’s
positive and negative to controller’s positive and negative input ports in order to prevent charger
disturbing the controller’s normal working.
— SPEED SENSOR INPUT
Speed sensor is the magnetic equipment which be installed in starter and for detecting flywheel
teeth. Its connection wires to controller should apply for 2 cores shielding line. The shielding layer
should connect to No. 1 terminal in controller while another side is hanging in air. The else two signal
wires are connected to No.1 and No.10 terminals in controller. The output voltage of speed sensor
should be within AC (1~24) V (effective value) during the full speed. AC12V is recommended (in
rated speed). When install the speed sensor, let the sensor is spun to contacting flywheel first, then,
port out 1/3 lap, and lock the nuts of sensor at last.
— OUTPUT AND EXPAND RELAYS
HGM1791_HGM1791CAN Genset Controller User Manual Page 32 of 41
All outputs of controller are relay contact output type. If need to expand the relays, please add
freewheel diode to both ends of expand relay’s coils (when coils of relay have DC current) or,
increase resistance-capacitance return circuit (when coils of relay have AC current), in order to
prevent disturbance to controller or others equipment.
— AC INPUT
Current input of controller must be connected to outside current transformer. And the current
transformer’s secondary side current must be 5A. At the same time, the phases of current
transformer and input voltage must correct. Otherwise, the current of collecting and active power
maybe not correct.
WARNING: When there is load current, transformer’s secondary side is prohibited to open circuit.
— WITHSTAND VOLTAGE TEST
When controller had been installed in control panel, if need the high voltage test, please
disconnect controller’s all terminal connections, in order to prevent high voltage into controller and
damage it.
HGM1791_HGM1791CAN Genset Controller User Manual Page 33 of 41
12 FAULT FINDING
Table 14 Fault Finding
Symptoms Possible Solutions
Check starting batteries;
Controller no response with
Check controller connection wirings;
power.
Check DC fuse.
Check the water/cylinder temperature is too high or not;
Genset shutdown Check the genset AC voltage;
Check DC fuse.
Low oil pressure alarm after
Check the oil pressure sensor and its connections.
crank disconnect
High water temp. alarm after
Check the temperature sensor and its connections.
crank disconnect
Check related switch and its connections according to the
Shutdown alarm in running information on LCD;
Check programmable inputs.
Check fuel circuit and its connections;
Check starting batteries;
Crank not disconnect
Check speed sensor and its connections;
Refer to engine manual.
Check starter connections;
Starter no response
Check starting batteries.
HGM1791_HGM1791CAN Genset Controller User Manual Page 34 of 41
13 CONNECTIONS OF CONTROLLER WITH J1939 ENGINE
13.1. CUMMINS-ISB/ISBE
Table 15 B Connector
Terminals of controller B connector Remark
Fuel Relay Output 39
Crank Relay Output - Connect to starter coil directly.
Connect to extension 30A
ECU power
relay to provide battery
Aux. Output Configure the auxiliary output 2 as ”ECU
voltage for terminal 01,
power”.
07, 12, and 13.
Table 16 9-pin Connector
Terminals of controller 9 pins connector Remark
Use connection cable in 120 ohms
CAN(H) SAE J1939 signal
impedance.
Use connection cable in 120 ohms
CAN(L) SAE J1939 return
impedance.
Engine type: Cummins-ISB.
13.2. CUMMINS QSL9
Table 17 50-pin Connector
Terminals of controller 50 pins connector Remark
Fuel Relay Output 39
Crank Relay Output - Connect to starter coil directly.
Table 18 9-pin Connector
Terminals of controller 9 pins connector Remark
Use connection cable in 120 ohms
CAN(H) SAE J1939 signal-C
impedance.
Use connection cable in 120 ohms
CAN(L) SAE J1939 return-D
impedance.
Engine type: Cummins-CM850. Suitable for CM850 engine control module.
13.3. CUMMINS QSM11
Table 19 C1 Connector
Terminals of controller C1 connector Remark
Connect to external extension relay.
Fuel Relay Output 5&8 When it is configured as fuel output,
connect terminal 5 to terminal 8.
Crank Relay Output - Connect to starter coil directly.
Table 20 3-pin Data Link Connector
Terminals of controller 3 pins data link connector Remark
Use connection cable in 120 ohms
CAN(H) A
impedance.
Use connection cable in 120 ohms
CAN(L) B
impedance.
Engine type: Cummins-ISB. Suitable for CM570 engine control module. The engine model is
HGM1791_HGM1791CAN Genset Controller User Manual Page 35 of 41
QSM11 G1 and QSM11 G2.
13.4. CUMMINS QSX15-CM570
Table 21 50-pin Connector
Terminals of controller 50 pins connector Remark
Fuel Relay Output 38 Oil injection switch.
Crank Relay Output - Connect to starter coil directly.
Table 22 9-pin Connector
Terminals of controller 9 pins connector Remark
Use connection cable in 120 ohms
CAN(H) SAE J1939 signal-C
impedance.
Use connection cable in 120 ohms
CAN(L) SAE J1939 return-D
impedance.
Engine type: Cummins-CM570. Suitable for CM570 engine control module. The engine model is
QSX15.
13.5. CUMMINS QSM11
Table 23 Engine OEM Connector
Terminals of controller Engine OEM connector Remark
Fuel Relay Output 38
Crank Relay Output - Connect to starter coil directly.
CAN(H) 46 Use connection cable in 120 ohms
impedance.
CAN(L) 37 Use connection cable in 120 ohms
impedance.
Engine type: Common J1939.
13.6. CUMMINS QSZ13
Table 24 Engine OEM Connector
Terminals of controller Engine OEM connector Remark
Fuel Relay Output 45
Crank Relay Output - Connect to starter coil directly.
Configure it as “Idle control”, and output
normal closing. Use external relay to
Aux. output 1 16&41
make controller into high speed running,
and terminal 19 and 41 close.
Configure it as “Pulsed speed up
control”, and output normal opening.
Aux. output 2 19&41 Use external relay to make controller
into warming up, and terminal 19 and 41
close for 0.1s.
CAN(H) 1 Use connection cable in 120 ohms
impedance.
CAN(L) 21 Use connection cable in 120 ohms
impedance.
Engine type: Common J1939.
HGM1791_HGM1791CAN Genset Controller User Manual Page 36 of 41
13.7. DETROIT DIESEL DDEC III / IV
Table 25 Engine CAN Port
Terminals of controller Engine CAN port Remark
Connect to extension 30A
Fuel Relay Output relay to provide battery
voltage for ECU.
Crank Relay Output - Connect to starter coil directly.
CAN(H) CAN(H) Use connection cable in 120 ohms
impedance.
CAN(L) CAN(L) Use connection cable in 120 ohms
impedance.
Engine type: Common J1939.
13.8. DEUTZ EMR2
Table 26 F Connector
Terminals of controller F connector Remark
Connect to extension 30A
relay to provide battery
Fuel Relay Output voltage for terminal 14.
Fuse is 16A.
Crank Relay Output - Connect to starter coil directly.
- 1 Connect to negative pole of battery.
CAN(H) 12 Use connection cable in 120 ohms
impedance.
CAN(L) 13 Use connection cable in 120 ohms
impedance.
Engine type: VOLVO-EDC4.
13.9. JOHN DEERE
Table 27 21-pin Connector
Terminals of controller 21-pin connector Remark
Fuel Relay Output G, J
Crank Relay Output D
CAN(H) V Use connection cable in 120 ohms
impedance.
CAN(L) U Use connection cable in 120 ohms
impedance.
Engine type: JOHN DEERE.
HGM1791_HGM1791CAN Genset Controller User Manual Page 37 of 41
13.10. MTU MDEC
Table 28 X1 Connector
Terminals of controller X1 connector Remark
Fuel Relay Output BE1
Crank Relay Output BE9
CAN(H) G Use connection cable in 120 ohms
impedance.
CAN(L) F Use connection cable in 120 ohms
impedance.
Engine type: MTU-MDEC-303. Suitable for MTU engines of 2000 series and 4000 series.
13.11. MTU ADEC (SMART Module)
Table 29 ADEC (X1 Port)
Terminals of controller ADEC (X1 port) Remark
Connect X1 9 to negative pole of
Fuel Relay Output X1 10
battery.
Connect X1 33 to negative pole of
Crank Relay Output X1 34
battery.
Table 30 SMART Module (X4 Port)
Terminals of controller SMART (X4 port) Remark
Use connection cable in 120 ohms
CAN(H) X4 1
impedance.
Use connection cable in 120 ohms
CAN(L) X4 2
impedance.
Engine type: MTU-ADEC. Suitable for MTU engines with ADEC (ECU8) or SMART module.
13.12. MTU ADEC (SAM Module)
Suitable for MTU engines with ADEC (ECU7) and SAM module.
Table 31 ADEC (X1 Port)
Terminals of controller ADEC (X1 port) Remark
Connect X1 28 to negative pole of
Fuel Relay Output X1 43
battery.
Connect X1 22 to negative pole of
Crank Relay Output X1 37
battery.
Table 32 SAM (X23 Port)
Terminals of controller SAM (X23 port) Remark
Use connection cable in 120 ohms
CAN(H) X23 2
impedance.
Use connection cable in 120 ohms
CAN(L) X23 1
impedance.
Engine type: Common J1939. Suitable for MTU engines with ADEC (ECU7) or SAM module.
HGM1791_HGM1791CAN Genset Controller User Manual Page 38 of 41
13.13. PERKINS
Table 33 Connector
Terminals of controller Connector Remark
Fuel Relay Output 1,10,15,33,34
Crank Relay Output - Connect to starter coil directly.
CAN(H) Use connection cable in 120 ohms
31
impedance.
CAN(L) Use connection cable in 120 ohms
32
impedance.
Engine type: PERKINS. Suitable for ADEM3/ADEM4 engine control module. The engine models are
2306, 2506, 1106, 2806.
13.14. SCANIA
Table 34 B1 Connector
Terminals of controller B1 connector Remark
Fuel Relay Output 3
Crank Relay Output - Connect to starter coil directly.
CAN(H) Use connection cable in 120 ohms
9
impedance.
CAN(L) Use connection cable in 120 ohms
10
impedance.
Engine type: SCANIA. Suitable for S6 engine control module. The engine models are DC9, DC12,
DC16.
13.15. VOLVO EDC3
Table 35 “Stand Alone” Connector
Terminals of controller “Stand Alone” connector Remark
Fuel Relay Output H
Crank Relay Output E
ECU power
Aux. output 1 P Configure the auxiliary output 1 as ”ECU
power”.
Table 36 “Data Bus” Connector
Terminals of controller “Data Bus” connector Remark
Use connection cable in 120 ohms
CAN(H) 1
impedance.
Use connection cable in 120 ohms
CAN(L) 2
impedance.
Engine type: VOLVO. Suitable for engine models of TAD1240, TAD1241, TAD1242.
NOTE: When this engine type is selected, preheating time should be set at least 3 seconds.
HGM1791_HGM1791CAN Genset Controller User Manual Page 39 of 41
13.16. VOLVO EDC4
Suitable for engine models of TD520, TAD520 (optional), TD720, TAD720 (optional), TAD721,
TAD722, TAD732.
Table 37 Connector
Terminals of controller Connector Remark
Connect to extension 30A
relay to provide battery
Fuel Relay Output voltage for terminal 14.
Fuse is 16A.
Crank Relay Output - Connect to starter coil directly.
1 Connect to negative pole of battery.
CAN(H) 12 Use connection cable in 120 ohms
impedance.
CAN(L) 13 Use connection cable in 120 ohms
impedance.
Engine type: VOLVO-EDC4.
13.17. VOLVO-EMS2
Table 38 Engine CAN Port
Terminals of controller Engine CAN port Remark
ECU shutdown
Aux. output 1 6 Configure the auxiliary output 1 as “ECU
shutdown”.
ECU power
Aux. output 2 5 Configure the auxiliary output 1 as “ECU
power”.
3 Negative pole of battery
4 Positive pole of battery
CAN(H) 1(Hi) Use connection cable in 120 ohms
impedance.
CAN(L) 21(Lo) Use connection cable in 120 ohms
impedance.
Engine type: VOLVO-EMS2. Suitable for Volvo engine models of TAD734, TAD940, TAD941,
TAD1640, TAD1641, TAD1642.
NOTE: When this engine type is selected, preheating time should be set at least 3 seconds.
13.18. YUCHAI
Table 39 Engine 42-pin Port
Terminals of controller Engine 42 pins port Remark
Fuel Relay Output 1.40 Connect to engine ignition switch.
Crank Relay Output - Connect to starter coil directly.
Use connection cable in 120 ohms
CAN(H) 1.35
impedance.
Use connection cable in 120 ohms
CAN(L) 1.34
impedance.
HGM1791_HGM1791CAN Genset Controller User Manual Page 40 of 41
Table 40 Engine 2-pin Connector
Terminals of controller Engine 2-pin connector Remark
The diameter of connection cable
Negative pole of battery 1
should be 2.5mm2.
The diameter of connection cable
Positive pole of battery 2
should be 2.5mm2.
Engine type: BOSCH. Suitable for Yuchai BOSCH common rail electronic-controlled engine.
13.19. WEICHAI
Table 41 Engine Port
Terminals of controller Engine port Remark
Fuel Relay Output 1.40 Connect to engine ignition switch.
Crank Relay Output 1.61
CAN_SCR CAN communication shielded cable
CAN(H) 1.35 Use connection cable in 120 ohms
impedance.
CAN(L) 1.34 Use connection cable in 120 ohms
impedance.
Engine type: GTSC1. Suitable for Weichai BOSCH common rail electronic-controlled engine.
NOTE: If there is any question of connection between controller and ECU communication, please feel free to
contact SmartGen’s service personnel.
_________________________________
HGM1791_HGM1791CAN Genset Controller User Manual Page 41 of 41